Manual 12692468
DATA SHEET
LS Programmable Logic Controller
Analog Output Option Board
 Safety Precautions
► Safety Precautions is for using the product safely and correctly in order to prevent
the accidents and danger, so please go by them.
► The precautions explained here only apply to this module. For safety precautions
on the PLC system, refer to User‟s manual.
► The precautions are divided into 2 sections, „Warning‟ and „Caution‟. Each of the
meanings is represented as follows.
If you violate instructions, it can cause death, fatal injury or a
XGB
Warning considerable loss of property
XBO-DA02A
Caution
If you violate instructions, it can cause a slight injury or a slight
loss of products
► The symbols which are indicated in the PLC and User‟s Manual mean as follows.
This symbol means paying attention because of danger of injury, fire,
or malfunction
► This symbol means paying attention because of danger of electric shock.
Store this datasheet in a safe place so that you can take it out and read
it whenever necessary. Always forward it to the end user
Related Manual
Read this data sheet carefully prior to any operation, mounting, installation or start-up of the
product.
Name
Code
XGB analog
10310000920
XGK/XGB Instruction & Programming
10310000754
XG5000
10310000512
XGB Hardware
10310000926
Revision History
Date
2011.01
2011.05
Version
V1.0
V1.1
Updated Information
First Edition
CI changed
Applicable version
For system configuration, the following version is necessary.
Segment
XGB E type
XGB S type
XGB SU type
XG5000
Version
V1.1 or above
V1.1 or above
V1.0 or above
V3.61 or above
 Handling Precautions
► Don‟t drop or make impact.
► Don‟t detach PCB from case. It may cause problem.
► When wiring, let no foreign material go into the module. If it goes into the module,
remove it.
► Don‟t detach the module from slot while power is on
- When using LSIS equipment, thoroughly read this
datasheet and associated manuals introduced in this
datasheet. Also pay careful attention to safety and handle
the module properly.
- Store this datasheet in a safe place so that you can take it
out and read it whenever necessary.
Warning
2. Performance Specifications
Following presents performance specification of analog input option board.
Item
Number of channel
Type
Performance specification
2 channels
Current
DC 4 ~ 20㎃
DC 0 ~ 10V
DC 0 ~ 20㎃
Analog
(load resistance:
(load resistance:
output
2㏀ or above)
Range
450Ω)
Output range can be set at user program or
I/O parameter per each channel-Note1)
Form
12 bit binary data
Unsigned 0 ~ 4000
Digital
Signed -2000 ~ 2000
Input
Range
Precise 0 ~ 1000 (DC 0 ~10V) 400~2000 (DC 4~20㎃)
0 ~ 2000 (DC 0~20㎃)
value
Percentile 0 ~ 1000
1/4000 (DC 4~20㎃: 1/3200)
Max. resolution
5㎂ (DC 0~20㎃)
2.5mV (DC 0 ~10V)
6.25㎂ (DC 4~20㎃)
Precision
±1.0% or less
Max. conversion speed
1ms/channel + scan time
CH output status setting
Additional function
(select among former, min, middle, max value)
Gain adjustment function
Non-insulation
between
analog
output
channels
Insulation method
Non-insulation between output terminal and
PLC basic unit
Input terminal
5-point terminal block
I/O occupation point
Fixed type: 64 point
Max. installation count
Supply power
Consumption current
Weight
► Do not contact the terminals while the power is applied.
Risk of electric shock and malfunction.
► Protect the product from being gone into by foreign metallic matter.
Risk of fire, electric shock and malfunction.
Voltage
1EA (when using XBC-DR10E/DR14E “E” type)
2EA (when using XBC-DR20E/DR30E “E” type)
2EA (when using XBC-DxxxS/SU “S” type)
Internal DC5V
150㎃
20g
Remarks
Note1) Offset/gain value on the analog output range can be adjusted at
XG5000- I/O parameter
► Risk of fire, electric shock and malfunction.
Risk of injury and fire by explosion and ignition.
1. General Specifications
 HEAD OFFICE
LS Tower, 127, LS-ro, Dongan-gu, Anyang-si,Gyeonggi-do, 431-848, Korea
Tel: 82-2-2034-4870
Fax: (82-2)2034-4648 e-mail: cshwang@lsis.biz
Caution
► Be sure to check the rated voltage and terminal arrangement for the
module before wiring work.
Risk of electric shock, fire and malfunction.
 LSIS(ME) FZE _ Dubai, U.A.E.
Tel: 971-4-886-5360
Fax: 971-4-886-5361
e-mail: jungyongl@lsis.biz
► Tighten the screw of terminal block with the specified torque range.
If the terminal screw is loose, it can cause fire and electric shock.
 LSIS Tokyo Office _ Tokyo, Japan
Tel: 81-3-3582-9128
Fax: 81-3-3582-2667
.
e-mail: jschuna@lsis.biz
 LSIS Shanghai Office _ Shanghai, China
Tel: 86-21-5237-9977(609) Fax: 89-21-5237-7189
► Use the PLC in an environment that meets the general
specifications contained in this datasheet.
Risk of electrical shock, fire, erroneous operation and deterioration of the
PLC.
e-mail: liyong@lsis.com.cn
 LSIS Beijing Office _ Beijing, China
Tel: 86-10-5825-6027(666) Fax: 86-10-5825-6028
► Be sure that external load does not exceed the rating of output
module.
Risk of fire and erroneous operation.
e-mail: xunmj@lsis.com.cn
► Do not use the PLC in the environment of direct vibration
Risk of electrical shock, fire and erroneous operation.
 LSIS Guangzhou Office _ Guangzhou, China
Tel: 86-20-8328-6754
Fax: 86-20-8326-6287
e-mail: chenxs@lsis.com.cn
 LSIS Chengdu Office _ Chengdu, China
Tel: 86-20-8328-6754
Fax: 86-20-8326-6287
► Do not disassemble, repair or modify the PLC.
Risk of electrical shock, fire and erroneous operation
No
Item
2
4
5
Vibration
resistance
6
Shocks
resistance
e-mail: comysb@lsis.biz
 LSIS Europe B.V., Netherlands
Tel: +31 (0)20 654 1420
Fax: +31(0)20 654 1429 e-mail: junshickp@lsis.biz
 Precautions for use
► Do not Install other places except PLC controlled place.
► Make sure that the FG terminal is grounded with class 3 grounding which is
dedicated to the PLC. Otherwise, it can cause disorder or malfunction of PLC
PLC
Others
PLC
Others
PLC
Noise
resistance
7
LS constantly endeavors to improve our products so that information in this
datasheet is subject to change without notice.
The date of issue: 2011. 5
10310001188 Ver 1.1
3. Parts Name and Descriptions
35.0mm
►
►
►
►
►
① Hook for fixation
② Terminal block
③ Cover
⑤ Connector for
option board
⑥ Input
connector
⑤
⑥
C) Bad
Connect expansion connector correctly when expansion module is needed.
Do not detach PCB from the case of the module and do not modify the module.
Turn off power when attaching or detaching module.
Cellular phone or walkie-talkie should be farther than 30cm from the PLC.
Input signal and communication line should be farther than10cm from a hightension and a power line in order not to be affected by noise and magnetic field.
(1) Precautions for wiring
(a) Don‟t let AC power line near to analog output option board‟s external output signal
line. With an enough distance kept away between, it will be free from surge or
inductive noise.
(b) Cable shall be selected in due consideration of ambient temperature and allowable
current. More than AWG22 (0.3㎟) is recommended.
(c) Don‟t let the cable too close to hot device and material or in direct contact with oil for
long, which will cause damage or abnormal operation due to short-circuit.
(d) Check the polarity when wiring the terminal.
(e) Wiring with high-voltage line or power line may produce inductive hindrance causing
abnormal operation or defect.
(f) Enable the channel that you want to use
Wiring example
④ Hook for fixation
③
B) Good
4. Wiring
49.0mm
②
-
5 ~ 95%RH, non-condensing
-
5 ~ 95%RH, non-condensing
-
For discontinuous vibration
Acceleration
Frequency
Amplitude
times
10≤f∠57 Hz
0.075 mm
10 times in
57 ≤f≤150 Hz 9.8㎨ (1G)
each
For continuous vibration
direction
Acceleration
Frequency
Amplitude
for
10≤f∠57 Hz
0.035 mm
X, Y, Z
57≤f≤150 Hz 4.9㎨(0.5G)
 Max. impact acceleration : 147 ㎨ (15G)
 Authorized time : 11㎳
 Pulse wave : Sign half-wave pulse
(Each 3 times in X,Y,Z directions)
Square wave
AC: ±1,500V
impulse noise
DC: ±900V
Electrostatic
Voltage: 4kV (Contact discharge)
discharge
-
Radiated
electromagnetic
field noise
Name
Description
Hook for fixation ▶ Hook for fixing the option board to basic unit
▶ Wiring terminal block to connect with external
Term nal block
device(Analog output)
Cover
▶ Option board cover
Connector for ▶ Connection connector for connecting the option
option board
board to the basic unit
▶ Wiring connector for connecting with the external
Input connector
device
Ambient
conditions
Operating
height
Pollution
degree
Cooling
type
8
9
10
11
Power
supply
module
2 kV
IEC61131-2
IEC61131-2
LSIS
standard
IEC61131-2
IEC61000-4-2
IEC61131-2
IEC61000-4-3
80 ~ 1,000 MHz, 10 V/m
Voltage
A) Best
No.
①④
-
-25 ~ 70℃
Fast transient Segment
/burst noise
Others
 Homepage: http://eng.lsis.biz
10.3mm
Standard
0 ~ 55℃
Operating
humidity
Storage
humidity
3
► When disposing of PLC and battery, treat it as industrial waste.
Risk of poisonous pollution or explosion.
 LSIS Qingdao Office _ Qingdao, China
Tel: 86-532-8501-6068
Fax: 86-532-8501-6057 e-mail: wangzy@lsis.com.cn
Specification
Operating
temperature
Storage
temperature
1
Digital/analog
input/output
communication
interface
1 kV
IEC61131-2
IEC61000-4-4
No corrosive gas or dust
-
2000m or less
-
2 or less
-
Natural air cooling
-
5. Internal memory
7. Dimension (㎜)
Internal memory area for analog output option board
(1) Analog/digital conversion data I/O area
type
Device
_0x_ERR
_0x_RDY
_0x_DA0_ACT
_0x_DA1_ACT
_0x_DA0_ERR
_0x_DA1_ERR
Variable
BIT
BIT
BIT
BIT
BIT
BIT
U0x.00.0
U0x.00.F
U0x.01.2
U0x.01.3
U0x.01.A
U0x.01.B
_0x_DA0_OUTEN
BIT
U0x.06.0
_0x_DA1_OUTEN
BIT
U0x.06.1
WORD
WORD
U0x.07
U0x.08
_0x_DA0 DATA
_0x_DA1_DATA
Comment
Module Error
Module Ready
CH0 active
CH1 active
CH0 error
CH1 error
CH0 output state
setting
CH1 output state
setting
CH0 input value
CH1 input value
Read/
Write
Signal
direction
Read
Option→
CPU
Write
Option↔
CPU
a) Current Output
Load
Remarks
How to express U device
U0x.00.0
450 Ω
or
less
b) Voltage Output
Load
2kΩ
or
above
Slot
Bit no.
Word no.
Ex1) CH0 input value of the module at slot 9 -> U09.07
Ex2) CH0 error of the module at slot 9 -> U09.01.A
(2) Analog/digital operation parameter setting area
Memory address
Description
Hex
Dec
0H
1H
2H
8H
BH
CH
DH
0
1
2
8
11
12
13
Enable CH
Output range setting
Input data type setting
CH output state setting
Output CH0 gain weighting
Output CH1 gain weighting
Setting error information output area
Read/Write
Instruction
Read/Write
PUT
GET
Read
GET
6. Error code
(1) It saves error code detected when setting (in case of setting by program)
(2) Setting error is canceled when setting goes in the normal range by re-setting
(3) When U0X.01.8~ U0X.01.9 (setting error flag) is on, check this area and fix the
corresponding setting to cancel the error
(4) When using GET instruction, setting error information address is as follows.
Error
Type
Description
Priority
Remark
code
50# Output CH range setting error
2
60# Output CH data type setting error
3
Setting
# means CH No.
70# Output CH count average setting error
4
error
Output ch0,1
80# Output CH gain weighting setting error
5
90# Output CH input value out of range error
1
(5) When more than one error occurs, it saves error code having higher priority.
8. Warranty
(1) Warranty period
LSIS provides an 18-month-warranty from the date of the production.
(2) Warranty conditions
For troubles within the warranty period, LSIS will replace the entire PLC or
repair the troubled parts free of charge except the following cases.
(a) The troubles caused by improper condition, environment or treatment
except the instructions of LSIS.
(b) The troubles caused by external devices.
(c) The troubles caused by remodeling or repairing based on the user‟s own
discretion.
(d) The troubles caused by improper usage of the product.
(e) The troubles caused by the reason which exceeded the expectation from
science and technology level when LSIS manufactured the product.
(f) The troubles caused by natural disaster.
(3) This warranty is limited to the PLC itself only. It is not valid for the whole
system which the PLC is attached to.