Temperature Controllers Manual

Temperature Controllers Manual
Global Water
800-876-1172 • globalw.com
Global Water
Instrumentation, Inc.
11390 Amalgam Way
Gold River, CA 95670
T: 800-876-1172
Int’l: (916) 638-3429, F: (916) 638-3270
PRODUCT NAME: 378 TEMPERATURE CONTROLLER
-1-
Global Water
800-876-1172 • globalw.com
The model 378 is a high performance industrial grade digital indicating single set point
PROPORTIONAL /ON - OFF controller for use with type K, J ,T and E thermocouple.
Thermocouple gain and cold junction are automatically compensated by internal
electrode circuits.
An accurate 1 mV per display count analog is provided to interface the instrument with a
recorder, printer, and so on.
Table of Contents
I)
II)
III)
IV)
V)
VI)
VII)
VIII)
IX)
X)
XI)
XII)
Inspection................................................................................................................ 3
Specifications.......................................................................................................... 3
Mounting procedure................................................................................................ 4
Wiring diagram ....................................................................................................... 6
Analog voltage output............................................................................................. 6
Controller action ..................................................................................................... 6
Bandwidth adjust .................................................................................................... 7
Controller set and reset ........................................................................................... 7
Relay and front panel LED format.......................................................................... 8
Thermocouple burn out protection.......................................................................... 8
Trouble Shooting .................................................................................................... 9
Warranty ................................................................................................................. 9
* Copyright © Global Water Instrumentation, Inc. 2006
-2-
Global Water
800-876-1172 • globalw.com
I)
Inspection
a) Your 378 TEMPERATURE CONTROLLER unit was carefully inspected and
certified by our Quality Assurance Team before shipping. If any damage has
occurred during shipping, please notify Global Water Instrumentation, Inc. and
file a claim with the carrier involved.
II) Specifications
Model
378KC
378KF
378JC
378JF
Type
K
K
J
J
On/Off control
Hysteresis:
Range
0 to 1000°C
0 to 1999°F
0 to 550°C
0 to 1000°F
Resolution
1°C
1°F
1°C
1°F
Accuracy
± 0.50% ± 1 count
± 0.50% ± 1 count
± 0.40% ± 1 count
± 0.40% ± 1 count
°C model 6°C (± 3°C)
°F model 10°F (± 5°F)
Proportional control
Proportional band Adjustable from on/off to 100°C or 100°F with built in
hysteresis
Cycle time
20 ± 3 second
Reset
Manual adjust
General
Operating temp.
Analog output
T/C burnout
Output relay
Power source
Dimension
Weight
0 to 40
1 mV/count, ± 0.30% of span ± 1 mV
Upscale
8 A at 115 VAC, 4A at 230 VAC, resistive load
115/230VAC , ± 10% 50/60 Hz
96mm X 48mm X 105mm
0.38 kgs
-3-
Global Water
800-876-1172 • globalw.com
III) Mounting procedure
a) Make a cutout on any panel, with a thickness of 1/16 inch (1.5mm to 3/8 inch
(9.5mm)). Refer to drawing 1.
b) Remove the mounting brackets assembly from the panel meter and insert the
panel meter into the cutout. Refer to drawing 2.
c) Replace the mounting brackets assembly onto the panel meter and fasten the
mounting screws to secure the panel meter to mounting panel .Refer to drawing 3.
-4-
Global Water
800-876-1172 • globalw.com
-5-
Global Water
800-876-1172 • globalw.com
IV) Wiring diagram
a) Connect the AC line to the rear of the instrument. The model 378 can be used
with 115/230 VAC 50/60Hz, refer to drawing 4.
b) Connect the two thermocouple leads to the rear of the instrument .Be sure to
observe the correct polarity of the thermocouple leads. Refer to drawing 4.
V) Analog voltage output
a) The analog voltage output can be used to interface with instruments such as
recorder, printer, remote indicator, 4 to 20 mA converter, etc.
b) The following rules must be observed in order to avoid reading inaccuracies or
possible damage to the instrument.
1.
If grounded or naked thermocouple is used, the interface device's circuit
common mustn't be connected to earth ground.
2.
The input impedance of the interface device must be greater than 10 K
Ohms.
3.
Be sure that the AC line voltage is never connected to the analog output.
VI) Controller action
a) The Model 378 is a single set point Proportional/On-off controller. The
proportional bandwidth is adjustable from On-off to 100°C or 100°F. with built-in
hysteresis. The cycle time is factory set to 20-second ± 3 seconds. Refer to
drawing 6 (Page 8) for proportional controller timing.
-6-
Global Water
800-876-1172 • globalw.com
VII) Bandwidth adjust
a) Set the B.W. adjust control on the front panel to the desired Proportional
Bandwidth. The controller action will be On-off when the B.W. adjust control is
fully counter clockwise. Refer to drawing 5.
VIII) Controller set and reset
a) Press the Set point switch on the front panel. The meter indicates the temperature
value of the set point. Refer to drawing 5.
b) Adjust the Set control on the front panel for the desired temperature value.
c) Release the Set point switch, the meter again indicates the process temperature
value.
-7-
Global Water
800-876-1172 • globalw.com
d) The process temperature may settle at any value within the proportional band.
e) Adjust the Reset control clockwise if the process temperature is less than the set
temperature. The Reset control is disengaged for On/off control.
f) Repeat Step 5 (e) until the process temperature is equal to the set temperature.
IX) Relay and front panel led format
a) Connect the heater circuit to the N.O. and COM terminals of the relay. Make sure
that the load doesn't exceed the rating of the relay, 8 A at 115VAC and 4A at
230VAC. The relay rating is for resistive load only.
b) The LED on the front panel will be On when the relay is energized .Power is
delivered to the heater through the N.O. and COM terminals of the relay.
X) Thermocouple burn out protection
a) The thermocouple burn out normally would result in an open circuit. The meter
will be roll up scale, exceeding the set point and de-energized the relay. Power to
the heater will be cut off.
-8-
Global Water
800-876-1172 • globalw.com
XI) Trouble Shooting
Other issues
a) Call us for tech support: 800-876-1172 or 916-638-3429 (many problems can be
solved over the phone). Fax: 916-638-3270 or Email: globalw@globalw.com.
Be prepared to describe the problem you are experiencing including specific
details of the application and installation and any additional pertinent information.
b) In the event that the equipment needs to be returned to the factory for any reason,
please call to obtain an RMA# (Return Material authorization). Do not return
items without an RMA# displayed on the outside of the package.
Clean and decontaminate the 378 TEMPERATURE CONTROLLER if necessary.
Include a written statement describing the problems.
Send the package with shipping prepaid to our factory address. Insure your
shipment, as the warranty does not cover damage incurred during transit.
c) When calling for tech support, please have the following information ready;
1.
2.
3.
4.
5.
Model #.
Unit serial number.
P.O.# the equipment was purchased on.
Our sales number or the invoice number.
Repair instructions and/or specific problems relating to the product.
XII) Warranty
a) Global Water Instrumentation, Inc. warrants that its products are free from defects
in material and workmanship under normal use and service for a period of one
year from date of shipment from factory. Global Water’s obligations under this
warranty are limited to, at Global Water’s option: (I) replacing or (II) repairing;
any products determined to be defective. In no case shall Global Water’s liability
exceed the products original purchase price. This warranty does not apply to any
equipment that has been repaired or altered, except by Global Water
Instrumentation, Inc., or which has been subject to misuse, negligence, or
accident. It is expressly agreed that this warranty will be in lieu of all warranties
of fitness and in lieu of the warranty of merchantability.
The warranty begins on the date of your invoice.
-9-