on
SPRINKLERS, AUTOMATIC AND OPEN
Viking Corp.
Hastings, MI
Copyright © 1996 Underwriters Laboratories Inc.
Underwriters Laboratories Inc. authorizes the above named company to
reproduce this Report provided it is reproduced in its entirety.
File Ex643
Page G1
Issued:
7-16-96
GENERAL
INTRODUCTION:
This Report describes the investigation of automatic
sprinklers intended to be installed in accordance with the
National Fire Protection Association Standard For The
Installation of Sprinkler Systems, NFPA 13.
OBJECT:
The object of this investigation was to determine compliance
of the automatic sprinklers with the Standard For Automatic
Sprinklers For Fire Protection Service, UL 199.
PLAN:
The investigation of the automatic sprinklers consisted of
conducting a product conformance evaluation and performance
testing as described in UL 199.
MGM/GEL:tjm
NKDLS
File EX643
Page 1
Issued:
Revised:
1996-07-16
2006-05-23
DESCRIPTION
PRODUCT COVERED:
Automatic sprinklers incorporating frangible 5 mm glass bulb heat
responsive element of the following model, type, and temperature ratings.
USL, CNL
Model
Response Type
K-Factor
N.P.T.
Description
Temperature
VK540
Standard
11.2
½, ¾
Large Drop - Upright
155,175,200,286
*
CONSTRUCTION DETAILS:
The devices have been examined and found to comply with the Standard For
Automatic Sprinklers in effect as of the date of this Report.
USE:
The products covered by this Report are for use in accordance with the
National Fire Protection Association Standard For The Installation of
Sprinkler Systems, NFPA 13, and the manufacturer's installation instructions
(see Fig. 1.)
ENGINEERING CONSIDERATIONS ONLY:
CNL - Indicates Listing to Canadian National Standards for ULC-C199.
File Ex643
Page C1
Issued:
Revised:
7-16-96
1-17-97
C O N C L U S I O N
Samples of the products covered by this Report have been
found to comply with the requirements covering the class and the
products are judged to be eligible for Listing and Follow-Up
Service. The manufacturer is authorized to use the Laboratories'
Mark on such products which comply with the Follow-Up Service
Procedure and any other applicable requirements of Underwriters
Laboratories Inc. Only those products which properly bear the
Laboratories' Mark are considered as Listed by Underwriters
Laboratories Inc.
Report by:
MICHAEL G. McCORMICK
Engineering Associate
Reviewed by:
GEORGE E. LAVERICK
Engineering Group Leader
*Test Record No. 2 by:
JENNIFER OWERS
Engineer
GEORGE E. LAVERICK
Engineering Group Leader