JD300
Diesel Product Line
208-600 Volt
60 Hz / 1800 RPM
JD300-03IT4
300 kWe / 265 kWe
Standby / Prime
Ratings
240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1.0
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
572RSL4029
433CSL6216
433CSL6216
432CSL6212
432PSL6246
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
300
300
300
300
300
AMPS
1250
1042
904
452
361
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
265
265
265
265
265
AMPS
1104
921
798
399
319
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment
Engine
„„Radiator
Cooled Unit Mounted (50˚C)
Generator
„„Brushless
Single Bearing
Voltage Regulator
Additional
„„Microprocessor
Based Digital Control
„„Blower
Fan & Fan Drive
„„Automatic
„„Base
- Structural Steel
„„Starter
& Alternator
„„±
1.0% Voltage Regulation
„„Main
Line Circuit Breaker Mounted & Wired
Pole, Rotating Field
„„Battery
„„Oil
Pump & Filter
„„4
„„Oil
Drain Extension w/Valve
„„130˚C
Standby Temperature Rise
„„105˚C
Prime Temperature Rise
of Rated Load - One Step
„„Governor
- Electronic Isochronous
„„24V
Battery System & Cables
„„100%
„„SAE
Flywheel & Housing
„„5%
„„Air
Cleaner (Dry Single Stage)
„„Exhaust
Particulate Filter / Silencer Mtd
„„Flexible
Fuel Connectors
„„EPA
Certified - Tier IT4
JD300-03IT4
Maximum Harmonic Content
„„NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
„„Jacket
Charger 24V 5 Amp
Water Heater -20˚F 4000W 240V
w/Isolation Valves
„„Vibration
Isolation Mounts
„„Radiator
Duct Flange (OPU Only)
„„Single
Source Supplier
„„2YR
/ 2000HR Standby Warranty
„„1YR
/ 1500HR Prime Warranty
„„Standard
Colors - White / Tan / Gray
1
Diesel Product Line
300 kWe / 265 kWe
Application Data
Engine
Manufacturer:
Model:
John Deere
6135HFG95
Type:
Aspiration:
Cylinder Arrangement:
Displacement - Cu. In. (lit):
Bore - in. (cm) x Stroke - in. (cm):
4-Cycle
Compression Ratio:
Turbo Charged, CAC
Rated RPM:
6 Cylinder Inline
Max HP Stby (kWm):
824 (13.5)
5.2 (13.2) x 6.5 (16.5)
15.3:1
1800
477 (356)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
705 (374)
705 (374)
Gas Volume at Stack Temp: CFM (m³/min)
1670 (47.3)
1670 (47.3)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
68.0 (17.0)
68.0 (17.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
204 (774)
204 (774)
Heat Rejection to Coolant: BTUM (kW)
13,877 (243.8)
Heat Rejection to CAC: BTUM (kW)
4,377 (76.9)
4,377 (76.9)
Heat Radiated to Ambient: BTUM (kW)
2,775 (48.6)
2,451 (42.9)
Cooling System
13,877 (243.8)
Air Requirements
Aspirating: CFM (m³/min)
858 (24.3)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
36,563 (1,034)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
858 (24.3)
36,563 (1,034)
Consult Factory For Remote Cooled Applications
Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)
23.1 (87.4)
21.0 (79.3)
At 75% of Power Rating: gal/hr (lit/hr)
17.7 (66.9)
16.1 (60.9)
At 50% of Power Rating: gal/hr (lit/hr)
12.5 (47.3)
11.42 (43.2)
Total Oil System: gal (lit)
15.9 (60.0)
15.9 (60.0)
Engine Jacket Water Capacity: gal (lit)
6.6 (25.0)
6.6 (25.0)
System Coolant Capacity: gal (lit)
18.7 (70.8)
18.7 (70.8)
Fluids Capacity
Deration Factors
Rated Power is available up to 10,114 ft (3082 m) at ambient temperatures to 122°F (50°C) standby and prime.
Consult factory for site conditions above these parameters.
JD300-03IT4
2
Diesel Product Line
300 kWe / 265 kWe
DGC-2020 Control Panel
Standard Features
„„Digital
Metering
„„Engine
Parameters
„„Generator
„„Engine
„„CAN
Protection Functions
Protection
Bus ECU Communications
„„Windows-Based
„„Multilingual
„„Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
„„16
Programmable Contact Inputs
„„Up
to 15 Contact Outputs (7 standard)
„„UL
Recognized, CSA Certified, CE Approved
„„Event
„„IP
Recording
54 Front Panel Rating with Integrated Gasket
„„NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data
LxWxH
Weight lbs
OPU
140 x 66 x 91 in
8275
Level 1
140 x 66 x 111 in
9250
Level 2
140 x 66 x 125 in
9725
Level 3
195 x 66 x 114 in
10,200
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
80 dBA
86 dBA
Level 1
79 dBA
83 dBA
Level 2
78 dBA
81 dBA
Level 3
68 dBA
72 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice.
Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
JD300-03IT4
3
Diesel Product Line
300 kWe / 265 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available).
**Level 2 & 3 enclosures are 150 MPH Wind Rated as standard.
***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks
24 Hour (750 Gallon)
48 Hour (1500 Gallon)
72 Hour (2250 Gallon)
A
B
C
A
B
C
A
B
C
OPU
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 1
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 2
140.00
66.00
28.00
200.00
66.00
36.00
294.00
66.00
36.00
Level 3
195.00
66.00
20.00
200.00
66.00
36.00
294.00
66.00
36.00
*All specification sheet dimensions are represented in inches.
**All enclosures and fuel tanks are based on the standard unit configuration. Any deviation can change dimensions.
***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice.
PowerDak Power Products LLC
Distributed By:
3350 Jet Dr. Rapid City SD 57703
Phone + 1 605-718-9960
JD300-03IT4
www.dakgenerator.com
Rev1.1
4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF