4TWR4036D-SUB-1

4TWR4036D-SUB-1
4TWR4036D-SUB-1
S U BM IT TA L
TAG: _________________________________
3 Ton Split System
Heat Pump – 1 Phase
NOTE: All dimensions are in mm/inches.
4TWR4036D
Product Specifications
OUTDOOR UNIT 12
POWER CONNS. — V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR. PROT. RTG. – MAX. (AMPS)
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
FACTORY INSTALLED
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
LBS. — R-410A (O.D. UNIT) 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
CHARGING SPECIFICATION
SUBCOOLING
DIMENSIONS
CRATED (IN.)
WEIGHT
SHIPPING (LBS.)
NET (LBS.)
MODELS
4TWR4036D
BASE
A
B
C
4
841
(33-1/8)
946
(37-1/4)
870
(34-1/4)
D
3/4
E
3/8
F
D
H
J
K
152 (6)
98
(3-7/8)
219
(8-5/8)
86
(3-3/8)
508 (20)
4TWR4036D1000A
208/230/1/60
22
35
CLIMATUFF® - SCROLL
1-1
208/230/1/60
16.7 - 79
NO
NO
NO
PROPELLER
27.5 - 1
DIRECT - 1
4385
1 - 1/5
850
200/230/1/60
0.95
SPINE FIN™
1 - 24
22
3/8
6 LBS. - 2 OZ.
YES
3/4
3/8
8°F
H X W X D
38.4 x 35.1 x 38.7
229
198
1 Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which
is based on AHRI standard 210/240.
2 Rated in accordance with AHRI standard 270.
3 Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses.
4 Standard Air — Dry Coil — Outdoor
5 This value approximate. For more precise value see unit nameplate.
6 Max. linear length 60 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft.
For greater length consult refrigerant piping software Pub. No. 32-3312-0*
(* denotes latest revision).
7 This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to
compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection
current.
8 No means no start components. Yes means quick start kit components. PTC means positive temperature
coefficient starter.
Sound Power Level
Model
A-Weighted
Sound Power
Level [dB(A)]
63 Hz
125 Hz
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
4TWR4036D
76
84
75
70
72
67
62
57
50
Full Octave Sound Power [dB]
Note: Rated in accordance with AHRI Standard 270-2008
© 2014 Trane
Mechanical
­Specification Options
General
The 4TWR4 is fully charged from the
factory for up to 15 feet of piping. This
unit is designed to operate at outdoor
ambient temperatures as high as 115°F.
Cooling capacities are matched with
a wide selection of air handlers and
furnace coils that are AHRI certified. The
unit is certified to UL 1995. Exterior is
designed for outdoor application.
Condenser Coil
The outdoor coil provides low airflow
resistance and efficient heat transfer.
The coil is protected on all four sides by
louvered panels.
Casing
Unit casing is constructed of heavy
gauge, G90 galvanized steel and
painted with a weather-resistant powder
paint on fan top cover and louvered
panels, prepaint on all other panels.
Corrosion and weatherproof CMBP-G30
base.
Accessories
Thermostats — Cooling only and
heat/cooling (manual and automatic
changeover). Sub-base to match
thermostat and locking thermostat cover.
Low Ambient Cooling
As manufactured, this unit has a cooling
capability to 55°F. The addition of an
evaporator defrost control with TXV
permits low ambient cooling to 20° F.
Refrigerant Controls
Refrigeration system controls include
condenser fan and compressor
contactor. High and low pressure
controls are inherent to the compressor.
A factory installed liquid line drier is
standard.
Compressor
The compressor features internal over
temperature and pressure protection
and total dipped hermetic motor. Other
features include: centrifugal oil pump
and low vibration and noise.
Trane
www.trane.com
07/14
Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising