Convertible Console R410A / EOHC 18 to 48

Convertible Console R410A / EOHC 18 to 48
minisplit systems
Convertible Console
EOHC 18 to 48
A complete range from 5.2 kW to 14.0 kW
NEW
R410A
by johnson controls
Features
Remote controller
• Convertible - floor or ceiling
• Horizontal and vertical
air sweep function
• Wide angle air distribution
• Slim profile - flush mounting
• Service valve protection cover
• Rustproof casing
• Wireless
• 5 operation modes
(Cool/Heat/Auto/Dry/Fan)
• Sleep mode
• Room temperature setting
• Fan speed selection
• Timer
• Air flow direction setting
• LCD display
Convertible Console
EOHC 18 to 48
Technical features
Set reference
EOHC
Indoor unit
Sizes
EOKC 18 FS
EOKC 24 FS
EOKC 36 FS
EOKC 42 FS
EOKC 48 FS
Outdoor unit
Sizes
ENJC 18 FS
ENJC 24 FS
ENJC 36 FS
ENJC 42 FS
ENJC 48 FS
Cooling capacity
kW
5.2
7.2
10.0
12.0
14.0
Heating capacity
kW
5.7
8.0
11.0
14.0
15.5
Compressor
Type
Rotary
Scroll
Refrigerant
R410A
Power supply
V/Ph/Hz
230 / 1 / 50 + E
400 / 3 / 50 + E + N
cooling
kW
1.80
2.50
3.50
4.50
5.70
heating
kW
2.00
2.59
3.30
4.70
5.80
EER
2.89
2.88
2.86
2.67
2.46
COP
2.85
3.09
3.33
2.98
2.67
cooling
C
C
C
D
E
heating
D
D
C
D
E
25
25
16
16
16
Power input
Energy Class
Fuse rating
A
Indoor airflow (high speed)
Sound pressure
at 1 m
m3/h
700
1 170
1 800
1 800
2 000
Indoor (H/M/L)
dB(A)
54 / 50 / 46
50 / 48 / 46
54 / 51 / 48
54 / 51 / 48
58 / 55 / 52
Outdoor
dB(A)
56
59
58
60
63
H (mm)
695
600
695
695
695
W (mm)
836
1 300
1 590
1 590
1 590
D (mm)
238
188
238
238
238
H (mm)
540
700
840
1 250
1 250
W (mm)
848
1 018
1 018
950
950
D (mm)
320
412
412
412
412
Indoor unit
kg
27
32
42
42
42
Outdoor unit
kg
40
59
90
112
112
Gas
1/2”
5/8”
3/4”
3/4”
3/4”
Liquid
1/4”
3/8”
1/2”
1/2”
1/2”
g
1 500
2 200
3 200
3 550
3 800
Length
m
20
30
50
50
50
Height
m
15
15
30
30
30
Indoor
Dimensions
Outdoor
Net weight
Type of connection
Piping
Diameter
Refrigerant charge
Pipe run
Flare
Operating limits - cooling mode
min/max
+18°C / +43°C
Operating limits - heating mode
min/max
-15°C / +24°C
Nominal cooling capacity based on : - Indoor Air Temp. 27°C DB / 19°C WB - Outdoor Air Temp. 35°C DB
Nominal heating capacity based on : - Indoor Air Temp. 21°C DB - Outdoor Air Temp. 7°C DB/6°C WB
Piping length : 5 m with initial charge
Codes / Options / Accessories
Sizes
18
24
36
42
48
Set code
S693890501
S693890701
S693891001
S693891203
S693891403
Indoor unit code
S683835011
S683897031
S683893711
S683894581
S683894081
Outdoor unit code
S683810501
S683810701
S683811011
S683811203
S683811403
Wired control
O
Weekly timer control
O
Centralised control
O
Condensate pump
A
Low ambient kit
A
Wall mounting kit
A
AMW50A
A
AMF44B
Floor mounting kit
O= option (factory fitted)
E-COM-M1008
AMR01Y
AMR02M
-
AMR03M
AMP01C
A= accessory (supplied loose)
Manufacturer reserves the rights to change specifications without prior notice.