Technical Data – All Heaters Part L2B Compliant EVD Vertical Ducted

Technical Data – All Heaters Part L2B Compliant EVD Vertical Ducted
All Heaters
Part L2B Compliant
Technical Data –
External Oil and Gas Cabinet Heaters
For Models
EVD Vertical Ducted
EHD Hortizontal Ducted
Range & Configuration
Vertical Forced Draught Oil and Gas 29 kW to 381 kW
Horizontal Forced Draught Oil and Gas 58 kW to 381 kW
Specification
Cabinet: Machine punched and folded to form a robust
monocoque cabinet with access to the burner and controls
compartment via a front located access door. For added
weather protection all external panels are manufactured
from electro-zinc plated steel and then finished with
stove hardened epoxy powder coat with a durable
Kestrel Grey paint finish. All cabinets are IP44 rated.
Heat Exchanger: The combustion chamber/
heat exchanger assembly has been designed
to combine optimum thermal efficiency with
extended service life. Manufactured from
304/316 stainless steel each fabricated assembly
comprises of a drum type combustion chamber
coupled to a tubular heat exchanger.
Burner: All oil and gas fired cabinet heaters
have been carefully matched with a fully
automatic packaged pressure jet oil or forced
draught gas burner. Oil fired cabinet heaters
are complete with factory fitted fire valve
and oil filter. Models 1200 and 1300 oil and
1300 gas are fitted as standard with high/low
burners. High/low and modulating gas burners
are available as an option for models 200 and
above.
Efficiency: Each heater within the range has been
designed and developed with fuel efficiency in mind
and efficiencies exceed the mandatory requirements
of CE legislation. Additionally for the United Kingdom
market all heater efficiencies are compliant with the
needs of Part L2B of the 2006 Building Regulations whilst
most models within the range have also been rated to
meet the criteria necessary for inclusion into the Enhanced
Capital Allowance (ECA) scheme.
Fuel: Oil heaters are design to operate on Class D light
distillate ‘gas oil’ having a maximum viscosity of 4.5 c.St at 20oC
(35 sec Redwood at 100oF). Forced draught gas heaters can be
specified to operate on either natural gas (G20) or Lpg Propane
(G31). Most oil fired models can be operated on kerosene.
Fan: Air movement is provided by either a single or duplex
forward curved blade dynamically balanced centrifugal fan
assembly complete with double inlet rotors. Fans on models
100 - 300 are powered by integral motors whilst all others
employ pulley and belt drive arrangements.
Air Distribution: Air is discharged through a duct outlet
spigot located on the top face of a vertical heater and on the left
hand or right hand end of a horizontal heater.
Generally return air to the heaters is via a duct spigot located
on either the left hand or right hand side of a vertical heater (a
rear located spigot is an option for certain vertical models) or,
for horizontal heaters, return air entry is on the opposite end of
the heater to the duct outlet spigot. However heaters can, as an
option, be fitted with fresh air inlet louvres.
Controls: Benson cabinet heaters are supplied ready for fully
automatic operation and are complete with both safety and
comfort controls. Each heater is fitted with a safety overheat
thermostat as well as a time and temperature control system.
Two alternative control options are available.
As standard, heaters are offered with a digital time switch,
mechanical day temperature and frost protection thermostats.
Alternatively heaters may be specified with an optimised control
that includes a secure entry code facility, an optimised digital time
switch with override facility, electronic day thermostat and frost
protection thermostat.
Unless otherwise specified the controls for both vertical and
horizontal external heaters are housed within a console for
remote mounting. Inter-connecting wiring between heater and
remote consoles is by others.
All heaters have the facility of ‘fan only’ operation for summer
air movement.
Testing, Approvals & Certification: Benson Heating
is accredited with ISO 9001 quality assurance certification
– certificate number FM14923. All gas fired heaters have been
type tested by an independent notified body and conform to
CE requirements. Each heater is inspected and test fired prior
to despatch.
Guarantee: Benson cabinet heaters are provided with a
comprehensive package of guarantees covering both the
appliance and the combustion chamber/heat exchanger, which
has the further benefit of an extended guarantee. For sales
within the United Kingdom the guarantee includes a ‘whole
appliance’ twelve months parts and labour guarantee supported
by a further twelve months ‘parts only’ guarantee whilst the
combustion chamber/heat exchanger assembly has a ten year
time related warranty. For cabinet heaters supplied to overseas
markets please refer to the relevant country documentation. All
guarantees are subject to terms and conditions.
Specification
External Vertical & Horizontal Cabinet Heaters EVD/EHD
Model
100
125
150
200
250
300
400
43
58
73
86
117
3
3
3
2.15
2.65
3.11
Vertical Only
Output
Airflow
Airside Data
Fan
Static
Electrics
29
3
3
3
3
m3/s
0.61
0.71
0.71
1.03
1.39
1.39
700
800
1000
1200
1300
132
177
205
235
284
350
381
3
3
3
3.40
4.32
4.86
6.88
6.88
Standard
Pa
75
100
100
125
100
100
137
150
175
188
125
175
250
250
Up-rated
Pa
n/a
n/a
n/a
n/a
n/a
n/a
175
200
225
225
188
225
n/a
n/a
Standard
V/ph/hz
Optional
V/ph/hz
EVD
600
Vertical & Horizontal
kW
ECA Approved
36
500
230/1/50
n/a
415/3/50
415/3/50
230/1/50
n/a
Height
mm
1665
1665
1665
1915
1915
1915
2040
2040
2140
2140
2125
2125
2712
2712
Width
mm
660
660
660
660
660
660
740
740
916
916
1100
1100
1244
1244
Depth
mm
1165
1165
1165
1430
1430
1430
1590
1590
2200
2200
2400
2400
2550
2550
Length
mm
n/a
n/a
n/a
1960
1960
1960
2085
2085
2185
2185
2170
2170
2757
2757
Width
mm
n/a
n/a
n/a
1661
1661
1661
1801
1801
2456
2456
2676
2676
2816
2816
Height
mm
n/a
n/a
n/a
750
750
750
830
830
1006
1006
1440
1440
1590
1590
Flue Diameter
mm ø
125
125
125
150
150
175
175
175
200
200
225
225
250
250
Combustion Air Spigot
mm ø
125
125
125
125
125
125
150
150
150
150
150
150
150
150
Overall
Dimensions
EHD
Noise Level
Nett Weight
dBA
62
64
64
67
67
67
69
70
72
72
73
74
74
74
EVD
kg
230
230
230
280
280
280
380
380
595
610
720
735
1200
1200
HVD
kg
n/a
n/a
n/a
300
300
300
400
400
625
640
750
765
1240
1240
Note
Where heaters are selected for the UK Enhanced Capital Allowance (ECA)
scheme then they must be specified with CP4 controllers
All models have efficiency levels which meet with the minimum efficiency
requirements of UK Part L2B Building Regulations
Air handling data is assessed at room ambient conditions
Overall heater height excludes flue and cowl - for more detailed dimensions
refer to dimensions page
Overall dimensions model EHD include base frame.
Noise levels are for units with both inlet and outlet ductwork attached and
measured 3m from appliance
Installation
Installation Standards: Benson oil and gas fired external cabinet
heaters must be installed and commissioned by a competent person
and in accordance with Benson’s installation and commissioning
instructions, relevant local and national standards, Codes of Practice,
and any requirements of Local Authorities, Fire Officer or insurers.
Air Supply: External cabinet heaters are designed specifically
for outdoor location and as such obtain necessary combustion air
directly from an external source. Care should be taken to ensure
that the combustion air inlet louvre or combustion air duct (if fitted)
is not modified, repositioned, damaged or in anyway restricted.
Siting: The position chosen for the heater will need to take account
Flues: External cabinet heaters are supplied complete with a flue kit
of the following points External cabinet heaters are specifically designed for external
location and must be positioned on a flat, level and noncombustible surface. Care should always be taken to ensure
that any base, platform or structural steelwork supporting
the heater is structurally adequate and that there is both
access and provision for maintenance purposes.
Care should be taken to ensure that the recommended
clearances are maintained and that there is sufficient
space for the connection of discharge and/or
return ductwork or, if fitted, that there is sufficient
clearance for the passage of air to the fresh air inlet
weather louvre.
Consideration should be given to the location
of the appliance so that the flue exit point does
not discharge exhaust gases beneath or adjacent
to doors, windows, building overhangs or in
passageways.
So far as controls are concerned siting will often
depend upon the type selected. Where controls
have in-built or remote temperature sensors then
consideration should be given to ensure that the
sensor is located in a position which adequately
reflects the working zone serviced by the heater.
Sensors should not be located in areas subject to
cold draughts.
In case of doubt relating to any aspect of heater or
control siting please consult with Benson.
Oil & Gas Pipework: The oil and gas supply
pipework should be sized and installed with due regard
to all relevant standards and legislation, flow rates and the
maximum/minimum inlet pressure requirements of both oil
and gas fired heaters. Isolating gas cocks, oil line gate valves and
service unions should be provided for each heater.
which permits the free discharge of flue gases directly to atmosphere.
For particular applications it may be possible to extend the flue to
enable the point of discharge to be repositioned. However should
this be necessary then the diameter of flue must not be less than
stated in the data sections of this brochure.
In the event that it is necessary to extend the flue then the route and
exit point needs to be selected carefully and it is recommended that
the installer consult the installation and commissioning instructions or
Benson before commencing installation.
Further Information: The foregoing is given for guidance
purposes. More detailed information can be found within the
relevant installation, commissioning and servicing instructions or
alternatively contact Benson.
Installation Data
External Vertical & Horizontal Cabinet Heaters EVD/EHD
Model
100
125
150
200
250
300
400
Vertical Only
Fuel
Connection
Oil
Gas
Minimum Gas Inlet
Pressure
Fuel Consumption
230/1/50
Electrics
BSP/Rc
415/3/50
3
⅜8
3
⅜
8
3
500
600
700
800
1000
1200
1300
Vertical & Horizontal
⅜8
3
⅜
8
3
⅜8
3
⅜8
3
⅜8
3
⅜
8
3
⅜8
3
⅜8
3
⅜8
3
⅜8
3
⅜8
3
⅜8
BSP/Rc
½
½
½
½
½
½
¾
¾
1
1¼
1¼
1¼
1½
2
Nat Gas
mbar
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
17.5
Lpg
mbar
37.0
37.0
37.0
37.0
37.0
37.0
37.0
37.0
37.0
37.0
37.0
37.0
37.0
37.0
Oil
l/h
3.3
4.2
5.0
6.6
8.6
10.0
13.6
15.2
20.3
24.1
27.1
33.0
37.5
44.5
Nat Gas
3
m /h
3.3
4.2
5.1
6.7
8.5
10.1
13.6
15.3
20.2
24.3
27.0
33.0
40.7
45.8
Lpg
m3/h
1.3
1.7
2.0
2.6
3.4
4.0
5.4
6.0
8.0
9.6
10.7
13.0
16.1
18.1
Motor
kW
0.55
0.55 0.55
0.99
0.99
0.99
1.50
2.20
n/a
n/a
n/a
n/a
n/a
n/a
FLC
amp
3.2
4.8
4.8
6.0
7.2
7.2
12.0
14.0
n/a
n/a
n/a
n/a
n/a
n/a
Motor
kW
n/a
n/a
n/a
1.0
1.0
1.0
1.5
2.2
3.0
3.0
4.0
5.5
n/a
n/a
FLC
Amp
n/a
n/a
n/a
2.2
2.2
2.2
3.6
5.2
6.5
6.5
8.4
11.0
n/a
n/a
kW
n/a
n/a
n/a
n/a
n/a
n/a
2.2
3.0
4.0
4.0
5.5
7.5
11.0
11.0
Amp
n/a
n/a
n/a
n/a
n/a
n/a
5.2
6.5
8.4
8.4
11.0
14.0
24.0
24.0
Flue Diameter
mm ø
125
125
125
150
150
175
175
175
200
200
225
225
250
250
Combustion Air Spigot
mm ø
125
125
125
125
125
125
150
150
150
150
150
150
150
150
Front
mm
500
500
500
500
500
500
600
600
600
900
900
900
900
900
Side
mm
150
150
150
150
150
150
150
150
150
150
400
400
500
500
Rear
mm
700
700
700
1000
1000
1000
1200
1200
1500
1500
2000
2000
2000
2000
Front
mm
n/a
n/a
n/a
500
500
500
600
600
600
900
900
900
900
900
415/3/50
Motor
Up-rated Fan FLC
EVD
Installation
Clearances
EHD
Nett Weight
Top
mm
n/a
n/a
n/a
150
150
150
150
150
150
150
400
400
500
500
Rear
mm
n/a
n/a
n/a
1000
1000
1000
1200
1200
1500
1500
2000
2000
2000
2000
EVD
kg
230
230
230
280
280
280
380
380
595
610
720
735
1200
1200
HVD
kg
n/a
n/a
n/a
300
300
300
400
400
625
640
750
765
1240
1240
Note
Fuel consumption and output figures based upon gross calorific values as -
Class D light distillate fuel oil @ 37.9 MJ/l
Natural gas (G20) @ 37.78 MJ/m3
Lpg Propane (G31)@ 95.65 MJ/m3
Electrics details in bold refer to standard configurations, other
configurations optional
Clearances refer to heaters with standard return air louvre arrangements
Models 1200 and 1300 have an up-rated fan motor as standard
Dimensions
External Vertical Cabinet Heaters EVD
Model
100
125
150
200
250
300
400
500
600
700
800
1000
1200
1300
1620
1620
1620
1870
1870
1870
1995
1995
2095
2095
2080
2080
2667
2667
916
916
1100
1100
1244
1244
2200
2200
2400
2400
2550
2550
510
510
505
505
797
797
200
200
225
225
250
250
968
1068
1068
1054
1054
1372
1372
714
890
890
1000
1000
1086
1086
A
All
mm
B
All
mm
660
660
660
660
660
660
740
740
C
All
mm
1165
1165
1165
1430
1430
1430
1590
1590
D
All
mm
408
408
408
335
335
335
335
335
E
All
mm ø
125
125
125
150
150
175
175
175
F
All
mm
835
835
835
984
984
984
968
G
All
mm
570
570
570
634
634
634
714
H
All
mm
570
570
570
770
770
770
950
950
1120
1120
1450
1450
1365
1365
J
All
mm
640
640
640
690
690
690
770
770
945
945
1130
1130
1203
1203
K
All
mm
522
522
522
702
702
702
904
904
1078
1078
1145
1145
1150
1150
L
All
mm
348
348
348
427
427
427
542
542
692
692
654
654
796
796
Notes
Side return air inlet spigot shown is optional and can be left hand or right hand side. Side
must be specified at time of order
Rear return air inlet spigot is optional and is available for certain models - details on request
Dimensions
External Horizontal Cabinet Heaters EHD
Note
Heater shown is with airflow right to left.
Left to right airflow optional - to be specified at time of order.
Model
A
All
mm
200
250
300
400
500
600
700
800
1000
1200
1300
1870
1870
1870
1995
1995
2095
2095
2080
2080
2667
2667
B
All
mm
660
660
660
740
740
916
916
1350
1350
1500
1500
C
All
mm
1430
1430
1430
1590
1590
2200
2200
2400
2400
2550
2550
D
All
mm
335
335
335
335
335
510
510
505
505
797
797
E
All
mm ø
150
150
175
175
175
200
200
225
225
250
250
F
All
mm
984
984
984
968
968
1068
1068
1054
1054
1372
1372
G
All
mm
634
634
634
714
714
890
890
1000
1000
1086
1086
H
All
mm
770
770
770
950
950
1120
1120
1450
1450
1365
1365
J
All
mm
570
570
570
640
640
725
725
665
665
675
675
K
All
mm
1585
1585
1585
1725
1725
2380
2380
2600
2600
2740
2740
L
All
mm
1806
1806
1806
1935
1935
2035
2035
2020
2020
2610
2610
www.bensonheating.com
Ludlow Road
Knighton
Powys
LD7 1LP
Telephone (main) + 44 (0)1547 528534
Facsimile (main) + 44 (0)1547 520399
Telephone (sales) + 44 (0)1547 529245
Facsimile (sales) + 44 (0)1547 529195
e.mail information@bensonheating.co.uk
sales@bensonheating.co.uk
exportsales@bensonheating.co.uk
Benson Heating is a division of the Benson Group of Companies Limited
Guarantees and warranties subject to terms and conditions. It is the policy of Benson Heating to pursue a programme of continuous development.
We therefore reserve the right to change models, types, specifications and prices without prior notice. Details are believed to be correct but do not form the