Evo-Lite Radiant Heating Products that perform... by people who care

Evo-Lite Radiant Heating Products that perform... by people who care
Evo-Lite Radiant Heating
Products that perform... by people who care
Contents
Identification
Page
Identification
2
2
2
Introduction
Authority
Description
Range
Types of standard panels
Composition
2
2
3
4
Performance
6
Heat outputs
Masses
Hydraulic resistances
6
7
7
Application
7
7
7
8
9
General
Comfort conditions
Selection
Typical panel arrangements
Dimensions
Style CG Panels
Styles CS/WS Panels
10
10-13
13-16
Engineering Specification 17
General
Styles
Panel Types
Panel Lengths
Composition
Accessories
Finish
Site test & working pressures
17
17
17
17
17
17
17
17
Construction
18
Handling
Storage
Preparation
Installation
Pipework connections
Installation details
Introduction
Dunham Bush Evo-Lite is a radiant heating panel system for applications
where heat-output demand requires a cost-effective solution. It realises a
simple yet innovative design, utilising basic materials with proven
manufacturing techniques. The superior product finish is complemented by
lightweight construction and simple installation.
Authority
It is accepted practice and policy at Dunham-Bush to maintain exceptional
standards in engineering and quality. To this end, Dunham-Bush operates
a quality system and is registered as a firm of assessed capability
to BS EN ISO 9001 : 2000.
Description
Range
Evo-Lite radiant panels comprise aluminium alloy sheet finished in durable
coating, with an extruded aluminium channel bonded to the upper surface.
Copper tube (which transports the heating medium) is mechanically located
inside the extruded channel with special spring clips. Optional accessories for
hanging are supplied loose.
The main element comprises an aluminium sheet panel bonded to an extruded
aluminium profile for locating copper tube. LTHW or MTHW carried in the
copper tube gives up it heat, which is radiated from the aluminium sheet.
Insulation is fitted to the upper side of the panel to prevent heat losses
from the rear of the panel; the insulation is 50mm thick mineral wool,
fully-encapsulated in aluminium foil, factory-fitted and rated as a Class 0
material.
Evo-Lite typically weighs 9.8kg/m2; it is extremely lightweight, easy to handle
and install. Installation can be completed without the need for specialist tools
or training,
18
18
18
18
18
19-22
Prices & Conditions of Sale 23
Prices
Conditions of sale
23
23
Supply
23
23
23
23
Availability
Packaging
Ordering
2
Types of standard panels
• 15mm copper tube for rapid pipework connections
• Durable white coating; any colour and gloss level from
the RAL or BS4800 ranges also available
• Fully encapsulated mineral wool insulation
to inhibit dust and particle migration
• Optional headered panels giving finished pipe circuits
• Air vents fitted as standard
• Lightweight construction for minimal support fixings and
easy handling.
• Available in single panel lengths up to 3m
• Panels can be interconnected to make longer panel
runs with multiple circuits
3
Composition - Typical parts for Evo-Lite Style CG
Composition - Typical parts for Evo-Lite Style CS
4
Composition - Typical parts for Evo-Lite Style WS
Evo-Lite Style CG - Typical panel connection
5
Performance
Heat outputs
Mean water
temperature (°C)
Ambient air
temperature (°C)
65
16
18
20
21
16
18
20
21
16
18
20
21
16
18
20
21
16
18
20
21
16
18
20
21
16
18
20
21
16
18
20
21
16
18
20
21
16
18
20
21
70
75
80
85
90
95
100
105
110
Total output (W/m)
Styles CG/CS
201
192
182
178
224
215
206
201
248
239
229
224
273
263
253
248
297
287
277
273
322
312
302
297
347
337
327
322
372
362
352
347
397
387
377
372
423
413
402
397
Style WS
226
216
205
200
253
242
232
226
281
270
259
253
308
297
286
281
336
325
314
308
364
353
342
336
393
382
370
364
422
410
399
393
451
439
428
422
481
469
457
451
Table 1: Heat outputs for Evo-Lite based on testing to BS EN 442 : Pt 2. Total output is both radiant and convective.
For style CG, approx. 60% of total output is radiant. For styles CS/WS, approx. 53% of total output is radiant.
N.B. Max flow water temperature is 120°C
6
Masses
Nominal panel length (mm)
Style CG (Ceiling Grid)
Styles CS/WS (Ceiling/Wall Surface)
600
3.6
5.7
1200
7.1
9.2
1800
10.7
12.8
2400
14.2
16.3
3000
17.8
19.8
Table 2: Masses in kg of Evo-Lite radiant panels.
Masses given include radiant panel, insulation, accessories and water content.
N.B. Style CG Evo-Lite panels have a nominal installed mass of 9.8kg/m2
Graph 1: Hydraulic resistance of Evo-Lite pipework. Note that water mass flow rates apply for each circuit in the system.
Application
General
Evo-Lite radiant panels are designed for a wide range of
applications, in particular hospitals, school classrooms,
assembly halls, residential care homes and offices.
Style CG (Ceiling Grid) panels can be fitted into a
suspended ceiling system with 600mm grid, positioned in
place of ceiling tiles.
Alternatively, style CS (Ceiling Surface) panels can be
fixed directly onto the underside of a ceiling slab or soffit.
Evo-Lite can also be mounted vertically onto a wall
surface. Style WS (Wall Surface) is used, which results in
higher heat outputs (see table 1 on page 6).
7
Any installation angle is possible. Evo-Lite can be fitted to
sloping surfaces, with the panel axis lying in any direction ;
manual vents are fitted to the highest point in the pipe
circuit. When the installed angle is greater than 10° to the
horizontal, style WS heat outputs should be used.
Comfort Conditions
It is recommended that for radiant heating systems,
comfort conditions are achieved when dry-bulb air
temperature is slightly lower than mean radiant
temperature. The combination of the two temperatures is
the dry-resultant temperature, upon which most comfort
conditions are specified.
Selection
The following guidelines are to assist the designer in
deciding the best layout for Evo-Lite:-
6. Expansion joints
Expansion joints should be fitted every 6m in a straight
panel run.
1. Heat loads
The total heat load of the room must be calculated in
accordance with recognised practice.
2. Panel run length
The total heat load should be divided by the total heat
output per metre, as given in table 1. This will then give
the require overall length radiant panels. Note that
vertical panels will give greater heat output, which
arises from greater convective heat transfer from the
panel surface.
3. Layout
Panel runs should be set out on a layout plan. Radiant
panels should be concentrated in areas of highest heat
loss i.e. around the outside perimeter of the room,
particularly, near windows. This will counteract
disproportionately high heat losses. Single or dual
circuit runs should be considered - see Water flow rates
and Hydraulic Resistances below.
7. Panel runs
Refer to page 9 for typical arrangements in a panel run.
If requested, Dunham-Bush will prepare complete
baseboard layout drawings for approval.
8. Water flow rates
To ensure rated heat outputs are achieved, water
velocity in the tube should be such the water flow is
turbulent. This maximises heat-transfer from the water,
through the tube and to the radiating surface. Water
flow rates should also be limited to inhibit noise and
erosion and high pressure drops. Water velocities
should ideally be between 0.3 - 1.0m/s.
9. Hydraulic resistances
Evo-Lite utilises 15mm OD copper tube to transport hot
water.To calculate the total pressure drop, determine
the water flow rate :Water flow
rate (kg/s)
4. Maximum mounting height
There is no maximum mounting height for Evo-Lite.
However, when mounting heights exceed 4m, the heat
load should be adjusted to allow additional losses of
radiant heat incident on walls, and stratification of air
which absorbs some heat by convection
5. Minimum mountint height
There is no minimum mounting height for Evo-Lite. For
comfort and safety the following rule of thumb can be
applied:Styles CG and CS
LTHW - minimum mounting height 2.4m
MTHW - minimum mounting height 3.0m
Contact Dunham-Bush for further information on
mounting heights and comfort conditions.
8
=
Q
Cp x ∆T
Q
= total heat output (kW)
Cp
= specific heat capacity of
water (kJ/kgK)
= approx. 4.187kJ/kgK
∆T
= water temperature
drop (K)
Obtain the hydraulic resistance from the graph 2. Note
that the water flow rate should be halved if dual circuit
panel runs are used (i.e. type EH and EJ panels)
N.B. circuit length applies for one circuit only.
Typical panel runs
9
Dimensions
DIMENSIONS Style CG - LA600 and LB600 panels
10
Style CG - LC600 and LD600 panels
11
Style CG - LE600 and LH600 panels
12
Style CG - LJ600 panel
Styles CS/WS - LA600 panel
13
Styles CS/WS - LB600 and LC600 panels
14
Styles CS/WS - LD600 and LE600 panels
15
Styles CS/WS - LH600 and LJ600 panels
16
Engineering Specification
General
Evo-Lite radiant panels shall be manufactured by
Dunham-Bush Ltd, Downley Road, Havant, Hants, PO9
2JD. The style, panel types, lengths, quantities and
accessories shall be as detailed in the schedule or as
shown on the drawings.
50mm thick mineral wool insulation shall be fitted to
the upper side of the panel to prevent heat losses
from the rear of the panel; the insulation shall be
fully-encapsulated in class 0 aluminium foil.
Interconnecting panel types (LA600, LB600, LC600,
LH600 and LJ600) shall be supplied with 15mm
compression straight couplings for on-site jointing.
Styles
Evo-Lite radiant panels shall be suitable in the following
styles for the respective application
Style CG
Ceiling grid application
Style CS
Ceiling/soffit surface application
Style WS
Wall surface application
Expansion panels (LE600) shall be supplied with
stainless steel hoses with 15mm compression joint
at each end.
Accessories
Style CG Evo-Lite shall be supplied with optional
brackets (if specified on the schedule) for suspending
from drop-rods or similar.
Panel types
Evo-Lite radiant panels, suitable for the required output
and application, shall be selected from the following list of
panel types:-
Suspension hanging kits are available for rapid
installation, and also as safety wires when panels are
suspended directly by the ceiling grid.
Styles CS and WS Evo-Lite shall be supplied with end
brackets and connection brackets for fixing to a ceiling,
soffit or wall surface, as well as end cover plates and
connection cover plates to cover and finish pipe
connections between panels.
LA600 - standard panel
LB600 - end panel
LC600 - connection panel
LD600 - single (stand-alone) panel
LE600 - expansion panel
Finish
LH600 - flow connection panel
Radiant panels, end cover plates and connection cover
plates shall be finished in standard colour white RAL 9010
- gloss level approx. 30% (satin).
LJ600 - return connection panel
Panel lengths
For all styles and panel types, panel lengths will be
selected from the following list of nominal lengths
600mm, 1200mm, 1800mm, 2400mm, 3000mm.
Composition
Evo-Lite radiant panels shall comprise aluminium alloy
sheet finished in a durable coating, with an extruded
aluminium channel bonded to the upper surface. 15mm
OD copper tube to EN 1057 shall be mechanically located
inside the extruded channel with steel spring clips. Factory
made joints shall be jointed and formed using lead free
solder fittings to make the appropriate panel circuitry.
17
Site test and working pressures
Maximum cold test pressure 12 bar gauge.
Maximum working pressure 5 bar gauge at 120°C.
Maximum recommended safe working pressure with
manual air vents 7 bar gauge
Construction
Handling
Style CG
The purchaser is responsible for off-loading. Radiant
panels are supplied ready for mounting with accessories
and insulation fitted separately. When a significant
quantity of panels is delivered, they may be palletised and
shrink-wrapped, so a fork-lift or similar of lifting equipment
is required. Radiant panels and accessories must not
dropped or suffer impact under any circumstances.
Panels are designed for suspension within a 600mm
ceiling grid; where the weight of Evo-Lite exceeds the
ceiling grid load limit, M6 drop rods or similar should be
used, with optional hanging brackets supplied by
Dunham-Bush. If panels are supported by the ceiling grid,
then safety wires should be fitted.
Style CS
Storage
Radiant panels should be stored in clean, dry indoor
conditions. Packaging should not removed until installation
takes place, unless damage in transit is suspected. Upon
receipt of product, the purchaser should examine the
panels promptly and any claims for damage will only be
accepted if, at the time of delivery, the consignment note
is endorsed with a note detailing the damage and
countersigned by the transport company.
Preparation
Style CG panels can be installed before or after ceiling
grids have been fitted. Styles CS /WS require suitable wall
or ceiling structure. The designer/installer should ensure
that fixings are suitable for the appllcation and provide
adequate support. Fixings and hangers are not supplied
by Dunham-Bush. Pipework to the panels should have
been completed as far as possible.
Installation
Reference should be made to a working layout or
services drawing, which shows how panels are arranged
and connections made. Please refer to Sitework
Instructions enclosed with the panels; further copies are
available on request.
Panels are designed for fixing direct to a ceiling slab or
soffit using end and connection brackets provided by
Dunham-Bush. End cover plates and connector cover
plates are used to finish panel joints and ends. Note that
additional braces or noggins may be required to match
panel fixing positions.
Style WS
Panels are designed for fixing direct to a wall using end
and connection brackets provided by Dunham-Bush. End
cover plates and connector cover plates are used to finish
panel joints and ends. Note that additional braces or
noggins may be required to match fixing positions.
Pipework Connections
Evo-Lite radiant panels are supplied with pipe-circuitry
complete; interconnecting panels are supplied with 15mm
compression couplings or expansion hoses, as required.
Pipework can be connected to the panel with solder,
push-fit or compression fittings; flexible hoses are
recommended to allow for rapid installation and flexibility.
Style WS Evo-Lite: Connection bracket and radiant panel
18
Installation Detail - Style CG
19
Installation Detail - Style CG
20
Installation Detail - Styles CS/WS
21
Installation Detail - Styles CS/WS
22
Prices and Conditions of Sale
Prices
Condition of sale
Dunham-Bush Ltd do not issue product price lists, but will
be pleased to supply a written quotation upon request.
Refer to ‘Ordering’ below for guidance on information
required for quoting.
Dunham-Bush standard conditions of sale appear on all
quotations and order acknowledgements. Additional
copies are available upon request.
Supply
Availability
Ordering
Evo-Lite radiant panels are supplied direct from our
manufacturing plant in Havant. Availability varies with
demand and should be checked at the time of ordering.
Contact a Dunham-Bush sales representative for
prevailing lead times.
To enable rapid and efficient processing of your order,
please refer to the relevant quotation and/or
correspondence. All orders should be sent to the
Dunham-Bush respresentative who provided the quotation.
Packaging
The following information should be supplied to
Dunham-Bush for the selection and preparation of a
baseboard layout (BL) drawing.
Radiant panels are packed for storage in dry, indoor
conditions. If specified, each panel will be marked with its
own unique stencil reference for on-site identification.
a) Panel style
b) Quantity and lengths of panel runs
c) Details of special finish or accessories required
d) Panel markings or stencil references for on-site
identification
e) A dimensioned drawing with panel runs marked on
clearly, with connections and circuitry shown.
23
Q
Quality
Dunham-Bush operates a quality control
system and is a firm of assessed capability
to BS EN ISO 9001 : 2000
Whatever the product, wherever its eventual
destination, the Dunham-Bush design and
manufacturing policy has always been firmly
based on technical quality.
Product support
In the United Kingdom and Ireland,
Dunham-Bush have a network of sales
agents and representatives, situated at
strategic locations, to provide local support
in pricing and selection. Further technical
and application support is available at
Dunham-Bush head office and factory
in Havant.
Other Dunham-Bush products
Series
Series
Series
Series
AM fan convectors
BM fan convectors
CM fan convectors
L fan convectors
Series F fan coil units
Panther fan coil units
Cougar fan coil units
Leopard fan coil units
Lynx fan coil units
Evolution radiant panels
Dunham Strip radiant panels
Voidpak air handling units
ECS air handling units
Sentry air curtains
Finvector perimeter heating system
Trench Finvector heating system
Series UH unit heaters
Warmsafe LST radiators
Systema gas fired products
Thermocold Packaged chillers
Manufacturer reserves the
right to change any product
specification without notice.
DUNHAM-BUSH Ltd.
Downley Road, Havant
Hampshire PO9 2JD
Tel: 023 9247 7700
Fax: 023 9245 0396
email: info@dunham-bush.co.uk
www.dunham-bush.co.uk
24
PDS-1000-H-0220-01
March 2002
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF