MODEL: T20004R CLASS CTL DISTRIBUTION /CONTROL PANEL WITH TIME SWITCH

MODEL: T20004R CLASS CTL DISTRIBUTION  /CONTROL PANEL WITH  TIME SWITCH
MODEL: T20004R
CLASS CTL DISTRIBUTION /CONTROL
PANEL WITH TIME SWITCH
LR3730
UL508
UL1563
NEC680
IN RAINPROOF (TYPE 3R) ENCLOSURE FOR INDOOR/OUTDOOR USE.
SUITABLE FOR SWIMMING POOL / SPA APPLICATIONS AND FOR DIRECT CONNECTION TO A WET-NICHE OR NO NICHE LUMINAIRE.
ALL DEIVCES IN THIS CONTROL MUST BE SUPPLIED BY BRANCH CIRCUIT PROTECTORS LOCATED WITHIN THIS ENCLOSURE.
60 AMP 120/240 VOLT OR 120/208 VOLT SINGLE PHASE, (THREE WIRE) AC
The short circuit rating of this panel is 10000 symmetrical amperes.
IMPORTANT:
This control panel must be installed according to the National Electrical Code (including
article 680) or Canadian Electrical Code (including section 68) and local code requirements. This installation is subject to the
approval by the local inspection authority. The main lugs and neutral main are suitable for No. 14 to 2 AWG COPPER conductors. Use No. 14 to 6 AWG COPPER conductors for branch circuit wiring. Follow gauge selection table and
corresponding terminal screw tightening torque requirements below. Install inter-changeable circuit breakers with
an interrupting current rating of 10000 symmetrical amperes, or higher. All circuit breakers in this control panel
shall be of the same manufacturer and type. See list of suitable types below. Follow manufacturers instructions for
installing and testing of ground fault circuit breakers (GFCB) and interrupters (GFCI). Install only LISTED receptacle(s)
and/or wiring device(s) inside the enclosure. A LISTED wiring device may be installed in the rectangular side knockout
provided. When panel is outdoors, a LISTED rainproof cover must be installed over the wiring device in the side knockouts.
If this enclosure is used for direct conduit connection to a wet-niche or no niche luminaire, one of the connection
kits listed below in Note 4 must be used. This control should not be connected to any equipment which would cause
bodily injury or property damage should it be activated unexpectedly. After wiring, install front panel over wiring
compartment and close unused breaker openings with filler plates. KEEP DOOR CLOSED AT ALL TIMES.
WIRING INFORMATION - COPPER CONDUCTORS ONLY
SUITABLE LISTED BREAKERS
TERMINAL TORQUEa
GENERAL
CIRCUIT BREAKER
FILLER
GENERAL PURPOSE
MAX MOTOR PURPOSE BRANCH
MANUFACTURER
STD. TWIN QUAD GFCB
PLATE SUPPLY LINE AND
LOAD
BRANCH CIRCUIT
CROUSE-HINDS
MP
--
-- MP115GF FP-1
WIRE SIZE CIRCUIT NEUTRAL NEUTRAL (CONTINUOUS CIRCUIT MAXIMUM
75˚C MIN BREAKER MAIN
AND
DUTY)
BREAKER CURRENT
CUTLER-HAMMER
BR
--
--
GFCB
FP-1
INSULATION RATING LUGS GROUND 120V. 240V. RATING CAPACITY
G.E.
THQL
--
-- THQLGF THFP
AWG
AMP
LB-IN LB-IN
HP
HP
AMP
AMP
SIEMENS/ITE
QP
--
--
--
QF-3
14
15
35
20
1/2
1
15
12
SQUARE D
HOM HOMT
-- HOM-GFI FP
12
20
35
20
1
2
20
16
THOMAS & BETTS
TB
--
--
GFB
FP
10
8
6
30
50b
60
35
40
45
20
25
35
1 1/2
2
---
3
5
---
30
40
60
24
32
44
NOTES:
1. Any Intermatic T100M or ET100CM series Time Switch PF1000M Series freeze aTORQUE CIRCUIT BREAKER LUGS TO VALUES SPECIFIED ON CIRCUIT BREAKERS
protection or RC2000M Series air switch mechanism may be installed in b45 AMP FOR CANADA.
the bracket provided or in the event an existing mechanism is replaced. .
2. If this control panel requires bonding, attach a LISTED bonding terminal of
a suitable size using the mounting hole(s) provided on the bottom of the
enclosure (156T11047A may be ordered).
TIME SWITCH
3. Wiring devices may be installed in this control panel (order 21T156A (4)
CLOCK
L2
Standoffs for mounting).
MOTOR
4. The following kits are available to connect under water luminaires to
this enclosure:
1/2” non-metallic - order 156PA13713A
3/4” non-metallic - order 156PA13714A
1” non-metallic - order 156PA13715A
1/2” metallic - order 156PA14336A
TIME SWITCH RATINGS: (SPST)
30 AMP, RESISTIVE, INDUCTIVE, TUNGSTEN OR
1000 VA PILOT DUTY - 120/208/240 VOLT A.C.
2 HP (24 FLA)-120 VOLT A.C., 5HP (28 FLA) -24 VOLT A.C.
CLOCK MOTOR: 208/277 VOLTS - 60 HZ.
(to order clock motor replacement, specify part no. WG - on motor cover)
TIME SWITCH OPERATING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES:
Hold TRIPPERS against edge of CLOCK-DIAL,
TIME
POINTER
pointing to time (AM or PM) when ON and OFF
ON
operations are desired. Tighten tripper screws firmly.
TIME
TRIPPER
DIAL
2. TO SET TIME-OF-DAY:
Pull CLOCK-DIAL outward. Turn in either direction
and align the exact time-of-day on the CLOCKOFF
DIAL (the time now, when switch is being put
TRIPPER
into operation) to the pointer.
MANUAL
LEVER
-DO NOT MOVE POINTER• TO OPERATE SWITCH MANUALLY: Move MANUAL-LEVER below left
or right as indicated by arrows. This will not affect the next operation.
• FOR MORE THAN ONE DAILY ON-OFF OPERATION: Place additional
tripper pairs on CLOCK-DIAL (order 156T1978A).
• IN CASE OF POWER FAILURE: Reset CLOCK-DIAL to proper time of
day. See step 2 above.
L1
RAINPROOF
COVER
N
TO
LOAD
EQUIPMENT GROUND
OPTIONAL
SWITCH
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
154--00520