3331
Temperature converter, loop-powered - isolated
3331
– Excellent accuracy, better than 0.05% of span
– Slimline housing of 6 mm
– Excellent EMC performance and 50/60 Hz noise suppression
– Selectable < 30 ms / 300 ms response time
– Pre-calibrated temperature ranges selectable via DIP-switches
Application
• The 3331 temperature converter measures a standard Pt100,
TC J and K temperature sensor, and provides an isolated
passive analog current output signal.
• High 2 port isolation provides surge suppression and protects
the control system from transients and noise.
• The 3331 can be mounted in the safe area or in Zone 2 /
Division 2 areas.
• Approved for marine applications.
Connections
Technical characteristics
• Flexibly loop powered by 5.5...35 VDC via connectors.
• < 30 ms fast response time with simultaneous sensor error
detection when selected.
• Selectable 300 ms response time when signal dampening is
needed.
• Selectable internal/external CJC.
• Excellent conversion accuracy in all available ranges, better
than 0.05% of span.
• Meeting the NAMUR NE21 recommendations, the 3331
provides top measurement performance in harsh EMC
environments.
• The device meets the NAMUR NE43 standard defining out of
range and sensor error output values.
• All terminals are protected against overvoltage and polarity
error.
• High galvanic isolation of 2.5 kVAC.
• Excellent signal/noise ratio of > 60 dB.
Mounting / installation / programming
• Selectable DIP-settings for easy configuration of more than
1000 factory calibrated measurement ranges.
• The narrow 6 mm housing allows up to 165 units to be
mounted per meter of DIN rail, without any air gap between
units.
• Wide ambient temperature range of -25...+70°C.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
-25°C to +70°C
-40°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...25 Hz........................................
Vibration: 25...100 Hz....................................
113 x 6.1 x 115 mm
70 g
DIN EN 60715/35 mm
0.13 x 2.5 mm2 / AWG 26...12
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1.6 mm
±4 g
Common specifications
Supply
Supply voltage............................................... 5.5...35 VDC
Isolation voltage
Isolation voltage, test /
working........................................................... 2.5 kVAC / 300 VAC
(reinforced)
Zone 2 / Div. 2................................................ 250 VAC
Response time
Response time (0...90%, 100...10%)............. < 30 ms / 300 ms (selectable)
Voltage drop...................................................
Internal consumption......................................
Signal / noise ratio.........................................
Programming.................................................
Signal dynamics, input...................................
Signal dynamics, output.................................
EMC immunity influence................................
Extended EMC immunity: NAMUR
NE 21, A criterion, burst.................................
Incorrect DIP-switch setting
identification...................................................
5.5 VDC
19 mW...0.8 W
> 60 dB
DIP-switches
23 bit
18 bit
< ±0.5% of span
< ±1% of span
3.5 mA
Min. measurement range (span)
- TC J & K....................................................... 50°C
Accuracy: the greater of................................. Better than 0.05% of span or
0.5°C
Temperature coefficient: the
greater of........................................................ 0.1°C/°C or ≤ ±0.01%/°C
Sensor cable resistance................................. < 5 kΩ per wire
Cold junction compensation
(CJC): Accuracy @ external
Pt100 input..................................................... Better than ±0.15°C
Cold junction compensation
(CJC): Accuracy @ internal
CJC................................................................ Better than ±2.5°C
Internal CJC error detection........................... Yes
External CJC error detection.......................... Yes - selectable via DIPswitch
Open Thermocouple detection....................... Yes - selectable via DIPswitch
Output specifications
Common output specifications
Updating time................................................. 10 ms
Current output
Signal range...................................................
Programmable signal ranges.........................
Load (@ current output).................................
Load stability..................................................
0...23 mA
4...20 and 20...4 mA
≤ (Vsupply - 5.5) / 0.023 [Ω]
≤0.01% of span / 100 Ω
Sensor error indication................................... 3.5 mA or 23 mA / acc. to
NAMUR NE43 or OFF
Observed authority requirements
EMC............................................................... 2014/30/EU
LVD................................................................ 2014/35/EU
RoHS.............................................................. 2011/65/EU
Approvals
ATEX 2014/34/EU.......................................... KEMA 10ATEX0147 X, II 3 G
Ex nA IIC T4 Gc
IECEx............................................................. KEM 10.0068X
FM.................................................................. 3041043-C
DNV Marine.................................................... Stand. f. Certific. No. 2.4
GL.................................................................. V1-7-2
EAC................................................................ TR-CU 020/2011
UL................................................................... UL 61010-1
Input specifications
RTD input
Temperature range, Pt100............................. -200...+850°C
Min. measurement range (span).................... 10°C
Accuracy: the greater of................................. Better than 0.05% of span or
0.1°C
Temperature coefficient: the
greater of........................................................ 0.02°C/°C or ≤ ±0.01%/°C
Sensor current............................................... < 150 µA
Sensor cable resistance................................. < 50 Ω per wire
Effect of sensor cable resistance
(3-/4-wire)....................................................... < 0.002 Ω / Ω
Sensor error detection................................... Yes - selectable via DIPswitch
Broken sensor detection................................ > 800 Ω
Shorted sensor detection............................... < 18 Ω
3331-042916
TC input
Temperature range, TC J............................... -100...+1200°C
Temperature range, TC K.............................. -180...+1372°C