Bulletin A-34A
Series DPG-200 Digital Pressure Gage
Specifications - Installation and Operating Instructions
3
[76.20]
2-3/8
[60.45]
1-5/8
[40.39]
3-5/8
[91.39]
The Series DPG-200 Digital Pressure Gage has a precise
±0.25% full scale accuracy. The 4 digit digital display will reduce the potential for errors in readings by eliminating parallax error commonly produced with analog gages. The DPG-200 is packaged in a durable extruded aluminum case designed to meet
NEMA 4X (IP66). The unit is powered by 12-24 VDC/VAC and contains two alarm set points along with a 4-20 mA process output. A four-button keypad allows easy access to features. These features include backlight, peak and valley, auto zero and conversion of the pressure units.
INSTALLATION
When installing gage always use 1˝ hex at the base of the housing to tighten the gage to a mating fitting. Do not apply wrench to housing.
WIRING
WHITE
RED
BLACK
N.O.
COM
N.C.
HIGH ALARM
BLUE
ORANGE
GREEN
N.O.
COM
N.C.
LOW ALARM
RED
BLACK
ORANGE
BROWN
SHEILD
POWER SUPPLY
10-28 VDC OR VAC
4-20 mA
RECEIVER
1/4 NPT
SPECIFICATIONS
DIGITAL GAGE SPECIFICATIONS
Service: Liquids and non-combustible compatible gases.
Wetted Materials: Type 316L SS.
Housing: Black polycarbonate front & back cover, anodized aluminum extruded housing with recessed grooves, polycarbonate overlay, Buna-N O-rings, 316L SS sensor construction.
Accuracy: 0.25% F.S. ±1 least significant digit.
(Includes linearity, hysteresis, repeatability).
Pressure Limit: 2x pressure range for models 1000 psi;
5000 psi for 3000 psi range; 7500 psi for 5000 psi range.
Temperature Limits: 0 to 158°F (0 to 70°C).
Process Connection: 1/4˝ male NPT.
Display: 4 digit (.425 H x .234 W digits).
Size: 3.00˝ OD x 1.90 deep (not including cables).
Weight: 8.84 oz (275 g).
SWITCH SPECIFICATIONS
Switch Type: 2 SPDT Form C contacts.
Electrical Rating: 0.5A @ 125 VAC resistive, 1A @ 24 VDC.
Relay Differential: 1 least significant digit.
Electrical Connections: Two 3 ft (.91 m) cables.
Mounting Orientation: Mount in any position.
Set Point Adjustment: Via menu.
TRANSMITTER SPECIFICATIONS
Temperature Limits: 0 to 158°F (0 to 70°C).
Thermal Effect: Between 70 to 158°F = 0.016%/°F. Between
0 to 70°F = 0.026%/°F.
Power Requirements: 12-24 VAC +/- 20% 50-400 HZ, 12-24
VDC +/-20%.
Output Signal: 4-20 mA.
Loop Resistance: 600 ohms maximum.
Power Consumption: 0.8 W max.
Electrical Connections: 2 three foot cables.
Enclosure Rating: Designed to meet NEMA 4X (IP66).
Agency Approvals: CE.
WARNING: DO NOT pressurize DPG over maximum allowable pressure limits. Extreme damage can occur if limits are exceeded
(see Pressure Limit under Specifications). An overflow “OFL” designator will flash to acknowledge that the gages pressure range has been exceeded.
DWYER INSTRUMENTS, INC.
P.O. Box 373 • Michigan City, IN 46361-0373, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057 www.dwyer-inst.com
e-mail: [email protected]
Bulletin A-34A
Page 2
POWER UP
BUTTON
OPERATION
•
•
HOME
•
•
•
Top line shows units.
Bottom line shows pressure.
If pressure is 1% F.S. below range of instrument the pressure value will alternate UFL on a 1 second interval.
If pressure is 1% F.S. above range of instrument the pressure value will alternate with OFL on a 1 second interval.
Factory set to PSI.
See menu page.
Zeros display if within ±4% F.S. of zero.
See units chart below.
See peak/valley.
PEAK VALLEY
UNITS CHART
Model
Number
DPG-200
DPG-202
DPG-203
DPG-204
DPG-205
DPG-206
DPG-207
DPG-208
DPG-209
DPG-210
DPG-211
Range psi
-14.70-0
15.00
30.00
50.00
100.0
200.0
300.0
500.0
1000
3000
5000 kg/cm
-1.033
1.055
2.109
3.515
7.03
14.06
21.09
35.15
70.3
210.9
351.5
2 bar
-1.013
1.034
2.069
3.448
6.895
13.79
20.69
34.48
68.98
206.9
344.8
in Hg
-29.93
30.54
61.08
101.8
203.6
407.2
610.8
1018
2036
6108 ft wc
-33.94
34.61
69.21
115.4
230.7
461.4
692.1
1154
2307
6921
Pressure Ranges ft sw*
-33.06
33.73
67.45
112.4
224.8
449.7
674.5
1124
2248
6745 kPa
-101.4
103.4
206.9
344.8
689.5
1379
2069
3448
6895 oz/in 2
-235.2
240
480
800
1600
3200
4800
8000 in wc
-407.3
415.2
830.4
1384
2768
5536
8304 mbar
-1013
1034
2069
3448
6895 cm wc
-1034
1055
2109
3515
7031 mm Hg
-760.7
775.7
1551
2586
5172
Compound Ranges Available: DPG-220 Range: 30˝ Hg-0-15 psi; DPG-221 Range: 30˝ Hg-0-30 psi; DPG-222* Range: 30˝ Hg-0-45 psi;
DPG-223*: Range 30˝ Hg-0-60 psi; DPG-224: 30˝ Hg-0-100 psi.
*feet of seawater @ 4°C
Bulletin A-34A
Page 3
MENU
MENU BUTTON OPERATION
SECURITY
• 1=full access, password is 1110.
• 2=protected, password is 1101.
• Factory set to full access.
• All menus except backlight are protected.
ALARM #1 SETPOINT
• Activates Alarm #1 relay on increase.
• AL1 indicator and alarm #1 relay turned on when pressure is greater than or equal to setpoint.
ALARM #1 DIFFERENTIAL
• AL1 indicator and alarm #1 relay turned off when pressure is less than the setpoint minus the differential.
ALARM #2 SETPOINT
• Activates Alarm #2 relay on decrease.
• AL2 indicator and alarm #2 relay turned on when pressure is less than or equal to setpoint.
ALARM #2 DIFFERENTIAL
• AL2 indicator and alarm #2 relay turned off when pressure is greater than the setpoint plus the differential.
ALARM #2 INHIBIT
• Prevents low alarm on power up.
• When set to “On” alarm #2 is disabled until the pressure is greater than the setpoint plus the differential.
• Factory set to ON.
MENU CONTINUED
BACKLIGHT
• Turns backlight on or off.
• Factory set to off.
PROCESS OUTPUT HIGH
• Pressure at which current output is set to 20 mA.
• Factory set to maximum scale.
MENU BUTTON OPERATION
PROCESS OUTPUT LOW
• Pressure at which current output is set to 4 mA.
• Factory set to minimum scale.
SPAN ADJUSTMENT
• Display shows pressure using existing span.
• Apply full scale pressure to instrument and hold enter for one second to acquire new span.
ALARM OPERATION
50
40
30
AL1S
(psi) 20
10
0
AL1S - AL1D
0
AL1D
Alarm 1
AL1S sets the relay on point, and
AL1S - AL1D sets the relay off point. The relay’s output functions in the direct acting mode, which means the relay activates with an increase in pressure. In the above graph, an instrument with a 50 psi range has the
AL1S set at 40. The relay will turn on at 40 psi increase. The
AL1D is set at
30. The relay will turn off at 10 psi decrease (40 - 30 = 10).
(psi)
50
40
30
20
10
0
0
AL2S + AL2D
AL2S
AL2D
Alarm 2
AL2S sets the relay on point, and
AL2S + AL2D sets the relay off point. The relay’s output functions in the reverse acting mode, which means the relay activates with a decrease in pressure. In the above graph, an instrument with a 50 psi range has the AL2S relay turn on at 10 psi decrease. The
AL2D is set at 30. The relay will turn off at 40 psi increase (10 + 30 = 40).
©Copyright 2006 Dwyer Instruments, Inc. Printed in U.S.A. 8/06 FR# 18-443202-30