AxisAX Series AX-BMS
Product Data Sheet
BMS / Graphics Interface
AX-BMS
Providing superior monitoring and control in a remote
location, via a serial RS-232 interface, the Advanced
BMS/Graphics Interface (AX-BMS) provides building
management system or color graphics package
interfacing to a single AxisAX Series Intelligent Fire Alarm
Control Panel or to a complete AxisAX Series peer-topeer network (AD-NeT-PluS) installation.
The BMS/Graphics Interface (AX-BMS) consists of
the AX-BMS PCB and an enclosure. It consumes one
node address on an AD-NeT-PluS network, and can be
utilized on either the Advanced Style 4 or Style 7 fault
tolerant peer-to-peer network.
The state of each network node and the status of
individual devices (such as analog values of intelligent
smoke detectors) of an AD-NeT-PluS network can
be sent to the building management system or color
graphics package at any time in a user-friendly, clear
and concise manner. In addition, at any time control
and view requests can be sent to the AX-BMS interface
device.
Unique Features:
• AD-NeT-PluS Network Module
• Style 4 (Class B) and Style 7 (Class A) Versions
• Sector Base/Building Partition Programming
• Easy Configuration via PC-NeT
• Ad-VIEW Graphics Interface
Features:
• One-Way / Two-Way Interface to AD-NeT-PluS
• Adjustable Baud Rate Interface
• Power Supply Contact Monitoring Input
• Uncomplicated and Simplistic Installation
Listings and Approvals:
• ETL ANSI/UL 864 Listed: 3118002NYM-001B
• NYCFD COA#6105
900-055
Rev. 1.1
Page 1 of 2
www.advancedco.com
AX-BMS Wiring
SUPPLY
24V
0V
FAULT I/P
0V 24V
FLT FLT
RS232
USB
GND RX
SCN
TX
B
A
SCN
B
A
REBOOT
SETUP
DC Power Input
Fault Input
RS232
RUN PROG
Ad-NeT-PluS
Network In
Network Out
Setup Switch
AX-BMS Specifications
Operating Voltage
18 - 28 VDC
Operating Current (AX-NET4 & 7)
AX-BMS (Style 4 network)
AX-BMS/ST7 (Style 7 network)
70 mA
110 mA
Environment
Indoor, Dry
Operating Temperature
32-1200 F (0-480 C)
Humidity
10-95% (non-condensing)
Enclosure
Dimensions
Knockouts
8 3/8“ H x 11 3/4“ W x 1 5/8” D
4 top, 4 bottom rear
Weight (PCB & enclosure)
4.5 lb
Wiring
Twisted pair 18 - 20 AWG minimum
Recommended Twisted Shielded (Belden 8760, 8762)
Serial Interface
Isolated RS-232 w/Adjustable Baud Rate
Fault Input
Remote Power Supply Monitoring Input
Indications
Microprocessor Heartbeat
Network Transmit/Receive
Ordering Information
AX-BMS
BMS/Graphics Interface Style 4 w/enclosure
AX-BMS/ST7
BMS/Graphics Interface Style 7 w/enclosure
AX-BMS-PCB
BMS/Graphics Interface PCB
AX-BMS-CAB
BMS/Graphics Interface enclosure
Advanced Fire Systems Inc
100 South Street, Hopkinton, MA 01748
As our policy is one of constant product improvement the right is therefore
reserved to modify product specifications without prior notice.
900-055
Rev. 1.1
Page 2 of 2
www.advancedco.com
Tel:
Fax:
Email:
Web:
(508) 435-9995
(508) 435-9990
usa@advancedco.com
www.advancedco.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising