TRICON Condensing Water Heater AQUAPLEX

TRICON Condensing Water Heater  AQUAPLEX
TRICON® Condensing Water Heater
®
AQUAPLEX STORAGE TANK (UNLINED DUPLEX ALLOY)
TANK SERIES 250 Gallon ■ 1500 to 2000 MBH
GPH RECOVERY - Thermal Efficiency
MODEL
BTU INPUT
70° to 140°F

40° to 140°F

SHIPPING WEIGHT
(LBS.)
OPERATING
WEIGHT (LBS.)
150 L 250A-PVIF
1,500,000
2238 (87%)
1603 (89%)
1835
3095
180 L 250A-PVIF
1,800,000
2685 (87%)
1923 (89%)
1835
3095
200 L 250A-PVIF
2,000,000
2984 (87%)
2137 (89%)
1835
3095
 Recoveries and thermal efficiency derived from DOE 10 CFR 431 testing requirements (ANSI Z21.10.3 @ 70°F to 140°F).
Recoveries and thermal efficiency based upon 40°F entering water temperature at full fire.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form PV 8008.
Standard Electrical
120V, 1Ø, 60 Hz., 15 amp circuit
Venting
Use an ETL, UL, ULC or CSA listed
single or double wall 6” stainless steel
Category IV vent, minimum distance
5 ft., maximum distance 100 eq. ft.
Longer vents, ETL listed w/larger
diameters, see I&M.
Inlet Combustion Air
Up to 100 eq. ft. using 6" PVC or
galvanized vent pipe.
Longer lengths, ETL listed with larger
diameters, see I&M.
Gas Pressure - Natural
Minimum inlet flow pressure: 4.5" W.C.
Maximum static pressure: 14" W.C.
For < 4.5”W.C., consult factory.
For LP option, consult factory.
Minimum Service Clearances
18" from sides,
24" from front and top
Emissions
< 20 ppm NOx
PV 8012 11-2015
PVI Industries, LLC
Engineered Water Heating Solutions
www.pvi.com
Fort Worth, TX ▪ 800-784-8326
PVI RESERVES THE RIGHT TO CHANGE
THE DESIGN AND SPECIFICATION
WITHOUT NOTICE.