D2412 Wiring Diagram
™
Radionics D2412
Radionics recommends testing the entire system at least
once a week, and having a qualified technician check the
system at a minimum of once every 3 years.
This system should be installed in accordance with Chapter 2 of the National Fire Alarm Code,
ANSI/NFPA 72-1996, (NFPA, Batterymarch Park, Quincy MA 02269). Printed information
describing proper installation, operation, testing, maintenance, repair service and response to
an alarm is to be provided with this equipment. Warning: Owner's Instruction Notice: Not to
be removed by anyone except occupant.
This equipment has been type tested and found to comply with the specifications in Part 15 of FCC
rules for Class B Computing Devices. Operation is subject to the two following conditions (1) this
device may not cause any interference, and (2) this device must accept any interference received
including interference that may cause undesired operation.
Complies with Part 68, FCC Rules.
Suitable for the following applications:
FCC Registration Number: ESVUSA-30727-AL-E
1) Household Burglar Alarm System Units, Grade A.
Ringer Equivalence: 0.3B
2) Household Fire Warning System Units. 3) Police
Station connect, Grade A Mercantile Premise alarm system,
Grade A Mercantile Safe and Vault alarm system and Grade AA Mercantile Safe and Vault alarm system when installed in conjunction with Model D8122
derived channel subscriber terminal unit. For all Police Station applications and grades, Model D8108A Attack Resistant Enclosure with a UL Listed local
sounding device is required. 4) Local, Grade A Mercantile Premise alarm system and Grade A Mercantile Safe and Vault alarm system. For all local
applications and grades, Model D8108A Attack Resistant Enclosure and a UL Listed local sounding device is required. 5) Central Station Mercantile, Grade
C application. Central Station Mercantile, Grade B when installed with a UL Listed local sounding device. Central Station Mercantile, Grade AA when installed
with Model D8122 derived channel subscriber terminal unit. 6) Proprietary Burglar Alarm units, Grade B, when installed with a UL Listed local sounding device.
Proprietary Burglar Alarm unit, Grade BB when installed with the Model D8122 derived channel subscriber terminal unit. D2412 must be installed in accordance
with Installation Instructions P/N 35115.
All external connections are inherently power limited.
Do not connect to a receptacle controlled by
a switch. Do not share with other equipment.
POWER SUPPLY REQUIREMENTS
Radionics D1640 UL Listed
Class 2 Transformer
16.5VAC 40VA 60HZ
Use compatible NAC
such as Radionic's D440
Alarm Output +
The Power Supply provides a maximum of 1.0
Amps for the Control Panel and All Accessory
Devices. For System loading, See Installation
Manual P/N 35115.
Requirements for battery standby time may
reduce allowable output.
Alarm Output -
CAUTION: See Manual for power requirements
relating to terminals [Alrm+] and [+Aux].
Earth Ground
720mA available for Fire
see
systems, 1.85A for Burglary
Note 1
systems.
Note 1: A
supervisory
alarm output
module must
be used on
these terminals for
household
fire appliKeypads and
cations
Expanders (up to 8)
Up to 4 Keypads with
expanded points
P
P
P
S
S
S
S
A
B
C
D
Supervised with 1k Ω
EOL Resistor. Typical
Initiating Devices are
Door Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Detectors, etc.
System Delay Chart
Smoke Detector
Model
Delay - Sec
Local
Programmer
Connect
Lock Standby
Switch to
program.
(a)
4 sec
(a) The delay (power-up) (start-up) time marked
on the installation wiring diagram of the smoke
detector or on the installed smoke detector(s) is
to be used.
Reference Manual P/N 35115
for System Wiring Diagram
_
Auxilliary Powered
Devices 10.2 to
13.9 VDC.
With 7.0Ah battery,
140mA for 24 hrs
for Fire, 350mA for
4 hrs for Burglary.
Include keypads in
calculations.
1
BATTERY: Replace every 3 to 5 years.
Use Radionics' Model D126, 12V 7 Amp
HR Sealed Lead Acid Battery for Burglary
or Combination Fire and Burglary
Systems. For additional load or standby
power, refer to battery calculation sheet
in Installation Manual P/N 35115.
Aux Pwr -
Standby Switch
Disables Arming,
Reports, and Relays.
Lock for local
programming.
Circuit Control Unit
(Zone) Delay - Sec
Data
Aux Pwr +
Ext1 Ext2 1+
P
WARNING:
Heat Sink is Hot.
DO NOT TOUCH!
+
9
1-
Com
2
3
Com 4
5
Com 6
T
T1
R1
R
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1
Battery- Black
Battery+ Red
+
2
4
3
5
6
T
T1
R1
R
-
Maximum charging
current is 860mA.
CAUTION: Applying
positive voltage directly
to terminals [Alrm-],
[Ext1], or [Ext2] will
damage panel.
External Relays
require D133/D134
Relay Module
Powered Sensor Loop suitable for Two-Wire Smoke Detectors 2.0 KΩ Resistor required at
End of Line. For compatible smoke detectors, see Technogram P/N 35112. The U.L. Panel
Compatibility Identifier = B. Also available for Four-Wire Smoke Detectors such as
Radionics' D273TH. Voltage range for Two-Wire Smoke Detectors is 10.2 to 13.9 VDC.
WARNING: THIS UNIT INCLUDES AN ALARM VERIFICATION FEATURE
FOR POINT 1 THAT RESULTS IN A DELAY OF THE SYSTEM ALARM SIGNAL
WHEN PROGRAMMED FOR THIS FEATURE. THE TOTAL DELAY (CONTROL
UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60 SECONDS. NO
OTHER INITIATING DEVICES SHALL BE CONNECTED TO POINT 1 WHEN
PROGRAMMED FOR ALARM VERIFICATION, UNLESS APPROVED BY THE
LOCAL AUTHORITY HAVING JURISDICTION.
Supervised Points
Open
Normal
Short
8.9 - 13.9VDC
2.5 - 8.5VDC
0.0 - 2.0VDC
Premises
Phone
1.0 KΩ Resistor
Required at End of Line
This box will be checked if
Point 1 is programmed for
Alarm Verification.
P/N 35116B
Incoming
Phone
Line
8/06/97
Use Radionics D164
Phone Cord or
equivalent. Ground
Start requires
D133/D134.
1997 © Radionics