12/24 VDC Input Module
HE800DIM210 /
HE-DIM210*
Positive or Negative Logic
8 Channels
* HE- denotes plastic case.
This datasheet also covers products starting with IC300.
NOTE: There are two models of DIM210. The first model (fully isolated inputs) covers
Revision A and Revision B. The second model covers Revision C and higher (bus
isolated inputs).
1
DIM210 – Revision A and Revision B Only
1.1
Specifications (Rev. A and Rev. B Only)
Inputs per Module
Commons per Module
Input Voltage Range
Peak Voltage
Isolation Voltage
(Channel to Channel
and Channel to
Common)
Required Power
(Steady State)
Required Power
(Inrush)
ON Voltage Level
OFF Voltage Level
Input Impedance
Minimum ON Current
CE
UL
8
12–24 VDC
35 VDC Max.
Maximum OFF Current
Base Power Required
OFF to ON Response
Differential and
BiDirectional
200 µA
30 mA
1 ms.
500 VDC
ON to OFF Response
1 ms.
8 isolated
0.92 W (38.5 mA
@ 24 VDC)
Negligible
9 VDC Min.
3 VDC Max.
10 K Ohms
1 mA.
Input Characteristics
Terminal Type
Spring Clamp, Removable
Status Indicator
8 LEDs
Relative Humidity
Operating Temperature
Weight
5–95% Non-condensing
0°–60° Celsius
9 oz. (256 g)
See Compliance Table at http://www.heapg.com/Support/compliance.htm
Information is subject to change without notice.
SmartStack is a trademark of Horner APG, LLC.
PAGE 2
1.2
10 NOV 2006
MAN0228-09
DIM210
Wiring – (Rev. A and Rev. B Only)
*
DIM210 Rev. A and B only
OCS Bottom View – Shows
Corresponding I/O Pin
12-24VDC
1
2
12-24VDC
Pin
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Signal
Input 1 +/Input 1 -/+
Input 2 +/Input 2 -/+
Input 3 +/Input 3 -/+
Input 4 +/Input 4 -/+
Input 5 +/Input 5 -/+
Input 6 +/Input 6 -/+
Input 7 +/Input 7 -/+
Input 8 +/Input 8 -/+
*
1
2
3
12-24VDC
3
4
12-24VDC
4
5
12-24VDC
5
6
12-24VDC
6
7
12-24VDC
7
8
12-24VDC
8
001DIM001
Warning: Connecting high voltage to any I/O pin may cause high voltage to appear at other I/O
pins.
1.3
Internal Circuit Schematic (Rev. A and Rev. B Only)
I/O Connector
Field
Side
SmartStack
VCC
1
1
Information is subject to change without notice.
To
Controller
SmartStack is a trademark of Horner APG, LLC.
MAN0228-09
DIM210
10 NOV 2006
PAGE 3
1.4 Configuration (Rev. A and B Only)
Note: The status of the I/O can be monitored in Cscape Software.
Preliminary configuration procedures that apply to SmartStack™ Modules are contained in the hardware
manual of the controller you are using. Refer to the Additional References section in this data sheet for a
listing of hardware manuals. Although the module has no user defined parameters, the I/O Map describes
which I/O registers are assigned to a specific SmartStack™ Module and where the module is located in
the point map. The I/O Map is determined by the model number and location within the SmartStack™.
The I/O Map is not edited by the user.
Information is subject to change without notice.
SmartStack is a trademark of Horner APG, LLC.
PAGE 4
10 NOV 2006
2
DIM210 – (Revision C and Higher)
2.1
Specifications (Rev. C and Higher)
INPUT
Inputs per Module
Commons per Module
Input Voltage Range
Peak Voltage
Isolation
(Channel to Bus)
ON Voltage Level
OFF Voltage Level
Required Power
(Steady State)
Required Power
(Inrush)
Input Impedance
Weight
CE
UL
2.2
MAN0228-09
DIM210
DIM210
DIM210
8 Non-isolated
1
12–24 VDC
35 VDC Max.
Input Characteristics
Maximum OFF Current
Minimum ON Current
OFF to ON Response
Bidirectional
200 µA
1 mA
1 ms.
500 VDC
ON to OFF Response
1 ms.
9 VDC Minimum
3 VDC Maximum
0.18 W (7.7 mA @
24 VDC)
Negligible
Status Indicator
Relative Humidity
8 LEDs
5–95% Non-condensing
Operating
Temperature
0°–60° Celsius
Terminal Type
10 K Ohms
9 oz. (256 g)
Spring Clamp,
Removable
See Compliance Table at http://www.heapg.com/Support/compliance.htm
*
Wiring (Rev. C and Higher)
I1
I2
*
OCS Bottom View – Shows
Corresponding I/O Pin
I3
I4
12-24VDC
Pin
I5
I6
I7
I8
C
DIM210 Rev. C and higher
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
I1
I2
I3
I4
I5
I6
I7
I8
C
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
Signal
DIM210
Rev. C or higher
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Common
No Connection
No Connection
No Connection
No Connection
No Connection
No Connection
No Connection
No Connection
No Connection
No Connection
001DIM002
Information is subject to change without notice.
SmartStack is a trademark of Horner APG, LLC.
MAN0228-09
DIM210
10 NOV 2006
PAGE 5
Warning: Connecting high voltage to any I/O pin may cause high voltage to appear at other I/O
pins.
2.3
Internal Circuit Schematic (Rev. C and higher)
SmartStack
I/O Connector
Field
Side
VCC
I1
To
Controller
C
2.4
Configuration (Rev. C and higher)
Note: The status of the I/O can be monitored in Cscape Software.
Preliminary configuration procedures that apply to SmartStack™ Modules are contained in the hardware
manual of the controller you are using. Refer to the Additional References section in this data sheet for a
listing of hardware manuals.
Selecting the I/O Map tab provides information about the I/O registers, which are assigned to a specific
SmartStack™ Module and where the module is located in the point map. The I/O Map is determined by
the model number and location within the SmartStack™. The I/O Map is not edited by the user.
The Module Setup is used in applications where it is necessary to change the default states of the
outputs when the controller (e.g., OCS100) enters idle/stop mode. The default turns the outputs OFF
when the controller enters idle/stop mode. By selecting the Module Setup tab, each output can be set to
either turn ON, turn OFF or to hold the last state. Generally, most applications use the default settings.
Warning: The default turns the outputs OFF when the controller enters idle/stop mode. To
avoid injury of personnel or damages to equipment, exercise extreme caution when changing
the default setting using the Module Setup tab.
3
INPUT CHARACTERISTICS
Digital Input Chart
0 .125 (±15%) V-A
0
35VDC
Information is subject to change without notice.
SmartStack is a trademark of Horner APG, LLC.
PAGE 6
4
10 NOV 2006
MAN0228-09
DIM210
INSTALLATION / SAFETY
Warning: Remove power from the OCS controller, CAN port, and any peripheral equipment
connected to this local system before adding or replacing this or any module.
Use the following wire type or equivalent:
•
Belden 8917
•
16 AWG or larger
For detailed installation and a handy checklist that covers panel box layout requirements and minimum
clearances, refer to the hardware manual of the controller you are using. (See the Additional References
section in this document.).
When found on the product, the following symbols specify:
Warning: Consult user documentation.
Warning: Electrical Shock Hazard.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the
source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of fire
and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure
indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this
equipment. Read and understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in severe bodily injury or loss
of life.
Information is subject to change without notice.
SmartStack is a trademark of Horner APG, LLC.
MAN0228-09
DIM210
10 NOV 2006
PAGE 7
For detailed installation and a handy checklist that covers panel box layout requirements and minimum
clearances, refer to the hardware manual of the controller you are using. (See the Additional References
section in this document.):
•
•
All applicable codes and standards need to be followed in the installation of this product.
For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or
larger.
Adhere to the following safety precautions whenever any type of connection is made to the module.
•
•
•
•
•
•
•
•
Connect the green safety (earth) ground first before making any other connections.
When connecting to electric circuits or pulse-initiating equipment, open their related breakers.
Do not make connections to live power lines.
Make connections to the module first; then connect to the circuit to be monitored.
Route power wires in a safe manner in accordance with good practice and local codes.
Wear proper personal protective equipment including safety glasses and insulated gloves
when making connections to power circuits.
Ensure hands, shoes, and floor are dry before making any connection to a power line.
Make sure the unit is turned OFF before making connection to terminals. Make sure all
circuits are de-energized before making connections.
Before each use, inspect all cables for breaks or cracks in the insulation. Replace
immediately if defective.
Information is subject to change without notice.
SmartStack is a trademark of Horner APG, LLC.
PAGE 8
5
10 NOV 2006
MAN0228-09
DIM210
ADDITIONAL REFERENCES
The following information serves as a general listing of Horner controller products and other references of
interest and their corresponding manual numbers. Visit our website listed in the Technical Support section
to obtain user documentation and updates.
Note: This list is not intended for users to determine which products are appropriate for their
application; controller products differ in the features that they support. If assistance is required,
see the Technical Support section in this document.
Controller
Manual Number
XLE Series (e.g., HE-XExxx)
QX Series (e.g., HE-QXxxx)
NX Series (e.g., HE-NXxxx)
LX Series (e.g., LX-xxx; also covers RCS116)
Color Touch OCS (e.g., OCSxxx)
OCS (Operator Control Station) (e.g., OCS1xx / 2xx; Graphic
OCS250)
Remote Control Station (e.g., RCS2x0)
MiniOCS (e.g., HE500OCSxxx, HE500RCSxxx)
MAN0805
MAN0798
MAN0781
MAN0755
MAN0465
MAN0227
MAN0305
Other Useful References
CAN Networks
Cscape Programming and Reference
Wiring Accessories and Spare Parts Manual
DeviceNet™ Implementation
Wiring Accessories and Spare Parts Manual
6
MAN0799
MAN0313
MAN0347
SUP0326
MAN0347
TECHNICAL SUPPORT
For assistance and manual up-dates, contact Technical Support at the following locations:
North America:+
Europe:
(317) 916-4274
(+) 353-21-4321-266
www.heapg.com
www.horner-apg.com
Information is subject to change without notice.
SmartStack is a trademark of Horner APG, LLC.