19RELAY 62
62 Series - Power relays 16 A
Features
62.22 / 62.23
62.22-0300 / 62.23-0300
Printed circuit mount
16 A Power relay
2 & 3 Pole changeover contacts or NO
(≥ 3 mm contact gap)
• AC coils & DC coils
• Reinforced insulation between coil and
contacts according to EN 60335-1, with
6 mm clearance & 8 mm creepage distance
• SELV coil-contact separator option
• Cadmium Free contact material options
•
•
•
62.22
62.23
62.22-0300 62.23-0300
62.2x
2 & 3 pole changeover contact
PCB mount
2 & 3 pole normally open contact
(≥ 3 mm contact gap)
• PCB mount
•
62.2x-0300
* Distance between contacts ≥ 3 mm
(EN 60730-1).
** With the AgSnO2 material the maximum
peak current is 120 A - 5 ms (NO contact).
FOR UL HORSEPOWER AND PILOT DUTY RATINGS
SEE “General technical information” page V
62.22
Copper side view
62.23
Copper side view
2 CO (DPDT)
3 CO (3PDT)
62.22 - 0300
Copper side view
62.23 - 0300
Copper side view
Contact specification
Contact configuration
2 NO (DPST-NO), ≥ 3 mm* 3 NO (3PST-NO), ≥ 3 mm*
A
16/30**
16/30**
Rated voltage/Maximum switching voltage V AC
250/400
250/400
Rated current/Maximum peak current
Rated load AC1
VA
4,000
4,000
Rated load AC15 (230 V AC)
VA
750
750
Motor rating (230/400 V AC)
kW
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
mW (V/mA)
Standard contact material
0.8/—
0.8/1.5
0.8/—
0.8/1.5
16/0.6/0.4
16/1.1/0.7
1,000 (10/10)
1,000 (10/10)
AgCdO
AgCdO
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power AC/DC
VA (50 Hz)/W
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
6 - 12 - 24 - 48 - 60 - 110 - 125 - 220
V DC
Operating range
AC
DC
2.2/1.3
3/3
(0.8…1.1)UN
(0.85…1.1)UN
(0.8…1.1)UN
(0.85…1.1)UN
Holding voltage
AC/DC
0.8 UN/0.6 UN
0.8 UN/0.6 UN
Must drop-out voltage
AC/DC
0.2 UN/0.1 UN
0.2 UN/0.1 UN
10 · 106/30 · 106
10 · 106/30 · 106
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
cycles
cycles
ms
Insulation between coil and contacts (1.2/50 µs) kV
Dielectric strength between open contacts
Ambient temperature range
Environmental protection
V AC
°C
3
100 · 10
100 · 103
11/4
15/3
6
6
1,500
2,500
–40…+70
–40…+50
RT I
RT I
Approvals (according to type)
1
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Features
62.32 / 62.33
62.32-0300 / 62.33-0300
Plug-in mount/Faston 187
16 A Power relay
Plug-in (92 series sockets) or Faston 187
(4.8x0.5 mm) with optional mounting adaptors
• 2 & 3 Pole changeover contacts or NO
(≥ 3 mm contact gap)
• AC coils & DC coils
• UL Listing (certain relay/socket combinations)
• LED, mechanical indicator & test button options
• Reinforced insulation between coil and
contacts according to EN 60335-1, with
6 mm clearance & 8 mm creepage distance
• SELV coil-contact separator option
• Cadmium Free contact material options
• Sockets and accessories
•
62.32
62.33
62.32-0300 62.33-0300
62.3x
•
•
2 & 3 pole normally open contact
(≥ 3 mm contact gap)
• Plug-in / Faston 187
•
2 & 3 pole changeover contact
Plug-in / Faston 187
62.3x-0300
* Distance between contacts ≥ 3 mm (EN 60730-1).
** With the AgSnO2 material the maximum
peak current is 120 A - 5 ms (NO contact).
