General Specifi cations EJX110A Differential Pressure Transmitter

General Specifi cations EJX110A Differential Pressure Transmitter
<<Contents>> <<Index>>
EJX110A
Differential Pressure Transmitter
General
Specifications
[Style: S3]
GS 01C25B01-01EN
The high performance differential pressure transmitter
EJX110A features single crystal silicon resonant
sensor and is suitable to measure liquid, gas, or
steam flow as well as liquid level, density and
pressure. EJX110A outputs a 4 to 20 mA DC signal
corresponding to the measured differential pressure.
Its highly accurate and stable sensor can also
measure the static pressure which can be shown on
the integral indicator or remotely monitored via BRAIN
or HART communications. Other key features include
quick response, remote set-up using communications,
diagnostics and optional status output for pressure
high/low alarm. The multi-sensing technology provides
the advanced diagnostic function to detect such
abnormalities as an impulse line blockage or heat
trace breakage. FOUNDATION Fieldbus and PROFIBUS
PA protocol types are also available. All EJX series
models in their standard configuration, with the
exception of the Fieldbus and PROFIBUS types, are
certified by TÜV as complying with SIL 2 for safety
requirement.
 STANDARD SPECIFICATIONS
Refer to GS 01C25T02-01EN for Fieldbus
communication type and GS 01C25T04-01EN for
PROFIBUS PA communication type for the items
marked with “◊.”
□ SPAN AND RANGE LIMITS
Measurement
Span/Range
Span
F*
Range
L*
M
H
V
Span
Range
Span
Range
Span
Range
Span
Range
*:
mmH2O
(/D4)
0.1 to 5
10 to 500
-500 to
-5 to 5
-20 to 20
-50 to 50
500
0.1 to 10
0.4 to 40
1 to 100 10 to 1000
-100 to
-1000 to
-10 to 10
-40 to 40
100
1000
50 to
0.5 to 100 2 to 400
5 to 1000
10000
-100 to
-400 to
-1000 to
-10000 to
100
400
1000
10000
0.025 to 5
2.5 to 500 10 to 2000 25 to 5000
kgf/cm2
-500 to
-2000 to
-5000 to
-5 to 5
500
2000
5000
kgf/cm2
0.07 to 14 10 to 2000 0.7 to 140 0.7 to 140
MPa
psi
bar
kgf/cm2
-0.5 to 14
-71 to
-5 to 140
-5 to 140
MPa
2000
bar
kgf/cm2
kPa
inH2O
(/D1)
0.4 to 20
mbar
(/D3)
1 to 50
F capsule is applicable for wetted parts material
code S.
L capsule is applicable for wetted parts material
code other than S.
□ PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted
parts material code S and silicone oil, unless
otherwise mentioned.
For Fieldbus and PROFIBUS PA communication
types, use calibrated range instead of span in the
following specifications.
Specification Conformance
EJX series ensures specification conformance to at
least ±3σ.
Reference Accuracy of Calibrated Span
(includes terminal-based linearity, hysteresis, and
repeatability)
Measurement span
Reference X ≤ span
accuracy X > span
X
URL
(upper range limit)
Measurement span
Reference X ≤ span
accuracy X > span
X
URL
(upper range limit)
Measurement span
Reference X ≤ span
accuracy X > span
X
URL
(upper range limit)
F
±0.04% of Span
±(0.015+0.01 URL/span)% of Span
2 kPa (8 inH2O)
5 kPa (20 inH2O)
M
±0.04% of Span
±(0.002+0.0019 URL/span)% of Span
5 kPa (20 inH2O)
100 kPa (400 inH2O)
H
±0.04% of Span
±(0.005+0.0049 URL/span)% of Span
70 kPa (280 inH2O)
500 kPa (2000 inH2O)
Yokogawa Electric Corporation
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-5690 Fax.: 81-422-52-2018
GS 01C25B01-01EN
©Copyright Feb. 2004
23rd Edition Jul. 2015
2
<<Contents>> <<Index>>
Measurement span
Reference X ≤ span
accuracy X > span
X
URL
(upper range limit)
V
±0.04% of Span
±(0.005+0.00125 URL/span)% of Span
500 kPa (2000 inH2O)
14 MPa (2000 psi)
Square Root Output Accuracy
The square root accuracy is a percent of flow span.
Output
50% or Greater
50% to Dropout point
Accuracy
Same as reference accuracy
Reference accuracy × 50
Square root output (%)
Ambient Temperature Effects per 28°C (50°F)
Change
Capsule
F
M
H, V
Effect
±(0.055% Span + 0.18% URL)
±(0.04% Span + 0.009% URL)
±(0.04% Span + 0.0125% URL)
 Total Probable Error (M capsule)
±0.12% of Span @1:1 to 5:1 Rangedown
Total probable error, known as a measure of the total
performance of the transmitters under the condition of
fixed line presurre.
Total Probable Error = ± E12 + E22 + E32
E1: Reference Accuracy of Calibrated Span
E2: Ambient Temperature Effects per 28°C change
E3: Static Span Effects per 6.9 MPa change
 Total Accuracy (M capsule)
±0.12% of Span @1:1 Rangedown
±0.25% of Span @ 5:1 Rangedown
Total accuracy is a comprehensive measure of
transmitter total performance, covering all major
factors in actual installation, that cause errors in
measurement.
As a standard measure, YOKOGAWA uses this to
evaluate transmitter performance.
Total Accuracy = ± E12 + E22 + (E3 + E4)2 + E52
E1: Reference Accuracy of Calibrated Span
E2: Ambient Temperature Effects per 28°C change
E3: Static Span Effects per 6.9 MPa change
E4: Static Zero Effects per 6.9 MPa change
E5: Overpressure Effects upto overpressure 25MPa
Not only a day-to-day changes in temperature can
affect the measurement and lead to unnoticed errors;
fluctuaion of line pressure, incorrect operation of
three/five valve manifold leading to over-pressure
events, and other phenomena can have the similar
result. Total Accuracy factors in such changes and
errors and provides much comprehensive and
practical determination of how a transmitter will
perform under actual plant operation.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
Static Pressure Effects per 6.9 MPa (1000 psi)
Change
Span Effects
F, M, H and V capsules
±0.075% of span
Effect on Zero
Capsule
F
M
H, V
Effect
±0.1% URL
±0.02% URL
±0.028% URL
Overpressure Effects
Overpressure condition: up to maximum working
pressure
M, H and V capsules
±0.03% of URL
Stability (All normal operating condition, including
overpressure effects)
M, H and V capsules
±0.1% of URL per 10 years
F capsule
±0.1% of URL per one year
Power Supply Effects(Output signal code D, E
and J)
±0.005 % per Volt (from 21.6 to 32 V DC, 350Ω)
Vibration Effects
Amplifier housing code 1 and 3:
Less than 0.1% of URL when tested per the
requirements of IEC60770-1 field or pipeline
with high vibration level (10-60 Hz, 0.21 mm
displacement/60-2000 Hz 3 g)
Amplifier housing code 2:
Less than ±0.1% of URL when tested per the
requirements of IEC60770-1 field with general
application or pipeline with low vibration level (10-60
Hz 0.15mm displacement /60-500 Hz 2g)
Mounting Position Effects
Rotation in diaphragm plane has no effect. Tilting
up to 90 degree will cause zero shift up to 0.4 kPa
(1.6 inH2O) which can be corrected by the zero
adjustment.
Response Time (Differential pressure) “◊”
90 ms for Wetted Parts material code S except for
Measuring span code F. 150 ms for Wetted Parts
Material Code H, M, T, A, B and D or Measuring span
code F.
When amplifier damping is set to zero and including
dead time of 45 ms (nominal)
Static Pressure Signal Range and Accuracy
(For monitoring via communication or on
indicator. Includes terminal-based linearity,
hysteresis, and repeatability)
Range
Upper Range Value and Lower Range Value of the
statice pressure can be set in the range between 0
and Maximum Working Pressure(MWP). The upper
range value must be greater than the lower range
value. Minimum setting span is 0.5 MPa(73 psi).
Measuring either the pressure of high pressure side
or low pressure side is user-selectable.
GS 01C25B01-01EN
Jul. 24, 2015-00
3
<<Contents>> <<Index>>
Accuracy
Absolute Pressure
1 MPa or higher: ±0.2% of span
Less than 1 MPa: ±0.2%×(1 MPa/span) of span
Gauge Pressure Reference
Gauge pressure reference is 1013 hPa (1 atm)
Note: Gauge pressure variable is based on the above
fixed reference and thus subject to be affected by
the change of atomospheric pressure.
□ FUNCTIONAL SPECIFICATIONS
Output “◊”
Two wire 4 to 20 mA DC output with digital
communications, linear or square root programmable.
BRAIN or HART FSK protocol are superimposed on
the 4 to 20 mA signal.
Output range: 3.6 mA to 21.6 mA
Output limits conforming to NAMUR NE43 can be
pre-set by option code C2 or C3.
Failure Alarm (Output signal code D, E and J)
Analog output status at CPU failure and hardware
error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: −5%, 3.2 mA DC or less
Analog output status at process abnormality (Option
code /DG6);
The result of process abnormality detected by the
advanced diagnostic function can be reflected to
an analog alert status. The following three setting
modes are available.
Mode
Burnout
Fall back
Off
110%,
Standard
21.6mA or more Holds to a
-2.5%,
specified value
/C1
Normal output
3.6mA or less
within the
(No analog
output range
Option
-1.25%,
output alarm)
/C2
Code
3.8mA or less from 3.6mA to
21.6mA
103.1%,
/C3
20.5mA or more
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable from
0.00 to 100.00 s by software and added to response
time.
Note: For BRAIN protocol type, when amplifier software
damping is set to less than 0.5 s, communication
may occasionally be unavailble during the
operation, especially while output changes
dynamically. The default setting of damping
ensures stable communication.
Update Period “◊”
Differential pressure: 45 ms
Static pressure: 360 ms
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the
lower and upper range limits of the capsule.
External Zero Adjustment
External zero is continuously adjustable with
0.01% incremental resolution of span. Re-range
can be done locally using the digital indicator with
rangesetting switch.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
Integral Indicator (LCD display, optional) “◊”
5-digit numerical display, 6-digit unit display and bar
graph.
The indicator is configurable to display one or up to
four of the following variables periodically.;
Measured differential pressure, differential pressure
in %, scaled differential pressure, measured static
pressure. See also “Factory Setting.”
Local Parameter Setting (Output signal code D, E,
and J)
Parameter configuration by the external zero
adjustment screw and push button (Integral indicator
code E) offers easy and quick setup for parameters of
Tag number, Unit, LRV, URV, Damping, Output mode
(linear/square root), Display out 1, and Re-range by
applying actual pressure (LRV/URV).
Burst Pressure Limits
69 MPa (10,000 psi) for wetted parts material S,
except for Measurement span F.
47 MPa (6,800 psi) for wetted parts material other
than S or Measurement span F.
Self Diagnostics
CPU failure, hardware failure, configuration error,
and over-range error for differential pressure, static
pressure and capsule temperature.
User-configurable process high/low alarm for
differential pressure and static pressure is also
available, and its status can be output when optional
status output is specified.
Advanced Diagnostics (optional) “◊”
Applicable for Output signal code E, J and F.
• Impulse line blockage detection
The impulse line condition can be calculated and
detected by extracting the fluctuation component
from the differential pressure and static pressure
signals. The EJX110A detects the impulse line
abnormality particularly which side of impulse line is
plugged.
• Heat trace monitoring
The change of the flange temperature calculated by
using the two temperature sensors built in the EJX
enables to detect the heat trace breakage or the
abnormal temperature due to the failure.
Signal Characterizer (Output signal code D, E
and J)
User-configurable 10-segment signal characterizer
for 4 to 20 mA output.
Status Output (optional, output signal code D, E
and J)
One transistor contact output (sink type) to output
the status of user configurable high/low alarm for
differential pressure/static pressure.
Contact rating: 10.5 to 30 V DC, 120 mA DC max.
Refer to ‘Terminal Configuration’ and ‘Wiring Example
for Analog Output and Status Output.’
SIL Certification
EJX series transmitters except Fieldbus and
PROFIBUS PA communication types are certified by
TÜV in compliance with the following standards;
IEC 61508: 2000; Part1 to Part 7
Functional Safety of Electrical/electronic/
programmable electronic related systems; SIL 2
capability for single transmitter use, SIL 3 capability
for dual transmitter use.
GS 01C25B01-01EN
May 19, 2014-00
4
<<Contents>> <<Index>>
□ NORMAL OPERATING CONDITION
(Optional features or approval codes may
affect limits.)
Ambient Temperature Limits
−40 to 85°C (−40 to 185°F)
−30 to 80°C (−22 to 176°F) with LCD display
Process Temperature Limits
−40 to 120°C (−40 to 248°F)
Ambient Humidity Limits
0 to 100% RH
Working Pressure Limits (Silicone oil)
Maximum Pressure Limits (MWP)
Capsule
F, L
Wetted Parts Material: S
M, H, V Wetted Parts Material:
H, T, M, A, D, B
600
MWP
16 MPa (2300 psi)
25 MPa (3600 psi)
16 MPa (2300 psi)
Minimum Pressure Limit
See graph below
Atmospheric
pressure
Working
pressure
kPa abs
(psi abs)
Applicable range
2.7(0.38)
1(0.14)
-40
(-40)
0
(32)
External
load
resistance
R=
E-10.5
0.0244
Digital
Communication
range
BRAIN and HART
250
R (Ω)
25.2
10.5 16.6
Power supply voltage E (V DC)
100(14.5)
10(1.4)
Supply & Load Requirements
(Output signal code D, E and J. Optional
features or approval codes may affect electrical
requirements.)
With 24 V DC supply, up to a 550Ω load can be
used. See graph below.
40
(104)
80
(176)
120
(248)
Process temperature °C (°F)
F01E.ai
Figure 1. Working Pressure and Process Temperature
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
42
F02E.ai
Figure 2. Relationship Between Power Supply
Voltage and External Load Resistance
Supply Voltage “◊”
10.5 to 42 V DC for general use and flameproof type.
10.5 to 32 V DC for lightning protector
(option code /A.)
10.5 to 30 V DC for intrinsically safe, type n, or
nonincendive.
Minimum voltage limited at 16.6 V DC for digital
communications, BRAIN and HART
Load (Output signal code D, E and J)
0 to 1290Ω for operation
250 to 600Ω for digital communication
Communication Requirements “◊”
(Approval codes may affect electrical requirements.)
BRAIN
Communication Distance
Up to 2 km (1.25 miles) when using CEV
polyethylene-insulated PVC-sheathed cables.
Communication distance varies depending on type of
cable used.
Load Capacitance
0.22 µF or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10 kΩ or more at 2.4 kHz.
GS 01C25B01-01EN
Apr. 01, 2013-00
5
<<Contents>> <<Index>>
EMC Conformity Standards
EN 61326-1 Class A, Table2 (For use in industrial
locations)
EN 61326-2-3
EN 61326-2-5 (for fieldbus)
European Pressure Equipment Directive 97/23/EC
Sound Engineering Practice (for all capsules)
With option code /PE3 (for M, H and V capsules and
wetted parts material code S.)
Category III, Module H, Type of Equipment: Pressure
Accessory-Vessel, Type of Fluid: Liquid and Gas,
Group of Fluid: 1 and 2
Safety Requirement Standards
EN 61010-1, EN 61010-2-030
C22.2 No.61010-1, C22.2 No.61010-2-030
• Altitude of installation site:
Max. 2,000 m above sea level
• Installation category: I
(Anticipated transient overvoltage 330 V)
• Pollution degree: 2
• Indoor/Outdoor use
< Related Instruments>
Power Distributor: Refer to GS 01B04T01-02E or
GS 01B04T02-02E
BRAIN TERMINAL: Refer to GS 01C00A11-00E
< Reference >
is a registered trademark of Yokogawa
Electric Corporation.
2. FieldMate; Trademark of Yokogawa Electric
Corporation.
3. Teflon; Trademark of E.I. DuPont de Nemours &
Co.
4. Hastelloy; Trademark of Haynes International Inc.
5. HART; Trademark of the HART Communication
Foundation.
6. FOUNDATION Fieldbus; Tradmark of Fieldbus
Foundation.
7. PROFIBUS; Registered trademark of Profibus
Nutzerorganisation e.v., Karlsruhe, Germany.
Other company names and product names used in
this material are registered trademarks or trademarks
of their respective owners.
1.
□ PHYSICAL SPECIFICATIONS
Wetted Parts Materials
Diaphragm, Cover Flange, Process Connector,
Capsule Gasket, and Vent/Drain Plug
Refer to “MODEL AND SUFFIX CODES.”
Process Connector Gasket
PTFE Teflon
Fluorinated rubber for option code N2 and N3
Non-wetted Parts Materials
Bolting
B7 carbon steel, 316L SST or 660 SST
Housing
Low copper cast aluminum alloy with polyurethane,
mint-green paint (Munsell 5.6BG 3.3/2.9 or its
equivalent), or ASTM CF-8M Stainless Steel
Degrees of Protection
IP66/IP67, Type 4X
Cover O-rings
Buna-N, fluoro-rubber (optional)
Name plate and tag
316 SST
Fill Fluid
Silicone, fluorinated oil (optional)
Weight
[Installation code 7, 8 and 9]
2.8 kg (6.2 lb) for measurement span code M, H
and V, wetted parts material code S without integral
indicator, mounting bracket, and process connector.
3.7 kg (8.2 lb) for measurement span code F without
integral indicator, mounting bracket, and process
connector.
Add 1.5 kg (3.3lb) for Amplifier housing code 2.
Connections
Refer to “MODEL AND SUFFIX CODES.”
Process connection of cover flange: IEC61518
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Jul. 24, 2015-00
6
<<Contents>> <<Index>>
MODEL AND SUFFIX CODES
Model
Suffix Codes
EJX110A
...............................
Differential pressure transmitter
Output signal
-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART 5 protocol)
4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
(Refer to GS 01C25T01-01EN)
Digital communication (FOUNDATION Fieldbus protocol, refer to
GS 01C25T02-01EN)
Digital communication (PROFIBUS PA protocol, refer to
GS 01C25T04-01EN)
0.1 to 5 kPa (0.4 to 20 inH2O) (For Wetted parts material code S)
0.1 to 10 kPa (0.4 to 40 inH2O) (For Wetted parts material code M, H, T, A,
D and B)
0.5 to 100 kPa (2 to 400 inH2O)
2.5 to 500 kPa (10 to 2000 inH2O)
0.07 to 14 MPa (10 to 2000 psi)
Refer to “Wetted Parts Material” Table.
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measurement
span (capsule)
Wetted parts
material *1
Process connections
F . . . . . . . . . . . . . . . . . . . . . . . . . . . L . . . . . . . . . . . . . . . . . . . . . . . . . . . M . . . . . . . . . . . . . . . . . . . . . . . . . . . H . . . . . . . . . . . . . . . . . . . . . . . . . . . V . . . . . . . . . . . . . . . . . . . . . . . . . . .  . . . . . . . . . . . . . . . . . . . . . . . . .
0 . . . . . . . . . . . . . . . . . . . . . .
1 . . . . . . . . . . . . . . . . . . . . . .
2 . . . . . . . . . . . . . . . . . . . . . .
3 . . . . . . . . . . . . . . . . . . . . . .
4 . . . . . . . . . . . . . . . . . . . . . .
► 5 . . . . . . . . . . . . . . . . . . . . . .
Bolts and nuts materia
J . . . . . . . . . . . . . . . . . . . G . . . . . . . . . . . . . . . . . . . C . . . . . . . . . . . . . . . . . . . Installation
-7 . . . . . . . . . . . . . . . . .
-8 . . . . . . . . . . . . . . . . .
► -9 . . . . . . . . . . . . . . . . .
-B . . . . . . . . . . . . . . . . .
-U . . . . . . . . . . . . . . . . .
Amplifier housing
1 . . . . . . . . . . . . . . 3 . . . . . . . . . . . . . . 2 . . . . . . . . . . . . . . Electrical connection
0 . . . . . . . . . . . ► 2 . . . . . . . . . . . 4 . . . . . . . . . . . 5 . . . . . . . . . . . 7 . . . . . . . . . . . 9 . . . . . . . . . . . A . . . . . . . . . . . C . . . . . . . . . . . D . . . . . . . . . . . Integral indicator
D . . . . . . . . E . . . . . . . . ► N . . . . . . . . Mounting bracket
► B . . . . . .
D . . . . . .
J . . . . . .
K . . . . . .
M . . . . . .
N . . . . . .
Optional Codes
Description
without process connector (Rc1/4 female on the cover flanges)
with Rc1/4 female process connector
with Rc1/2 female process connector
with 1/4 NPT female process connector
with 1/2 NPT female process connector
without process connector (1/4 NPT female on the cover flanges)
B7 carbon steel
316L SST
660 SST
Vertical piping, left side high pressure, and process connection downside
Horizontal piping and right side high pressure
Horizontal piping and left side high pressure
Bottom Process Connection, left side high pressure*2
Universal flange*2
Cast aluminum alloy
Cast aluminum alloy with corrosion resistance properties*4
ASTM CF-8M stainless steel*5
G1/2 female, one electrical connection without blind plugs
1/2 NPT female, two electrical connections without blind plugs
M20 female, two electrical connections without blind plugs
G1/2 female, two electrical connections and a blind plug*6
1/2 NPT female, two electrical connections and a blind plug*6
M20 female, two electrical connections and a blind plug*6
G1/2 female, two electrical connections and a SUS316 blind plug
1/2 NPT female, two electrical connections and a SUS316 blind plug
M20 female, two electrical connections and a SUS316 blind plug
Digital indicator*7
Digital indicator with the range setting switch (push button)*8
None
304 SST 2-inch pipe mounting, flat type (for horizontal piping)
304 SST or SCS13A 2-inch pipe mounting, L type (for vertical piping)
316 SST 2-inch pipe mounting, flat type (for horizontal piping)
316 SST or SCS14A 2-inch pipe mounting, L type (for vertical piping)
316 SST 2-inch pipe mounting (for bottom process connection type)
None
/ Optional specification
The “►” marks indicate the most typical selection for each specification.
*1: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of
inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm
and the fill fluid can contaminate the user’s process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium
hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the
wetted parts material.
*2: Only applicable for Wetted parts material code S.
*3: Not applicable for measurement span code F.
*4: Not applicable for electrical connection code 0, 5, 7, 9 and A. Content rate of copper in the material is 0.03% or less and
content rate of iron is 0.15% or less.
*5: Not applicable for electrical connection code 0, 5, 7 and 9.
*6: Material of a blind plug is aluminum alloy or 304 SST.
*7: Not applicable for output signal code G.
*8: Not applicable for output signal code F.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Jul. 24, 2015-00
7
<<Contents>> <<Index>>
Table. Wetted Parts Materials
Wetted parts
material code
Cover flange and process
connector
S#
ASTM CF-8M *1
H#
M#
T
A#
D#
B#
ASTM CF-8M *1
ASTM CF-8M *1
ASTM CF-8M *1
Hastelloy C-276 equivalent *3
Hastelloy C-276 equivalent *3
Monel equivalent *4
Capsule
Hastelloy C-276 *2 (Diaphragm)
F316L SST, 316L SST (Others)
Hastelloy C-276 *2
Monel
Tantalum
Hastelloy C-276 *2
Tantalum
Monel
Capsule gasket
Vent/Drain plug
Teflon-coated 316L SST
316 SST
PTFE Teflon
PTFE Teflon
PTFE Teflon
PTFE Teflon
PTFE Teflon
PTFE Teflon
316 SST
316 SST
316 SST
Hastelloy C-276 *2
Hastelloy C-276 *2
Monel
*1: Cast version of 316 SST. Equivalent to SCS14A.
*2: Hastelloy C-276 or ASTM N10276.
*3: Indicated material is equivalent to ASTM CW-12MW.
*4: Indicated material is equivalent to ASTM M35-2.
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO15156.
Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.
OPTIONAL SPECIFICATIONS (For Explosion Protected type) “◊”
Item
Factory Mutual
(FM)
ATEX
Description
FM Explosionproof Approval *1
Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
Explosionproof for Class I, Division 1, Groups B, C and D, Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G, in Hazardous locations, indoors and outdoors (Enclosure: Type 4X)
“FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Temperature class: T6, Amb. Temp.: –40 to 60°C (–40 to 140°F)
FM Intrinsically safe Approval *1*2
Applicable Standard: FM3600, FM3610, FM3611, FM3810
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Groups E, F & G and Class III, Division 1, Class I, Zone 0, in Hazardous Locations, AEx ia IIC
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups F & G, Class I, Zone 2, Group IIC, in Hazardous Locations
Enclosure: Type 4X, Temp. Class: T4, Amb. Temp.: –60 to 60°C (–75 to 140°F)
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G] Vmax=30 V, Imax=200 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
[Groups C, D, E, F and G] Vmax=30 V, Imax=225 mA, Pmax=1 W, Ci=6 nF, Li=0 µH
Combined FF1 and FS1 *1*2
ATEX Flameproof Approval *1
Applicable Standard: EN 60079-0:2009, EN 60079-1:2007, EN 60079-31:2009
Certificate: KEMA 07ATEX0109 X
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db IP6X
Degree of protection: IP66/IP67
Amb. Temp. (Tamb) for gas-proof :
T4; –50 to 75°C (–58 to 167°F), T5; –50 to 80°C (–58 to 176°F), T6; –50 to 75°C (–58 to 167°F)
Max. process Temp. for gas-proof (Tp): T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)
Max. surface Temp. for dust-proof: T85°C (Tamb: –30 to 75°C, Tp: 85°C) *3
ATEX Intrinsically safe Approval *1*2
Applicable Standard: EN 60079-0:2009, EN 60079-11:2007, EN 60079-11:2012, EN 60079-26:2007,
EN 61241-11:2006
Certificate: DEKRA 11ATEX0228 X
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85°C T100°C T120°C Db
Degree of protection: IP66/IP67
Amb. Temp. (Tamb) for EPL Ga: –50 to 60°C (–58 to 140°F)
Maximum Process Temp. (Tp) for EPL Ga:120°C
Electrical data: Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=27.6 nF, Li=0 µH
Amb. Temp. for EPL Db: –30 to 60°C *3
Max. surface Temp. for EPL Db: T85°C (Tp: 80°C), T100°C (Tp: 100°C), T120°C (Tp: 120°C)
Combined KF22, KS21 and ATEX Intrinsically safe Ex ic *1*2
[ATEX Intrinsically safe Ex ic]
Applicable Standard: EN 60079-0:2009, EN 60079-0:2012, EN 60079-11 :2012
II 3G Ex ic IIC T4 Gc, Amb. Temp.: –30 to 60°C (–22 to 140°F) *3
Ui=30 V, Ci=27.6 nF, Li=0 μH
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Code
FF1
FS1
FU1
KF22
KS21
KU22
Jun. 08, 2015-00
8
<<Contents>> <<Index>>
Item
Canadian
Standards
Association
(CSA)
IECEx
Scheme
Combination of
Approval
*1:
*2:
*3:
*4:
Description
CSA Explosionproof Approval *1
Certificate: 2014354
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,
C22.2 No.94, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1, C22.2 No.61010-2-030
Explosion-proof for Class I, Groups B, C and D.
Dustignition-proof for Class II/III, Groups E, F and G.
When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: Type 4X,
Temp. Code: T6...T4
Ex d IIC T6...T4 Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6 *3
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe Approval *1*2
Certificate: 1606623
[For CSA C22.2]
Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157,
C22.2 No.213, C22.2 No.61010-1, C22.2 No.60079-0, C22.2 No.61010-2-030
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G,
Class III, Division 1, Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2,
Groups F & G, Class III, Division 1
Enclosure: Type 4X, Temp. Code: T4 Amb. Temp.: –50 to 60°C(–58 to 140°F) *3
Electrical Parameters: [Intrinsically Safe] Vmax=30V, Imax=200mA, Pmax=0.9W, Ci=10nF, Li=0 µH
[Nonincendive] Vmax=30V, Ci=10nF, Li=0 µH
[For CSA E60079]
Applicable Standard: CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529:2001
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP66/IP67
Amb. Temp.: –50 to 60°C(–58 to 140°F) *3, Max. Process Temp.: 120°C(248°F)
Electrical Parameters:[Ex ia] Ui=30V, Ii=200mA, Pi=0.9W, Ci=10nF, Li=0 µH
[Ex nL] Ui=30V, Ci=10nF, Li=0 µH
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1*2
IECEx Flameproof Approval *1
Applicable Standard: IEC 60079-0:2011, IEC60079-1:2004-7
Certificate: IECEx CSA 07.0008
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6
IECEx Intrinsically safe and Flameproof Approval *1*2
Intrinsically safe Ex ia
Certificate: IECEx DEK 11.0081X
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011, IEC 60079-26:2006
Ex ia IIC T4 Ga
Amb. Temp.: –50 to 60°C(–58 to 140°F), Max. Process Temp.: 120°C(248°F)
Electrical Parameters: Ui=30V, Ii=200mA, Pi=0.9W, Ci=27.6nF, Li=0 μH
Intrinsically safe Ex ic
Certificate: IECEx DEK 13.0061X
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011
Ex ic IIC T4 Gc IP code: IP66
Amb. Temp.: –30 to 60°C(–22 to 140°F) *3, Max. Process Temp.: 120°C(248°F)
Electrical Parameters: Ui=30V,Ci=27.6 nF, Li=0 μH
Flameproof
Certificate: IECEx CSA 07.0008
Applicable Standard: IEC 60079-0:2011, IEC60079-1:2007-4
Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66/IP67
Max.Process Temp.: T4;120°C(248°F), T5;100°C(212°F), T6; 85°C(185°F)
Amb.Temp.: –50 to 75°C(–58 to 167°F) for T4, –50 to 80°C(–58 to 176°F) for T5,
–50 to 75°C(–58 to 167°F) for T6
Combination of KU22, FU1 and CU1 *1*2*4
Code
CF1
CS1
CU1
SF2
SU21
V1U1
Applicable for Electrical connection code 2, 4, 7, 9, C and D.
Not applicable for option code /AL.
Lower limit of ambient temperature is –15°C (5°F) when /HE is specified.
When this option code is specified, a wired tag plate (as of N4 option) shall be used.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Jul. 24, 2015-00
9
<<Contents>> <<Index>>
OPTIONAL SPECIFICATIONS
Painting
Item
Color change
Coating change
316 SST exterior parts
Fluoro-rubber O-ring
Lightning protector
Status output*2
Oil-prohibited use*3
Oil-prohibited use with
dehydrating treatment*3
Capsule fill fluid
Calibration units*4
Long vent*5
Gold-plated capsule gasket *11
Gold-plated diaphragm *12
Output limits and failure
operation*6
Body option*7
Terminal
Side
L
H
F03E.ai
Wired tag plate*23
Data configuration at factory*8
Advanced diagnostics*21
European Pressure
Equipment Directive*13
Material certificate*14
Pressure test/
Leak test certificate*17
Description
Amplifier cover only*9
Amplifier cover and terminal cover, Munsell 7.5 R4/14
Anti-corrosion coating*1*9
316 SST zero-adjustment screw and setscrews*10
All O-rings of amplifier housing. Lower limit of ambient temperature: –15°C (5°F)
Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type.)
Allowable current: Max. 6000 A (1×40 µs), Repeating 1000 A (1×40 µs) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Transistor output (sink type)
Contact rating: 10.5 to 30 V DC, 120 mA DC(max ) Low level: 0 to 2 V DC
Degrease cleansing treatment
Degrease cleansing treatment and fluorinated oilfilled capsule.
Operating temperature −20 to 80°C (−4 to 176°F)
Degrease cleansing and dehydrating treatment
Degrease cleansing and dehydrating treatment with fluorinated oilfilled capsule.
Operating temperature −20 to 80°C ( −4 to 176°F)
Fluorinated oil filled in capsule
Operating temperature −20 to 80°C (−4 to 176°F)
P calibration (psi unit)
bar calibration (bar unit)
(See Table for Span and Range Limits.)
M calibration (kgf/cm2 unit)
Total length: 119 mm (standard: 34 mm); Total length when combining with option code K1,
K2, K5, and K6: 130 mm. Material: 316 SST
Gold-plated 316L SST capsule gasket. Without drain and vent plugs.
Surface of isolating diaphragms are gold plated, effective for hydrogen permeation.
Overpressure effects for M, H and V capsules: ±0.06% of URL
Failure alarm down-scale: Output status at CPU failure and hardware error is −5%, 3.2mA DC
or less.
Failure alarm down-scale: Output status at CPU
NAMUR NE43 Compliant
failure and hardware error is −5%, 3.2 mA DC or less.
Output signal limits:
Failure
alarm up-scale: Output status at CPU
3.8 mA to 20.5 mA
failure and hardware error is 110%, 21.6 mA or more.
Code
P
PR
X2
HC
HE
A
AL
K1
K2
K5
K6
K3
D1
D3
D4
U1
GS
A1
C1
C2
C3
Right side high pressure, without drain and vent plugs
N1
N1 and Process connection, based on IEC61518 with female thread on both sides of cover
flange, with blind kidney flanges on back.
N2
N2, and Material certificate for cover flange, diaphragm, capsule body, and blind kidney flange
N3
316 SST tag plate wired onto transmitter
N4
Data configuration for HART communication type
Software damping, Descriptor,
Message
Software damping
Data configuration for BRAIN communication type
Multi-sensing process monitoring
• Impulse line blockage detection *22
• Heat trace monitoring
PED 97/23/EC
Category III, Module H, Type of Equipment: Pressure Accessory-Vessel,
Type of Fluid: Liquid and Gas, Group of Fluid: 1 and 2
Lower limit of ambient and process temperature: −29°C
Cover flange *15
Cover flange, Process connector *16
Test Pressure: 16 MPa(2300 psi)*18
Nitrogen(N2) Gas*20
*19
Retention time: one minute
Test Pressure: 25 MPa(3600 psi)
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
CA
CB
DG6
PE3
M01
M11
T12
T13
Jun. 08, 2015-00
10
<<Contents>> <<Index>>
*1:
*2:
*3:
*4:
*5:
*6:
*7:
*8:
*9:
*10:
*11:
*12:
*13:
*14:
*15:
*16:
*17:
*18:
*19:
*20:
*21:
*22:
*23:
Not applicable with color change option.
Check terminals cannot be used when this option code is specified. Not applicable for output signal code F and G.
Applicable for Wetted parts material code S, M, H and T.
The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specified by option codes D1,
D3, and D4.
Applicable for vertical impulse piping type (Installation code 7) and Wetted parts material code S, H, M and T.
Applicable for output signal codes D, E and J. The hardware error indicates faulty amplifier or capsule.
Applicable for wetted parts material code S, M, H and T; process connection codes 3, 4, and 5; installation code 9; and
mounting bracket code N. Process connection faces on the other side of zero adjustment screw.
Also see ‘Ordering Information’.
Not applicable for amplifier housing code 2 and 3.
316 or 316L SST. The specification is included in amplifier housing code 2.
Applicable for wetted parts material code S; process connection code 0 and 5; and installation code 8 and 9.
Not applicable for option code U1, N2, N3 and M11. No PTFE is used for wetted parts.
Applicable for wetted parts material code S.
Applicable for measurement span code M, H and V and wetted parts material code S. If compliance with category III is
needed, specify this option code.
Material traceability certification, per EN 10204 3.1B.
Applicable for process connections codes 0 and 5.
Applicable for process connections codes 1, 2, 3, and 4.
The unit on the certificate is always Pa unit regardless of selection of option code D1, D3 or D4.
Applicable for capsule code F and L. Also applicable for capsule M, H and V when combined with Wetted Parts Material
code H, M, T, A, D and B.
Applicable for capsule codes M, H and V when combined with Wetted Parts Material code S.
Pure nitrogen gas is used for oil-prohibited use (option codes K1, K2, K5, and K6).
Applicable only for output signal code E and J.
The change of pressure fluctuation is monitored and then detects the impulse line blockage.
See TI 01C25A31-01E for detailed technical information required for using this function.
Maximum number of characters to be engraved on N4 tag plate is 16. Not applicable when option code V1U1 is specified.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Jun. 08, 2015-00
11
<<Contents>> <<Index>>
DIMENSIONS
Unit: mm (approx.inch)
● Vertical Impulse Piping Type (INSTALLATION CODE ‘7’)
Wetted Parts Material code: S (except for Measurement span code F)
6(0.24)
Integral indicator
(optional)
2-inch pipe
(O.D. 60.5 mm)
Vent/Drain
plugs
High
pressure
side
Zero adjustment
138(5.43)*2
ø70(2.76)
Process connector
(optional)
Conduit connection
Process connection
39
(1.54)
External indicator
Conduit connection
(optional)
95(3.74)
97(3.82)
12
(0.47)
ø78(3.07)
52
(2.05)
Mounting bracket
(L-type,optional)
41
(1.61)
67(2.64)
223(8.78)
110(4.33)
Electrical connection
for code 5 and 9.
54
(2.13)
97
(3.82)
242(9.53)
175(6.89)
129(5.08)
54
(2.13)
Low
pressure
side
Ground terminal
F04E.ai
● Horizontal Impulse Piping Type (INSTALLATION CODE ‘9’)
(For CODE ‘8’, refer to the notes below.)
Wetted Parts Material code: S (except for Measurement span code F)
110(4.33)
12
(0.47)
39
(1.54)
Ground terminal
129(5.08)
175(6.89)
Integral indicator
(optional)
Zero
adjustment
ø70
(2.76)
Conduit
connection
ø78(3.07)
67
(2.64)
95(3.74)
Vent plug*4
Vent plug*4
47
(1.85)
Electrical connection
for code 5 and 9.
124(4.88)
6
(0.24)
54
(2.13)
89(3.50)
145(5.71)
External indicator
Conduit connection
(optional)
41
(1.61)
115(4.53)
Mounting bracket
(Flat-type,optional)
Process
Drain plug*4
connection
High
Process
connector
(optional)
54(2.13)
pressure
side
Low
pressure
side
Drain plug*4
2-inch pipe
(O.D. 60.5mm)
130(5.12)*3
F05.ai
*1:
*2:
*3:
*4:
When installation code 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)
When option code K1, K2, K5 or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.
When option code K1, K2, K5 or K6 is selected, add 30 mm (1.18 inch) to the value in the figure.
Not available when option code GS is selected.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Feb. 28, 2014-00
12
<<Contents>> <<Index>>
Unit: mm (approx.inch)
● Vertical Impulse Piping Type (INSTALLATION CODE ‘7’)
256(10.10)
194(7.64)
143(5.63)
39
(1.54)
12
(0.47)
2-inch pipe
(O.D. 60.5 mm)
52
(2.05)
Vent/Drain plugs
External indicator
Conduit connection
(optional)
102(4.02)
Mounting bracket
(L-type,optional)
ø70
(2.76)
148(5.83)*2
ø78(3.07)
95
(3.74)
Integral indicator
(optional)
46
(1.81)
72(2.83)
234(9.21)
110(4.33)
Electrical connection
for code 5, 9, A, and D.
54
(2.13)
97
(3.82)
6(0.24)
Wetted Parts Material code: H, M, T, A, B and D or Measurement span code F
Process connector
(optional)
Conduit connection
Zero adjustment
Process connection
54
(2.13)
High
pressure
side
Ground terminal
Low
pressure
side
F06E.ai
● Horizontal Impulse Piping Type (INSTALLATION CODE ‘9’)
(For CODE ‘8’, refer to the notes below.)
Wetted Parts Material code: H, M, T, A, B and D or Measurement span code F
Conduit connection
Integral indicator
(optional)
54
(2.13)
47
(1.85)
124(4.88)
194(7.64)
Electrical connection
for code 5, 9, A, and D.
9*4
(0.35)
Ground terminal
Vent plug
46
(1.81)
125(4.92)
Vent plug
Drain plug
Process connection
Process
connector
(optional)
Drain plug
54
(2.13)
Mounting bracket
(Flat-type,optional)
2-inch pipe
(O.D. 60.5 mm)
*1:
*2:
*3:
*4:
39
(1.54)
143(5.63)
95(3.75)
110(4.33)
Zero
adjustment
ø70
(2.76)
72(2.83)
159(6.26)
6
(0.24)
94(3.70)
ø78(3.07)
External indicator
Conduit connection
(optional)
133*3
(5.24)
F07E.ai
When Installation code 8 is selected, high and low pressure side on above figure are reversed.
(i.e. High pressure side is on the right side.)
When Option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure.
When Option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value in the figure.
15 mm (0.59 inch) for right side high pressure.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Feb. 28, 2014-00
13
<<Contents>> <<Index>>
Unit: mm (approx.inch)
● Universal Flange (INSTALLATION CODE ‘U’)
Measurement span code M, H and V
95(3.74)
Integral indicator
(optional)
54
(2.13)
175(6.89)
Electrical connection
for code 5, 9, A, and D.
Drain plug
Vent plug
110(4.33)
Zero
Conduit connection adjustment
12
(0.47)
39
(1.54)
ø70
(2.76)
129(5.08)
67
(2.64)
145(5.71)
6
(0.24)
58
(2.28)
ø78(3.07)
External indicator
Conduit connection
(optional)
Ground terminal
Vent plug
41
(1.61)
115(4.53)
Process connection
Drain plug
High
pressure
side
Process connector
(optional)
Drain plug
54
(2.13)
130*1
(5.12)
Low
pressure
side
F08E.ai
● Universal Flange (INSTALLATION CODE ‘U’)
Measurement span code F
Drain plug
Vent plug
Drain plug
110(4.33)
12
(0.47)
39
(1.54)
ø70
(2.76)
143(5.63)
Ground terminal
Vent plug
46
(1.81)
125(4.92)
*1:
Integral indicator
(optional)
194(7.64)
Electrical connection
for code 5, 9, A, and D.
Zero
adjustment
Conduit connection
54
(2.13)
159(6.26)
6
(0.24)
72
63
(2.48) (2.83)
95(3.74)
ø78(3.07)
External indicator
Conduit connection
(optional)
Process connection
High
pressure
side
Process connector (optional)
54
(2.13)
133(5.24)*1
Drain plug
Low
pressure
side
F09E.ai
When Option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Jun. 08, 2015-00
14
<<Contents>> <<Index>>
Unit: mm (approx.inch)
● Bottom Process Connection Type (INSTALLATION CODE ‘B’)
Measurement span code M, H and V
95(3.74)
73
(2.87)
Integral indicator
(optional)
188(7.40)
Zero
adjustment
110(4.33)
12
(0.47)
Conduit connection
2-inch pipe
(O.D. 60.5 mm)
ø70
(2.76)
159(6.26)
Mounting bracket*1
(optional)
ø78(3.07)
Extenal indicator
Conduit connection
(optional)
60
(2.36)
Electrical connection
for code 5, 9, A, and D.
39
(1.54)
109(4.29)
6
(0.24)
54
(2.13)
Ground terminal
Vent plug
Process connector
(optional)
High
pressure
side
Process connection
54
(2.13)
130(5.12)*2
Low
pressure
side
129(5.08)
F12E.ai
● Bottom Process Connection Type (INSTALLATION CODE ‘B’)
Measurement span code F
6
(0.24)
54
(2.13)
238(9.37)
79(3.11)
2-inch pipe
(O.D. 60.5 mm)
Zero
adjustment
ø78(3.07)
Conduit connection
Process connector
(optional)
Mounting bracket
(optional)
Vent plug
ø70
(2.76)
95(3.74)
159(6.26)
Extenal indicator
Conduit connection
(optional)
192(7.56)
110(4.33)
9
39
(0.35) (1.54)
Ground terminal
Vent plug
High
pressure
side
54
(2.13)
133(5.24)*2
Low
pressure
side
129(5.08)
Electrical connection
for code 5, 9, A, and D.
*1:
*2:
143(5.63)
Integral indicator
(optional)
95(3.74)
F13E.ai
A transmitter with SST housing is not applicable for mounting to horizontal 2-inch pipe.
When Option code K1, K2, K5, or K6 is selected, add 30 mm (1.18 inch) to the value.
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Jun. 08, 2015-00
15
<<Contents>> <<Index>>
● Terminal Configuration
● Terminal Wiring
SUPPLY
CHECK
or
ALARM
+
–
+
–
1
2
Power supply and output terminals
3
2
+
–
3
2
External indicator (ammeter) terminals*1*2
or
Status contact output terminals*2
(when /AL is specified)
Ground terminal
Terminal
Terminal
1
Terminal
*1: When using an external indicator or check meter, the internal
resistance must be 10 Ω or less. A check meter or indicator
cannot be connected when /AL option is specified.
*2: Not available for FOUNDATION Fieldbus and PROFIBUS PA
communication types.
3
2
F10E.ai
● Wiring Example for Analog Output and Status Output
Connection
Analog output
Description
EJX electrical terminal
SUPPLY
+
+
–
CHECK
A
250Ω
*1
–
*1: Either A or +
EJX electrical terminal
Analog and
status output
(when /AL is specified)
SUPPLY +
If shield cable is not
used, communication
is not possible.
Shielded cable
A
Distributor
24V DC
+
–
–
ALARM
Distributor
24V DC
250Ω
*1
*1: Either A or +
Magnetic
valve
External power supply
30V DC, 120mA max
Use two-wire separately shielded cables.
AC power supply
F11E.ai
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
GS 01C25B01-01EN
Jun. 08, 2015-00
16
<<Contents>> <<Index>>
< Ordering Information > “◊”
Specify the following when ordering.
For output signal code –J, refer to GS 01C25T0101EN.
1. Model, suffix codes, and option codes
2. Calibration range and units
1)Calibration range can be specified with range
value specifications up to 5 digits (excluding
any decimal point) for low or high range limits
within the range of -32000 to 32000. When
reverse range is designated, specify Lower
Range Value(LRV) as greater than Upper Range
Value(URV). When square root output mode is
specified, LRV must be “0 (zero) ”.
2)Specify only one unit from the table, ‘Factory
setting.’
3. Select linear or square root for output mode and
display mode.
Note: If not specified, the instrument is shipped set for
linear mode.
4. Display scale and units (for transmitters equipped
with the integral indicator only)
Specify either 0 to 100 % or ‘Range and Unit’ for
engineering units scale:
Scale range can be specified with range limit
specifications up to 5 digits (excluding any decimal
point) for low or high range limits within the range
of -32000 to 32000. Unit display consists of 6-digit,
therefore, if the specified scaling unit excluding ‘/’ is
longer than 6-characters , the first 6 characters will
be displayed on the unit display.
5. Tag Number (if required)
Specified characters (up to 16 characters for
BRAIN, 22 characters for HART) are engraved on
the stainless steel tag plate fixed on the housing.
6. SOFTWARE TAG (for HART only. If required)
Specified characters (up to 32 characters) are set
as “Tag” (the first 8 characters) and “Long tag”*1
(32 characters) in the amplifier memory. Use
alphanumeric capital letters.
When the “SOFTWARE TAG” is not specified,
specified “TAG NO” is set as “Tag” (the first 8
characters) and “Long tag”*1 (22 characters) in the
amplifier memory.
< Factory Setting > “◊”
Tag number
Software
damping *1
Output mode
Calibration range
lower range value
Calibration range
upper range
value
Calibration range
unit
Display setting
Static pressure
display range
*1:
*2:
As specified in order
‘2.00 s’ or as specified in order
‘Linear’ unless otherwise specified in order
As specified in order
As specified in order
Selected from mmH2O, mmH2O(68°F),
mmAq*2, mmWG*2, mmHg, Pa, hPa*2,
kPa, MPa, mbar, bar, gf/cm2,
kgf/cm2, inH2O, inH2O(68°F), inHg, ftH2O,
ftH2O(68°F) or psi. (Only one unit can be
specified.)
Designated differential pressure value
specified in order. (% or user scaled
value.) Display mode ‘Linear’ or ‘Square
root’ is also as specified in order.
‘0 to 25 MPa’ for M, H, and V capsule with
wetted parts material S, and ‘0 to 16 MPa’
for F capsule with wetted parts material S
and all capsules with wetted parts material
other than S, absolute value.
Measuring high pressure side.
To specify these items at factory, option code CA
or CB is required.
Not available for HART protocol type.
< Material Cross Reference >
ASTM
316
F316
316L
F316L
304
F304
660
B7
CF-8M
JIS
SUS316
SUSF316
SUS316L
SUSF316L
SUS304
SUSF304
SUH660
SNB7
SCS14A
*1: applicable only when HART 7 is selected.
7. Other factory configurations (if required)
Specifying option code CA or CB will allow further
configuration at factory. Following are configurable
items and setting range.
[/CA : For HART communication type]
1)Descriptor (up to 16 characters)
2)Message (up to 30 characters)
3)Software damping in second (0.00 to 100.00)
[/CB : For BRAIN communication type]
1)Software damping in second (0.00 to 100.00)
All Rights Reserved. Copyright © 2004, Yokogawa Electric Corporation
Subject to change without notice.
GS 01C25B01-01EN