datablad 146 2eb11

datablad 146 2eb11
GAMMA instabus
Technical Product Information
May 2005
Interface UP 142E/146E
Product
DELTA profil
USB Interface
pearl grey
titanium white
anthracite
silver
5WG1 142-2EB_1
5WG1 146-2EB_1
DELTA ambiente
5WG1 146-2EB01
5WG1 146-2EB11
5WG1 146-2EB21
5WG1 146-2EB71
arctic white
cosmos grey
royal blue
DELTA style
5WG1 142-2EB01
5WG1 142-2EB11
5WG1 142-2EB21
titanium white
5WG1 146-2EB11
To be ordered separately from the DELTA range
Frame
____
cut-out frames
____
Tier frame
Bus coupling
unit
titanium white
5TG1 1328
UP 110; UP 114
B1
B9
B1
B2
B3
B4
B5
B6
B7
B8
B9
B2
B3
B4
B5
B6
B7
Bus coupling unit UP
Socket connector *)
Mounting screws *)
Frame
Base module *)
Supporting plate *)
Note label *)
Cover *)
Tier frame (style)
B8
Diagram 1: USB Interface flush mounted
Siemens AG
Automation and Drives Group
Electrical Installation Technology
P.O. Box 10 09 53, D-93009 Regensburg
*) Scope of supply
UP 14_, 4 pages
© Siemens AG 2005
Subject to change without prior notice
Technical Manual
Update: http://www.siemens.com/gamma
2.11.1.9/1
GAMMA instabus
Technical Product Information
May 2005
Interface UP 142E/146E
5WG1 142-2EB_1
5WG1 146-2EB_1
Product and Applications Description
Installation Instructions
The USB interface enables with its built-in USB socket
(Type B) a personal computer (AT compatible PC) to be
attached for addressing, parameterising, visualising,
logging and diagnosis of bus devices.
With the USB interface it is possible to operate all bus
devices isolated and under observation of the standardised EIB protocol in the whole bus system.
Communication with the BCU is carried out using one
of two protocols, standard protocol or FT1.2 protocol,
the switching is done by the connected PC and depends on the used BCU.
The USB interface is compatible to USB 1.1, the transmission rate between the PC and the interface is therefore up to 12 Mbit/s.
The connection of the USB interface and the PC is
arranged between the USB socket of the USB interface
and any USB socket of the PC or a connected USB
hub.
The required USB cable is not part of the shipment but
has to be bought separately, e.g. at an authorised computer store.
The interface is slid onto the bus coupling unit UP together with its frame. It requires a bus coupling unit to
work properly.
It is possible e.g. to remove a UP push button from its
bus coupling unit UP and replace it with an interface
UP. This does not destroy the application program of
the bus coupling unit UP.
The bus coupling unit UP and frame are not included
and therefore have to be ordered separately. Cut-out
frames should be used for DELTA profil.
The device may be used for permanent interior installations in dry locations within box mounts (in combination
with a bus coupling unit UP).
Note:
The USB interface is supported by ETS only from ETS3
onwards!
10 CO Dummy 700002
• converts the bus coupling unit UP into interface mode
and erases the bus coupling unit UP memory
Update: http://www.siemens.com/gamma
2.11.1.9/2
• The device must be mounted and commissioned by
an authorised electrician.
• The device must not be mounted in box mounts together with 230 V devices.
• The device may be mounted to switch and socket
combination box mounts (together with a bus coupling unit UP) if VDE-certified devices are used exclusively.
• The prevailing safety rules must be heeded.
• For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical data
Power supply
via bus coupling unit UP and via USB from the connected PC
Transmission rate
• between PC and USB interface:
USB1.1 speed (max. 12 MBit/s)
• between USB interface and bus coupling unit:
9600 (standard protocol) or 19200 Baud (FT1.2 protocol),
depending on the used BCU and PC program
• between USB interface and bus line:
9600 Baud
Connection cable
available from authorised computer stores
(normal USB cable for PC peripherals with plugs A-B)
Application programs
Technical Manual
V WARNING
Connections
• 10-pin connector (PEI): for connection to a
bus coupling unit UP
• USB socket type B
length of data cable: max. 5 m
UP 14_, 4 pages
© Siemens AG 2005
Subject to change without prior notice
Siemens AG
Automation and Drives Group
Electrical Installation Technology
P.O. Box 10 09 53, D-93009 Regensburg
GAMMA instabus
Technical Product Information
May 2005
Interface UP 142E/146E
5WG1 142-2EB_1
5WG1 146-2EB_1
Physical specifications
• housing: plastic
• dimensions (L x W x D): 65 x 65 x 42 mm (without
PEI)
• weight: approx. 65 g
• fire load: approx. 1450 kJ
• installation: slide onto bus coupling unit UP and secure with the mounting screws included
Location and function of the operating elements
A4
Electrical safety
• degree of pollution (according to IEC 60664-1): 2
• protection (according to EN 60529): IP 20
• protection class (according to IEC 61140): III
• overvoltage class (according to IEC 60664-1): III
• bus: safety extra low voltage SELV DC 24 V
• device complies with
EN 50 090-2-2 and IEC 60664-1
Reliability
rate of failure: <500 fit at 40 °C
Electromagnetic compatibility
complies with EN 50081-1, EN 61 000-6-2 and EN
50090-2-2
A1
A3
A2
Diagram 2: Main module and supporting plate
A1
A2
A3
A4
Socket connector
Mounting screws
USB socket type B
Base modul
Environmental specifications
• climatic conditions: EN 50 090-2-2
• ambient temperature operating: - 5 ... + 45 °C
• storage temperature: - 25 ... + 70 ° C
• relative humidity (non-condensing): 5 % to 93 %
Certification
EIB certificate
CE norm
complies with the EMC regulations (residential and
functional buildings), and low voltage regulations
Siemens AG
Automation and Drives Group
Electrical Installation Technology
P.O. Box 10 09 53, D-93009 Regensburg
UP 14_, 4 pages
© Siemens AG 2005
Subject to change without prior notice
Technical Manual
Update: http://www.siemens.com/gamma
2.11.1.9/3
GAMMA instabus
Technical Product Information
May 2005
Interface UP 142E/146E
5WG1 142-2EB_1
5WG1 146-2EB_1
Mounting and wiring
Dismounting
General description
The interface is slid onto the bus coupling unit UP
together with its frame.
The UP bus coupling unit is mounted and connected to
the UP box mount (see mounting instructions of bus
coupling unit UP).
Sequence of assembly
- The base module (B5) is slid together with the frames
(B4/B9) onto the bus coupling unit UP (B1).
- Drive the mounting screws (B3) into (B1).
- Mount the supporting panel (B6) onto the base module (B5).
- Snap on the cover (B8).
- The cover of the note label (B7) can be removed by
meshing into the recesses on its side faces if a note
shall be applied.
• Seize the cover (B8) on both sides and remove it by
sliding it upwards.
• Loosen the screws (B3) and remove (B5) from (B1).
Dimension diagram
DELTA profil, DELTA ambiente and DELTA style
65
Dimensions in mm
B1
B9
B2
65
B3
9
40
B4
B5
B6
General Notes
•
B7
B8
Diagram 3: Mounting the USB interface
B1
B2
B3
B4
B5
B6
B7
B8
B9
Bus coupling unit UP
Socket connector
Mounting screws
Frame
Base module
Supporting panel
Note label
Cover
Tier frame (style)
Technical Manual
Update: http://www.siemens.com/gamma
2.11.1.9/4
Any faulty devices should be returned to the local
Siemens office.
•
If you have further questions about the product,
please contact our Technical Support:
℡ +49 (0) 180 50 50-222
" +49 (0) 180 50 50-223
# www.siemens.com/automation/support-request
UP 14_, 4 pages
© Siemens AG 2005
Subject to change without prior notice
Siemens AG
Automation and Drives Group
Electrical Installation Technology
P.O. Box 10 09 53, D-93009 Regensburg
Was this manual useful for you? yes no