ASCO 7000 Series ATS Brochure
ᓼ
ASCO 7000 S ERIES
Critical Loads Demand ASCO
Healthcare Facilities
Commercial Buildings / Industrial Buildings
Web Hosting, Internet Data Centers
Telecom Central Offices
Process Manufacturing / Wafer Fabrication Plants /
Distributed Power / Load Management
As we become more dependent on the quality and reliability of electrical power, interruption or complete loss of
power can create serious and
even crippling financial losses,
or impose dangers to life and
safety.
ASCO Power Technologies
(ASCO) provides the solutions
to handle the transfer of
critical loads to emergency
sources reliably and with state
of the art products. Using
ASCO products can mean the
difference between a minor
inconvenience and a major
catastrophe. You’ll find ASCO
Power Transfer Switches
wherever there is a critical
load to be protected.
2
When flexibility in power
switching is a must, ASCO
offers a variety of product
solutions to meet virtually
every application requirement, including distributed
generation applications.
That’s why the 7000 SERIES
is available in open, delayed,
closed and closed soft load
configurations. Additionally,
switched or overlapping
neutral options provide for
reliable operation of ground
fault protection systems and
reduction of voltage transients from unbalanced load
switching.
ASCO Power Transfer Switches
are the first CE Marked, IEC
60947-6-1 compliant Transfer
Switches in the world.
ASCO
ᓼ
The Recognized Leader in Power Transfer Switch Technology
Offers the Most Advanced Transfer Switches in the World.
7000 SERIES
ASCO Power Transfer Switches are the standard of the
industry. High speed transfer of loads between alternate sources of power, regardless of ampacity size, is
achieved by a reliable, field proven solenoid operating
mechanism. When combined with a programmable
microprocessor controller with keypad and LCD display,
they offer the most advanced method of transferring all
types of loads, such as motors, electronic drives, UPSs
and microprocessor based systems. 7000 SERIES Power
Transfer Switches are available open or enclosed, in
ampacity sizes from 30 through 4000 amperes with the
largest selection of optional accessories offered anywhere. All switching configurations are available with an
integrally mounted bypass-isolation switch and/or rated
for use in service entrance applications.
Fig. 1: Three Pole 7000 SERIES Automatic Transfer Switch
rated 1600 amperes (shown with optional front
connected terminals and Power Manager).
7000 SERIES Power Transfer Switches
Product Features
• Conventional two-position transfer configuration,
plus closed and delayed transition modes of operation.
All configurations available with either automatic or nonautomatic control.
• UL listed to 1008 Transfer Switch Equipment &
CSA certified to CSA 22.2 No.178-1978 Automatic
Transfer Switches.
• Qualified and certified to IEC 60947-6-1, CE marked
(optional). (Limited to certain accessories.)
• Rated up to 600 VAC, 30 through 4000 amperes.
• Reliable and field proven solenoid operating mechanism.
• High withstand and close-on ratings including short time
withstand current rating for optimum flexibility in circuit
breaker coordination (600-4000 amperes).
• Solid, switched, or overlapping neutral conductor options.
• Front replaceable main and arcing contacts (800-4000 amperes).
• Programmable microprocessor controller with keypad and
LCD display.
• Centrally located terminal block for customer control
connections (260-4000 amperes).
• 16mm, industrial grade control switches and indicating lights.
• Switch position LED indicators and source acceptability lights.
• Standard ground conductor connections.
• Four auxiliary contacts, two contacts closed when switch
is in normal position and two contacts closed when switch
is in emergency position.
• Local/remote communications capability for interfacing
with ASCO PowerQuest ® or SiteWeb® communication
products.
3
ASCO
ᓼ
7000 SERIES Power Switching Solutions
Closed Transition Transfer Switching
ASCO Automatic Closed Transition Transfer Switches feature
main contacts that overlap, permitting the transfer of electrical
loads without power interruption. The switch transfers in a
make-before-break mode if both sources are within acceptable
parameters. Control logic continuously monitors source
conditions and automatically determines whether the load
transfer should be open (conventional non-overlap mode) or
closed transition. Available 150 through 4000 amperes.
Closed Transition Transfer within 5 electrical degrees is achieved
passively, without control of engine generator set. Therefore, no
additional control wire runs are required between the ATS and
engine generator set governor. Plus, protective relaying may
not be required under normal operation since the contact overlap time is less than 100 milliseconds (consult your local utility
on protective relay requirements).
Failure to synchronize indication and extended parallel time
protection is built-in to all 7000 SERIES closed transition
controls to prevent abnormal operation.
Fig. 2: Four pole, Closed Transition Transfer Switch
rated 1000 amperes in Type 1 enclosure.
Delayed Transition Transfer Switching
ASCO Delayed Transition Transfer Switches are designed to
provide transfer of loads between power sources with a
timed load disconnect position for an adjustable period of
time. Applications include older style variable frequency
drives, rectifier banks, and load management applications.
• Available 150 through 4000 amperes.
• Utilizes reliable, field proven solenoid operating
mechanisms.
• Mechanical interlocks to prevent direct connection of both
sources.
• Indicator light (16mm, industrial grade
type LED) for load disconnect position.
• Adjustable time delay for load disconnect position.
Fig. 3: Four pole, Delayed Transition
Transfer Switch rated 2000 amperes.
4
ASCO
ᓼ
7000 SERIES Power Switching Solutions
Non-Automatic Transfer Switching
ASCO Non-Automatic Transfer Switches are electrically
operated units which are operated with manual control
switches mounted locally or at remote locations.
• Sizes from 30 through 4000 amperes.
• Microprocessor based controller provides for addition
of optional accessories.
• Controller prevents inadvertent operation under low
voltage conditions.
• Low control circuit operating currents allow for long
line runs between remotely mounted manual control
switches and the transfer switch.
• Source acceptability lights inform operator if sources
are available to accept load.
• Standard inphase monitor can be activated for
transferring motor loads.
Fig. 4: Three pole Non-Automatic,
electrically operated 400 ampere switch
shown in Type 1 enclosure.
Withstand and Close-On Ratings for all 7000 SERIES Products(1)(2)
Switch Rating (Amps)
Transfer
Switches
UL 1008 Withstand and Close-On Ratings
Max. Fuse
Type
Short Time Short Time
Specific Breaker “Any” Breaker Withstand Duration
Ratings(4)
(Cycles)
Rating
(3) Rating
Tested
Voltages
Bypass Switches
Current - Limiting
Fuse Rating
amps
types
30
-
100,000
60
J
10,000
10,000
N/A
-
480V
70, 100, 125,
-
200,000
200
J
22,000
10,000
N/A
-
480V
150, 200
-
230
-
100,000
300
J
22,000
10,000
N/A
-
480V
150, 260, 400
200,000
600
J
42,000
35,000
N/A
-
600V
200,000
800
L
200,000
600
J
50,000
35,000
N/A
-
480V
200,000
800
L
200,000
600
J
65,000
65,000
N/A
-
240V
200,000
800
L
200,000
1600
L
65,000
50,000
36,0005
18
600V
100,000
65,000
30
600V
100,000
100,000
65,000
30
600V
65,000
30
480V
260, 400, 600
260, 400, 600
260, 400, 600
800, 1000, 1200
600, 800 1000,
1200
1600, 20005
1600, 20006
200,000
3000
L
100,000
3000
3000
100,000
4000
4000
6000
L
4000
200,000
200,000
L
100,000
Notes: 1) All values are available symmetrical RMS amperes and tested in accordance with the withstand and close-on requirements of UL 1008.
See publication 1128 for more information on withstand and close-on ratings for ASCO transfer switches.
2) Application requirements may permit higher withstand ratings for certain size switches. Contact ASCO for guidance if available short circuit current exceeds the WCR
ratings shown.
3) “Any” breaker ratings are based on 1.5 cycles for 30 - 230 amp & 3 cycles for 260 - 4000 amps. Applicable to breakers with instantaneous trip elements.
4) Short time ratings are provided for applications involving breakers that do not have instantaneous trips for system coordination.
5) Short time rating applicable to transfer switch design only.
6) Optional front connected service limited to 85,000 amps for specific and any breaker rating.
5
ASCO
ᓼ
7000 SERIES Power Switching Solutions
Automatic Transfer Bypass-Isolation Switching
ASCO Automatic Transfer & Bypass-Isolation Switches are available in
open transition, closed transition and delayed transition designs. The
bypass and isolation features allow power transfer switches to
be inspected, tested, and maintained without any interruption of
power to the load.
• Available 150 to 4000 amperes.
• Allows bypass-isolation without load interruption.
• Bypass switch and transfer switch have identical electrical ratings.
• Heavy duty mechanical interlocks prevent undesirable operation.
• Bypass contacts carry current only during bypass mode.
• Transfer switch is drawout design for ease of maintenance.
• Bypass and isolation handles are permanently mounted. The bypass
switch has dead front quick-make, quick-break operation for
transferring of loads between live sources.
• Bypass switch is fully rated for use as a manual 3-position
transfer switch.
• Bypass and isolation functions are simple, requiring a total of two
operating handles.
• No toggle switches, push buttons, selector switches or levers are
required for bypass-isolation operation.
Fig. 5: Three Pole 7000 SERIES Automatic BypassIsolation Transfer Switch Rated 1000 Amps
• Mechanical indicators show bypass and transfer switch positions.
• 600 -1200 ampere available in shallow depth, front connected or
rear connected designs.
Transfer Switch Drawout Features (600-3000 amperes)
Automatic
Secondary
Disconnects
Automatic
Shutters
(optional)
Fig. 6: Bypass-Isolation Transfer
Switch secondary disconnects and
optional automatic shutters.
6
• Automatic secondary disconnects
remove all control power as switch is
withdrawn.
• Drawout carriage provides for easy
transfer switch maintenance and/or
removal via commercially available
breaker hoists.
Self
Aligning
Jaws
• For optional transfer switch lifting yoke,
specify accessory 82B.
• For optional automatic shutters which
close when the transfer switch is
withdrawn to provide bus isolation,
specify accessory 82C.(1000-3000A
only)
Fig. 7: Bypass-Isolation
Transfer Switch self
aligning power jaws.
ASCO
ᓼ
7000 SERIES Power Switching Solutions
Bypass and Isolation Handles - Simple as 1, 2, 3
LED Indicators
Bypass switch
position
Source
availability
1
Bypass to Normal
Push in bypass
handle and turn
it counter
clockwise
Bypass Switch
Bypass Handle
Transfer
switch
position
Isolation
handle
position
E
L
Isolation Handle
N
Not in
“auto”
flashing
LED
Automatic Transfer Switch
2
Fig. 8: Transfer Bypass
Status Panel
Test Position
Bypass Switch
E
L
Isolation Handle
Mechanical
bypass
switch position
flags
Turn isolation
handle counter
clockwise until
window shows
“Test”
3
N
Automatic Transfer Switch
Isolation Position
Bypass Switch
Isolation
handle
Padlocking
provisions
Mechanical isolation handle position
window (connected/test/isolate)
Fig. 9: Bypass-Isolation
Switch user interface
E
L
Isolation Handle
Turn isolation
handle counter
clockwise
until window
shows “Isolate”
N
Automatic Transfer Switch
Key:
Represents Current Flow
In test position control panel remains
energized to allow for electrical
operation of a transfer switch.
7
ASCO
ᓼ
7000 SERIES Service Entrance Power Transfer Switches
The ASCO Service Entrance Power Transfer Switch
combines automatic power switching with a disconnect and overcurrent protective device on the utility
source. The power transfer switch meets all National
Electric Code requirements for installation at a facility’s main utility service entrance. Service entrance
rated transfer switches generally are installed at
facilities that have a single utility feed and a single
emergency power source. A circuit breaker serves as
the utility disconnect and links are provided to disconnect both neutral and ground connections.
This product is UL 1008 and UL 891 listed and is
available up to 600V and 4000A in Standard, Delayed,
Closed Transition, Soft Load, and Bypass Isolation
Configurations.
Fig. 10: Ground and neutral
disconnect links
Standard Features
• Available from 150 to 4000 amperes
• ASCO 7000 SERIES Power Transfer Switch,
UL 1008 Listed
• Standard UL Type 1 Enclosure
• Disconnect and overcurrent protective device on
the utility source: molded case circuit breaker 150
to 2000 Amp; insulated case 3000 to 4000 Amp
• Disconnect link on Neutral
• Disconnect link on Ground
• Ground and Neutral Bus, all silver-plated copper
• Solderless screw type terminals for External
Power Connections
• Labeled UL 891, meets all NEC requirements for
service entrance
• Internet Enabled Command and control available
with optional ASCO 5500 SERIES Thin Web Server
Ground Disconnect
Link
Circuit
Breaker
Neutral
Disconnect
Link
Load
Utility
N
Ground Fault
Current
Transformer*
Switched
Neutral
Ø
ATS
GFCT Ground Fault
Current
Transformer
ATS - Automatic Transfer
Switch
Ø
N
Emergency
One line diagram of a typical service entrance rated transfer switch
available in Solid, Switched or Overlapping Neutral
* Ground fault trip protection provided on sizes of 1000 amperes
and above
Optional Features
• Enclosures - Secure Double Door
UL Type 3R w/strip heater & thermostat
UL Type 4 or 4X
UL Type 12
• Connections
Crimp lugs
Bus Riser on Normal, Emergency or Load
• Protective Relays/Metering
Accessory 85L , see page 15
• Surge Suppression
Accessory 73, 80KA Surge protector (see pg. 14)
• Communications
ASCO 72A Communication interface module
ASCO PowerQuest ®, see page 18
ASCO 5500 SERIES Thin Web Server for internet
connection , see page 21
• Additional Breaker(s)
Circuit Breaker on Emergency
Load Distribution Panel
• Optional high AIC ratings on breakers
Consult ASCO for additional features
8
ASCO
ᓼ
7000 SERIES Service Entrance Power Transfer Switches
Ordering Information
To order an ASCO 7000 SERIES Service Entrance Power Transfer Switch, complete the following catalog number.
7
A
US
+
Automatic
US
N
NonAutomatic
UB
CUS
CUB
DUS
DUB
+
Neutral
Code*
Product
A
A
Conventional
2-Position
Open
Transition
Bypass
Closed
Transition
Closed
Transition
Bypass
Delayed
Transition
Delayed
Transition
Bypass
3
+
Phase
Poles
A Solid Neutral
(standard)
B Switched
Neutral
C Overlapping
Neutral
2
3
400
Amperes
70
100
150
200
225
250
400
600
800
1000
1200
1600
2000
3000
4000
+
N
+ 5X
Voltage
Code
C
D
E
F
H
J
K
L
M
N
P
Q
R
208
220
230
240
380
400
415
440
460
480
550
575
600
+
C
Grp
Code
Enclosure
5
5Xoptional
accessories
C Type 1 enclosure
M Type 3R secure
double door
N Type 4 secure
double door
P Type 4X secure
double door
Q Type 12 secure
double door
*Note. Switches rated 150, 600-3000 amps available with 2, 3 or either conventional switched neutral (4 poles) or overlapping neutral (optional). For 4 pole
applications on switches rates 150 to 400 amps (bypass switches only) and 4000 amps specify overlapping switched neutral (optional). Conventional switched neutral
is provided on delayed transition transfer products when specified.
The Example Catalog Number above is 7AUSA3400N5XC (X is used to specify optional accessories).
Dimensions and Weights for non-bypass configurations
only in type 1 enclosures.*
Switch Rating
Depth
Height
Width
Weight
amps
inches (mm) inches (mm) inches (mm) lbs (kg)
Ampere Interrupting Capacity
(AIC) Ratings
70 - 225
36.5 (927)
48.5 (1232)
13.25 (337)
408 (188)
250, 400
36.5 (927)
48.5 (1232)
13.25 (337)
408 (188)
600, 800
38 (965)
91 (2311)
28 (711)
820 (378)
1000-1200
38 (965)
91 (2311)
48 (1219)
1105 (510)
1600, 2000
38 (965)
91 (2311)
48 (1219)
2590 (1198)
70 - 225
25
35
3000
38 (965)
91 (2311)
72 (1829)
4590 (2148)
250
25
35
4000
46 (1168)
91 (2311)
72 (1829)
5640 (2609)
400
35
35
600, 800
65
N/A
1000,1200
65
N/A
1600, 2000
65
100
3000
100
N/A
4000
100
N/A
Dimensions and Weights for non-bypass configurations
only in type 3R enclosures.*
Switch Rating
Depth
Height
Width
Weight
amps
inches (mm) inches (mm) inches (mm) lbs (kg)
AIC Rating (kA)
Switch Rating
amps
Standard Standard
70 - 225
36.5 (927)
48.5 (1232)
13.25 (337)
408 (188)
250, 400
36.5 (927)
48.5 (1232)
13.25 (337)
408 (188)
600, 800
38 (965)
91 (2311)
28 (711)
820 (378)
1000-1200
38 (965)
91 (2311)
48 (1219)
1105 (510)
1600, 2000
38 (965)
91 (2311)
48 (1219)
2590 (1198)
3000
38 (965)
91 (2311)
72 (1829)
4590 (2148)
*All dimensions and weights shown are approximate and
4000
46 (1168)
91 (2311)
72 (1829)
5640 (2609)
should not be used for construction purposes. Certified
dimensions can be furnished upon request.
9
ASCO
ᓼ
7000 SERIES Microprocessor Controller
The 7000 SERIES Microprocessor Based Controller is used with all sizes of Power
Transfer Switches from 30 through 4000 amperes. It represents the most advanced
digital controller in the industry and includes, as standard, all of the voltage,
frequency, control, timing and diagnostic functions required for most emergency
and standby power applications.
Because of severe voltage transients frequently encountered with industrial
distribution systems, the microprocessor logic board is separated and isolated from
the power board as shown below. This improves electrical noise immunity performance and helps assure compliance with the rigorous transient suppression standards
highlighted below.
Fig. 11: 7000 SERIES
Microprocessor Controller.
Fig.12: Microprocessor Power and Logic PC Boards.
7000 SERIES Microprocessor Based Controller
Emission Standard - Group 1, Class A
Generic Immunity Standard, from which:
Electrostatic Discharge (ESD) Immunity
Radiated Electromagnetic Field Immunity
Electrical Fast Transient (EFT) Immunity
Surge Transient Immunity
Conducted Radio-Frequency Field Immunity
Voltage Dips, Interruptions and Variations Immunity
10
EN 55011:1991
EN 50082-2:1995
EN 61000-4-2:1995
ENV 50140:1993
EN 61000-4-4:1995
EN 61000-4-5:1995
EN 61000-4-6:1996
EN 61000-4-11:1994
ASCO
ᓼ
7000 SERIES Microprocessor Controller
Features
• Digital microprocessor.
• Touch pad programming of features and settings
without the need for meters, or variable power supplies.
• Password protection to prevent unauthorized tampering
of settings.
• Sixteen (16) selectable operating voltages available in a
single Controller.
• Remote monitoring and control with ASCO
PowerQuest ® and SiteWeb™ communications
products. Specify optional accessory 72A or 72E.
• On-board diagnostics provide control panel and ATS status information to analyze system performance.
• Load shed option for SYNCHROPOWER® bus
optimization applications. Specify optional accessory 30B.
• Displays and counts down active timing functions.
• Historical event log
• Selectable multi-language display
(English, German, Portuguese, Spanish, or French. For
others contact ASCO).
• Statistical ATS systems monitoring information
Voltage and Frequency Sensing
Time Delays
• 3-Phase under and over voltage settings on normal
and emergency sources.
• Engine start time delay - delays engine starting signal to
override momentary normal source outages - adjustable
0 to 6 seconds.
• Under and over frequency settings on normal and
emergency.
• True RMS Voltage Sensing with +/- 1% accuracy;
Frequency Sensing Accuracy is +/- 0.2%.
• Transfer to emergency time delay - adjustable 0 to 60
minutes.
• Selectable settings: single or three phase voltage
sensing on normal and emergency; 50 or 60Hz.
• Emergency source stabilization time delay to ignore
momentary transients during initial generator set
loading - adjustable 0 to 6 seconds.
• Phase sequence sensing for phase sensitive loads.
• Retransfer to normal time delay with two settings:
• Voltage unbalance detection between phases.
• Power failure mode - 0 to 60 minutes.
• Test mode - 0 to 60 minutes.
Status and Control Features
• Output contact (N/O or N/C) for engine-start signals.
• Selection between “commit/no-commit” on transfer
to emergency after engine start and normal restores
before transfer.
• Advanced inphase algorithm which automatically
measures the frequency difference between the two sources and
initiates transfer at appropriate phase angles to minimize
disturbances when transferring motor loads.
• Unloaded running time delay for engine cooldown adjustable 0 to 60 minutes.
• Pre and post transfer signal time delay for selective
load disconnect with a programmable bypass on source
failures - adjustable 0 to 5 minutes. This signal can be
used to drive a customer furnished relay, or for (2) sets of
double throw contacts rated 3 amps at 480 volts AC,
specify ASCO optional accessory 31Z.
• Event log displays 99 logged events with the time and
date of the event, event type and event reason.
• Fully programmable engine exerciser with seven
independent routines to exercise the engine generator,
with or without loads, on a daily, weekly, bi-weekly or
monthly basis.
• Output signals for remote indication of normal and emergency source acceptability
• Contains all alarm signals, logic and time delays for
use with closed transition switches.
• Statistical ATS/System monitoring data screens which provide:
• Insynch time delay - 0 to 3 seconds.
• Total number of ATS transfers.
• Failure to synchronize - 1 to 5 minutes.
• Number of ATS transfers caused by power source failure.
• Extended parallel - 0.1 to 1.0 seconds.
• Total number of days ATS has been in operation.
• Total number of hours that the normal and emergency
sources have been available.
• Delayed transition load disconnect time delay adjustable 0 to 5 minutes.
11
ASCO
ᓼ
7000 SERIES User Controls and Indicators
Control Switches and Indicating Lights for Conventional 2-Position Switches
• Switch position indicating lights (16 mm, industrial grade LEDs).
• Source acceptability indicating lights with true indication of the
acceptability of each source, as determined by the voltage, frequency,
voltage unbalance, and phase sequence settings of the control panel
(16mm, industrial grade LEDs).
• Three position (16mm, industrial grade type) selector switch:
• Automatic: Normal maintained position.
• Test: Momentary position to simulate normal source failure for
system test function.
Fig. 13: 7000 SERIES User Controls and Indicators.
• Reset Delay Bypass: Momentary position to bypass transfer and
re-transfer time delay.
Control Switches and Indicating Lights for Closed Transition Switches
• Extended Parallel Time - Provides visual indication when the
pre-set extended parallel time has been exceeded. The controls
automatically open the emergency or normal main contacts.
Separate contact also available to shunt trip external breaker.
• Failure To Synchronize - Visually displays a failure to synchronize
alarm if the time delay settings is exceeded, during closed
transition transfer operation.
• TS Locked Out - Prevents transfer in either direction if the
extended parallel time is exceeded.
• Alarm Reset - Resets extended parallel and failure to
synchronize alarms.
Fig. 14: 7000 SERIES User Controls and Indicators.
• Closed Transition Bypass - Pushbutton allows transfer between
sources in an open transition mode.
7000 SERIES Power Control Center
The 7000 SERIES microprocessor controller is a Power Control Center which
allows the user to easily access detailed information on: system status; power
source parameters; voltage, frequency and time delay settings; optional
feature settings; historical event log; and system diagnostics. A four line, (20)
character LCD has a backlit display which enables easy viewing under all
conditions. The user can navigate through all screens using only six buttons,
which also allows selection of: (18) different source parameter settings; (16)
standard time delays; (12) standard feature settings; up to seven independent
engine exercise routines; and even the language (English, German, Spanish,
French, etc.) which appears on the display.
Since the Power Control Center must be visible and operable through
the enclosure door, it has been qualified for use in industrial and outdoor
applications. This includes installation in Type 3R (outdoor/rainproof),
4 (weatherproof) and 12 (indoor/industrial) enclosures.
Fig. 15: 7000 SERIES
Power Control Center.
12
ASCO
ᓼ
7000 SERIES Power Control Center Screens
Status
System Status
Normal OK
Load on Normal
Displays system status in clear, concise language.
Message shown indicates normal source is acceptable
and the load is connected to the normal source.
Source Status
Normal Source
Vab=480V....................ABC
Vbc=480V.........Vunbal=1%
Vca=480V................60.0Hz
Displays voltage for each phase, frequency,
phase rotation and voltage unbalance for both
normal and emergency sources.
Time Delay Status
Inphase Transfer Mode
Normal OK
Emerg OK
TD.Engine.Cooldown:
4min15s
Waiting for In-Sync
-45o 0.02Hz
Active time delay status displays time
remaining until next control event.
Displays the relative phase angle between
sources and frequency differential to indicate
the controller is awaiting an inphase condition.
Settings
Voltage and Frequency Settings
Time Delay Settings
Normal Voltage
Dropout.............85%.408V
Pickup...............90%.432V
O.V. Trip.........110%.528V
TD N>E Xfer Signal
Bypass if N Fail: No
Pre Xfer: 0 min 20S
Post Xfer: 0 min 20S
Provides voltage and frequency setting values for
normal and emergency sources. Voltage pick-up,
dropout and trip settings are set in percentage of nominal
voltage and are also displayed in rms voltage values.
Engine Exerciser
P1..................Engine.Exerciser
Enable:.....Yes....WLoad:....Yes
Start:19h30. ALL MON
Run.Time:...............2h15min
Seven independent programs, load/no load
selection, flexible run times and daily, weekly,
bi-weekly and monthly exercise routines.
Provides direct reading display for setting time delays.
Feature Settings
Shed Load
Direction:
Inphase: No
From E
TD/0.25
Standard features can be activated with the keypad. As an
example, when enabled, the “shed load” option causes the
transfer switch to transfer the load off of the specified source.
If desired, the load shed transfer can be made inphase.
Data Logging
ATS Statistics
ATS Statistics
ATS Total Xfers: 46
SRC Fail Tot Xfers: 20
Days Energized: 36.5
Instant availability of statistical information on total number of
ATS transfers, number of transfers caused by power failures and
total days controller has been energized, plus more.
Historical Event Log
16.AUG02/95..........13h10:17
Eng.Start...............NormFail.
15.AUG02/95...........13h10:25
Xfer.N>E................................
Displays detailed information for last 99 events,
including time of occurrence, length of event,
date and reason for event.
13
ASCO
ᓼ
7000 SERIES Optional Accessories
Time Delays
Neutral Conductor Options
2C
• Solid neutral, with fully-rated terminals. (AL-CU) UL Listed.
1G
Provides an extended time delay on engine starting.
The standard feature one time delay is adjustable
from zero to six seconds. Accessory 2C allows this
time delay to be adjustable from zero to sixty minutes
in one second intervals factory set at five minutes.
Similar to accessory 2C except using 24 volt DC
external input signal. 7000 SERIES controller remains
active when both power sources are de-energized
Manual Controls for Automatic
Transfer Switches
6C
6D
Reset switch for manual retransfer to normal with
automatic retransfer in the event of emergency
source failure.
Selector switch for automatic/manual retransfer to
normal. Automatic bypass if emergency fails.
Engine Generator Controls
and Accessories
12
Three position engine control selector switch.
Positions: 1- Stop 2- Automatic 3 - Engine Test
Note: Switches with accessory 12 must be labeled as a non-automatic
transfer switch according to UL 1008.
Engine controls containing “engine stop” positions should be located at the engine
generator. (Consult ASCO for application assistance.)
Indicators
14A/14B Additional auxiliary contact sets to indicate switch
position. Two sets are standard. Specify total number of sets if more are required.
18B
Two-pole, double-throw contacts operate when
emergency source voltage is present at transfer
switch terminals.
18G
Two-pole, double-throw contacts operate when normal
source voltage is present at transfer switch terminals.
99
“Push-to-Test” feature on all pilot light indicators.
Customer Control Circuits
• Conventional neutral switching pole.
• Overlapping neutral transfer contacts. Allows for proper
ground-fault sensing and avoids generator voltage
transients during transfer.
Note: Specify neutral option in catalog number, see page 21 for instructions.
Extension Harness
37B
Six foot (6’) extension harness to increase distance between
transfer switch and control panel on open-type units.
Analog Load Metering Options
23B
Three phase ammeter with selector switch
(with current transformers and shorting blocks).
24B
Three phase voltmeter with selector switch.
Note: Refer to ASCO 5200 SERIES Power Manager on page 15 which provides
voltage, frequency and power monitoring.
Serial Communications
72A
72E
Serial communication module for remote
communications to ASCO PowerQuest® products.
Connectivity module for remote communications
using ethernet TCP/IP networks
Surge Protection
ASCO Pulsar 450 rated 40KA
73AC1
73AC2
73AC3
Normal source protection. (3Ø, 4wire WYE)
Emergency source protection. (3Ø, 4wire WYE)
Load side protection. (3Ø, 4wire WYE)
Note: Other distribution voltages available (Contact ASCO).
Special Applications
111A Generator - to - Generator for Standby Applications
111B Generator - to - Generator for Prime Power
Applications
Bypass Isolation Switch Options
14A1
Auy contact to close in “Bypass to Normal” position.
14B1
Auxiliary contact to close in “Bypass to Emergency” position.
30A
Load-shedding circuit initiated by opening of a
customer-supplied contact.
14T
Auxiliary contact to close when transfer switch is in
“Automatic” position.
30B*
Load-shedding circuit initiated by removal of
customer-supplied control voltage. *(Specify voltage).
14U
Auxiliary contact to close when transfer switch is in
“Isolate” position.
31Z
Selective load disconnect control contacts (two
provided) which operate with time delay prior to
and/or after load transfer and retransfer.
14V
43R
Terminal block for all customer control connections
on 30-150 amp only (standard on all other sizes).
Auxiliary; contact to close when transfer switch is in
“Test” position.
Lifting yoke for transition switch removal on 6003000 amp.*
Automatic shutters for bus isolation when transfer
switch is withdrawn.*
* see page 6 for details
Note: An externally operable quick-make, quick-break (QMQB), manual handle is available on some 7000 SERIES product configurations. (Consult ASCO for guidance.)
14
82B
82C
ASCO
ᓼ
7000 SERIES Optional Accessories
ASCOᓼ 5200 SERIES
POWER SYSTEM TOTAL
404 KW
+1.00 PF
0 KVAR
60.00 Hz
404 KVA
ATSºn NORM
Power Manager
The ASCO 5200 SERIES Power Manager is a microprocessor
based metering device that provides real-time measurements of single and three phase power systems. The
Power Manager uses digital signal processing technology
to measure voltage and current per phase; real, reactive
and apparent power, and bi-directional energy. All measurements can be viewed locally with a backlit liquid crystal
display and/or displayed remotely with ASCO
PowerQuest ® or SiteWeb® products.
Direct voltage input for systems up to 600 Volts AC
can be monitored without the use of external potential
transformers (PTs). Measures three phase currents and a
fourth current input is available for measuring current
in the neutral conductor. The Power Manager includes
one discrete input for transfer switch position, eight
general purpose discrete inputs, and four relay outputs
for monitoring and controlling external devices.
Fig. 16: ASCO 5200 SERIES Power Manager.
Configurable Designations
• Local - A four line, 20 character LCD backlit display.
• Remote - Integrated 4 wire RS485 port; optional 5110 Serial
Module (72A) or 5150 Communications Module (72E) and
power manager monitoring systems.
• Frequency: 45.0 to 66.0 Hertz
• Provides user programmable setpoints based on twelve metering and I/O parameters. Each setpoint allows the user to select
the parameter, the trip & reset levels, the trip & reset time
delays and the alarm type or relay output to trigger. This can be
used for protective relaying and peak shaving applications.
• 100 event data logging feature.
• Current: IA, IB, IC, IAVERAGE
Integrated ATS Features
• Unbalance %: Voltage, Amps
When configured on load of ATS:
Power Metering
• Voltage:
Line - Line: VAB, VBC, VCA, VAVERAGE
Line - Neutral: VAN, VBN, VCN, VAVERAGE
• Real Power: KWA, KWB, KWC, KWNET
• Displays ATS position.
• Reactive Power: KVARA, KVARB, KVARC, KVARNET
• Displays power data as a function of ATS position
(normal/emergency).
• Apparent Power: KVAA, KVAB, KVAC, KVANET
• Real Energy: KWHIMPORT, KWHEXPORT, KWHNET
• Reactive Energy: KVARHIMPORT, KVARHEXPORT,
KVARHNET
• Power Factor: PFA, PFB, PFC, PFNET
Data Access
• Eight digital inputs, four relay outputs.
• Input/Output 15-character, user definable screen
display for identification of input/output signals.
Communications
• Accumulates energy data separately for normal and
emergency sources.
Optional Configurations and
Connection Arrangements
Connected To:
Load
Normal
Emergency
Load (BPS only)
With Display
Acc. 85L
Acc. 85N
Acc. 85M
Acc. 85R*
Without Display
Acc. 75L
Acc. 75N
Acc. 75M
Acc. 75R*
• RS485 (2) or (4) wire serial capability.
Add suffix “A” to above designations if neutral conductor monitoring is required.
• Includes Modbus RTU.
Note: Accessory 75 and 85 includes component mounting, CTs, shorting
blocks and all necessary interwiring.
• Ethernet compatible when combined with
5150 Connectivity Module (72E).
*Bypass & isolation switch contacts wired to discrete Power Manager
inputs.
Note: The ASCO Power Manager is also available as a separate unit for monitoring electrical parameters anywhere in the power distribution system.
15
ASCO
ᓼ
7000 SERIES Power Monitoring & Control
ASCO Connectivity Solutions
ASCO PowerQuest ® and SiteWeb ® communications products allow for the monitoring and control of
power transfer switches in your Emergency or Standby Power Distribution System. Local Area networks
and Remote networks are supported with either single or multiple points of access, and web-enabled
communications allow access to your power system from anywhere around the world.
Features
• Monitors and controls Power Transfer Switches and Engine Generators
• Monitors normal and emergency voltages and frequency
• Indicates transfer switch position and source availability
• Provides transfer and re-transfer of loads for system testing
• View normal and emergency voltage and frequency settings
• View transfer switch time-delay settings
• Provides transfer switch rating and identification
• Automatic paging notifies personnel, by e-mail or text message, of selected system alarms
• View current, power and power factor with ASCO Power Managers Connected to the System
• View transfer switch event log
• Provides transfer switch test schedule
®
Typical Network Connection
ASCO 5110 (72A) Serial Modules
Dial - Up
ASCO 5200
Power
Manager
ASCO 5100
Telephone
Interface
Module
To Additional
Automatic
Transfer
Switches
Generator
ASCO
ATS 1
ASCO
PowerQuest ®
VPi 32.15
Software
ASCO 5110 (72A) Serial Modules
Serial
RS-485
ASCO 5200
Power Manager
To Additional
Automatic
Transfer
Switches
Generator
ASCO
ATS 1
16
ASCO
ATS 2
ASCO
ATS 2
ASCO
ᓼ
7000 SERIES Power Monitoring
PowerQuest ® is a PC based software package. When combined with the ASCO 5110 Serial Module (Acc 72A), the ASCO 5120
Telephone Interface Module and ASCO 5200 SERIES Power Manager provide the most economical communication system for
monitoring and control of power transfer switches and engine generators.
The local RS-485 network allows communications with up to 32 power transfer switches and four engine generators. An
analog phone connection and ASCO telephone interface module allow for direct dial up, monitoring and control of remote
locations. The ASCO Power Manager not only allows you to view current power and power factor readings, but also has a
programmable KW set point to initiate transfer of loads to a standby source for peak shaving operations.
5110 Serial Module
The 5110 Serial Module is used to allow local or remote communications with ASCO
PowerQuest ® or SiteWeb® communication products.
The module is used to connect the 7000 SERIES transfer switches to a serial network
via an RS-485 interface. The module has two port connectors used for ATS & Power
Manager connectivity.
The serial connection is accomplished from a 5-pin terminal header/socket block.
RS- 485 serial networks allow for up to 32 modules to be set up in a daisy chain
configuration to connect to PowerQuest ® or SiteWeb® systems.
Fig. 17: Serial
Module 72A
5150 Connectivity Module
The 5150 Connectivity Module is used to bring several different serial devices that
communicate at different baud rates and with different protocols to a common
Ethernet media.
The module is used to connect 7000 SERIES transfer switches, and ASCO Remote
Annuciators to a standard Ethernet TCP/IP network with standard 10base T(RJ-45)
connectors. The module has customized embedded JAVATM applets (program
applications for an internet browser) for each monitored device that loads
automatically to a standard Web Browser.
The module is designed to communicate with up to 8 clients such as Web
applications (web pages), PowerQuest ® , or third party Modbusᓼ devices
simultaneously over an Ethernet connection.
Fig. 18: Connectivity
Module 72E
5120 Telephone Interface Module
(for use with PowerQuest ® )
The 5120 Telephone Interface Module (TIM) allows users to dial directly into
their ASCO communications network for monitoring and/or control. The TIM
connects to the ASCO communication network via RS-485 and the phone port
connects directly into an analog phone jack. Also, the TIM has an RS-232
connector which allows the TIM to be used as the dialing modem.
Supplied with 120 VAC to 18 VDC (nominal) UL approved, class 2 power supply.
Fig. 19: Telephone
Interface Module 92A
17
ASCO
ᓼ
®
Summary Screen
X
ATS 1-8 Summary Screen
ASCO d
ATS 1 - 8 Summary Screen
1901 lavg
548 KW
1901 lavg
548 KW
208 NVca
0 EVca
208 NVca
0 EVca
ATS 1
E
N
N
E
N
Transfer
Engine 1 Stopped
0
0.00
0.00
0
0
L
E
KW Total
Frequency
Power Factor
Vavg.
lavg.
N
N
N
OTTS
Previous
1901 lavg
548 KW
1901 lavg
548 KW
1901 lavg
548 KW
1901 lavg
548 KW
208 NVca
0 EVca
208 NVca
208 EVca
208 NVca
208 EVca
208 NVca
208 EVca
ATS 4
ATS 3
L
E
OTTS
E
208 NVca
0 EVca
ATS 2
L
E
1901 lavg
548 KW
E
N
L
E
N
E
N
L
N
E
OTTS
OTTS
Re-Transfer
ATS 6
ATS 5
E
N
L
N
E
OTTS
E
N
E
N
OTTS
Re-Scan
ATS 8
N
L
E
E
N
E
OTTS
Engine 2 Stopped
Engine 3 Stopped
Engine 4 Running
0
0.00
0.00
0
0
0
0.00
0.00
0
0
136
60.01
0.82
208
472
KW Total
Frequency
Power Factor
Vavg.
lavg.
N
OTTS
ATS 9-16
KW Total
Frequency
Power Factor
Vavg.
lavg.
N
L
?
TD Bypass
KW Total
Frequency
Power Factor
Vavg.
lavg.
Convenient One-Line Diagram
• Colored icons highlighted to show source availability and which source is connected to load.
• Contacts move on icon to indicate main contact position of transfer and bypass switch. (Automatic
transfer and automatic transfer and bypass isolation switches must be provided
with optional accessory 14 auxiliary contacts shown on page 14.)
• Bypass switch contacts appear on icon when configured by user input data.
18
0 NVca
208 EVca
ATS 7
L
E
472 lavg
136 KW
ASCO
ᓼ
®
Power Manager / Data Monitor Screen
ASCO d
ADDRESS
Current
Voltage
Voltage AB
Power Manager Detail Screen
8
• Voltage: phase to phase; phase to neutral and
voltage unbalance.
Normal Energy
475
KWH imp
207
Current A
890763
KVARH lag
Voltage BC
209
Current B
469
KWH exp
0
KVARH lead
78
Voltage CA
208
Current C
472
KWH net
890763
KVARH net
163
• 3 phase currents and neutral (optional).
Voltage AN
119
Unbal %
40
Voltage BN
120
2
Voltage CN
121
• Frequency.
85
Emergency Energy
KWH imp
Power
21
KVARH lag
KWatt
136
KWH lead
7
KVARH lead
1
Unbal % L-L 1
KVAR
0
KWH net
25
KVARH net
3
Frequency
KVA
136
59.97
Reset Normal
• Kilowatt hours - normal and emergency.
Reset Emergency
Power Factor 1
• Status and control of four relay outputs.
Digital Input
Toggle
Status
Status Input 1
Start Engine
Relay 1
on
CT Ratio
1000
Bypass to Normal
Output 2
Relay 2
off
PT Ratio
120
Bypass to Emergency
Output 3
Relay 3
Previous
off
ATS Test
Output 4
Relay 4
Previous
off
Digital Output
Status
Device
• Status of eight digital inputs.
• Device ratings: CT and PT ratio.
ATS Isolated
Normal Breaker Trip
ATS Summary
Status Input 7
Status Input 8
NONE
USER
Transfer Switch Detail Screen
ATS Details Screen
ASCO d
Transfer Switch
• ATS rating and identification data is displayed.
Description ATS 8
8
• Allows remote testing and time delay bypass.
• Voltage, frequency, phase sequence, voltage unbalance
and time delay settings can be checked.
205 NVca
0 EVca
ATS1
PRESENT STATE
Transfer
ATS
Locked Out
N0
Ver. ADRTST-E12
Location Switch 1
In-Phase
Monitor
Enabled
Yes
Load On Normal
L
E
N
Re Transfer
PC
Normal OK
• Viewing of engine exercise schedules.
6/15/99
11:08:54 AM
Timer Bypass
OTTS
• Displays phase to phase voltage on normal and
emergency.
Normal Voltage Frequency Settings
Voltage or Freq % Nom
Value
Time Delay Settings
[min]:[sec]
Engine Start-Norm Fail
00 : 03
00 : 10
Voltage P.U.
95
197.6
Norm to Emerg
• Provides complete system status message from
7000 series microprocessor controller.
Voltage D.O.
70
197.6
Emerg to Norm-Src Fail
30 : 00
Voltage Trip
Freq P.U.
0
95
0
47.5
Emerg to Norm-Test Xfer
02 : 00
Emerg to Norm-Emerg Fail
00 : 00
Freq D.O.
90
45
Engine Cool Down
03 : 00
• View event log on the last 99 events for each ATS.
Freq Trip
0
0
Volt Unbal P.U.
10
20.8
Select
Standard TD
Volt Unbal D.O.
20
41.6
Pre/Post Signal TD
• Arrange test schedules for transfer switches.
Select Emergency Settings
• Provides for monitoring of local site or remote sites.
USER
Engine-Generator Screen
ASCO d
ENGINE
Voltage
Current
Energy
Voltage AB
207
Current A
475
KW Total
136
KWH imp
890784
KVARH lag
85
Voltage BC
209
Current B
469
KWH net
43441
KWH exp
0
KVARH lead
78
60
KWH net
890784
KVARH net
163
208
Current C
472
Frequency
119
Unbal %
40
Power Factor 60
Voltage BN
120
Voltage CN
121
Unbal % L-L
1
Digital Input
Alarm
Enabled
Reset
Digital Output
Toggle
Status
No
Start Engine
Relay 1
on
No
Output 2
Relay 2
off
Low Oil Pressure
Yes
Output 3
Relay 3
Previous
off
Bypass Closed
No
Output 4
Relay 4
Previous
off
Bypass on Test
No
Normal Brkr Temp
No
No
No
USER
NONE
1
Normal Vab
202
Normal Vbc
205
Normal Vca
205
Normal Freq
59
Emerg Vab
0
Emerg Vbc
0
Emerg Vca
0
Emerg Freq
0
Update Time
Event Logging (Max. 99 Entries)
1
Event Log
Event Cause
Emerg Became
Not Vail
Emergency
Failure
Date
06/12/01
Time
16:05:42
Test Schedules
ATS Summary
• Current for each phase.
• Kilowatts and kilowatt hours total.
• Status and control of four digital outputs which can be
customized by the user.
Engine Oil Temp
Status Input 8
50
# Phases
• Frequency and power factor.
Low Fuel
Status Input 7
None
1200
Nom Freq
• Voltage: Phase to phase; Phase to neutral
Power
Voltage AN
Non - Standard TD
6/13/99
10:02:42
208
Current Rating
Engine-Generator Details
4
Voltage CA
CP
Switch Data
Nom Voltage
Status
• Status of eight digital inputs.
• “Alarm Enabled” selection. These alarms flash the
“engine-generator” icon on the summary screen.
• Digital inputs for engine malfunctions are derived
from engine mounted sensors (supplied by others).
ATS Summary
19
ASCO
ᓼ
SiteWeb®
Remote Access
Computer
Local Computer
Ethernet
RS 485
Ethernet Hub
Internet
Firewall
Pager
ASCO 5500
Thin Web
Server
Email Server
ATS Annunciator
Ethernet
Monitoring
and Control
RS 485 Modbus
RS 485
(72E)
Building
Management
Computer
ASCO
Digital Paralleling
System
Monitoring and Control
Ethernet Hub
Monitoring
ASCO
5110 (72A)
Serial
Modules
ASCO
5150 (72E)
Connectivity
Modules
To Additional
Automatic
Transfer
Switches
ASCO
ATS 1
20
ASCO
ATS 2
To Additional
Automatic
Transfer
Switches
ASCO
ATS 1
ASCO
ATS 2
ASCO
ᓼ
SiteWeb®
SiteWeb® is a client-server application requiring no software to be installed on the client computer. When combined with the ASCO
Communication Interface Modules (Acc 72A / Acc 72E), the ASCO 5500 SERIES Thin Web Server and the ASCO 5200 SERIES Power
Manager provide the most comprehensive Intranet and Internet communication system for the monitoring and control of power
transfer switches and engine generators located in your emergency or standby power distribution system.
The SiteWeb® communication system allows multiple client access, from local or remote locations, and provides for the monitoring of up to 64 power transfer switches and eight engine generators. In addition, automatic email paging is provided for all alarm
signals.
ASCOᓼ 5500 SERIES
Thin Web Server
The ASCO Thin Web Server allows you to monitor and control transfer
switches and engine generators anytime over an Intranet
or the Internet from anywhere in the world. It also transmits an email
message that an alarm has occurred with one or more of the transfer
switches. Plus, this is possible from your home computer or
anywhere that has Internet service, using the ASCO Thin Web Server with
the SiteWeb® monitoring and control system.
Fig. 20: Thin Web Server
Communications Products for 7000 SERIES Transfer Switches
Description
Acc. Option
Catalog No.
Serial Module
72A
5110
Connectivity Module
72E
5150
Power Manager with Display*
85L
5220D
Thin Web Server*
—
5510E
PowerQuest VPi Software Package*
—
VPi 32.15
*Note: These products are available as separate items only. They can be ordered by catalog numbers shown in above chart.
®
VS.
ASCO Connectivity Solution Guide
Feature
Quantity of Monitored / Controlled Power Transfer
Switches per LAN
PowerQuest
VPi 32.15
32
Thin Web Server
with SiteWeb
5150
Connectivity Module
64
1024+
4
8
1024+
Yes
Yes
No
Embedded Web Pages
No
Yes
Yes
Ethernet Network Compatible
Yes
Yes
Yes
Monitor Multiple Protocols & Baud Rates
(ASCO I, ASCO II, Modbus)
No
No
Yes
Monitor Multiple Sites
Dial-Up
Internet
Intranet
Multiple Client Access
No
Up to 8
Up to 8
Client Software Required
Yes
Internet Explorer
Internet Explorer
Monitors Dissimilar ASCO Controllers on Common LAN
No
No
Yes
Communicates with ASCO Remote Annuciators
No
No
Yes
Email / Paging Alarms
No
Yes
No
Historical Trending Option Alarms
No
Yes
No
Number of Monitored / Controlled Gensets
Control & Monitoring Capability
21
ASCO
ᓼ
7000 SERIES Ordering Information
To order an ASCO 7000 SERIES Power Transfer Switch, complete the following catalog number:
A
7
TS
A
+
Neutral
Code*
Product
A
N
M
Automatic
NonAutomatic
Manually
Operated
TS
Conventional
2-Position
TB
Open
Transition
Bypass
CTS
Closed
Transition
CTB
Closed
Transition
Bypass
DTS
Delayed
Transition
DTB
Delayed
Transition
Bypass
---
No Neutral
A
Solid Neutral
B
C
3
+
+
400
Phase
Poles
Amperes
2
3
30
70
100
150
200*
230 *
260
400
600
800
1000
1200
1600
2000
3000
4000
Switched
Neutral
Overlapping
Neutral
N
+ 5X +
C
Voltage
Code
Grp
Code
Enclosure
+
A
B
C
D
E
F
H
J
K
L
M
N
P
Q
R
115
120
208
220
230
240
380
400
415
440
460
480
550
575
600
5
5Xoptional
accessories
---
No enclosure
C
Type 1 enclosure
E
Type 2 enclosure
F
Type 3R
enclosure
G
Type 4 enclosure
H
Type 4X
enclosure
(stainless steel)
K
Type 7 enclosure
L
Type 12
enclosure
M
Type 3R secure
double door
N
Type 4 secure
double door
P
Type 4X secure
double door
Q
Type 12 secure
double door
*Note: For 4 pole applications on switches rated 150 to 400 (Bypass configurations only) amps and 4000 amps specify overlapping switched neutral (optional).
Conventional switch neutral is provided on delayed transition transfer products when specified.
200 and 230 amp switch limited to 480 volts maximum.
The Example Catalog Number above is 7ATSA3400N5XC
(X is used to specify optional accessories).
Transfer Switch Configurations
Transfer/Bypass Configurations
7A TS, 7N TS, 7A DTS, 7A CTS, 7N DTS, 7N CTS
7A TB, 7N TB, 7A DTB, 7A CTB, 7N DTB, 7N CTB
Sizes of UL-Listed Solderless Screw-Type
Terminals for External Power Connections
Sizes of UL-Listed Solderless Screw-Type
Terminal for Power Connections
Switch Rating
amps
Max # of Conductors
per Terminal
Range of AL- CU
Conductor Sizes
30 -2303
One
#14 to 4/0 AWG
260-400
One
#4 AWG to 600 MCM
Two
#1/0 AWG to 250 MCM
150,260,400
6004
4
Max # of Conductors
per Terminal
Range of AL-CU
Conductor Sizes
One
# 4 AWG to 600 MCM
Two
# 1/0 AWG to 250 MCM
Two
# 2 AWG to 600 MCM
600
Two
#1/0 AWG to 600 MCM
800,1000,1200
Four
# 1/0 AWG to 600 MCM
800-12001
Four
#1/0 AWG to 600 MCM
1600-20004
Six
# 1/0 AWG to 600 MCM
#1/0 AWG to 600 MCM
30004
Ten
# 2 AWG to 600 MCM
Twelve
#1/0 AWG to 600 MCM
4
Twelve
# 2 AWG to 600 MCM
Twelve
#2/0 AWG to 600 MCM
1600-2000
3000
4000
2
Six
Notes: 1. Unit is designed for top cable entry of emergency and load and bottom entry of
normal. Optionally, the switch may be supplied with reverse source and/or bottom entry load, when specified.
2. All main terminals are rear connected. The 4000 amp switch is arranged for bus
bar connection. Contact ASCO if provisions for cable connection are required.
22
Switch Rating
amps
4000
3. 200 and 230 amp rating for copper conductors only.
4. All main terminals are rear connected. A front connected version is
available in 600 and 1200 amp ratings only with top cable entry only.
See pages 25-27 for dimensional data and additional information.
ASCO
ᓼ
7000 SERIES Designed to Fit Anywhere*
2-Position Transfer Switching 7A TS, 7N TS (Non-Bypass)
Switch Rating
Amps
Poles
Width
Height
Depth
inches (mm) inches (mm) inches (mm)
Enclosed UL Type 1 2
30, 70, 100, 125, 150, 200, 230
260, 400
600
800, 1000
1200
1600, 2000 1
2, 3 or 3 with neutral A/B/C
2, 3 or 3 with neutral A/B/C
2, 3 or 3 with neutral A/B/C
2, 3 or 3 with neutral A/B/C
2, 3 or 3 with neutral A/B/C
2, 3 or 3 with neutral A/B/C
18 (457)
24 (610)
24 (610)
34 (864)
38 (965)
38 (965)
48 (1219)
56 (1422)
63 (1600)
72 (1829)
87 (2210)
91 (2311)
13 (330)
14 (356)
17 (432)
20 (508)
23 (584)
48 (1219)
1600, 20001,3 (front connected) 2, 3 or 3 with neutral A/B/C
38 (965)
87 (2210)
23 (584)
2600, 3000 1
2, 3 or 3 with neutral A/B/C
38 (965)
91 (2311)
60 (1524)
4000 1
2, 3 or 3 with neutral A/C
46 (1168)
91 (2311)
72 (1829)
2, 3 or 3 with neutral B/C
2, 3 or 3 with neutral B/C
2, 3 or 3 with neutral B/C
2, 3 or 3 with neutral B/C
2, 3 or 3 with neutral B/C
10-1/4 (260)
18-1/2 (470)
19 (483)
27 (686)
33-1/4 (845)
10-1/4 (260)
25 (635)
30 (762)
31 (787)
28 (711)
5-1/2 (140)
8 (203)
9-7/8 (251)
12-7/8 (327)
26-1/4 (667)
2600, 3000
2, 3 or 3 with neutral B/C
33-1/4 (845)
4000
2, 3 or 3 with neutral C
Notes:
1. Enclosures for 1600 - 4000 amp
are free-standing with removable
top, sides, and back.
2. Consult ASCO for dimensions on
enclosures other than UL type 1.
3. Order accessory 40MY for
1600A and 40NY for 2000A F/C
design.
*All dimensions and weights
shown are approximate and should
not be used for construction
purposes. Certified dimensions can
be furnished upon request.
Open Configuration
30, 70, 100, 125,150, 200, 230
260, 400
600
800, 1000, 1200
1600, 2000
41 (1041)
28 (711)
30-3/4 (781)
52 (1321)
25-1/2 (648)
Shipping Weights
2-Position Transfer Switching 7A TS, 7N TS
Switch Rating
Amps
30, 70, 100, 125
30, 70, 100, 125
30, 70, 100, 125
150, 200, 230
150, 200, 230
150, 200, 230
260, 400
260, 400
260, 400
600
600
600
800, 1000
800, 1000
800, 1000
1200
1200
1200
1600, 2000
1600, 2000
1600, 2000
2600, 3000
2600, 3000
2600, 3000
4000
4000
4000
Poles
2
3
3 with B/C
2
3
3 with B/C
2
3
3 with B/C
2
3
3 with B/C
2
3
3 with B/C
2
3
3 with B/C
2
3
3 with B/C
2
3
3 with B/C
2
3
3 with C
Enclosed*
lb (kg)
67 (31)
70 (32)
73 (33)
69 (32)
72 (33)
75 (34)
216 (98)
223 (101)
230 (105)
316 (143)
324 (147)
332 (151)
400 (182)
420 (192)
446 (203)
685 (312)
705 (321)
731 (333)
1110 (503)
1160 (525)
1210 (548)
1365 (620)
1430 (649)
1495 (679)
2208 (1002)
2433 (1104)
2533 (1149)
Open*
lb (kg)
15 (7)
18 (8)
21 (10)
17 (8)
20 (9)
23 (11)
82 (37)
89 (40)
102 (46)
88 (40)
96 (44)
104 (47)
150 (68)
170 (78)
196 (90)
150 (68)
170 (78)
196 (90)
370 (167)
420 (190)
470 (213)
405 (184)
470 (213)
535 (243)
975 (443)
1200 (545)
1300 (590)
*All dimensions and weights
shown are approximate and should
not be used for construction
purposes. Certified dimensions can
be furnished upon request.
23
ASCO
ᓼ
7000 SERIES Designed to Fit Anywhere*
Closed Transition and Delayed Transition Transfer Switching
7A DTS, 7A CTS, 7N DTS, 7N CTS
Switch Rating
Amps
Poles
Width
inches (mm)
Height
Depth
inches (mm) inches (mm)
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/C
24 (610)
24(610)
34 (864)
38 (965)
38 (965)
38 (965)
38 (965)
46 (1168)
56 (1422)
63 (1600)
72 (1829)
87 (2210)
91 (2311)
87 (2210)
91 (2311)
91 (2311)
14 (356)
17(432)
20 (508)
23 (584)
48 (1219)
23 (584)
60 (1524)
72 (1829)
150, 260, 400
2, 3 or 3 with neutral B
18-1/2 (470)
25 (635)
8 (203)
600
800, 1000, 1200
1600, 2000
3000
4000
2, 3 or 3 with neutral B
2, 3 or 3 with neutral B
2, 3 or 3 with neutral B
2, 3 or 3 with neutral B
2, 3 or 3 with neutral C
19 (483)
27 (686)
33-1/4 (845)
33-1/4 (845)
41 (1041)
30 (762)
31 (787)
28 (711)
28 (711)
52 (1321)
9-7/8 (251)
12-7/8 (327)
26-1/4 (667)
30-3/4 (781)
29-1/2 (749)
Enclosed UL Type 1 2
150, 260, 400
600
800, 1000
1200
1600, 2000 1
1600, 20001,3 (front connected)
3000 1
4000 1
Open Configuration
Notes:
1. Enclosures for 1600 4000 amp are free-standing
with removable top, sides,
and back.
2. Consult ASCO for dimensions on enclosures other
than UL type 1.
3. Order accessory 40MY for
1600A and 40NY for 2000A
front connected design.
*All dimensions and weights
shown are approximate and
should not be used for
construction purposes.
Certified dimensions can be
furnished upon request.
Shipping Weights
Closed Transition and Delayed Transition Transfer Switching
7A DTS, 7A CTS, 7N DTS, 7N CTS
24
Switch Rating
Amps
Poles
Enclosed*
lb (kg)
Open*
lb (kg)
150, 260, 400
150, 260, 400
150, 260, 400
600
600
600
800, 1000
800, 1000
800, 1000
1200
1200
1200
1600, 2000
1600, 2000
1600, 2000
2600, 3000
2600, 3000
2600, 3000
4000
4000
4000
2
3
3 with B
2
3
3 with B
2
3
3 with B
2
3
3 with B
2
3
3 with B
2
3
3 with B
2
3
3 with C
235 (107)
242 (110)
250 (113)
335 (152)
343 (156)
352 (159)
420 (192)
450 (205)
480 (219)
710 (324)
740 (337)
770 (351)
1300 (590)
1350 (612)
1400 (635)
1555 (706)
1620 (735)
1685 (765)
2360 (1071)
2580 (1171)
2680 (1217)
101 (46)
108 (49)
115 (52)
107 (48)
115 (52)
124(56)
175 (80)
205 (94)
235 (108)
175 (80)
205 (94)
235 (108)
505 (229)
555 (252)
605 (274)
540 (245)
660 (300)
725 (329)
1127 (511)
1347 (611)
1447 (657)
Notes:
1. Open weights include
transfer switch and control
panel. 1200-4000 amp enclosures require ventilation openings, refer to drawings for
details. Export shipments may
require a wooden box, contact
ASCO for weights and
dimensions.
*All dimensions and weights
shown are approximate and
should not be used for
construction purposes.
Certified dimensions can be
furnished upon request.
ASCO
ᓼ
7000 SERIES Designed to Fit Anywhere*
Automatic Transfer Bypass-Isolation Switching
with Transfer Switch Engaged 7A TB, 7N TB
Switch Rating
amps
Power Connection
Configuration
Width
Height
Depth
inches (mm) inches (mm) inches (mm)
Poles
Enclosed UL Type 1
150, 260, 4001
600, 800 2, 5
600, 800, 1000, 12002, 3
1600, 20002, 3
30002, 3
40004
Front Connected
Front Connected
Rear Connected
Rear Connected
Rear Connected
Rear Connected
2, 3 or 3 with neutral A/C
2, 3 or 3 with neutral A/B/C
2, 3 or 3 with neutral A/B/C
2, 3 or 3 with neutral A/B/C
3 or 3 with neutral A/B/C
3 or 3 with neutral A/C
28-1/2 (724)
38 (965)
38 (965)
38 (965)
38 (965)
96-1/2 (2451)
62-1/2 (1588)
91 (2311)
91 (2311)
91 (2311)
91 (2311)
91 (2311)
19 (483)
32 (813)
48 (1219)
60 (1524)
72 (1829)
72 (1829)
Front Connected
Front Connected
Rear Connected
Rear Connected
2 or 3
2 or 3 with neutral C
2, 3 or 3 with neutral B/C
2, 3 or 3 with neutral B/C
14-3/4 (375)
19-3/4 (500)
38 (965)
38 (965)
37-1/8 (946)
61-1/2 (1553)
72 (1829)
72 (1829)
22-1/4 (565)
22-1/4 (565)
38 (965)
38 (965)
Open Configuration
150, 260, 4001
150, 260, 4001
600, 800, 1000, 12002, 3
1600, 20003, 30002, 3
Notes: 1. Handles extend 3-1/2 inches (89mm).
2. Handles extend 6-1/4 inches (159mm).
3. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch
drawout). Side or rear access required.
4. For 4000 amp size, ATS and bypass sections can be reversed, contact ASCO. Recommended clearance to
enclosure: 3 feet (914mm) from rear, 5 feet (1524mm) from front (3 feet required for transfer switch rollout).
5. Specify optional accessory 40HY for 600 amp front - connected arrangement and 40 JY for 800 amp. All service and load
cables limited to top entry only.
*All dimensions and weights shown are approximate and should not be used for construction purposes.
Certified dimensions can be furnished upon request.
Shipping Weights
Automatic Transfer Bypass-Isolation Switching
with Transfer Switch Engaged 7A TB, 7N TB
Switch Rating
amps
Poles
Enclosed*
lb (kg)
Open*
lb (kg)
150, 260, 400
150, 260, 400
150, 260, 400
600, 800, 1000, 1200
600, 800, 1000, 1200
600, 800, 1000, 1200
1600, 2000
1600, 2000
1600, 2000
3000
3000
4000
4000
2
3
3 with C
2
3
3 with B/C
2
3
3 with B/C
3
3 with B/C
3
3 with C
340 (154)
350 (158)
360 (163)
1510 (685)
1580 (717)
1650 (748)
2180 (989)
2360 (1070)
2540 (1152)
2730 (1240)
3360 (1525)
6300 (2858)
6900 (3130)
135 (61)
145 (66)
155 (70)
920 (417)
990 (449)
1060 (481)
1300 (589)
1550 (702)
1800 (815)
1690 (768)
1980 (899)
–
–
Notes: 1.Open weights include transfer switch, bypass-isolation switch and control panel.
1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.
*All dimensions and weights shown are approximate and should not be used for construction purposes.
Certified dimensions can be furnished upon request.
25
ASCO
ᓼ
7000 SERIES Designed to Fit Anywhere*
Automatic Transfer Bypass-Isolation in Closed Transition and Delayed
Transition Switching. 7A DTB6, 7A CTB, 7N DTB6, 7N CTB
Switch Rating
amps
Power Connection
Configuration
Width
Height
Depth
inches (mm) inches (mm) inches (mm)
Poles
Enclosed UL Type 1
150, 260, 4001, 5
600, 800 (Front Connected)2, 7
600, 800, 1000, 12002, 3
1600, 20002, 3
30002, 3
40004
Front Connected
Front Connected
Rear Connected
Rear Connected
Rear Connected
Rear Connected
2, 3 or 3 with neutral A/C
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
2, 3 or 3 with neutral A/B
3 or 3 with neutral A/B
3 or 3 with neutral A/C
28-1/2 (724)
38 (965)
38 (965)
38 (965)
38 (965)
96-1/2 (2451)
74 (1880)
91 (2311)
91 (2311)
91 (2311)
91 (2311)
91 (2311)
19 (483)
32 (813)
48 (1219)
60 (1524)
72 (1829)
72 (1829)
Front Connected
Front Connected
Rear Connected
Rear Connected
2 or 3
2 or 3 with neutral C
2, 3 or 3 with neutral B
2, 3 or 3 with neutral B
14-3/4 (375)
19-3/4 (500)
38 (965)
38 (965)
61-1/2 (1553)
61-1/2 (1553)
72 (1829)
72 (1829)
22-1/4 (565)
22-1/4 (565)
38 (965)
38 (965)
Open Configuration
150, 260, 4001, 5
150, 260, 4001, 5
600, 800, 1000, 12002, 3
1600, 20003, 30002, 3
Notes: 1. Handles extend 3-1/2 inches (89mm).
2. Handles extend 6-1/4 inches (159mm).
3. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch
drawout).Side or rear access required.
4. For 4000 amp size, ATS and bypass sections can be reversed, contact ASCO. Recommended clearance to
enclosure: 3 feet (914mm) from rear, 5 feet (1524mm) from front (3 feet required for transfer switch rollout).
5. Dimensions for 400 amp, 7A DTB and 7N DTB with neutral code B are 38(965)W x 91(2311)H x 48(1219)H.
6. Conventional switched neutral is provided on 7A DTB and 7N DTB switching arrangements when specified (optional Code B).
7. Specify optional accessory 40HY for 600 amp front - connected arrangement and 40 JY for 800 amps. All service and load
cables limited to top entry only.
*All dimensions and weights shown are approximate and should not be used for construction purposes.
Certified dimensions can be furnished upon request.
Shipping Weights
Automatic Transfer Bypass-Isolation in Closed Transition and Delayed
Transition Switching. 7A DTB, 7A CTB, 7N DTB, 7N CTB
Switch Rating
amps
Poles
Enclosed*
lb (kg)
Open*
lb (kg)
150, 260, 400
150, 260, 400
150, 260, 400
600, 800, 1000, 1200
600, 800, 1000, 1200
600, 800, 1000, 1200
1600, 2000
1600, 2000
1600, 2000
3000
3000
4000
4000
2
3
3 with C
2
3
3 with B
2
3
3 with B
3
3 with B
3
3 with C
440 (199)
450 (203)
460 (208)
1560 (708)
1630 (739)
1700(771)
2315 (10550)
2495 (1132)
2675 (1213)
2730 (1240)
3360 (1525)
6300 (2858)
6900 (3130)
165 (75)
175 (79)
185 (84)
970 (440)
1040 (472)
1110(503)
1435 (651)
1685 (764)
1935 (878)
1690 (768)
1980 (899)
–
–
Notes: 1. Open weights include transfer switch, bypass-isolation switch and control panel.
1600-4000 amp enclosures require ventilation openings, refer to drawings for details.
Export shipments may require a wooden box, contact ASCO for weights and dimensions.
*All dimensions and weights shown are approximate and should not be used for construction purposes.
Certified dimensions can be furnished upon request.
26
ASCO
ᓼ
7000 SERIES Designed to Fit Anywhere*
Standard and Optional Power Connection Configurations for 600-800 Amp, Automatic
Transfer Bypass Isolation Switches 7ATE, 7NTE, 7ADTB, 7ACTB, 7NDTB, 7NCTB
48.00
Standard Rear Connected Design
Cable
Compartment
Additional
Controls if
Required
17.00
Emergency Lugs
Poles 1 and 4
Emergency Lugs
Poles 2 and 3
Field Wiring
Terminal Block
(TB)
Bypass
Switch
Manual
Operation
Handle
Bypass Handle
Load Lugs Mounted
Pointing Upward
For Top Cable
Entry, Lug Plates May
Be Turned To
Point Downward For
Bottom Cable Entry
38.76
Group 5
Controller User
Interface
Isolation
Handle
91.00
Isolation Handle
Controls &
Indication
59.05
Ref
Transfer Switch
Compartment
35.24
12.42
Ref
Normal Lugs
Poles 2 and 4
Transfer
Switch
Drawn Out
(Isolated)
Position
Normal Lugs
Poles 1 and 3
Right Side View (Covers Removed)
Front View (Covers Installed)
Cable
Compartment
Optional Front Connected Design- 32 Inch Depth
32.00
Ground Bus
Load Lugs
17.00
Normal Lugs
Field Wiring
Terminal Block
(TB)
Bypass
Switch
Manual
Operation
Handle
Emergency Lugs
Bypass Handle
38.76
Group 5
Controller
User
Interface
91.00
Isolation
Handle
Controls and
Indication
*All dimensions and weights
shown are approximate and
should not be used for construction purposes. Certified
dimensions can be furnished
upon request.
59.05
REF
12.42 REF
Isolation
Handle
35.24
Transfer Switch
Compartment
Front View
(Doors and Top Covers Installed)
39.00
CG
Right Side View
(Covers Removed)
27
A SCO Power Te ch nol ogi es
F LO R H A M PA R K , N E W J E R S E Y 0 7 9 3 2
USA
8 0 0 8 0 0 A SCO
W W W. A S CO P OW ER.CO M
A SI A
AUS T R A L I A
BRAZIL
C A N A DA
GERMANY
J A PA N
M E X I CO
SOU TH AF RIC A
SOU TH AMERI C A
U N I T E D A R A B E M I R AT E S
UNITED KINGDOM
U N I T E D S TAT E S
Emerson Network Power.
The world leader in business-critical continuity.
EmersonNetworkPower.com
AC Power Systems
Connectivity
Embedded Power
Integrated Cabinet Solutions
Power Switching & Controls
Precision Cooling
DC Power Systems
Outside Plant
Services
Site Monitoring
Surge & Signal Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2006 Emerson Electric Co.
Publication 3040 R8
© February, 2006
Printed in the U.S.A.