Catalogue Sheet: Mini Invisilite

Catalogue Sheet: Mini Invisilite
Type:
Project/Location:
Contractor:
Prepared By:
Date:
Model No.:
Made in Canada
TYPICAL SPECIFICATIONS
Supply and install Ready-Lite® Mini Invislite™ Series. The unit shall be designed to be completely concealed in
walls with a cavity. The equipment shall consist of a metal housing containing two modules joined by a flexible
bracket and electric conduit. One module contains the battery, charger circuitry and electrical connection box;
the other module contains the emergency lights installed on the back of a door able to rotate several turns of
360°. The unit equipment shall be completely concealed in the wall after installation through a rectangular
opening not larger than 8.25” by 5.75”. In stand-by mode, the only visible parts of the unit shall be the flat
door and trim plate, coated with a high-quality off-white finish that can be customized on site with paint or
other suitable wall covering. Upon a power failure the unit will expose the emergency heads by rotating its door
180° and then will power the lamps. At the restoration of the AC power or at the end of the battery discharge,
the lamps will turn off and the unit will retract the heads by rotating the door 180° in the same direction. The
unit shall not require the presence of AC power in order to close the door and conceal the lights. The door of
the unit shall be easy to force-turn (open or close) by hand, in any rotation direction. The light source shall
be 12V MR16 lamps of specified technology, wattage and light output. The unit shall supply the rated load
for a minimum of 30 minutes or until the battery is discharged to 87.5% of its nominal voltage (whichever
duration is longer). The charger circuitry shall utilize a micro-controller IC that samples the battery in relation
to the ambient temperature, state of charge, and input voltage fluctuations. The charger shall be current
limited, temperature compensated, short-circuit proof, and reverse-polarity protected. The circuit will charge
in accordance with CSA C22.2 – 141 requirements. The unit shall be furnished with a recessed, illuminated
push button serving as test switch and status indicator light. When specified, the unit shall come complete with
the Ready-Lite® series of auto-test micro-controller circuitry to ensure the equipment readiness and reliability
by continuously monitoring every critical function of the unit. If a component failure occurs, the pilot light
located on the front of the unit will change colour from green to red and will flash indicating a fault. A detailed
diagnostic legend shall be available on the back side of the door and shall provide fault identification (battery,
charger circuitry, lamps) for maintenance personnel. The auto-test shall simulate a power loss for one minute
monthly, 10 minutes every 6 months, and a full 30-minute test every 12 months.
The equipment shall be Ready-Lite® model:
.
DIMENSIONS
Dimensions are approximate and subject to change.
9-1/8” [23.2 cm]
INSTALLED UNIT
17-5/8” [44.8 cm]
5-1/4” [13.2 cm]
7” [17.8 cm]
COMPLETE UNIT
MINI INVISLITE™
SERIES
Unseen Solution,
The Next Generation
FEATURES
• Easy to retrofit in finished walls: the unit
slides in through an 8.25” by 5.75” hole
• No back-box needed to pre-install
• Input: Standard AC input 120/347VAC;
optional 120/277VAC
• Output: 12VDC with up to 100W of
power
• Battery: choice of sealed, maintenancefree Lead-Calcium or Nickel-Metal
Hydride
• Remote capacity: can drive several wall
or ceiling-mount 12VDC remote
Invisilite™ fixtures
• Charger: micro-controller driven,
temperature compensated, high
precision, fast recharge
• Remote AC fixture: direct connection
to 120 or 347VAC power generators
• MR16 halogen lamps; power range
from 12W to 50W, LED; 4W, 5W and 6W
• Certification: CSA C22.2 No.141
3-1/2” [8.9 cm]
REPLACEMENT LAMPS: MR16 TYPE
POWER CONSUMPTION AND UNIT RATING
MODEL
LAMP TYPE
VOLTAGE/WATTAGE
580.0080-RL
580.0064-RL
MR16 halogen
MR16 halogen
12V-12W
12V-20W
580.0083-RL
580.0076-RL
580.0068-RL
MR16 halogen
MR16 halogen
MR16 high-lumen output
12V-35W
12V-50W
12V-20W
580.0090-RL
MR16 high-lumen output
12V-35W
580.0089-RL
MR16 high-lumen output
12V-50W
580.0093-RL
MR16, LED
12V-4W
580.0104-RL
MR16, LED
12V-5W
580.0106-RL
MR16, LED
12V-6W
MODEL
WATTAGE CAPACITY
30MIN 1H00 2H00 3H00
AC SPECS
MHL80
120/347VAC
-
80
40
24
-
MH100
120/347VAC
0.25/0.08 A
100
70
36
24
MHG1
120VAC
max. 0.95 A
maximum 100W load
MHG2
277VAC
max. 0.45 A
maximum 100W load
MHG3
347VAC
max. 0.35 A
maximum 100W load
ORDERING INFORMATION
SERIES
MH
UNIT CAPACITY
L80= lead-calcium,
12V-80W
H100= nickel-metal hydride,
12V-100W
LAMP WATTAGE (12V)
LD7= MR16 LED, 2X 4W
LD9= MR16 LED, 2X 5W
LD10= MR16 LED, 2X 6W
12W= MR16 halogen, 2X 12W
20W= MR16 halogen, 2X 20W
35W= MR16 halogen, 2X 35W
50W= MR16 halogen, 2X 50W
20WH= 2X 20W MR16, high lumen output lamp
35WH= 2X 35W MR16, high lumen output lamp
50WH= 2X 50W MR16, high lumen output lamp
OPTIONS
AD= auto-diagnostics*
ADN= auto-diagnostics,
non-audible*
D3= time delay (15 mins.)
TB= T-Bar mounting kit
*Minimum lamp load required:
20% of unit capacity
EXAMPLE: MHL8012WAD
105
AC VOLTAGE
Blank= 120/347VAC
U2= 120/277VAC