Data sheet for KL2702, Version 2.0
2-channel solid state load relay up to 230 VAC/DC
The KL2702 output terminal uses an electronic load relay to switch a mains voltage of up to 230 VAC/DC. The
switching element is a high-power MOSFET, which is connected to the power contact potential. As a
semiconductor switch, it is not subject to wear. The KL2702 terminal has two independent outputs. Its signal
state is indicated by means of light emitting diodes.
Technical data
Number of outputs
Outputs mutually locked
Connection technology
Rated load voltage
Load type
Output current per channel
Surge voltage protection
Peak current
Contact resistance
Switch-on time
Switch-off time
Switch-on delay
Switch-off delay
Electrical isolation
Leakage current
Current consumption from Power Contacts
Current consumption from K-Bus
Bit with in the process image
KL2702-0000
KL2702-0020
KL2702-0002
2 make contacts
no
no
yes
2-, 3, or 4-wire
0…230 VAC/DC (DC ... 100 Hz)
ohmic, inductive
max. 0.3 A
max. 1.5 A
max. 2 A
from 400 VAC
0.5 A (20 s),
2.5 A (20 s),
2.5 A (20 s),
1.5 A (100 ms)
7.5 A (100 ms)
7.5 A (100 ms)
typ. 2,1 Ω,
typ. 0,3 Ω,
typ. 0,3 Ω,
max. 3,2 Ω
max. 0,4 Ω
max. 0,4 Ω
4…6 ms
0.2…0.4 ms
0.2…0.4 ms
0.05…0.1 ms
5…8 ms
5…8 ms
320 µs
6.2 ms
500 V (K-Bus / field potential), 2500 VDC (1 min.)
<< 1 mA (OFF state)
only leakage and load current
typ. 10 mA
typ. 50 mA
typ. 50 mA
2 output bits
Beckhoff® and EtherCAT are registered trademarks of Beckhoff. Information is subject to change without notice and warranted only to the extent agreed in the terms
of contract. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Tel.: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com
Data sheet for KL2702, Version 2.0
Technical data
Configuration
Weight
Dimensions (w x h x d)
permissible ambient
temperature range
during operation
during storage
permissible relative humidity
Vibration/shock resistance
EMC resistance burst/ESD
permissible mounting position
Protection class
Pluggable wiring
Approval
KL2702-0000
KL2702-0020
KL2702-0002
no address or configuration setting
app. 55 g
15mm x 100mm x 70mm (aligned width 12mm)
-0°C ... +55°C
-25°C ... +70°C
5% ... 95%, no condensation
conforms to EN60068-2-6 / EN60068-2-27, EN60068-2-29
conforms to EN61000-6-2 / EN61000-6-4
variable
IP20
KS2702-0000
CE, UL, GL, ATEX CE
CE
ATEX - Special conditions
WARNING
Observe the special conditions for the intended use of
Beckhoff fieldbus components in potentially explosive areas (directive 94/9/EU)!
• The certified components are to be installed in a suitable housing that guarantees
a protection class of at least IP54 in accordance with EN 60529! The
environmental conditions during use are thereby to be taken into account!
• If the temperatures during rated operation are higher than 70°C at the feed-in
points of cables, lines or pipes, or higher than 80°C at the wire branching points,
then cables must be selected whose temperature data correspond to the actual
measured temperature values!
• Observe the permissible ambient temperature range of 0 - 55°C for the use of
Beckhoff fieldbus components in potentially explosive areas!
• Measures must be taken to protect against the rated operating voltage being
exceeded by more than 40% due to short-term interference voltages!
• The individual terminals may only be unplugged or removed from the Bus
Terminal system if the supply voltage has been switched off or if a non-explosive
atmosphere is ensured!
• The connections of the certified components may only be connected or
disconnected if the supply voltage has been switched off or if a non-explosive
atmosphere is ensured!
• The fuses of the KL92xx power feed terminals may only be exchanged if the
supply voltage has been switched off or if a non-explosive atmosphere is ensured!
• Address selectors and ID switches may only be adjusted if the supply voltage has
been switched off or if a non-explosive atmosphere is ensured!
Operation of the Bus Terminal System in potentially explosive areas (ATEX)!
Note
Pay also attention to the continuative documentation
Notes about operation of the Bus Terminal System in potentially explosive areas (ATEX)
that is available in the download area of the Beckhoff homepage http://www.beckhoff.com!
Beckhoff® and EtherCAT are registered trademarks of Beckhoff. Information is subject to change without notice and warranted only to the extent agreed in the terms
of contract. Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Tel.: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising