p308trs1 spec eng
Relay Output Module
P3-08TRS-1
<--->
Isolated Relay Output
The P3-08TRS-1 High-Current Isolated Relay Output
Module provides eight 5A relay outputs with eight fused
commons.
C
UL
R
US
Terminal block sold
separately; terminal
block cover included
with module.
Output Specifications
Outputs per Module
Commons per Module
Operating Voltage Range
(Tolerance)
8 relays (non-latching)
8 (isolated)
(CE) 6.25-24 VDC (-15% / +20%)
6-240 VAC (-15% / +10%)
(UL) 5-30 VDC (-0% / +10%)
5-240 VAC (-0% / +10%)
Output Type
4 Form C (SPDT-NO/NC),
4 Form A (SPST-NO)
AC Frequency
47-63 Hz
On Voltage Drop
Minimal (90 mV max for fuse at 10A)
Max Output Current
6.3A at 23°C, 5.0A at 60°C
@ Temperature (Resistive)*
For both AC and DC
Maximum Leakage Current
Minimal (5 µA for TVS diode)
Minimum Load
10 mA @ 5 VDC
Maximum Inrush Current
12A
External DC Required
None
OFF to ON Response
10 ms
ON to OFF Response
5 ms (Excluding NO bounce)
Terminal Type (not included)
20-position removable terminal block
Status Indicators
Logic side
Fuses
6.3A user replaceable fuse per common
For replacement, order P3-FUSE-2 (5/Pkg.)
Dielectric Strength (Between nor- 1500 VAC @ 1 min logic to output and
mally open and normally closed isolated output to output, 750 VAC @ 1 min
contacts on the same relay)
between contacts on same relay (Same as
1800 VAC @ 1 sec and 900 VAC @ 1 sec)
Transient Voltage Suppression
482V clamp at 1.25A peak pulse current
(Bi-directional TVS diode)
Mechanical Life Expectancy
>100,000 at 30 operations per minute
*Rating is for a normally-open conact. Normally-closed contacts have 1/2 the
current handling capability.
Typical Relay Life*
Voltage & Type of Load
24VDC Resistive
24VDC Solenoid
120VAC Resistive
120VAC Resistive
120VAC Solenoid
240VAC Resistive
240VAC Resistive
1/4 HP Motor
Operating Current
6.3A
0.2A
6.3A
3A
0.5A
6.3A
3A
1.5 x FLA (motor)
Operations
600,000
1,000,000
600,000
1,000,000
500,000
450,000
600,000
30,000
*Ratings are for normally-open conacts. Normally-closed contacts have 1/2
the current handling capability.
Output Derating
Amps
8
Removable Terminal Block Specifications
6
Description
Wire Range
4
2
0
0
32
10
20
30
40
50
50
68
86
104
122
Ambient Temperature ( C/ F)
60 C
140 F
Screw Driver Width
Screw Size
Screw Torque
Part No. P3-RTB; 20 screw terminals
22-14 AWG (0.324 to 2.08 sq. mm)
Solid / stranded conductor
3/64 in. (1.2 mm) insulation maximum
"USE COPPER CONDUCTORS , 60°C" or equivalent.
1/4 inch (6.5 mm) maximum
M3 size
Field terminals – 7 - 9 in./lb (.0.882 - 1.02 Nm)
Self-jacking screws – 2.7 - 3.6 in./lb (0.3 - 0.4 Nm).
Do not overtighten screws when installing terminal block.
All 8 outputs on, 100% duty cycle allowed.
We recommend using prewired ZIPLink cables and
connection modules. See “Wiring Systems”.
WARNING: Explosion hazard – Substitution of components may
impair suitability for Class I, Division 2.
Terminal block cover included. If you wish to handwire your module, a removable terminal block is
sold separately. Order part number P3-RTB.
e68
PLC Products
1 - 80 0 - 633 - 0405
Relay Output Module
Company
Info.
PLCs
Field I/O
P3-08TRS-1 (Cont’d)
Software
C-more &
other HMI
General Specifications
Operating Temperature
Storage Temperature
Humidity
Environmental Air
Vibration
Shock
Field to Logic Side Isolation
Insulation Resistance
Heat Dissipation
Enclosure Type
Agency Approvals
0° to 60°C (32° to 140°F),
-20° to 70°C (-4° to 158°F)
5 to 95% (non-condensing)
No corrosive gases permitted
MIL STD 810C 514.2
MIL STD 810C 516.2
1800VAC applied for 1 second
>10M @ 500 VDC
3W
Open Equipment
UL508 file E157382, Canada & USA
UL1604 file E200031, Canada & USA
CE (EN61131-2*)
This equipment is suitable for use in Class 1,
Division 2, Groups A, B, C and D or non-hazardous
locations only.
Module Keying to Backplane Electronic
Module Location
Any I/O slot in any local, expansion, or remote
base in a Productivity3000 System.
Field Wiring
Removable terminal block (not included). Use
ZIPLink wiring system or optional terminal block.
See “Wiring I/O Modules”.
EU Directive
See the "EU Directive" topic in the
Productivity3000 Help File. Information can also
be obtained at: www.productivitypac.com
Terminal Type (not included) 20-position removable terminal block
Weight
286g (10.08 oz)
AC Drives
AC Motors
Power
Transmiss.
Steppers/
Servos
Motor
Controls
Proximity
Sensors
Replaceable Fuses
Order Part Number P3-FUSE-2
(Qty. 5/Pkg.) One spare included
with this module.
F7
F8 F6
F5 F4
F3 F2
Photo
Sensors
Limit
Switches
F1
Encoders
Current
Sensors
Pressure
Sensors
*Meets EMC and Safety requirements. See the Declaration of Conformity for details.
Temp.
Sensors
Pushbuttons/
Lights
Process
5-30VDC
5-240VAC
C1
5-30VDC =
5-240VAC
NO1
L
C2
NO2
L
COM
Internal module circuitry
6.3A
Relays/
Timers
Outputs
NO1 – NO4
Comm.
C3
Terminal
Blocks &
Wiring
L
NO3
L
C4
L
NO
NO4
L
Power
NC5
5-30VDC =
5-240VAC
C5
L
NO5
NC6
L
C6
NO6
L
L
Circuit
Protection
Outputs
NO5 / NC5 –
NO8 / NC8
Enclosures
L
L
NC7
Internal module circuitry
COM 6.3A
NO
Tools
NC
Appendix
C7
L
Part Index
NO7
NC8
L
C8
L
NO8
w w w. a u to m at i o n d i re c t . c o m / P ro d u c t i v i ty 30 0 0
PLC Products
e69
Wiring System for Productivity3000
Company
Info.
PLCs
Field I/O
Software
Specify your ZIPLink system
C-more &
other HMI
Use the Compatibility Matrix table below.
AC Drives
Step 1
Step 2
Step 3
Locate the I/O module part number.
Locate Connector Module Type. (Feedthrough Module, Fuse Module, etc...)
Select the cable length by replacing the # symbol with: Blank = 0.5m, -1 = 1.0m, -2 = 2.0m1
1
Note: Cable part number denotes compatibility between Connector Module and I/O Modules.
AC Motors
Power
Transmiss.
Productivity3000 ZIPLink Wiring System Compatibility Matrix
Step 2: Connector Module Type Feedthrough Modules
of
Step 1: I/O Module Number
Terminals
ZL-RTB20
ZL-RTB40
Fuse Modules
Relay
Module
Sensor Input
Mod.
Pigtail Cable
ZL-RFU20
ZL-RRL16-24
ZL-LTB16-24
ZL-RFU40
Step 3: Cables
20
20
20
20
40
40
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
P3-08TAS
P3-08TD1S
P3-08TD2S
P3-08TRS
P3-16TA
P3-16TD1
P3-16TD2
P3-16TR
P3-08TRS-1***
P3-32TD1
P3-32TD2
P3-64TD1*
P3-64TD2*
20
20
20
20
20
20
20
20
20
40
40
40
40
ZL-P3-CBL20#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20#
20
20
20
20
Matched Only
T/C Wire Only
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-CBL40#
ZL-CBL40#
ZL-P3-CBL40#
ZL-P3-CBL40#
I/O Module
ZL-P3-CBL20L#
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20#
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-CBL40#
ZL-CBL40#
ZL-CBL40#
ZL-CBL40#
20
20
20
20
20
20
20
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20L#
P3-8AD4DA-1
P3-8AD4DA-2
20
20
ZL-P3-CBL20L#
ZL-P3-CBL20L#
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
Pressure
Sensors
Temp.
Sensors
Pushbuttons/
Lights
Process
Terminal
Blocks &
Wiring
Power
Circuit
Protection
Enclosures
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
Analog Combo
ZL-P3-CBL20-#P
ZL-P3-CBL20-#P
*The P3-64ND3, P3-64TD1, and P3-64TD2 modules have two 32-point connectors and require 2 ZIPLink cables and 2 ZIPLink connector modules.
**These modules are not supported by the ZIPLink wiring system. Removable terminal block P3-RTB included.
***The P3-08TRS-1 output module is derated, not to exceed 2A per point maximum when used with the ZIPLink wiring system.
w w w. a u to m at i o n d i re c t . c o m / P ro d u c t i v i ty 30 0 0
Current
Sensors
Comm.
Analog Out
P3-04DA
P3-08DA-1
P3-08DA-2
P3-06DAS-1
P3-06DAS-2
P3-16DA-1
P3-16DA-2
Limit
Switches
Relays/
Timers
Analog In
P3-04ADS
P3-08AD
P3-16AD-1
P3-16AD-2
P3-08RTD**
P3-08THM**
Photo
Sensors
Encoders
Outputs
ZL-CBL40#
ZL-CBL40#
ZL-CBL40#
ZL-CBL40#
Motor
Controls
Proximity
Sensors
Inputs
P3-08NAS
P3-08ND3S
P3-16NA
P3-16ND3
P3-32ND3
P3-64ND3*
Steppers/
Servos
PLC Products
e29
Tools
Appendix
Part Index
I/O Modules
A variety of discrete and analog I/O
modules are available for use in local,
expansion, and remote I/O bases.
Specifications for each module are on the
following pages.
Discrete Output Modules
Productivity3000 Discrete Output Modules
A filler module is available for unused I/O
module slots (part number P3-FILL).
Discrete Input Modules
Productivity3000 Discrete Input Modules
of
Part Number Number
Inputs
16
P3-16SIM
8
P3-08ND3S
16
P3-16ND3
32
P3-32ND3*
64
P3-64ND3*
8
P3-08NAS
16
P3-16NA
Description
Price
Input Simulator Module
<--->
Isolated Sinking/Sourcing DC Input
<--->
Sinking/Sourcing DC Input
<--->
Sinking/Sourcing DC Input
<--->
Sinking/Sourcing DC Input
<--->
Isolated AC Input
<--->
AC Input
<--->
of
Part Number Number
Outputs
8
P3-08TD1S
8
P3-08TD2S
16
P3-16TD1
16
P3-16TD2
32
P3-32TD1*
32
P3-32TD2*
64
P3-64TD1*
64
P3-64TD2*
8
P3-08TAS
16
P3-16TA
8
P3-08TRS
16
P3-16TR
8
P3-08TRS-1
Description
Price
Isolated Sinking Output
<--->
Isolated Sourcing Output
<--->
Sinking Output
<--->
Sourcing Output
<--->
Sinking Output
<--->
Sourcing Output
<--->
Sinking Output
<--->
Sourcing Output
<--->
Isolated AC Output
AC Output
<--->
Isolated Relay Output
<--->
Relay Output
<--->
Isolated Relay Output
<--->
*ZIPLink required.
*ZIPLink required.
Module Installation Procedure
Analog I/O Modules
Productivity3000 Analog Input Modules
of
Part Number Number
Channels
4
P3-04ADS
8
P3-08AD
16
P3-16AD-1
16
P3-16AD-2
8
P3-08RTD
8
P3-08THM
WARNING: Do not apply field power until the
Align
here
following steps are completed. See hot-swapping procedure for exceptions.
Description
Price
Isolated Analog Input
<--->
Step One: Align circuit card with slot
Analog Input
<--->
Analog Input (Current)
<--->
and press firmly to seat module into
connector.
Analog Input (Voltage)
<--->
Analog RTD Input
<--->
Analog Thermocouple Input
<--->
Align
here
Step Two: Pull top and
bottom locking tabs toward
module face. Click indicates lock is
Productivity3000 Analog Output Modules
of
Part Number Number
Channels
4
P3-04DA
8
P3-08DA-1
8
P3-08DA-2
6
P3-06DAS-1
6
P3-06DAS-2
16
P3-16DA-1
16
P3-16DA-2
Description
Price
Analog Output
<--->
Analog Output (Current)
<--->
Analog Output (Voltage)
<--->
Isolated Analog Output (Current)
<--->
Isolated Analog Output (Voltage)
<--->
Analog Output (Current)
<--->
Analog Output (Voltage)
<--->
Step Three: Attach field
wiring using optional terminal
block or ZIPLink wiring system
and install cover.
To install or remove terminal
block cover, press middle to flex
cover.
Productivity3000 Analog Input/Output Modules
Part Number
P3-8AD4DA-1
P3-8AD4DA-2
e30
Number of
Channels
Description
8/4
Analog Input/Output (Current)
<--->
WARNING: Explosion hazard – Do not connect or disconnect connec-
8/4
Analog Input/Output (Voltage)
<--->
tors or operate switches while circuit is live unless the area is known to
be non-hazardous. Do not hot-swap modules unless the area is known
to be non-hazardous.