INSTALLATION INSTRUCTIONS
In no event shall Mircom be liable for any direct, indirect or consequential damages,
loss of anticipated profits, loss of time or any other losses incurred by the buyer in connection with the purchase, installation or operation or failure of this product.
Important!
Mircom recommends that the entire system be completely tested on a regular basis.
However, despite frequent testing and due to but not limited to, criminal tampering or
electrical disruption, it is possible for this product to fail to perform as expected.
INSTALLATION INSTRUCTIONS
RM-2200-4 Relay Expander for
FX-2200 Fire Alarm Control Panel
The RM-2200-4 is a four relay expander, connected via ribbon cable to a FX-2200
Main Board. This module occupies one spot of the three available mounting locations
within the FX-2200 cabinet. The RM-2200-4 provides four additional programable
function relays.
Parts List
•
•
•
Qty 1 ... RM-2200-4 module
Qty 4 ... No. 4 screws
Qty 1 ... Ribbon Cable (short)
Installing the RM-2200-4
The RM-2200-4 mounts inside the FX-2200 cabinet to the back plate in one of the
three expander locations.
1. Position the RM-2200-4 in the upper most empty expander module locations.
2. Secure the relay expander to the back plate with the No. 4 screws and lock washers (provided).
3. Connect the ribbon cable from the panel or previous expansion module to CON1
on the Relay Expander.
NOTE: This component must be included in the control panel battery calculation. Refer to the Battery Calculation Sheet included with the control panel.
Relay Circuits are non-supervised. Relays must be connected to a power limited source that is listed Fire Protective Signaling.
LT-2027MIR
Canada
25 Interchange Way
Vaughan, ON, L4K 5W3
Tel: (905) 660-4655
Fax: (905) 660-4113
www.mircom.com
Rev. 0
USA
60 Industrial Parkway PMB 278
Cheektowaga, NY, 14227
Tel: (888) 660-4655
Fax: (888)660-4113
RM-2200-4 Relay Expander
FX-2200 Panel Layout
FRONT PANEL
CON1 IN
BACK PANEL
DACT BD
OR
CITY BD
Normally Off
Equipment
#1- NO
#1 - C
DISPLAY HARNESS
MAIN BD
DISPLAY BD
NAC BD
OR
RELAY BD
CON4
#1 - NC
Normally Off
Equipment
#2- NO
#2 - C
Normally On
Equipment
#2 - NC
Normally Off
Equipment
#3- NO
Relays*
User Equipment
NAC BD
OR RELAY BD
Normally On
Equipment
#3 - C
Normally On
Equipment
#3 - NC
Normally Off
Equipment
#4- NO
#4 - C
Normally On
Equipment
NAC BD
OR
RELAY BD
CON2 OUT
LED DISPLAY
XFORMER
XFORMER
(optional)
T/B
RECTIFIER
BATTERY
BATTERY
(optional)
Figure 1. RM-2200-4 Relay Expander Installation
#4 - NC
* Relays shown in de-energized state.