FOR UL HORSEPOWER AND PILOT DUTY RATINGS
SEE “General technical information” page V
62.32
62.33
62.32-0300
62.33-0300
Contact specification
Contact configuration
2 CO (DPDT)
Rated current/Maximum peak current
3 CO (3PDT)
2 NO (DPST-NO), ≥ 3 mm* 3 NO (3PST-NO), ≥ 3 mm*
A
16/30**
16/30**
Rated voltage/Maximum switching voltage V AC
250/400
250/400
Rated load AC1
VA
4,000
4,000
Rated load AC15 (230 V AC)
VA
750
750
Motor rating (230/400 V AC)
kW
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
mW (V/mA)
Standard contact material
0.8/—
0.8/1.5
0.8/—
0.8/1.5
16/0.6/0.4
16/1.1/0.7
1,000 (10/10)
1,000 (10/10)
AgCdO
AgCdO
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power AC/DC
VA (50 Hz)/W
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
6 - 12 - 24 - 48 - 60 - 110 - 125 - 220
V DC
Operating range
2.2/1.3
3/3
AC
(0.8…1.1)UN
(0.85…1.1)UN
DC
(0.8…1.1)UN
(0.85…1.1)UN
Holding voltage
AC/DC
0.8 UN/0.6 UN
0.8 UN/0.6 UN
Must drop-out voltage
AC/DC
0.2 UN/0.1 UN
0.2 UN/0.1 UN
10 · 106/30 · 106
10 · 106/30 · 106
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
cycles
cycles
ms
Insulation between coil and contacts (1.2/50 µs) kV
Dielectric strength between open contacts
Ambient temperature range
Environmental protection
V AC
°C
3
100 · 10
100 · 103
11/4
15/3
6
6
1,500
2,500
–40…+70
–40…+50
RT I
RT I
Approvals (according to type)
2
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Features
62.82 / 62.83
62.82-0300 / 62.83-0300
Flange mount/Faston 250
16 A Power relay
Faston 250 (6.3x0.8 mm) termination Flange
or optional mounting adaptors
• 2 & 3 Pole changeover contacts or NO
(≥ 3 mm contact gap)
• AC coils & DC coils
• LED, mechanical indicator & test button options
• Reinforced insulation between coil and
contacts according to EN 60335-1, with
6 mm clearance & 8 mm creepage distance
• SELV coil-contact separator option
• Cadmium Free contact material options
•
62.82
62.82-0300
62.83
62.83-0300
62.8x
•
•
2 & 3 pole normally open contact
(≥ 3 mm contact gap)
• Flange mount / Faston 250
•
2 & 3 pole changeover contact
Flange mount / Faston 250
62.8x-0300
* Distance between contacts ≥ 3 mm
(EN 60730-1).
** With the AgSnO2 material the maximum
peak current is 120 A - 5 ms (NO contact).
FOR UL HORSEPOWER AND PILOT DUTY RATINGS
SEE “General technical information” page V
62.82
62.83
62.82-0300
62.83-0300
Contact specification
2 CO (DPDT)
Contact configuration
3 CO (3PDT)
2 NO (DPST-NO), ≥ 3 mm* 3 NO (3PST-NO), ≥ 3 mm*
A
16/30**
16/30**
Rated voltage/Maximum switching voltage V AC
250/400
250/400
Rated current/Maximum peak current
Rated load AC1
VA
4,000
4,000
Rated load AC15 (230 V AC)
VA
750
750
Motor rating (230/400 V AC)
kW
Breaking capacity DC1: 30/110/220 V
Minimum switching load
A
mW (V/mA)
Standard contact material
0.8/—
0.8/1.5
0.8/—
0.8/1.5
16/0.6/0.4
16/1.1/0.7
1,000 (10/10)
1,000 (10/10)
AgCdO
AgCdO
Coil specification
Nominal voltage (UN)
V AC (50/60 Hz)
Rated power AC/DC
VA (50 Hz)/W
6 - 12 - 24 - 48 - 60 - 110 - 120 - 230 - 240 - 400
6 - 12 - 24 - 48 - 60 - 110 - 125 - 220
V DC
Operating range
2.2/1.3
3/3
AC
(0.8…1.1)UN
(0.85…1.1)UN
DC
(0.8…1.1)UN
(0.85…1.1)UN
Holding voltage
AC/DC
0.8 UN/0.6 UN
0.8 UN/0.6 UN
Must drop-out voltage
AC/DC
0.2 UN/0.1 UN
0.2 UN/0.1 UN
10 · 106/30 · 106
10 · 106/30 · 106
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
cycles
cycles
ms
Insulation between coil and contacts (1.2/50 µs) kV
Dielectric strength between open contacts
Ambient temperature range
Environmental protection
V AC
°C
3
100 · 10
100 · 103
11/4
15/3
6
6
1,500
2,500
–40…+70
–40…+50
RT I
RT I
Approvals (according to type)
3
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Ordering information
Example: 62 series power relay + Faston 250 (6.3x0.8 mm), rear flange mount, 2 NO (DPST-NO), 12 V DC coil.
6 2 . 8
A
B
C
D
2 . 9 . 0 1 2 . 0
3
0
0
A: Contact material
0 = Standard AgCdO
4 = AgSnO2
Series
Type
2 = PCB
3 = Plug-in
8 = Faston 250 (6.3x0.8 mm)
with rear flange mount
B: Contact circuit
0 = CO (nPDT)
3 = NO (nPST),
≥ 3 mm contact gap
5 = CO (nPDT) + additional
physical separator between
coil and contacts (for SELV
applications)
6 = NO (nPST), ≥ 3 mm contact
gap + additional physical
separator between coil and
contacts (for SELV
applications)
No. of poles
2 = 2 pole
3 = 3 pole
Coil version
8 = AC (50/60 Hz)
9 = DC
Coil voltage
See coil specifications
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in bold.
Type
Coil version
62.22/23 AC-DC
62.32/33 AC-DC
AC-DC
AC
AC
AC
DC
DC
DC
62.82/83 AC-DC
AC-DC
AC
AC
DC
DC
A
0-4
0-4
0-4
0-4
0-4
0-4
0-4
0-4
0-4
0-4
0-4
0-4
0-4
B
0-3-5-6
0-3-5-6
0-5
0
0-3
0
0
0-3
0
0-3-5-6
0-5
0
0-3
0-4 0
0-4 0-3
C
0
0
2-4
2-3-4-5
3
54
4-6-7
6
74
0
2-4
2-3-4-5
3
D
0
0-6
0-6
0-6
0-6
/
0-6
0-6
/
0-9
0
0
0
4-6-7
6
0
0
D: Special versions
0 = Standard
6 = Rear flange mount
9 = Type 62.82/83 without rear flange
mount
C: Options
0 = None
2 = Mechanical indicator
3 = LED (AC)
4 = Lockable test button +
mechanical indicator
5* = Lockable test button + LED (AC)
54* = Lockable test button + LED (AC) +
mechanical indicator
6* = LED + diode
(DC, polarity positive to pin A/A1)
7* = Lockable test button + LED + diode
(DC, polarity positive to pin A/A1)
74* = Lockable test button + LED + diode
(DC, polarity positive to pin A/A1) +
mechanical indicator
* Options not available for 220 V DC and
400 V AC versions.
Descriptions: Options and Special versions
C: Option 3, 5, 54
LED (AC)
C: Option 6, 7, 74
LED + diode (DC, polarity
positive to pin A/A1)
B: Contact circuit 5, 6
Additional physical separator
between coil and contacts (for
SELV applications)
Lockable test button and mechanical flag indicator (0040, 0050, 0054, 0070, 0074)
3
1
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly above the test button) remains intact. In this case, when the
test button is pushed, the contacts operate. When the test button is released the contacts return to their
former state.
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition to
the above function), when the test button is pushed and rotated, the contacts are latched in the
operating state, and remain so until the test button is rotated back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
2
4
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Technical data
Insulation according to EN 61810-1
2 CO - 3 CO
Nominal voltage of supply system
V AC
Rated insulation voltage
V AC
Pollution degree
230/400
2 NO - 3 NO
230/400
400
400
3
3
Reinforced
Reinforced
III
III
6
6
4,000
4,000
Insulation between coil and contact set
Type of insulation
Overvoltage category
Rated impulse voltage
kV (1.2/50 µs)
Dielectric strength
V AC
Insulation between adjacent contacts
Type of insulation
Basic
Basic
Overvoltage category
III
III
4
4
2,500
2,500
Micro-disconnection
Full-disconnection
—
III
Rated impulse voltage
kV (1.2/50 µs)
Dielectric strength
V AC
Insulation between open contacts
Type of disconnection
Overvoltage category
Rated impulse voltage
kV (1.2/50 µs)
—
4
1,500/2
2,500/4
Burst (5...50)ns, 5 kHz, on A1 - A2
EN 61000-4-4
level 4 (4 kV)
Surge (1.2/50 µs) on A1 - A2 (differential mode)
EN 61000-4-5
level 4 (4 kV)
1/5 (changeover)
3/— (normally open)
Dielectric strength
V AC/kV (1.2/50 µs)
Conducted disturbance immunity
Other data
Bounce time: NO/NC
ms
Vibration resistance (10…150)Hz: NO/NC
g
Shock resistance
g
20/8
15
2 pole (CO)
Power lost to the environment
3 pole (CO)
2 pole (NO)
3 pole (NO)
without contact current
W
1.3
1.3
3
3
with rated current
W
3.3
4.3
5
6
mm
≥ 5
Recommended distance between relays mounted on PCB
5
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Contact specification
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
DC breaking current (A)
H 62 - Maximum DC1 breaking capacity
Changeover contacts
contacts in series
Voltage DC (V)
H 62 - Maximum DC1 breaking capacity
Normally open contacts
DC breeaking current (A)
Cycles
F 62 - Electrical life (AC) v contact current
contacts in series
Voltage DC (V)
• When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥ 100·103 can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.
Note: the release time of the load will be increased.
6
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Coil specifications
DC version data
Nominal
voltage
UN
V
6
12
24
48
60
110
125
220
Coil
code
9.006
9.012
9.024
9.048
9.060
9.110
9.125
9.220
AC version data
Operating range
Umin
V
4.8
9.6
19.2
38.4
48
88
100
176
Umax
V
6.6
13.2
26.4
52.8
66
121
138
242
Resistance Rated coil
consumption
R
I at UN
Ω
mA
28
214
110
109
445
54
1,770
27
2,760
21.7
9,420
11.7
12,000
10.4
37,300
5.8
Coil
code
9.006
9.012
9.024
9.048
9.060
9.110
9.125
9.220
Operating range
Umin
V
5.1
10.2
20.4
40.8
51
93.5
106
187
Umax
V
6.6
13.2
26.4
52.8
66
121
138
242
Coil
code
8.006
8.012
8.024
8.048
8.060
8.110
8.120
8.230
8.240
8.400
Operating range
Umin
V
4.8
9.6
19.2
38.4
48
88
96
184
192
320
Umax
V
6.6
13.2
26.4
52.8
66
121
132
253
264
440
Resistance Rated coil
consumption
R
I at UN (50Hz)
Ω
mA
4.6
367
19
183
74
90
290
47
450
37
1,600
20
1,940
18.6
7,250
10.5
8,500
9.2
19,800
6
AC (NO/nPST-NO) version data - ≥ 3 mm
DC (NO/nPST-NO) version data - ≥ 3 mm
Nominal
voltage
UN
V
6
12
24
48
60
110
125
220
Nominal
voltage
UN
V
6
12
24
48
60
110
120
230
240
400
Resistance Rated coil
consumption
R
I at UN
Ω
mA
12
500
48
250
192
125
770
63
1,200
50
4,200
26
5,200
24
17,600
12.5
Nominal
voltage
UN
V
6
12
24
48
60
110
120
230
240
400
Coil
code
8.006
8.012
8.024
8.048
8.060
8.110
8.120
8.230
8.240
8.400
Operating range
Umin
V
5.1
10.2
20.4
40.8
51
93.5
106
196
204
340
Umax
V
6.6
13.2
26.4
52.8
66
121
137
253
264
440
Resistance Rated coil
consumption
R
I at UN (50Hz)
Ω
mA
4
540
14
275
62
130
220
70
348
55
1,200
30
1,350
24
5,000
14
6,300
12.5
14,700
7.8
R 62 - DC coil operating range v ambient temperature
Changeover contacts
R 62 - AC coil operating range v ambient temperature
Changeover contacts
R 62 - DC coil operating range v ambient temperature
Normally open contacts
R 62 - AC coil operating range v ambient temperature
Normally open contacts
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
1 - Max. permitted coil voltage.
2 - Min. pick-up voltage with coil at ambient temperature.
7
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Accessories
Mounting adaptor for types 62.3x and 62.8x.xxxx.xxx9 (M4)
062.10
062.10
062.10 with relay
062.10 with relay
062.10
Flange mounting adaptor for types 62.3x and 62.8x.xxxx.xxx9
062.60
062.60
062.60 with relay
062.60 with relay
062.60
Top flange mount for types 62.3x and 62.8x.xxxx.xxx9
062.05
062.05
062.05 with relay
062.05
Top 35 mm rail (EN 60715) mount for types 62.3x and 62.8x.xxxx.xxx9
062.05 with relay
062.07
062.07
062.07 with relay
062.07
062.07 with relay
8
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
62 Series - Power relays 16 A
Accessories
Rear 35 mm rail (EN 60715) mount for types 62.3x and 62.8x.xxxx.xxx9
062.08
062.08
062.08 with relay
062.08
Sheet of marker tags for 62 series relays, plastic, 72 tags, 6x12 mm
062.08 with relay
060.72
060.72
9
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
92 Series - Sockets and accessories for 62 series relays
92.03
Approvals
(according to type):
Screw terminal (Box clamp) socket
panel or 35 mm rail (EN 60715) mount
For relay type
Accessories
Metal retaining clip (supplied with socket - packaging code SMA)
Identification tag
Modules (see table below)
Timer modules (see table below)
Technical data
Rated values
Dielectric strength
Protection category
Ambient temperature
°C
Screw torque
Nm
Wire strip length
mm
Max. wire size for 92.03 socket
mm2
AWG
92.03
Blue
62.32, 62.33
92.03.0
Black
092.71
092.00.2
99.02
86.00, 86.30
16 A - 250 V
6 kV (1.2/50 µs) between coil and contacts
IP 20
–40…+70
0.8
10
solid wire
stranded wire
1x10 / 2x4
1x6 / 2x4
1x8 / 2x12
1x10 / 2x12
86 series timer modules
Multi-voltage: (12…240)V AC/DC;
Multi-functions: AI, DI, SW, BE, CE, DE, EE, FE; (0.05s…100h)
(12…24)V AC/DC; Bi-function: AI, DI; (0.05s…100h)
86.00
86.00.0.240.0000
86.30.0.024.0000
(110...125)V AC; Bi-function: AI, DI; (0.05s…100h)
86.30.8.120.0000
(230...240)V AC; Bi-function: AI, DI; (0.05s…100h)
86.30.8.240.0000
Approvals
(according to type):
86.30
99.02
Approvals
(according to type):
DC Modules with
non-standard polarity
(+A2) on request.
99.02 coil indication and EMC suppression modules for 92.03 socket
Diode (+A1, standard polarity)
(6...220)V DC
LED
(6...24)V DC/AC
LED
(28...60)V DC/AC
LED
(110...240)V DC/AC
LED + Diode (+A1, standard polarity)
(6...24)V DC
LED + Diode (+A1, standard polarity)
(28...60)V DC
LED + Diode (+A1, standard polarity)
(110...220)V DC
LED + Varistor
(6...24)V DC/AC
LED + Varistor
(28...60)V DC/AC
LED + Varistor
(110...240)V DC/AC
RC circuit
(6...24)V DC/AC
RC circuit
(28...60)V DC/AC
RC circuit
(110...240)V DC/AC
Residual current by-pass
(110...240)V AC
99.02.3.000.00
99.02.0.024.59
99.02.0.060.59
99.02.0.230.59
99.02.9.024.99
99.02.9.060.99
99.02.9.220.99
99.02.0.024.98
99.02.0.060.98
99.02.0.230.98
99.02.0.024.09
99.02.0.060.09
99.02.0.230.09
99.02.8.230.07
10
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
92 Series - Sockets and accessories for 62 series relays
92.13
Approvals
(according to type):
PCB socket
For relay type
Accessories
Metal retaining clip (supplied with socket - packaging code SMA)
Technical data
Rated values
Dielectric strength
Ambient temperature
°C
92.13 (blue)
62.32, 62.33
92.13.0 (black)
092.54
10 A - 250 V
2.5 kV AC
–40…+70
62.3x plug on 92.13 is 63.3 mm high
92.33
Approvals
(according to type):
Panel mount solder socket mounted with M3 screw
For relay type
Accessories
Metal retaining clip (supplied with socket - packaging code SMA)
Technical data
Rated values
Dielectric strength
Ambient temperature
°C
92.33 (blue)
62.32, 62.33
092.54
10 A - 250 V
2.5 kV AC
–40…+70
Packaging code
How to code and identify retaining clip and packaging options for sockets.
Example:
9 2 . 0
3
S M
A
A
Standard packaging
SM Metal retaining clip
9 2 . 0
3
Without retaining clip
11
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising