High Performance Current Transducer IT 600-S ULTRASTAB

High Performance Current Transducer IT 600-S ULTRASTAB
Made by LEM Danfysik
High Performance Current Transducer
IT 600-S ULTRASTAB
IPM = 0 .. 600 A
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Features
Electrical data
IPN
IPN
IPM
Primary nominal current DC
Primary nominal current rms
Primary current, measuring range
600
425
0 .. ± 600
A
A
A
ÎP
RM
± 3000
RM min RM max
A
IS
ISN
KN
VC
Max overload capability 100 ms 1)
Measuring resistance
Over operating current, temperature and
supply voltage range
Secondary current
Secondary nominal current rms
Conversion ratio
Supply voltage (± 5 %)
2.5
2.5
0 .. ± 400
282
1 : 1500
± 15

mA
mA
IC
Current consumption ± 15 V
200 + IS
mA
V
Accuracy - Dynamic performance data

L
IOE
IOE
TCIOE
Linearity error 2)
Electrical offset current + self magnetization +
effect of earth magnetic field @ TA = 25°C 2)
Offset stability (no load) 2)
Temperature coefficient of IOE (10°C .. 50°C) 2)
Offset vs. power supply stability @ TA = 25°C 2)
@ VC = ± 15 V ± 5%
1
ppm
< 20
<1
< 0.2
ppm
ppm/month
ppm/K
< 1.5
ppm/% of
VC = ± 15 V
TS
RS
m
Special features
● D-Sub 9 pole male output
interface connector
● Output indicates the transducer
state.
Advantages
●
●
●
●
●
●
●
●
●
Very high accuracy
Excellent linearity
Extremely low temperature drift
Wide frequency bandwidth
High immunity to external
electrostatic and magnetic fields
interference
No insertion losses
High resolution
Low noise on output signal
Low noise feedback to main
conductor.
Applications
General data
TA
● Closed loop (compensated)
current transducer using an
extremely accurate zero flux
detector
● Electrostatic shield between
primary and secondary circuit.
Ambient operating temperature
Humidity (non condensing)
Ambient storage temperature
Humidity (non condensing)
Secondary coil resistance @ TA = 25°C
Mass
10 .. + 50
20 - 80 %
- 20 .. + 85
20 - 80 %
28
1
°C
RH
°C
RH

kg
Notes: 1) Single pulse only, not AC.
The transducer may requires a few seconds to return to normal operation
when autoreset system is running.
2)
All ppm figures refer to secondary measuring range 400 mA.
● Feed back element in high
performance gradient amplifiers
for MRI
● Feed back element in precision
current regulated devices (power
supplies...)
● Calibration unit
● Precise and high stability
inverters
● Energy measurement
● Medical equipment.
Application domain
● Industrial and Medical.
Page 1/5
100225/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Made by LEM Danfysik
Current Transducer IT 600-S ULTRASTAB
Isolation characteristics
Between primary and secondary
Vb
Vd
Vw
Vb
dCp
dCI
CTI
Rated isolation voltage rms, reinforced isolation
Rated isolation voltage rms, single isolation
with IEC 61010-1 standards and following conditions
- Over voltage category III
- Pollution degree 2
Rms voltage for AC isolation test, 50/60 Hz, 1 min
Impulse withstand voltage 1.2/50 μs
Rated isolation voltage rms, reinforced isolation
Rated isolation voltage rms, single isolation
with EN 50178 standards and following conditions
- Over voltage category III
- Pollution degree 2
Creepage distance
Clearance distance
Comparative Tracking Index (Group I)
300
2000
V
V
4.9 1)
9.1
600
1000
kV
kV
V
V
10
10
600
mm
mm
V
If isolated cable is used for the primary circuit, the voltage category could be
improved with the following table (for single isolation) (IEC 61010-1 standard):
Cable isolated (primary)
Note:
Category
HAR03
2150 V CAT III
HAR05
2250 V CAT III
HAR07
2350 V CAT III
1)
Between primary and secondary + shield.
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/5
100225/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Made by LEM Danfysik
Current Transducer IT 600-S ULTRASTAB
Output noise figures: @ 25°C
Random Noise ppm (rms):
0 – 10 Hz
0 – 10 kHz
0 – 50 kHz
< 0.05
<3
< 10
Re-injected noise measured on primary cable
(DC - 50 kHz)
< 10
μVRMS
Dynamic performance data
BW Frequency bandwidth for small signal 0.5 %, of IPN (DC)
(± 3 dB)
di/dt di/dt accurately followed
tr
Response time 1) to 90 % of IPN step
DC .. > 100
> 100
<1
kHz
A/μs
μs
Note: 1) With a di/dt of 100 A/μs.
Page 3/5
100225/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Made by LEM Danfysik
Current Transducer IT 600-S ULTRASTAB
Over current protection - Electrical specification - Status
As soon as electrical saturation appears, the transducer switches from normal
operation to over current mode.
This electrical saturation appears in any case beyond 1.1 time the current range.
The primary current corresponding to this trip level is related to the temperature
inside the transducer.
Under these conditions:
● the contact (operation status) between pin 8 to 3 (of D-SUB-9 connector)
switches off, this contact becomes open.
● Fault level (off state)
IP > 110 % of IPN DC
● Max voltage pin 8 to pin 3, off-State
30 V
● Max current pin 8 to pin 3, on-State
6 mA
● Reverse voltage pin 8 to pin 3, off-State
6V
To maintain safe start-up RM must not exceed 2.5  during fault condition.
The over current mode remains until the primary current decreases to a value lower
than the recovery current.
Max secondary current versus measuring resistor
MAX BURDEN RESISTOR VOLTAGE
MAX BURDENRESISTORVALUE
100.0
10
80.0
60.0
6
OHM
VOLT
8
4
40.0
2
20.0
0
0.0
50 100 150 200 250 300 350 400 450 500 550 600
PRIMARY CURRENT (A)
50 100 150 200 250 300 350 400 450 500 550 600
PRIMARY CURRENT (A)
To maintain safe start-up RM must not exceed 2.5  during fault condition.
Miscellaneous
Bus bar free zone (length: 75 mm) (from center)
r 75
mm
Page 4/5
100225/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Made by LEM Danfysik
Dimensions IT 600-S ULTRASTAB (in mm.)
Connection
Ip
OUTPUT
Vc
Vc
NORMAL OPERATION STATUS
NORMAL OPERATION STATUS
Closed contacts
= Normal operation
= ON state
optocoupler
output
E:Electrostatic shield
Mechanical characteristics
● General tolerance
● Transducer fastening
- Flat mounting
Recommended fastening torque
● Connection of secondary
connector
● Primary through hole
Remarks
± 0.3 mm
2 x M6 x 10
1.96 Nm
on D-SUB-9,
UNC 4-40
Ø  25.4 mm
Connection
● IS is positive when IP flows in the direction of the arrow.
● We recommend that a shielded output cable and plug
are used to ensure the maximum immunity against
electrostatic fields.
● Pin 4 should be connected to cable - and connector
shield to maintain lowest output noise.
● Temperature of the primary conductor should not exceed
50°C.
● Normal operation status (Pins 8 to 3)
Normal operation means:
- ± 15 V present
- zero detector is working
- compensation current
110 % of IPN DC
The contacts of the related relay are closed under normal
operation.
Page 5/5
100225/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising