87CB TM 3300 3400
Thermal-Magnetic Circuit Breakers 3300/3400
Description
Single pole thermal-magnetic circuit breakers with tease-free, trip-free,
press-to-reset, snap action mechanism (R-type TM CBE to EN 60934;
M-type with manual release (-H). Available with fast acting and standard
magnetic tripping characteristics - types 3300 and 3400 - both with
threadneck panel mounting. Options include auxiliary contacts, a
separate shunt tap terminal (-A3), and pull-to-trip manual release (-H).
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Control systems, instrumentation, medical equipment, machine tools,
robotics.
3300
3400
fast acting
standard delay
2
Ordering information
Technical data
Type No.
3300 fast acting
3400 standard delay
Mounting
iG2 moulded threadneck M12x1 (bulk-shipped), not with -H;
...
leave blank for metal threadneck, required for -H
Terminal design
P10 blade terminals 6.3-0.8 (QC .250)
K20 screw terminals M3.5x5.5 with clamp (not for -Si and -A3)
Shunt terminal (optional)
A3 same as main terminals, up to IN=7 A max. load 5 A
Manual release (optional)
H manual release facility (pull), without
reinforced insulation in operating area,
for M12x1 metal threadneck only.
Metal threadneck version for -H is not approved.
Auxiliary contacts (optional)
Si with silver-plated solder terminals
(N/O and N/C)
Push button marking (optional)
1 without
Current ratings
0.05...16 A
3400 - iG2 - P10 - .. - .. - Si - .. - 10 A ordering example, without manual
release and with moulded
threadneck
3400 - ... - P10 - .. - H - Si - .. - 10 A ordering example, with manual
release and metal threadneck
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
Standard current ratings and typical internal resistance values
Current
Internal resistance (Ω)
ratings (A) 3300
3400
Current
Internal resistance (Ω)
ratings (A) 3300
3400
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
3
4
5
6
7
8
10
12
13
14
15
16
447
131
41
19.6
10.4
7.2
4.8
2.5
1.93
0.81
0.44
0.27
211
131
40
19.3
10.4
7.1
4.3
2.5
1.67
0.61
0.38
0.24
0.18
0.109
0.066
0.046
0.032
0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
0.19
0.090
0.061
0.041
0.034
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
≤ 0.02
For further details please see chapter: Technical Information
Voltage rating
AC 240 V, 50/60 Hz; DC 65 V
(UL: AC 250 V; DC 80 V)
Current ratings
0.05...16 A
Auxiliary circuit
1 A, AC 240 V / DC 65 V
Typical life
with -H:
5,000 operations at 1 x IN, inductive
5,000 operations at 2 x IN, resistive
without -H: 0.05...8 A 5,000 operations at 2 x IN, inductive
>8A
1,500 operations at 2 x IN, inductive
Ambient temperature
-30...+60 °C (-22...+140 °F)
Insulation co-ordination
rated impulse
pollution
(IEC 60664 and 60664 A) withstand voltage
degree
operating area
2.5 kV
2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V double insulation
main circuit/aux. circuit AC 1,500 V
aux. circuit 4-5/6-7
AC 840 V
Insulation resistance
> 100 MΩ (DC 500 V)
Interrupting capacity Icn
0.05...0.8 A
self-limiting
1...2 A
200 A
2.5...16 A
400 A
Interrupting capacity
IN
UN
(UL 1077)
0.05...16 A
AC 250 V 1,000 A
0.05...16 A
DC 80 V
1,000 A
Degree of protection
operating area IP40
(IEC 60529/DIN 40050)
terminal area IP00
Vibration
5 g (57-500 Hz), ± 0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock
25 g (11 ms) to IEC 60068-2-27, test Ea
Corrosion
96 hours at 5 % salt mist
to IEC 60068-2-11, test Ka
Humidity
240 hours at 95 % RH,
to IEC 60068-2-78, test Cab
Mass
3300: approx. 55 g
3400: approx. 50 g
Approvals
Authority
VDE (EN 60934)
CSA, UL
UL: only type 3400
Voltage ratings
AC 240 V; DC 65 V
AC 250 V; DC 80 V
DC 65 V
Current ratings
0.05...16 A
0.05...16 A
0.05...25 A
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Issue B
www.e-t-a.com
2 - 49
Thermal-Magnetic Circuit Breakers 3300/3400
Dimensions
Internal connection diagrams
line 1
ON
ø6.4
.252
line 1
3
I>
4
6
3 (from IN=8 A)
2
with shunt terminal (-A3)
and auxiliary contacts (-Si)
2
11
.433
2
Terminal design
blade terminals
DIN 46244-A6.3-0.8
(QC .250)
42
1.65
14.5
.571
mounting hole
-P10-A3
1
ø12.2 -0.1
.480 -.004
ON
ø6.4
.252
3
2
-P10-Si
7
.276
current rating in A
-H
.453 -.004
5
11.5 -0.1
11.4
.450
.551
29
1.14
SW14
7
10
.394
50.3 (-iG2)
52.3 (-H)
1.98 (-iG2)
2.06 (-H)
I>
OFF
5
M12x1
tightening torque max. 1.5 Nm
22.5
.886
16
.630
OFF
-iG2-P10
1
10.5
.413
46
2
-K20
18.5
.728
24.5
.965
M12x1
5
.197
1.5
.059
2
.492
ø3 +0.2
.118+.008
M3.5x5.5 ISO 1207
tightening torque max. 0.8 Nm
+.008
9
.354
mounting holes
ø12.5 +0.2
9.5±0.2
.374±.008
1
Installation drawing
41
1.61
26
1.02
3
.118
max. 2.5
max .098
operating area
(reinforced insulation)
3
.118
1
.039
mounting area
(max. 2 mm/
.079 in. when
fitted with water
splash cover)
3
.118
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
2 - 50
www.e-t-a.com
Issue B
Thermal-Magnetic Circuit Breakers 3300/3400
Typical time/current characteristics
Type 3300 0.05 … 7 A
AC/DC 1)
Type 3400 0.05 … 7 A
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
10000
1000
Trip time in seconds
Trip time in seconds
1
10
1
0.1
0.01
0.01
2
0.001
1
2
Type 3300 8 … 16 A
4 6 8 10
20
40 60 80 100
… times rated current
1
AC/DC 1)
2
Type 3400 8 … 16 A
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
10000
1000
4 6 8 10
20
40 60 80 100
… times rated current
AC/DC 1)
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
10000
1000
100
100
Trip time in seconds
Trip time in seconds
100
0.1
0.001
10
1
10
1
0.1
0.1
0.01
0.01
0.001
0.001
1
1)
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
1000
100
10
AC/DC 1)
10000
2
4 6 8 10
20
40 60 80 100
… times rated current
1
Magnetic tripping currents are increased by 20% on DC supplies.
Accessories
For push buttons with M12 moulded threadneck (-iG2)
(not with manual release -H)
Hex nut with splash cover
Water splash cover,
transparent with knurled nut
X 201 296 01 black (IP64)
X 210 663 01 (IP64)
X 200 801 08 transparent,
with O-ring (IP66 and IP67)
M12x1
1)
2
4 6 8 10
20
40 60 80 100
… times rated current
Magnetic tripping currents are increased by 20% on DC supplies.
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section 9
– Technical information.
Ambient temperature °F
-22 -4
+14 +32 +73.4 +104 +122 +140
°C
-30 -20 -10 0
+23 +40 +50 +60
Derating factor
0.76 0.79 0.83 0.88 1
1.08 1.16 1.24
M12x1
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Issue B
www.e-t-a.com
2 - 51
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project