LEVITON OMNI IIe 20A00-50, 20A00-51, 20A00-52 security system Installation Manual
Below you will find brief information for OMNI IIe 20A00-50, OMNI IIe 20A00-51, OMNI IIe 20A00-52. These security systems offer a comprehensive range of features for home security, including burglary and fire protection. The OMNI IIe series is compatible with a variety of sensors and devices, including smoke detectors, motion detectors, door and window contacts, and thermostats. The system can be controlled from a variety of locations, including a central console, a mobile app, or a web interface.
Advertisement
Advertisement
O
MNI
II
e
Installation Manual
Includes the SIA CP-01 Control Panel Standard
Features for False Alarm Reduction
CONTENTS
INTRODUCTION .......................................................................................................................................... 1
PLANNING ........................................................................................................................................ 1
INSTALLATION ............................................................................................................................................ 2
CONTROLLER HOOKUP .................................................................................................................... 2
ABOUT SECURITY ZONES ................................................................................................................ 4
BURGLAR ZONE HOOKUPS ................................................................................................................................................... 4
ABOUT FIRE ZONES ......................................................................................................................... 5
TWO-WIRE SMOKE DETECTORS .......................................................................................................................................... 6
FOUR-WIRE SMOKE DETECTORS ......................................................................................................................................... 6
TELEPHONE CONNECTIONS ............................................................................................................. 9
DIGITAL SUBSCRIBER LINE (DSL) CONNECTIONS .......................................................................................................... 9
LCD CONSOLE HOOKUP .................................................................................................................. 11
CONSOLE SETUP ............................................................................................................................. 12
CONSOLE ADDRESS .............................................................................................................................................................. 12
SOUNDER ................................................................................................................................................................................. 12
KEY CLICK ............................................................................................................................................................................... 12
KEY BACKLIGHT .................................................................................................................................................................... 12
VIEWING ADJUSTMENT ....................................................................................................................................................... 12
LANGUAGE .............................................................................................................................................................................. 12
EXIT SETUP MODE ................................................................................................................................................................. 12
SOUNDER OUTPUTS ........................................................................................................................ 14
INTERIOR SOUNDER HOOKUP ............................................................................................................................................ 14
EXTERIOR SOUNDER HOOKUP ........................................................................................................................................... 14
CONTROLLER OUTPUTS .................................................................................................................. 16
RESET OUTPUTS .............................................................................................................................. 16
OUTPUT APPLICATIONS .................................................................................................................. 16
GENERAL PURPOSE SWITCHING APPLICATIONS .......................................................................................................... 16
SOUNDER TRIGGERING ........................................................................................................................................................ 16
COMMUNICATOR OUTPUTS ................................................................................................................................................ 17
"ARMED" AND "OK TO ARM" .............................................................................................................................................. 17
SWITCHED OUTPUT .............................................................................................................................................................. 17
LEVITON COMMUNICATING THERMOSTATS ................................................................................................................. 17
REMOTE ARM/DISARM SWITCH ...................................................................................................... 17
LEVITON THERMOSTATS ................................................................................................................ 19
PROGRAMMABLE ENERGY SAVER MODULES ................................................................................ 20
TEMPERATURE, OUTDOOR TEMPERATURE, AND HUMIDITY ........................................................ 21
BUILT-IN SERIAL PORTS ................................................................................................................. 23
BUILT-IN ETHERNET PORT ............................................................................................................. 24
CONTROLLER IP ADDRESS, PORT NUMBER, AND ENCRYPTION KEY ..................................................................... 24
CONTROLLER IP ADDRESS .................................................................................................................................................. 25
CONTROLLER PORT NUMBER ............................................................................................................................................ 25
ENCRYPTION KEY ................................................................................................................................................................. 25
OMNI IIe ETHERNET CONNECTIONS ................................................................................................................................. 25
CONNECTING TO NETWORK VIA PC ACCESS ................................................................................................................ 26
SYSTEM POWER UP PROCEDURE ....................................................................................................... 28
CONSOLE CHECK OUT .................................................................................................................... 28
TELEPHONE CHECK OUT ................................................................................................................ 28
BURGLAR ZONE CHECK OUT .......................................................................................................... 29
FIRE ZONE CHECK OUT .................................................................................................................. 29
CUSTOMER CHECKOUT ................................................................................................................... 29
IN CASE OF TROUBLE ..................................................................................................................... 30
CONSOLES ............................................................................................................................................................................... 30
CONTROLLER ......................................................................................................................................................................... 30
DIGITAL COMMUNICATOR ................................................................................................................... 32
DESCRIPTION OF CONTACT ID ....................................................................................................... 32
DESCRIPTION OF 4/2 FORMAT ........................................................................................................ 33
3/1 FORMAT .................................................................................................................................... 33
OPENING AND CLOSING REPORTS ................................................................................................. 33
INSTALLER SETUP ................................................................................................................................... 34
SETUP CONTROL ............................................................................................................................. 34
X-10 HOUSE CODE ................................................................................................................................................................. 34
UPB NETWORK ID .................................................................................................................................................................. 34
X-10 3-PHASE .......................................................................................................................................................................... 35
OUTPUT TYPES ....................................................................................................................................................................... 35
Z-WAVE NODE ID ................................................................................................................................................................... 38
SETUP ZONES .................................................................................................................................. 38
WIRELESS RECEIVER ............................................................................................................................................................ 38
ZONE RESISTORS ................................................................................................................................................................... 38
ZONE RESPONSE TIME ......................................................................................................................................................... 39
ZONE TYPES ............................................................................................................................................................................ 39
LATCHING ZONE TYPES ...................................................................................................................................................... 40
DESCRIPTION OF ZONE TYPES ........................................................................................................................................... 40
SETUP DIGITAL COMMUNICATOR .................................................................................................. 43
FIRST PHONE NUMBER, FIRST ACCOUNT NUMBER ..................................................................................................... 43
COMMUNICATOR TYPE ....................................................................................................................................................... 43
TWO-WAY AUDIO .................................................................................................................................................................. 44
REPORT OPEN/CLOSE ........................................................................................................................................................... 44
REPORT BYPASS / RESTORE ............................................................................................................................................... 44
AUTOMATIC TEST TIME ...................................................................................................................................................... 44
ALARM CODES (4/2 and 3/1 Formats) ................................................................................................................................... 44
SETUP AREAS ................................................................................................................................. 45
SETUP AREAS: CONTROL .................................................................................................................................................... 45
SETUP AREAS: ZONES .......................................................................................................................................................... 47
SETUP AREAS: BUTTONS ..................................................................................................................................................... 47
SETUP AREAS: CONSOLES ................................................................................................................................................... 49
SET-UP AREAS: THERMOSTATS ......................................................................................................................................... 49
SETUP AREAS: MESSAGES ................................................................................................................................................. 49
SETUP TEMPERATURES .................................................................................................................. 51
TEMPERATURE DISPLAY ..................................................................................................................................................... 51
THERMOSTAT TYPE .............................................................................................................................................................. 51
Z-WAVE THERMOSTAT NODE ID ....................................................................................................................................... 52
SETUP MISCELLANEOUS ................................................................................................................ 52
INSTALLER CODE .................................................................................................................................................................. 52
ENABLE PC ACCESS .............................................................................................................................................................. 52
PC ACCESS CODE ................................................................................................................................................................... 53
CALL BACK PHONE NUMBER ............................................................................................................................................. 53
OUTSIDE SIREN DELAY ....................................................................................................................................................... 53
DIAL OUT DELAY .................................................................................................................................................................. 53
ALARM RESET TIME ............................................................................................................................................................. 53
ARMING CONFIRMATION .................................................................................................................................................... 54
FIRE ALARM VERIFICATION ............................................................................................................................................... 54
SUPERVISE INT SNDR ........................................................................................................................................................... 54
SUPERVISE EXT SNDR .......................................................................................................................................................... 54
ENABLE EMERGENCY KEYS ............................................................................................................................................... 55
TIME DISPLAY ........................................................................................................................................................................ 55
DATE DISPLAY ....................................................................................................................................................................... 55
AC POWER FREQUENCY ...................................................................................................................................................... 55
DEAD LINE DETECT .............................................................................................................................................................. 55
OFF HOOK DETECT ............................................................................................................................................................... 55
PICKUP AFTER HANGUP ...................................................................................................................................................... 55
CLOCK ADJUSTMENT ........................................................................................................................................................... 56
MODEL AND SOFTWARE VERSION ................................................................................................................................... 56
RESET SYSTEM EEPROM ...................................................................................................................................................... 56
RESET SYSTEM RAM ............................................................................................................................................................. 56
ETHERNET MAC ADDRESS .................................................................................................................................................. 56
SETUP EXPANSION .......................................................................................................................... 57
MODULE 1 TYPE ..................................................................................................................................................................... 57
MODULE 2 TYPE - MODULE 4 TYPE .................................................................................................................................. 57
SERIAL 1 RATE ....................................................................................................................................................................... 57
SERIAL 1 FUNCTION .............................................................................................................................................................. 58
SERIAL 2 - SERIAL 5 RATE ................................................................................................................................................... 58
SERIAL 2 FUNCTION .............................................................................................................................................................. 58
SERIAL 3 FUNCTION .............................................................................................................................................................. 58
SERIAL 4 - SERIAL 5 FUNCTION ......................................................................................................................................... 58
SERIAL 6 RATE ....................................................................................................................................................................... 58
SETUP ZONE OPTIONS .................................................................................................................... 59
SWINGER SHUTDOWN NUMBER ........................................................................................................................................ 59
CROSS ZONE WINDOW ......................................................................................................................................................... 59
ZONE 1 OPTIONS – ZONE 48 OPTIONS ............................................................................................................................... 59
SIA CP-01 COMPLIANCE ......................................................................................................................... 60
Minimum Equipment Requirements for a CP-01 Compliant Installation: ................................................. 60
OMNI IIe SPECIFICATIONS .................................................................................................................... 61
UNDERWRITER'S LABORATORIES (UL) INSTALLATION REQUIREMENTS .......................... 62
24-HOUR STANDBY BATTERY CAPACITY ......................................................................................... 63
SMOKE DETECTOR INSTALLATION GUIDELINES ........................................................................ 64
APPENDIX A – CONTACT ID REPORTING FORMAT ...................................................................... 65
APPENDIX B - DIGITAL COMMUNICATOR CODE SHEET ............................................................ 66
APPENDIX C – FIRMWARE UPDATES ................................................................................................. 71
FIGURES
FIGURE 1 - CONTROLLER HOOKUP ............................................................................................................................................. 3
FIGURE 2 - OVERALL CONNECTIONS DIAGRAM ..................................................................................................................... 5
FIGURE 3 - TWO-WIRE FIRE ZONE CONNECTIONS .................................................................................................................. 7
FIGURE 4 - FOUR-WIRE FIRE ZONE CONNECTIONS ................................................................................................................ 8
FIGURE 5 - RJ31X JACK CONNECTIONS .................................................................................................................................... 10
FIGURE 6 - RJ31X JACK CONNECTIONS .................................................................................................................................... 11
FIGURE 7 - CONSOLE CONNECTIONS ....................................................................................................................................... 13
FIGURE 8 - SOUNDER CONNECTIONS ....................................................................................................................................... 15
FIGURE 9 - RESETTING CONTROLLER OUTPUTS ................................................................................................................... 16
FIGURE 10 - REMOTE KEYSWITCH CONNECTIONS ............................................................................................................... 18
FIGURE 11 - LEVITON THERMOSTAT CONNECTIONS ........................................................................................................... 19
FIGURE 12 - TEMPERATURE / HUMIDITY SENSOR CONNECTIONS ................................................................................... 21
FIGURE 13 - PESM CONNECTIONS ............................................................................................................................................. 22
FIGURE 14 - RS-232 CONNECTIONS ............................................................................................................................................ 23
FIGURE 15 - RS-485 CONNECTIONS ............................................................................................................................................ 24
FIGURE 16 - LOCAL NETWORK ................................................................................................................................................... 26
FIGURE 17 - LOCAL / WIDE AREA NETWORK ......................................................................................................................... 27
FIGURE 18 - 24-HOUR STANDBY CONNECTIONS ................................................................................................................... 63
INTRODUCTION
This installation guide is intended as an aid to installing the Omni IIe Control & Security System. The installer should also have thoroughly reviewed and understood the Omni IIe Owner's Manual, which has important information regarding final setup of the system. This manual assumes that the installer has a basic understanding of installing a security system.
This guide applies to the 20A00-50, -51, and -52 versions of the Omni IIe series controller. Refer to the Underwriters
Laboratories Installation Requirements section for details in the application of each. Failure to install the Omni IIe and its accessories in accordance with the UL Requirements in this manual and in the Owner's Manual is a violation of the Listing Mark.
PLANNING
Before you start, your system should be planned as follows:
1. Zones:
•
Decide where each contact or detector will be located
•
Decide which zone it will occupy
•
Decide zone type for each zone
•
Decide which area it will occupy
•
With the customer, decide what text and voice descriptors will be used. Consult table of voice descriptors, so that you can choose similar words for the text to avoid customer confusion.
•
See SMOKE DETECTOR INSTALLATION GUIDELINES to plan locations for smoke detectors
2. Consoles:
•
Consult the customer on the console location. The console should be easily accessible.
3. Interior Sounder and Outside Siren:
•
Locate both where they cannot be tampered with.
4. Lighting and Appliance Switches and Modules.
5. Plan for thermostats, energy saver modules, or other options.
6. Give consideration to where the controller will go. Remember that it needs a duplex receptacle not controlled by a switch, preferably on its own circuit, within 5 feet of the controller.
Page 1
INSTALLATION
Go over your plan with your customer.
1. Install the entire system. Refer to sections in this manual to see how to install various components.
2. Follow the Power-Up and Checkout procedures.
3. Explain the basics to the customer. Deliver all manuals and documentation.
4. Follow up with your customer to keep them satisfied.
CONTROLLER HOOKUP
1. When choosing a place to mount the controller, consider the following: a. A duplex outlet, preferably on its own circuit, is required to be within 5 feet of the controller for the power transformer and the UPB PIM or X-10 Interface Module. b. The controller should be protected from weather, temperature extremes, and burglars.
2. GROUND THE CONTROLLER "EARTH GND" TERMINAL TO A COLD WATER PIPE OR TO A 4-FOOT GROUND
ROD TO PRESERVE ITS BUILT-IN TRANSIENT PROTECTION. USE 14 GAUGE WIRE. TRANSIENT
PROTECTION WILL NOT WORK IF THE CONTROLLER IS NOT PROPERLY GROUNDED.
3. Connect the 24 VAC power transformer to the 24 VAC INPUT terminals.
4. Connect the BLACK battery wire to the minus (-) terminal on the battery. DO NOT connect the red wire at this time. DO
NOT reverse the connections; the battery fuse will blow. Note that the unit will NOT START on the battery alone.
5. Connect the Powerline Interface Module to the Omni IIe controller: a) UPB PIM (P/N: 36A00-1): Plug one end of the 6-conductor modular cable into the connector marked “J3” (SERIAL 3) on the Omni IIe controller and plug the other end into the modular connector on the PIM. b) X-10 Interface Module (P/N: TW523): Plug one end of the 4-conductor modular cable into the connector marked “J7”
(X-10) on the Omni IIe controller and plug the other end into the modular connector on the X-10 Interface Module.
6. Refer to FIGURE 1 (CONTROLLER HOOKUP) for this configuration.
Page 2
1/4"
SPACING
BLACK WIRE TO -
RED WIRE TO +
YUASA NP7-12
OR EQUIVALENT
BATTERY
12V 7AH
THE BATTERY IS NON-POWER
LIMITED. THE BATTERY LEADS
MUST BE SEPERATED FROM
ALL OTHER POWER LIMITED/CLASS II
WIRING IN THE ENCLOSURE
BY AT LEAST 1/4"
COLD WATER PIPE
OR GROUND ROD
POWER TRANSFORMER
24 VAC 40 VA
GOUNDING METHOD MUST BE IN
ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE, ANSI/NFPA 70.
REVERE
MODEL RT-2440SL
OR EQUIVALENT
FIGURE 1 - CONTROLLER HOOKUP
Page 3
Status
<Program
UPB™
Powerline Interface Module
ABOUT SECURITY ZONES
Each of the 48 security zone inputs on an Omni IIe system may be configured as a burglary zone, a fire zone, a temperature zone, or an auxiliary input. Zones 1-4, however, are the only inputs that can be used with 2-wire smoke detectors. Zones 9-16 are the only inputs that can be configured as a PESM.
An external 1000-ohm end-of-line zone resistor is required for all zones unless the Setup item ZONE RESISTERS is set to "No".
If the Setup item ZONE RESISTORS is disabled, all zones other than Supervised Fire and Gas, will not use an end-of-line resistor. In this configuration, all zone switches (other than Supervised Fire and Gas) must be normally closed (open for alarm).
If any zone requires a normally open (closed for alarm) switch (other than Supervised Fire and Gas), the Setup item ZONE
RESISTORS must be set to "Yes" and all zones will require and external 1000-ohm end-of-line resistor.
The zone type for each zone is selected through the INSTALLER SETUP menu or by using the PC ACCESS software.
The system supports a maximum zone resistance, excluding the end-of-line resistor, of 150 ohms. The default setting for ZONE
RESISTORS is "Yes". The default settings for all zone inputs on an Omni IIe controller are configured as Auxiliary inputs.
Omni IIe can be expanded to 48 zones by adding two 16 Zone Hardwire Expander Modules or one 16 Zone Hardware Expander
Module and one 16 Zone Wireless Receiver.
BURGLAR ZONE HOOKUPS
The Omni IIe system supports both normally open and normally closed switches. Most contacts designed for doors, windows, motion detectors, glassbreak detectors and other security devices meet this requirement. An external 1000-ohm end-of-line resistor must be used for all burglary zones if ZONE RESISTORS is set to "Yes".
1. When using a normally open switch, a 1000-ohm end-of-line resistor must be in parallel with the zone being used. Maximum loop resistance excluding end-of-line resistor should not exceed 150 ohms. ZONE RESISTORS must be set to "Yes".
2. When using a normally closed switch, a 1000-ohm end-of-line resistor must be put in series with the zone being used if
ZONE RESISTORS are set to "Yes". If ZONE RESISTORS are set to "No", the 1000-ohm end-of-line resistor is not used.
Maximum loop resistance excluding end-of-line resistor should not exceed 150 ohms.
3. Power motion detectors from AUXILIARY 12V.
4. Unused zones may be left open, and should be left at the default setting of AUXILIARY zone types.
5. When Zones 1-4 are configured to anything other than a Supervised Fire or Gas zone, the corresponding Zone Jumpers
(JP11-JP14) must be in the NRM (normal) position.
6. See FIGURE 2 (OVERALL CONNECTIONS DIAGRAM) for configurations of burglary zones.
Page 4
ZONE ZONE ZONE
(NO)
WARNING
COM
OUT
SWITCH 12V
(OUTPUT)
SMK
JP11-14
NRM
SMK
JP11-14
NRM
(NC)
1K EOL
(NO)
1K EOL
BURGLARY ZONES
(NC)
1K EOL
TO PREVENT RISK
FROM ELECTRIC SHOCK,
DE-ENERGIZE THIS
UNIT AND DISCONNECT
TELEPHONE LINES
BEFORE SERVICING.
12V
4-WIRE
SMOKE
ZN
ZONE (1-4)
IN
4-WIRE FIRE ZONE
1K
EOL
12V
ZN
SWITCH 12V
(OUTPUT)
OUTPUT
ZN
1K
EOL
INPUT
ZONE (1-4)
12V
2-WIRE
SMOKE
2-WIRE FIRE ZONE
NOTES:
1. SWITCH 12V, AUXILIARY 12V, CONSOLE, AND OUTPUTS 1-8 ARE INCLUDED IN THE TOTAL DEVICE LOAD, WHICH CANNOT EXCEED 1 AMP.
IN UL INSTALLATIONS, THE TOTAL DEVICE LOAD CANNOT EXCEED 250mA.
2. SOUNDERS CANNOT EXCEED 1 AMP, SPLIT BETWEEN INTERIOR AND EXTERIOR HORN OUTPUTS. IN UL INSTALLATIONS, SOUNDERS CANNOT EXCEED 350mA.
EARTH
GROUND
SWITCHED
12 VDC
1A Max.
(See NOTE 1)
AUXILIARY 12 VDC
1A Max.
(See NOTE 1)
TRANSFORMER
24 VAC 40 VA
OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT
100 mA Max. (See NOTE 1)
CONSOLE(S)
INTERIOR
SOUNDER
(See NOTE 2)
EXTERIOR
SOUNDER
ALL CIRCUITS EXCEPT FOR THE BATTERY
ARE POWER-LIMITED (CLASS II)
CONNECT CABLE
TO CONTROLLER,
PLUG MODULAR
END INTO
RJ31X JACK
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONES 1-16 ARE CONFIGURABLE FOR BURGLARY, FIRE, TEMPERATURE, OR AUXILIARY.
2-WIRE SOMKE DETECTORS MAY ONLY BE CONNECTED TO ZONES 1-4.
ONLY ZONES 9-16 MAY BE CONFIGURED AS ENERGY SAVER ZONES.
ONLY ZONE 16 MAY BE USED FOR HAI REMOTE CONTROL THERMOSTATS.
HAI REMOTE
CONTROL
THERMOSTAT(S)
FIGURE 2 - OVERALL CONNECTIONS DIAGRAM
ABOUT FIRE ZONES
The Omni IIe system supports normally open (closed for alarm), two-wire or four-wire smoke detectors. Two-wire smoke detectors can only be connected to Zones 1-4. Four-wire smoke detectors can be connected to any zone. An external 1000-ohm end-of-line resistor must be used for all fire (and gas) zones. When Zones 1-4 are configured as a Supervised Fire (two-wire or four-wire) or Gas zone, the corresponding Zone Jumpers (JP11-JP14) must be in the "SMK" (smoke) position. Zone Jumper
"JP11" corresponds to Zone 1, "JP12" corresponds to Zone 2, "JP13" corresponds to Zone 3, and "JP14" corresponds to Zone 4.
1. Smoke detectors must be powered from SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
2. End of line resistor: 1000 ohms. Maximum loop resistance EXCLUDING end of line resistor is a 150 ohms. Use LEVITON
Model 1503A0011 End of Line Resistor Assembly in UL Listed Installations.
3. Smoke detectors are reset when the security system is armed.
Page 5
TWO-WIRE SMOKE DETECTORS
Omni IIe supports two-wire smoke detectors connected to Zones 1-4.
1. Use normally open (closed for alarm) two-wire "SYSTEM" type smoke detectors (See - 2-Wire Smoke Detector
Compatibility Chart).
2. Smoke detectors must be connected to Zones 1-4 and configured as a Supervised Fire Zone.
3. An external 1000-ohm end-of-line resistor must be used.
4. Connect to the SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
5. The corresponding Zone Jumpers (JP11-JP14) must be in the SMK (smoke) position.
4. Refer to FIGURE 3 (TWO-WIRE FIRE ZONE CONNECTIONS) for this configuration.
Smoke detector compatibility identifier: A
Detector Models
Detector Manufacturer
Maximum Detectors/Zone
2W-B
2WT-B
System Sensor, Unincorporated Div. of Honeywell International Inc. 10
DS260
DS282
DS282S
DS282TH
DS282THS
DS250
DS250TH
F220-P
F220-PTH
F220-PTHC
DS230
DS230F
429AT
521B (SW 1 “ON”)
521BXT (SW 1 “ON”)
521NB (6V)
521NBXT (6V)
Bosch Security Systems
Bosch Security Systems
2-Wire Smoke Detector Compatibility Chart
GE Security Inc.
FOUR-WIRE SMOKE DETECTORS
Omni IIe supports four-wire smoke detectors connected to any zone (1-48).
10
8
10
1. Use normally open (closed for alarm) four-wire "SYSTEM" type smoke detectors (System Sensor 2112/24TR or equivalent), rated 8 - 14 VDC.
2. An End of Line Power Supervision Relay Module (System Sensor A77-716B or equivalent) is required for UL installations.
Install 1000-ohm end-of-line resistor as shown.
3. Power the smoke detector from SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
4. When connected to Zones 1-4, the appropriate Zone Jumper (JP11-JP14) must be in the SMK (smoke) position.
NOTE: Smoke detectors connected to Zones 1-4 are wired differently from those connected to Zones 5-48.
Refer to FIGURE 4 (FOUR-WIRE FIRE ZONE CONNECTIONS) for each configuration.
Page 6
WHEN Z1-Z4 IS CONFIGURED AS A
SUPERVISED FIRE OR GAS ZONE, THE
CORRESPONDING ZONE JUMPERS J11-J14
MUST BE IN "SMK" POSISTION
ZONE
ZONE
SYSTEM SENSOR
MODEL 2100TS
BOTTOM
PLATE
ZONE
ZONE
SYSTEM SENSOR
MODEL 2100TS
BOTTOM
PLATE
MODEL 1503A0011
1K OHM EOL RESISTOR
FIGURE 3 - TWO-WIRE FIRE ZONE CONNECTIONS
Page 7
WHEN Z1-Z4 IS CONFIGURED AS A
SUPERVISED FIRE OR GAS ZONE, THE
CORRESPONDING ZONE JUMPERS J11-J14
MUST BE IN "SMK" POSISTION
SYSTEM SENSOR
MODEL 2112/24TR
BLACK
RED
YELLOW
GREEN
BOTTOM
PLATE
ZONE
ZONE
+12V
GND
YELLOW
GREEN
RED
BLACK
SYSTEM SENSOR
MODEL 2112/24TR
GREEN
YELLOW
BLACK
RED
BOTTOM
PLATE
ZONE
ZONE
+12V
GND
YELLOW
GREEN
RED
BLACK
SYSTEM SENSOR
MODEL 2112/24TR
BOTTOM
PLATE
ZONE
ZONE
+12V
GND
YELLOW
GREEN
RED
BLACK
SYSTEM SENSOR
MODEL 2112/24TR
BOTTOM
PLATE
ZONE
ZONE
+12V
GND
YELLOW
GREEN
RED
BLACK
BLACK
RED
EOL POWER
SUPERVISION
RELAY
VIOLET
VIOLET
SYSTEM SENSOR
MODEL A77-716B
BLACK
RED
GREEN
YELLOW
MODEL 1503A0011
1K OHM EOL RESISTOR
SYSTEM SENSOR
MODEL A77-716B
BLACK
RED
EOL POWER
SUPERVISION
RELAY
E VIOLET
VIOLET
BLACK
RED
GREEN
YELLOW
MODEL 1503A0011
1K OHM EOL RESISTOR
FOUR-WIRE DETECTORS ON ZONES 1-4 FOUR-WIRE DETECTORS ON ZONES 5-16
FIGURE 4 - FOUR-WIRE FIRE ZONE CONNECTIONS
Page 8
TELEPHONE CONNECTIONS
1. If an RJ31X jack has been supplied by the telephone company, it is probably wired correctly and the controller can be connected by plugging the supplied 8 conductor telephone cable into the RJ31X jack. The other end of the cable is spaded.
The green, red, brown, and gray wires must be connected to the controller at the designated terminals under the section of the board marked 'PHONE'.
2. If required, install the supplied RJ31X jack as shown in the following diagram. The polarity must be correct for proper operation of the phone access feature.
3. IT IS IMPERATIVE THAT THE PHONE LINE COMING INTO THE HOUSE BE CONNECTED TO A GROUNDED
SURGE ARRESTOR OUTSIDE THE PREMISES. IT IS THE RESPONSIBILITY OF THE TELEPHONE COMPANY
TO PROVIDE THIS SURGE ARRESTOR.
4. INSPECT THE INCOMING PHONE LINES. THE FIRST THING THAT THEY SHOULD GO TO IS A SMALL BOX
ON THE OUTSIDE OF THE PREMISES. THERE SHOULD BE A HEAVY GROUND WIRE COMING FROM THIS
BOX GOING TO A COLD WATER PIPE OR A SEPARATE GROUNDING ROD.
5. IF THERE IS NO SURGE ARRESTOR OR IF THE GROUND WIRE IS MISSING, HAVE THE CUSTOMER INSIST
THAT THE TELEPHONE COMPANY INSTALL ONE FOR THE SAFETY OF THE CUSTOMER.
6. WHEN WIRING A RJ31X JACK, MAKE SURE THAT THE INCOMING PHONE LINES GO TO THE TELEPHONE
COMPANY SURGE ARRESTOR BEFORE THEY GO TO THE RJ31X JACK.
7. When the RJ31X is installed as shown, locate the green, red, brown, and gray spaded wires from the 8 conductor phone cable and connect to the section on the Omni IIe controller marked 'PHONE'. Plug the modular end of the cable into the RJ31X jack. If necessary, bend the tab up on the plug to ensure a tight fit that will not fall out.
8. Verify the following if you have trouble during check out: With the system running, the RJ31X jack properly connected and all phones on-hook (hung up), the PHONE LED, located in the upper left corner of the controller, should be OFF. If it is on, reverse the RED and GREEN wires to both the house phones and the telephone company wires at the RJ31X jack. When the receiver is picked up on any phone, the PHONE LED will come on. When the phone line rings, the PHONE LED will light.
9. If the Omni IIe is accessed on an in house telephone, the Omni IIe will disconnect the phones from the phone company lines and supply its own talk voltage to the phones. The PHONE LED will be on in this case.
10. Refer to FIGURE 5 (RJ31X JACK CONNECTIONS) for this configuration.
DIGITAL SUBSCRIBER LINE (DSL) CONNECTIONS
When the Omni IIe is connected to a Digital Subscriber Line (DSL), a DSL Splitter must be used to provide separate outputs for filtered voice (phone) and DSL (data). Splitting the voice and data is necessary because:
1. The higher frequencies of the DSL signal must not pass through the Omni IIe controller. It can cause problems with the
DTMF detection and the digital dialer.
2. Whenever the Omni IIe is accessed on an in house telephone, the Omni IIe will disconnect the phones from the phone company lines (in this case the DSL line). When that occurs, the DLS connection is temporarily lost.
Refer to FIGURE 6 (DSL SPLITTER CONNECTIONS) for this configuration.
Page 9
BEND TAB UP IF
NECESSARY TO
ENSURE TIGHT FIT
GREEN(+)
RED(-)
GREEN(+)
RED(-)
TELEPHONE
NETWORK
INTERFACE
CUSTOMER
ACCESS
SURGE ARRESTOR
RJ11
HOUSE
PHONE
JACK(S)
TO TELCO
INTERFACE AT
SURGE ARRESTOR
TO ALL HOUSE
TELEPHONES
OR PBX
FIGURE 5 - RJ31X JACK CONNECTIONS
SURGE ARRESTOR
MUST BE GROUNDED!
Page 10
GREEN(+)
RED(-)
GREEN(+)
RJ11
HOUSE
PHONE
JACK(S)
TO ALL HOUSE
TELEPHONES
RED(-)
DSL SPLITTER
VOICE
LINE IN
DATA
TELEPHONE
NETWORK
INTERFACE
CUSTOMER
ACCESS
SURGE ARRESTOR
SURGE ARRESTOR
MUST BE GROUNDED!
DSL MODEM
COMPUTER
FIGURE 6 - RJ31X JACK CONNECTIONS
LCD CONSOLE HOOKUP
1. 8 LCD Consoles (Models 33A00-1, 33A00-4, 11A00-1, 11A00-2, 11A00-9, and 15A00) MAXIMUM per system, subject to power availability.
2. Use 4-conductor 22-gage wire, 1000 feet maximum length. Consoles can be homerun or daisy chained. This length shall be divided by the total number of consoles at the end of the run. For example, for 8 consoles, the maximum length reduces to
125 feet. All LCD Consoles are connected to the same 4 wires, +12, GND, A, B.
3. The console should be mounted so that the LCD display is at or slightly above eye level. Consoles should be kept out of the reach of young children. A good height is approximately 58 inches from the floor to the bottom of the console enclosure.
4. Remove console face from back plate (slots on bottom of console will release back plate, use a screwdriver). Mount the back plate to the wall. Mounting holes are designed to fit on a single or double gang box, or directly to the wall. Pull the wires from the wall through the opening in the back plate. Splice the wires to the supplied cable. Connect the cable to the connector on the console board (J1). Snap the console face on to the back plate. Remove protective film from the LCD lens.
5. Refer to FIGURE 7 (CONSOLE CONNECTIONS) for this configuration.
Page 11
CONSOLE SETUP
The console has different operating options that can be setup from the console to the user's preference. If more than one console is being used, it is required that you give each console a different address. You can change the address of a console through the console setup mode.
To enter the console setup mode, simultaneously press and hold the 4 and up arrow () for approximately 1 second. The console will beep 5 times and enter the setup mode. The top line of the display will indicate what you are doing, followed by the current setting. The bottom line will show a menu of your options. To the lower right corner of the display is the direction arrow(s).
Where possible, the up (
↑
), down (
↓
), and two-headed (↕) arrow characters are shown on the console display to indicate which arrow keys may be pressed at that time. Press the down arrow () key to advance to the next item. Press the up arrow () key to go back to the previous item.
CONSOLE ADDRESS
If you are installing more than one console, each console must be set to a different address. The default address setting is (1) - this is adequate if only one console is being used. The choices at the bottom are 1-16. When making your choice, choose an address between 1-8, then press the # (pound) key.
SOUNDER
If you wish not to hear the beeper in the console for any reason, the sounder option can be turned off. Select (0) for OFF or (1) for ON, then press the # key.
KEY CLICK
The sounder makes a click every time a key is pressed. This option may also be turned off. Select (0) for OFF or (1) for ON, then press the # key.
KEY BACKLIGHT
The keys on the console keypad are lit. The keys can be never lit, always lit, or only lit when the LCD display is lit. Select (0)
OFF, (1) for ON, or (2) TIMED, then press the # key.
VIEWING ADJUSTMENT
This option is an adjustment for the viewing angle of the LCD display. This has been set to its best value at the factory, however, you may wish to tweak it. The display has 20 levels of adjustment. Select (1) for a lower viewing angle, or (2) for a higher viewing angle.
LANGUAGE
This option is to display the 'console setup' text on the LCD display in English, French, Italian, or Spanish. Select one of the languages, then press the # key.
EXIT SETUP MODE
To exit Setup Mode, press and hold the 4 and up arrow () keys simultaneously for about 1 second. The console will return to normal operation. You may need to press (*) to restore the display.
Page 12
FOR MODEL NUMBERS
SEE NOTE 1 UNDER
"LCD CONSOLE HOOKUP"
CONSOLE FACE
(SNAPS ON TO BOTTOM PLATE)
BOTTOM PLATE
CONTROL SECURITY BUTTONS
POL
ALL TEMP STATUS
FIRE
EVENTS MESSAGE SETUP
AUX
CANCEL MENU
CONSOLE PC BOARD
(MOUNTED TO CONSOLE FACE)
YELLOW
GREEN
RED
BLACK
SUPPLIED CABLE
(PLUGS INTO J1)
CONNECT ENDS OF SUPPLIED
CABLE TO CORRESPONDING
ENDS OF 4 - WIRE CABLE
FROM CONTROLLER
FIGURE 7 - CONSOLE CONNECTIONS
Page 13
SOUNDER OUTPUTS
The Horn Output provides 12VDC to power bells, piezo sirens, self-contained sirens, and siren drivers (do not connect speakers to the Horn Output). Sounders can draw up to 1 amp MAXIMUM, split between the Interior and Exterior Horn Outputs - (See
Specifications for UL Ratings). Use a relay connected to an auxiliary power supply if higher current draw is required.
INTERIOR SOUNDER HOOKUP
1. Locate the interior sounder in a central location. The sounder is very loud. Do not install it in a room where small children or animals could be trapped if the alarm is activated.
2. The Interior Horn Output monitors the wiring to bells and sirens. When enabled, it will report trouble and make a digital dial out when an open, short, or other wiring problem is detected in the supervised bell circuit. When violated, the following trouble is displayed on the console, "FIRE TAMPER TRBL NOW".
3. For UL Listed residential fire alarm applications, the UL Listed Wheelock Model MT-12/24-R Multitone Signal or equivalent must be used, and the "SUPERVISE INT SNDR" feature must be set to "ON".
4. Refer to FIGURE 8 (SOUNDER CONNECTION) for connections.
EXTERIOR SOUNDER HOOKUP
1. If used, wire tamper switches to a tamper zone with a 1000-ohm end-of-line resistor.
2. The Exterior Horn Output monitors the wiring to bells and sirens. When enabled, it will report trouble and make a digital dial out when an open, short, or other wiring problem is detected in the supervised bell circuit. When violated, the following trouble is displayed on the console, "FIRE TAMPER TRBL NOW".
3. To enable supervision of the Exterior Horn Output, the "SUPERVISE EXT SNDR" feature must be set to "ON".
5. Refer to FIGURE 8 (SOUNDER CONNECTION) for connections.
Page 14
FIGURE 8 - SOUNDER CONNECTIONS
Page 15
CONTROLLER OUTPUTS
The Omni IIe provides 8 programmable hardwired voltage outputs and two horn voltage outputs. These outputs are programmable for the following output types:
•
General Purpose low voltage switching applications (12 VDC) - Units 65 - 72
•
Sounder triggering (a trigger for siren and voice drivers for BURG and FIRE)
•
Communicator outputs (radio, cellular, or any other type of auxiliary communicator)
•
'ARMED' and 'OK TO ARM' outputs
•
Switched Output (to power smoke detectors and cycle power to latching devices)
Outputs 1 - 8 can supply a maximum of 100 mA each. These outputs are included in the total DEVICES load, which cannot exceed 1A.
If the Interior or Exterior Sounder is configured to an Output Type, the HORN outputs can supply a maximum of
1A. HORN outputs are included in the total HORNS load, which can not exceed 1A.
RESET OUTPUTS
Outputs 1-8 are protected from an overload condition. If an overload condition occurs on an output, it will shut off (the output will supply 0V). When this occurs, the "Output Fault" (D26) LED (marked "A" if Figure 8) will illuminate. To reset the output, remove the device causing the overload condition, then press the "Reset Outputs" (S1) Switch (marked "B" if Figure 9).
A
B
FIGURE 9 - RESETTING CONTROLLER OUTPUTS
OUTPUT APPLICATIONS
GENERAL PURPOSE SWITCHING APPLICATIONS
This output will supply 12 VDC to the output terminal when its corresponding unit is ON. Output 1 is designated Unit 65 through
Output 8 which is Unit 72. This can be used to drive relays for many different applications, including switching sprinkler valves and low-voltage lighting.
SOUNDER TRIGGERING
This output can be used as a trigger for siren and voice drivers. When a driver requires a separate input for burglary and fire, you can configure this output to give a voltage trigger to the driver. Also, each area can have its own sounder.
Page 16
COMMUNICATOR OUTPUTS
This output can be used for radio communications or any other type of auxiliary communications to augment the built-in digital and voice dialers. Any communications device can be used with the Omni IIe, provided that it is powered by 12 VDC, has 12
VDC triggered inputs, and has 2 (or more) channels.
The 'Communicator' outputs are activated 3 seconds before the Omni IIe dialer begins to dial either using its built-in digital dialer or voice dialer.
The following events will activate the BURG output: Burglar alarms (including panic zones), Auxiliary emergencies, Police emergencies, and Duress alarms. Fire alarms and the fire emergencies will activate the FIRE output.
Note: The Interior and Exterior Fire Sounder generates 12VDC in a 3 pulse temporal pattern.
"ARMED" AND "OK TO ARM"
ARMED: When the system is armed in any of the security modes (AWAY, NIGHT, DAY, or VACATION), this output is active. It is typically used to activate a red LED to indicate that the system is 'armed'.
OK TO ARM: When all security zones are secure, no zones are bypassed, and the system is in the 'OFF' mode, this output is active. It is typically used to activate a green LED to indicate that the system is 'ok to arm'.
SWITCHED OUTPUT
This output is used to cycle power to latching devices when the system is armed. This output will reset the smoke detectors when the system is armed after an alarm.
LEVITON COMMUNICATING THERMOSTATS
When LEVITON RC-Series thermostats are used, Output 8 is used to communicate with up to 4 thermostats. There is no need to configure this output when used with LEVITON thermostats. It may be left at the default setting of "General Purpose".
REMOTE ARM/DISARM SWITCH
1. If desired, a remote keyswitch, keypad, or hidden arm/disarm toggle switch can be connected to the system. The device should have a momentary close type switch.
2. Configure one of the zone inputs as a KEYSWITCH INPUT zone. A closure of the switch contacts will toggle the arming mode between OFF and AWAY (Entry and Exit delays are still active).
3. Configure one of the outputs as an "ARMED" and another output as an "OK TO ARM" output. These outputs are used to activate a red or a green LED based on the state of the alarm system. The "ARMED" and "OK TO ARM" outputs can supply a maximum of 100 mA each. These outputs are included in the total DEVICES load, which cannot exceed 1 A.
4. Refer to FIGURE 10 (REMOTE KEYSWITCH CONNECTION) for this configuration.
NOTE: In UL Listed Installations, the Listed Ademco Model 9789 keyswitch shall be used.
Page 17
1K EOL RESISTOR
RED
+
GREEN
+
YELLOW
GREEN
-
BLACK
RED
MOMENTARY CONTACT
KEYSWITCH
FIGURE 10 - REMOTE KEYSWITCH CONNECTIONS
Page 18
LEVITON THERMOSTATS
Omni IIe supports up to 4 LEVITON RC-Series Communicating Thermostats. The controller can send commands to the thermostat to change mode, cool setting, heat setting, status of fan and hold, and other items.
Run a 3 (or 4) conductor wire from Omni IIe to the thermostat location. All thermostats are connected in parallel to Zone 16 and
Output 8. Connect the red COMM cable wire with the black COMM cable wire. Make the connections (as shown in Figure 11) using the supplied wire splices.
FIGURE 11 - LEVITON THERMOSTAT CONNECTIONS
Page 19
PROGRAMMABLE ENERGY SAVER MODULES
NOTE: Programmable Energy Saver Modules must be connected to zones 9-16 on the Omni IIe controller.
1. Omni IIe can support up to 8 Programmable Energy Saver Modules (PESM). Each PESM requires one security zone input and one controller output. The zone input corresponds to the controller output (Zone 9 and Output 1 through Zone 16 and
Output 8, respectively). If Zone 9 is used, Output 1 must be used as its pair.
2. When setup as an Energy Saver Zone Type (Type 80), the zone and unit (output) is used as a pair to read in temperature and control the setback temperature of the house. Only zones 9-16 may be configured as an Energy Saver zone.
3. Run a 4-conductor wire from the Omni IIe controller to each PESM. Connect as shown in FIGURE 13 (PESM
CONNECTIONS).
4. The PESM should be mounted on an interior wall, preferably close to the HVAC thermostat. Run a 2-conductor wire from the PESM to the thermostat. Connect the PESM between the RED wire going to the thermostat and the RED terminal on the thermostat.
5. Program the zone type for PESMs as a Type 80, Energy Saver. It may also be programmed as a Temperature (Type 82), or
Temperature Alarm (Type 83) for special applications.
NOTES ON HVAC SYSTEMS
1. Description of the PESM
The PESM is a temperature sensor and control relay in a small enclosure that mounts near a central heating, ventilation, and air conditioning (HVAC) system thermostat. The PESM allows the automation system to read the temperature of the area that the HVAC system controls. The relay in the PESM is used to break the 24V RED wire between the thermostat and the
HVAC system. When the automation system is in setback mode and the actual temperature is between the LO and HI setpoints, the relay energizes to break the 24V red wire; hence, the HVAC system will no longer operate.
In heating season, when the actual temperature falls below the LOW setpoint, the automation system turns the relay in the
PESM off, thus restoring power to the thermostat, allowing the thermostat to heat as it normally would under the control of the thermostat. The PESM will cycle the thermostat on and off to maintain the LOW setpoint.
In cooling season, when the actual temperature rises above the HI setpoint, the automation system turns the relay in the
PESM off and the thermostat will cool as it normally would under the control of the thermostat. The PESM will cycle the thermostat on and off to maintain the HI setpoint.
The Red LED on the PESM will illuminate when the PESM is overriding the thermostat. The Red LED will be off when the thermostat is working normally.
If the PESM is disconnected from the automation system, the relay will not energize and the HVAC system will operate normally, under the control of the thermostat.
2. Standard Heating and Cooling Systems
The PESM is compatible with all mechanical thermostats. Recommended thermostats are simple, round Honeywell T-87 thermostats. For automatic switch-over from heat to cool, consider a Honeywell T-874 (mechanical) or an Enerstat DSL-300
(electronic) thermostat, although any other mechanical thermostat from White Rodgers, Robertshaw, etc. will work.
3. The PESM is also compatible with electronic thermostats that run totally on battery power.
4. Heat Pumps
Programmable Energy Saver Modules are compatible with heat pumps, however, the savings gained by setting the heat pump back may be erased by the auxiliary heaters when the heat pump tries to recover from the setback. A PESM will work best with heat pumps that have one or more of the following features:
Page 20
a. An outdoor temperature switch that prevents the auxiliary heat from coming on unless it is very cold outside. This is sometimes called a "heat balance" switch. b. A thermostat that uses rate of rise to determine if auxiliary heat is necessary: The Enerstat Model DSL-450. When recovering from setback, the thermostat runs the heat pump first. It will run the auxiliary heat only if the rate of temperature rise is less than 6 degrees F. per hour. c. An alternative auxiliary heat source that is inexpensive (i.e. gas).
These features will avoid the use of auxiliary heat (usually an electric strip heater) which is more expensive than using the heat pump when recovering from setback. In general, heat pumps take a longer time to recover from setback, so it may be advantageous to program a setback only for extended periods, such as a vacation.
TEMPERATURE, OUTDOOR TEMPERATURE, AND HUMIDITY
When connected to the controller, the Model 31A00-1 (31A00-7 Extended Range) Indoor/Outdoor Temperature and Model
31A00-2 (31A00-8 Extended Range) Indoor/Outdoor Temperature and Humidity Sensor is used for sensing indoor temperature and/or reporting the relative humidity from 0 to 100 percent or for sensing the outdoor temperature and/or reporting the outdoor relative humidity. The outdoor temperature can be displayed on the console, spoken over the telephone, or displayed on an
LEVITON Communicating Thermostat.
1. Each Temperature Sensor requires one zone input. Each Humidity Sensor requires one zone input.
- Program the zone type as an Outdoor Temperature (Type 81), Temperature (Type 82), Temperature Alarm (Type 83), for temperatures between 0 o
F - 120 o
F
- Humidity (Type 84), for humidity between 0% – 100%
- Extended Range Outdoor Temperature (Type 85), Extended Range Temperature (Type 86), and Extended Range
Temperature Alarm (Type 87), for temperatures between -40 o
F - 120 o
F
2. When mounting outdoors, plan to mount under an overhang or to the underside of an eave, otherwise known as the soffet, to protect it from direct sunlight and rain. Run a 4-conductor wire from the Omni IIe controller to the selected location.
BLACK
RED
YELLOW
GREEN
RED
BLACK
GREEN
YELLOW
INDOOR / OUTDOOR TEMPERATURE
AND HUMIDITY SENSOR
FIGURE 12 - TEMPERATURE / HUMIDITY SENSOR CONNECTIONS
Page 21
EXISTING
LOW VOLTAGE
THERMOSTAT
BLACK
RED
YELLOW
GREEN
RED LED
ON - ENERGY SAVER IS
OVERRIDING THERMOSTAT
OFF - THERMOSTAT IS
WORKING NORMALLY
HEAT / AIR
SYSTEM
PROGRAMMABLE ENERGY
SAVER MODULE
FIGURE 13 - PESM CONNECTIONS
Page 22
BUILT-IN SERIAL PORTS
Omni IIe has 5 serial ports (J1-J5) built onto the controller (labeled SERIAL 1 - SERIAL 5, respectively). The interface is a modular connector located in the upper left corner of the controller.
Each serial interface supports both RS-232 and RS-485 connections. RS-232 is the standard for connections to most personal computers and related systems. RS-485 can support greater wiring distances. The default setting is RS-232. To select RS-485, move the interface jumper (JP1-JP5) from the 232 to the 485 position. The jumpers (JP1-JP5) are located below the modular serial port connectors (J1-J5).
To connect a serial port to a PC, use the LEVITON Model 21A05-2 Serial Cable Kit. Plug one end of the cable into one of the modular serial port connectors on the controller. Plug the other end into the Model 21A05-1 Communication Cable Adaptor
(modular to DB-9 RS-232), which connects the Omni IIe serial port to the computer's DB-9 RS-232 port.
To make your own serial cable to connect to a PC, follow the diagrams (Figure 14 and Figure 15). When making connections, be sure to correctly orient the cable as shown (with the tab on the modular cable facing up, make sure that the Yellow wire is at the top). Connect the Yellow, Green, Red, and Black wires to the DB-9 connector as shown. Also, on the DB-9 connector, connect
Pins 1, 4, and 6 together and Pins 7 and 8 together.
4 POSITION MODULAR
PHONE CABLE
DB9-FEMALE
BOTTOM VIEW
7 RTS
- YELLOW WIRE ON TOP -
- TAB UP -
6
7
8
9
1
2
3
4
5
8 CTS
3 TX
2 RX
1 DCD
5 GND
4 DTR
YELLOW
GREEN
RED
BLACK
TOP
6 DSR
SIDE
RS-232 CONNECTIONS
FIGURE 14 - RS-232 CONNECTIONS
Built-In Serial Port Pin Out
1 - N/C
2 - Ground
3 - DCD
4 - TX (transmit)
5 - RX (receive)
6 - 12V +
PIN 6 PIN 1
Page 23
A
B
4 POSITION MODULAR
PHONE CABLE
- YELLOW WIRE ON TOP -
- TAB UP -
YELLOW
GREEN
TOP
SIDE
RS-485 CONNECTIONS
FIGURE 15 - RS-485 CONNECTIONS
BUILT-IN ETHERNET PORT
Omni IIe has an Ethernet port (J6) built onto the controller (labeled ETHERNET). The Ethernet port allows a device to connect to the Omni IIe controller via a network (i.e. Ethernet, Internet) using a secure, encrypted communication link. The Ethernet port transports LEVITON application-level packets containing Omni-Link serial protocol messages over IP. The controller supports 3 unique client “sessions” which means 3 devices may actively be connected and communicating with the controller simultaneously over the Ethernet port.
CONTROLLER IP ADDRESS, PORT NUMBER, AND ENCRYPTION KEY
The controller’s local IP address and port number set the local network parameters for the Omni IIe controller. The encryption key is used to establish a private, secure connection with the connected device.
The following Setup items can only be assigned and changed from an LEVITON console. These items can not be assigned or changed via PC Access; although the IP address and port number may be viewed via PC Access:
Page 24
CONTROLLER IP ADDRESS
The controller’s local network IP address is used to identify the Omni IIe controller on the network. To view and assign the controller’s local network IP address, from the Set Up menu, press the 6 (MISC) key. Using the down arrow key (↓), scroll to the following menu item:
IP ADDRESS
192.168.0.101 ↕
The format of the IP address is a 32-bit numeric address written as four numbers separated by periods. An IP address has two components, the network address, and the host address. The first two numbers (e.g. 192.168) represent the Class B network address and must be the same as the first two numbers of your local network. The second two numbers (e.g. 0.101) identify a particular host on the local network and may be assigned at random as long as each device on the local network has a unique address. Each number can be 0 to 255. Enter the 1, 2, or 3 digit number followed by the “#” key to move to the next number.
After the 4 th
number has been entered, press the “#” key to store the IP address.
CONTROLLER PORT NUMBER
The controller’s local network port number identifies the logical channel to the Omni IIe controller. For example, port 80 is used for HTTP traffic; the controller’s local network port number is used for Omni-Link traffic. To view and assign the controller’s local network port number, from the previous Setup item (IP ADDRESS), press the down arrow key (
↓
).
PORT NUMBER 4369
0-65535 ↕
In most installations, the default port number can remain the same. Port numbers range from 0 to 65535. To change the port number, enter the new port number followed by the “#” key to store the port number. Port numbers 0 to 1024 are reserved for designated services and should not be used.
ENCRYPTION KEY
Encryption and decryption of data between the Omni IIe controller and the connected device is based on the Advanced
Encryption Standard (AES) using a 128-bit cryptographic key. A unique encryption key is randomly assigned to each Omni IIe controller at the factory (no records of these keys are kept at the factory). It may be left the same (recommended) or it may be changed as desired. To view and assign the encryption key, from the previous Setup item (PORT NUMBER), press the down arrow key (
↓
).
ENCRYPTION KEY PT 1:
6F-1B-26-A2-FF-D9-E4-12↕
This key consists of 16 bytes (that is 16 2-digit values from 0-9 and/or the letters A-F). It is entered into the controller in two parts (PT 1 and PT 2) consisting of 8 bytes each. Enter the 2 digit value. To enter the digits A-F, first press the “OFF” key, then press the 0-5 key respectively (i.e. A1 = OFF 0 1 and CB = OFF 2 OFF 1). After the last digit (16 th
digit) has been entered, press the “#” key to store “PT 1” of the encryption key. Press the down arrow key (
↓
) to enter “PT 2” of the encryption key.
After the last digit (16 th
ENCRYPTION KEY PT 2:
DC-67-48-8F-D1-3A-EF-70
↑
digit) has been entered, press the “#” key to store “PT 2” of the encryption key.
OMNI IIe ETHERNET CONNECTIONS
Use a standard network cable to connect the controller to a hub, switch, or router. Use a network crossover cable when connecting the controller directly to the NIC card on a computer.
When connected to a switch or router, port forwarding must be configured. Port forwarding sets up public services on your network. The Omni IIe controller listens for all IP/UDP communications addressed to it on the specified UDP port number. The router will forward all communications on the specified port to the Omni IIe controller.
Page 25
CONNECTING TO NETWORK VIA PC ACCESS
To access the controller over the network via PC Access:
1. Open an Omni IIe account file.
2. Click Configure >> Network.
If you are connecting from the local network, enter the controller’s IP address under “Network IP Address or
Domain Name”.
If you are connecting from the Internet, enter either the public IP address (the way to reach your local network via the Internet) or domain name (e.g. www.homeauto.com).
3. Enter the port number that is configured for the controller.
4. Select the Encryption tab. Enter the two part encryption key as it is displayed on the console.
5. Select OK.
6. Click Connect >> Network >> Connect. PC Access should change from “Off-Line” to “On-Line”.
The “Modem” item on the main menu has been replaced with the “Connect” item. The submenu under “Connect” then allows selection of “Modem”, “Serial” or “Network”. When an account file is opened, the connection type will default to “Serial”.
192.168.0.101
Omni IIe
Controller
Hub or
Router
To connect to an Omni IIe controller on a local network using LEVITON PC
Access, under Configure >> Network enter the controller’s IP address:
(i.e. 192.168.0.101)
Computer
192.168.0.50
Computer
192.168.0.51
FIGURE 16 - LOCAL NETWORK
Page 26
To connect to an Omni IIe controller on a local network using Leviton PC Access, under Configure >> Network enter the controller’s IP address:
(i.e. 10.0.0.230)
To connect to an Omni IIe controller from the Internet using Leviton PC Access, under
Configure >> Network enter the public IP address:
(i.e. 134.42.112.8)
FIGURE 17 - LOCAL / WIDE AREA NETWORK
If the controller is connected to the Internet via a dynamic IP address, to locate and communicate with the controller from remote locations over the Internet using LEVITON PC Access, you must subscribe to a Dynamic DNS (Domain Name Service).
Dynamic DNS is a service that maps your dynamic (changing) IP address to a static (permanent) hostname, allowing you to access your Omni IIe controller over the Internet using your static hostname instead of an IP address.
A “client” program (typically provided by the Dynamic DNS provider) runs on a PC on your local network and is used to automatically update your Dynamic DNS provider with your current IP address. Several router/switch manufacturers have embedded a Dynamic DNS client into their router firmware. These devices work with several of the Dynamic DNS providers, including both free and commercial services. These devices are especially beneficial because the router can be powered up all the time, so the dynamic update is always current and is handled by a single device (the router/switch) in the local network. This allows you to locate and connect to the Omni IIe controller without having a computer on the local network powered up and running.
Page 27
SYSTEM POWER UP PROCEDURE
1. Carefully review hookups to the zones, grounds, sounders, and consoles.
2. Disconnect 1 lead of both the interior and exterior sounders.
NOTE: Follow this power up procedure to verify proper operation of the power supply, battery charger, and low voltage cut out relay.
3. The positive lead to the battery should be disconnected at this time. Make sure that the red battery wire is not touching anything.
4. Plug in the power transformer.
- The AC ON LED should illuminate.
- Within one minute, the STATUS LED should begin blinking at a rate of 1 blink per second. This indicates that the
Omni IIe processor and software are working.
- The PHONE LED should be OFF (if all telephones are on-hook and the RJ31X jack is properly connected.
5. Unplug the power transformer to kill the system. Connect the red battery wire to the + (positive) battery terminal. The system should not start.
6. Plug in the power transformer. The system should start.
7. Unplug the power transformer. The system should continue to run on the battery (the STATUS LED will continue to flash).
8. Plug the transformer back in and secure it to the outlet.
CONSOLE CHECK OUT
1. The console(s) should be operating. Press ' * ' to silence the trouble beeper if it is beeping. Press OFF, 1, 1, 1, 1 (or the current User code) if the alarm is tripped. If the consoles are not operating properly, make sure that no two consoles have the same address, and check the wiring.
2. With all doors and windows closed and all motion detectors secure, the bottom line of the display should read SYSTEM OK.
If there are any trouble indications that occurred during installation, press ' * ' to acknowledge them and silence the beeper.
3. Set the time and date by pressing the 9 key. Enter the Master Code, then press the 2 key. Enter the time on the keypad, then the DATE (enter date as 6 characters: January 1, 00 as 010100).
4. The console should now show the time and date on the top line and "SYSTEM OK" on the bottom line.
TELEPHONE CHECK OUT
1. Verify that the Telephone Company surge arrestor is properly grounded.
2. Verify that the incoming telephone lines are run to the surge arrestor first, then from the surge arrestor to the RJ31X jack, then from the RJ31X jack to the house phones.
3. The PHONE LED, on the controller, should be off when the phones are hung up.
4. Pick up an in-house phone, wait about 1 second, then press the ' # ' key. You should hear the Voice menu on the phone. If not, check to see that the RJ31X jack is properly wired and connected to the controller. There should be no interference from the Telephone Company while the menu is being read over the phone.
Page 28
5. Record the owner's NAME and ADDRESS in the ADDRESS speech memory as shown in SETUP ADDRESS in the
OWNER'S MANUAL (Press 8, 9, then 1111 or the current Master code to record the address).
NOTE: DO NOT record any TOUCH TONES in the ADDRESS!!
6. Check that all in-house phones are working.
BURGLAR ZONE CHECK OUT
1. With all doors and windows closed and all motion detectors and security devices secure, the console display should read
"SYSTEM OK".
2. If any zones are abnormal, check your wiring. If the battery indication is low, make sure that the battery is connected securely. Give the battery a chance to charge.
3. From the top-level display, have a partner go around the house and trip each sensor one at a time. The display should indicate the correct zone "NOT RDY" when the zone is tripped, then return to "SYSTEM OK" when the zone is secured. Be sure that the zone type indicated (ENTRY/EXIT, PERIMETER, ETC.) is correct for the zone being tested.
4. If the zone being checked is armed, (i.e. PANIC or TAMPER type, which is always armed) the alarm will be activated. Press
OFF and 1111 or the current User code to silence the alarm, or bypass the PANIC and TAMPER zone(s) before you start.
5. Reconnect the sirens. Be sure that no one is standing near a siren. Activate the alarm, and ensure that both the inside and, after a delay, outside sirens activate.
FIRE ZONE CHECK OUT
1.
Press ' * ' to return the console to the SYSTEM OK indication. Check the fire zone per the sensor manufacturer's instructions. The fire alarm should be activated (pulsing interior sounder, exterior siren).
2. Press ' * ' to silence the alarm. The display will still indicate that the FIRE ZONE is in alarm.
3. Press DAY or NIGHT or AWAY and the User code to arm the system, then OFF and the User code to disarm. This arm/disarm cycle will reset the smoke detector. If the cause for alarm (i.e. smoke) has cleared, the display will return to
SYSTEM OK.
NOTE: Be sure that the DIAL OUT DELAY is long enough so that you can cancel the alarm before the system dials out.
CUSTOMER CHECKOUT
After you have completed the system check out and everything works, be sure that the customer knows how to:
1. Disarm/silence the system (OFF, 1111 or current User code). HAVE THE CUSTOMER PRACTICE!
2. Change the codes.
3. Get the menu over the in-house phones.
Page 29
You should also:
4. Demonstrate arming and disarming.
5. Demonstrate home control.
6. Demonstrate setup and programming.
7. Show him/her how to program the dial out numbers.
8. Deliver the Owner's Manual.
9. If the customer has subscribed to a central monitoring service, this should be explained to him/her.
IN CASE OF TROUBLE
CONSOLES
If you experience trouble that seems to be with a console, try disconnecting the console and running the console self test as described under CONSOLE HOOKUPS in this manual. If the console does not run the self-test properly, it should be returned to
LEVITON for repair.
"NO CONTROLLER DATA" or erratic operation of the LCD display could be a result of: A and B terminals connected backwards, poorly, or 2 or more consoles have the same address.
CONSOLE SELF TEST
Use the self test mode to verify the proper operation of the console.
1. Disconnect the console from the controller. Connect +12 and GND terminals to a 12-volt source (or a fresh 9-volt transistor battery.) The console beeper will beep twice per second, the LCD backlight and the keypad key will be lit, and the LCD will display "NO CONTROLLER DATA".
2. Simultaneously press and hold the 7 and the down arrow () keys for approximately 3 seconds. The beeper will beep 5 times, the LCD backlight and keypad backlight will turn off, and the display will clear. The LED at the top right corner of the console will start to cycle through its different colors (red, green, yellow, then turns off). At the end of each cycle the beeper will beep once.
3. Press any key. The LCD backlight and the keypad key backlight will turn on.
4. Press the keys in the following order and verify that the appropriate character fills the screen. 0 - 9, *, #, AWAY (A),
NIGHT (B), DAY (C), OFF (D), (filled blocks), and (blanks).
If this is successful, the console is good. Simultaneously press and hold the 7 and down arrow () keys to exit the self test mode or disconnect power.
CONTROLLER
Check the AC ON (bottom) LED. If it is not lit, check for 24 VAC at the transformer connections.
Check the STATUS (top) LED on the controller board. It should be blinking once per second, indicating the proper operation of the microprocessor and memory. If not, try powering the system down by disconnect the power transformer and battery, then reconnect both. The status light should begin blinking.
If the AC ON LED is on and the STATUS light is still not blinking, check the AUX +12 V with a DC voltmeter. It should be
13.7 volts. If not, make sure that there isn't too much load on the system. Disconnect all loads. If the STATUS LED still won't blink, there is a problem with the controller board and it must be returned to LEVITON for repair.
Page 30
Phone line problems, or problems with the Omni IIe voice are usually the result of the RJ31X jack being improperly wired.
Check RJ31X jack wiring and polarity carefully, as described in TELEPHONE CONNECTIONS.
In the event that the controller is found defective, the controller board can be removed without disconnecting the entire wiring from their terminals. The terminal strips can be removed from the controller board. Then the controller (or processor board) can be repaired and reinstalled easily.
Follow this procedure for removing the controller board:
1. If possible, upload the programs and configuration. (This will not be possible if the status LED isn't flashing or if you can't get the voice to work.)
2. Unplug the power transformer.
3. Disconnect the battery
4. Disconnect the RJ31X modular cable at the jack!! If you only disconnect it at the Omni IIe controller only, the house phones won't work.
5. Disconnect the X-10 cable. Disconnect the serial cable.
6. Carefully remove the four terminal strips from the controller board. Gently push down on terminal strip retention clips.
These clips are located on either end of the strip and 2 in the middle. Slowly pull strip away from terminal block socket and secure.
7. Remove 9 screws and washers; 3 on the top edge, 3 on the bottom edge, and 3 in the middle of the controller.
8. Remove the controller board.
9. Wrap the controller board with protective material and pack carefully. LEVITON will not be responsible for returned items damaged due to inadequate packaging.
10. Call Home Automation, Inc. with the serial number for a Return Authorization number to help us track your return. Write the R. A. # on the outside of the package.
11. Return the controller to Home Automation, Inc. Please include your return address, any special shipping instructions and daytime phone number so that we can reach you if we have any questions. Also include a brief description of the problem that you are having.
12. INSTALLATION: follow the removal process in reverse. Follow the POWER UP and CHECK OUT procedures in this manual.
13. NOTE: When a controller is returned from being repaired, all setup and programming is lost. The board is returned with the factory default setup and programming.
FOR HELP: Call LEVITON between the hours of 9:00 AM and 5:00 PM Central time, Monday - Friday, at (800) 229-7256.
Page 31
DIGITAL COMMUNICATOR
The Omni IIe digital communicator can use Contact ID, or Standard 4/2 or 3/1, (20 pps, 1800 Hz data, 2300 Hz handshake), or
(10 pps, 1900 Hz data, 1400 Hz handshake), dual round compared format. Any central station with modern equipment can receive these formats. Compatible receivers are Ademco, Radionics, Osborne-Hoffman, Linear, FBI, and Silent Knight. It is up to the installer to verify compatibility. At the time of installation, the installer is required to verify compatibility and phone line seizure of the Digital Communicator.
If the digital dialer does not get a handshake signal from the central station 45 seconds after it begins dialing, it hangs up and tries again. The dialer will try the FIRST PHONE NUMBER 5 times, then go to the SECOND PHONE NUMBER and try that 5 times. After that, the system will indicate COMMUNICATIONS FAILURE on the console display and the digital communicator will not try again until another reportable event occurs.
The digital communicator will not dial out until the DIAL OUT DELAY has expired. If the alarm is canceled prior to the expiration of the DIAL OUT DELAY, no transmission will take place. After the DIAL OUT DELAY has expired, though, all alarm trips will be transmitted followed by a CANCEL code.
When the digital communicator is used, all voice dial outs will be delayed for five minutes after the expiration of the dial out delay to allow time for the central station to call the premises after an alarm code has been sent. If the digital communicator is unable to successfully communicate with the central station, the user will be alerted to the trouble condition. When the system status is requested using the voice, this condition is reported over the phone as "SECURITY PHONE MESSAGE" trouble.
Digital
Communicator in Controller
Phone
Line
Central
Station
Single Line Transmission Signal System Configuration
DESCRIPTION OF CONTACT ID
Contact ID reporting allows very specific event codes to be sent to the central station. A complete report takes under three seconds. Contact ID reporting uses predefined event codes that allow the central station to quickly identify the condition being reported. The specific security zone or user code is identified as part of the report.
For each event code transmitted, the report also includes an event qualifier that identifies whether the report is for a new event
(such as a security zone trip), or a restoration of an event (such as a security zone no longer tripped). Trouble conditions are reported, as well as restoration of these trouble conditions. For security armings and disarmings, this event qualifier is also used to identify whether the report is for an arm or disarm. The reporting format for Contact ID is listed in Appendix A in this manual.
When using Contact ID, the alarm codes and/or reporting format cannot be changed. However, if the DCM code (under the 4/2 and 3/1 Alarm Code Formats) is set to “0” or “00”, then Omni IIe will not make a call to the central station to report that code when using Contact ID.
Page 32
DESCRIPTION OF 4/2 FORMAT
The 4/2 format consists of a four-digit account code, from 0000 to FFFF and a two-digit alarm code from 00 to FF. When the digital communicator calls the central station receiver, the latter answers and sends a brief 2300 Hz tone or a 1400 Hz tone called a "Handshake" tone. The digital communicator then reports digits of the account and alarm codes as bursts of either (1800 Hz) or
(1900 Hz) tone; the digit 8 is represented by eight bursts of tone. A message, or "round" consists of an account code and an alarm code. Two rounds are sent, and two consecutive rounds must match at the receiver. If they do, the central station receiver sends another brief 2300 Hz or 1400 Hz tone to acknowledge to the digital dialer that the message has been properly received. If the rounds don't match, the receiver does not send the second tone and the digital dialer tries again, up to 5 times. If the rounds are not acknowledged after 5 tries, the digital dialer hangs up and tries the entire call again.
The digital communicator can report alarm zone trips, alarm cancels, low battery, and fire zone trouble. It may also be setup to generate an automatic test signal at periodic intervals. The communicator may be setup to call second phone number using a second account number in the event that it is unable to communicate successfully using the first phone number and account.
The digital communicator is setup at the factory to transmit a code when the battery is low or trouble with the fire zone is detected. If these codes are set to 0 or 00, no code will be sent when the trouble condition is detected.
Although the alarm codes can be changed, we recommend that the alarm codes setup at the factory be used to minimize the risk of installer error in programming the digital communicator. Simply enter the phone numbers and account codes, then verify the alarm codes.
3/1 FORMAT
Older central stations may require a 3/1 format. To use 3/1 format, both account numbers must be changed to 3 digit codes and
EVERY alarm code must be changed to a 1-digit code. Do not mix code lengths!
OPENING AND CLOSING REPORTS
The Omni IIe system can send opening and closing reports by user to the central station.
When the system is disarmed by user code 1-16, the communicator can call the central station and report that the system was disarmed (opened) with the user code that was used.
When the system is armed by user code 1-16, the communicator can call the central station and report that the system was armed
(closed) with the user code that was used.
If any other code or a method disarms the system (i.e. Keyswitch or Scheduled Program), the communicator will send a generic
OPEN report to the central station. The code that is sent is defined as OTHER OPEN. If the system is armed by any other method other than one that requires a code (i.e. Quick Arm, Keyswitch, or Scheduled Program), the communicator will send a generic CLOSE report to the central station. The code that is sent is defined as OTHER CLOSE.
Page 33
INSTALLER SETUP
This section describes the items that the installer must setup as part of system installation. The Installer Setup mode is used to configure the general operation of the system, the Outputs, the Areas, the Zone Types, the Digital Communicator, and various other settings. This information is covered only in this manual. All other SETUP items, including delay times, names and voices, voice dialer, and codes are covered in the Owner's Manual, Document No. 20R00-1.
SETUP items are stored permanently in the system, even if the battery and AC power are disconnected. The "default" settings are the ones that have been set at the factory. You can review or change the setup items easily, as shown below.
Note: The default Installer Code is 1111.
To access the SETUP menu, press the 9 key and enter the installer code. To access the INSTALLER SETUP menu, press the #
(INST) key.
INSTALLER SETUP MENU:
1=CTRL 2=ZONE 3=DCM
↓
4=AREA 5=TEMP 6=MISC
7=EXP
↑
SETUP CONTROL
To configure X-10, UPB, voltage outputs, and Vizia RF Z-Wave options, from the Installer Setup menu, select the 1 (CTRL) key.
The output type for both the interior and exterior horns may also be changed.
Press () to advance to the next item, () to go back.
X-10 HOUSE CODE
The base X-10 house code must be specified. The base house code is the house code for units 1-16 and is referenced as house code 1. The house code for the units 17-32 is the next house code after the base house code, or house code "B" if the base house code is "A". House codes "C" and "D" follows for Units 33-64, respectively.
X-10 HOUSE CODE: A
1-16=A-P
↓
UPB NETWORK ID
The Network ID is a unique number between 1 and 255 which identifies your UPB Network.
UPB NETWORK ID: 1
1-255 ↕
Enter the UPB Network ID (1-255) followed by the ' # ' key.
UPB PASSWORD:
The Network Password is a 4-digit number between 0001-FFFF that is used to protect your UPB network from unauthorized changes to the internal settings of your UPB devices.
UPB PASSWORD: 1234
0000-FFFF ↕
Enter the UPB Password (0000-FFFF) followed by the ' # ' key.
To enter the digits A-F, first press the “OFF” key, then press the 0-5 key respectively (i.e. “1A2B” = 1 OFF 0 2 OFF 1 #).
Page 34
UPB STATUS TIME (STATUS TRACKING):
When using HLC, “Status Tracking” is used to update the status of each HLC device in a room whenever a scene is executed in that room. For example, the scene “A” button is pushed on a Room Controller in the Living Room. All of the lighting loads in the Living Room are changed, but the status for the individual lighting loads isn’t updated in Omni IIe until a status request message is sent to each unit. When “Status Tracking” is enabled, this is done automatically after a scene is executed.
The value set for the UPB Status Time is the amount of seconds that the Omni IIe controller waits before requesting status after a scene is executed. By default, the time is set to 5 seconds. This gives lighting loads (with varying fade rates) the necessary time to “settle down” before the status is requested.
UPB STATUS TIME: 5
0-255 SECONDS ↕
Enter 1-255 for 1 to 255 seconds. Enter 0 to disable “Status Tracking”.
Note: “Status Tracking” must be enabled for Omni IIe to accurately set the LED indicators on Room and House Controllers.
X-10 3-PHASE
This setting is used to select whether the X-10 signal is transmitted only at zero crossing for single phase (120V/240V) electrical systems or is transmitted at 0, 60, and 120 degrees for three phase electrical systems.
X-10 3-PHASE: 0
0=NO 1=YES ↕
To turn 3-Phase On, press 1 then ' # '. To turn 3-Phase Off, press 0 then ' # '. The burst at 60 and 120 degrees will be eliminated.
The default setting for 3-Phase is No.
OUTPUT TYPES
An output type must be specified for each of the voltage outputs and for the interior and exterior horn outputs. The following output types are available:
OUTPUT TYPE
GENERAL PURPOSE
OK TO ARM
ARMED
PRE-ALM SNDR
NUMBER
0
1
2
3
DESCRIPTION
General Purpose Output
OK To Arm
Armed
Pre-Alarm Sounder
INT SNDR
INT BURG SNDR
INT FIRE SNDR
EXT SNDR
EXT BURG SNDR
EXT FIRE SNDR
BURG COMM
FIRE COMM
AUX COMM
SWITCHED POWER
9
10
11
12
4
5
6
7
8
13
Interior Sounder
Interior Burglary Sounder
Interior Fire Sounder (3 pulse temporal pattern)
Exterior Sounder
Exterior Burglary Sounder
Exterior Fire Sounder (3 pulse temporal pattern)
Burglary Communicator
Fire Communicator
Auxiliary Communicator
Switched Power Output
Page 35
A1 OK TO ARM
A1 ARMED
A1 PRE-ALM SNDR
A1 INT SNDR
A1 INT BURG SNDR
A1 INT FIRE SNDR
A1 EXT SNDR
A1 EXT BURG SNDR
A1 EXT FIRE SNDR
21
22
23
24
25
17
18
19
20
Area 1 OK To Arm
Area 1 Armed
Area 1 Pre-Alarm Sounder
Area 1 Interior Sounder
Area 1 Interior Burglary Sounder
Area 1 Interior Fire Sounder (3 pulse temporal pattern)
Area 1 Exterior Sounder
Area 1 Exterior Burglary Sounder
Area 1 Exterior Fire Sounder (3 pulse temporal pattern)
A1 BURG COMM
A1 FIRE COMM
A1 AUX COMM
26
27
28
Area 1 Burglary Communicator
Area 1 Fire Communicator
Area 1 Auxiliary Communicator
A1 SWITCHED POWER 29 Area 1 Switched Power Output
The first group of outputs is global. The sounder and communicator outputs will be activated for an alarm in any area. The remaining types are area specific. Area specific sounder and communicator types will only be activated for alarms in that area.
The Setup Control items are:
OUTPUT 1 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
OUTPUT 2 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
OUTPUT 3 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
OUTPUT 4 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
OUTPUT 5 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
OUTPUT 6 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
OUTPUT 7 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
OUTPUT 8 TYPE: 0
GENERAL PURPOSE #=CHNG ↕
INTERIOR HORN: 4
INT SNDR #=CHNG ↕
EXTERIOR HORN: 7
EXT SNDR #=CHNG
↑
For output types, the current setting is shown on the bottom line. Press the ' # ' key to select a new type from a list of types. The display shows:
SELECT TYPE: 6
INT SNDR ↕
Use the Up and Down arrow keys to scroll through the list, or select the appropriate output type number. Then press ' # ' to enter the new type.
If the Interior Horn is configured as a "General Purpose" output, Unit Number 73 is used to control the output. If the Exterior
Horn is configured as a "General Purpose" output, Unit Number 74 is used to control the output. In this configuration, Unit
Page 36
Numbers 73 and 74 should not be used as "Flags".
Page 37
Z-WAVE NODE ID
The Node ID is a unique number between 1 and 232 which identifies a Z-Wave device on the Vizia RF Z-Wave Network. Each
Node must be associated (mapped) with a unit number in the Omni IIe controller.
For Vizia RF Z-Wave pushbutton controllers, enter the Node ID for the Z-Wave pushbutton controller associated with that room
(e.g. Unit 1, Unit 9, Unit 17, etc). If desired, more than one pushbutton controller may be assigned to a room by associating the pushbutton controller on any unit number in that room. If a second pushbutton controller is used, do not assign in a name in the controller.
UNIT 1 NODE ID: 0
0-232 ↕
THROUGH
UNIT 64 NODE ID: 0
0-232 ↑
Enter the Node ID (0-232) for each Z-Wave device followed by the ' # ' key.
Enter 0 if there is no node associated with the specified unit number.
SETUP ZONES
To configure wireless receivers, zone resistors and the zone types (definitions) for each security zone, from the Installer Setup menu, select the 2 (ZONE) key.
Note: There zone options that define the way that each zone functions. To access Zone Options, press the 8 (ZOPT) key.
WIRELESS RECEIVER
A Wireless Receiver can be used to add 16 zones (33-48) to the Omni IIe. If used, you must enable the following item:
NOTES:
WIRELESS RECEIVER: 0
0=NO 1=YES
↓
1. Up to 2 Model 10A06 Hardwire Expanders can be used with the Omni IIe. Zones 1-16 on the first Expander are Zones 17-32 on Omni IIe. Zones 1-16 on the second Expander are Zones 33-48 on Omni IIe.
2. When used, the Model 10A06 Hardwire Expander Modules must be configured under Setup | Installer | Expansion.
3. If a Wireless Receiver is used, a second 10A06 Hardwire Expander cannot be used also. Transmitters 1-16 on the Wireless
Receiver are Zones 33-48 on Omni IIe.
ZONE RESISTORS
This item is used to specify if the 1000-ohm end-of-line zone resistors will be used with zone inputs other than Supervised Fire and Gas. If this item is set to "Yes", all zones other than Supervised Fire and Gas will require an end-of-line resistor.
The default setting is "Yes".
ZONE RESISTORS: 1
0=NO 1=YES ↕
Page 38
Z 1 TYPE THROUGH Z 48 TYPE
This item specifies the zone type for each zone. All choices are listed in this manual under DESCRIPTION OF ZONE TYPES.
For zone types, the current setting is shown on the bottom line.
THROUGH
ZONE 1 TYPE: 64
AUXILIARY #=CHNG ↕
ZONE 48 TYPE: 64
AUXILIARY #=CHNG ↑
To change a zone type, press the ' # ' key, then use the arrow keys to scroll through the list of zone types. Press the ' # ' key to select a new type
.
The display shows:
SELECT TYPE: 1
PERIMETER ↕
ZONE RESPONSE TIME
All zones, in the Omni IIe are set to a 300 millisecond fixed response time.
ZONE TYPES
ZONE TYPE NUMBER
DESCRIPTION
ENTRY/EXIT
PERIMETER
NIGHT INT
AWAY INT
2X ENTRY DELAY
4X ENTRY DELAY
LATCH PERIM
LATCH NIGHT INT
LATCH AWAY INT
PANIC
POLICE EMERG
SILENT DURESS
TAMPER
LATCH TAMPER
FIRE
FIRE EMERG
GAS
AUX EMERG
TROUBLE
FREEZE
WATER
FIRE TAMPER
AUXILIARY
KEY SWITCH
ENERGY SAVER
OUTDOOR TMP
TEMPERATURE
TEMP ALARM
HUMIDITY
ER OUTDOOR TMP
ER TEMPERATURE
ER TEMP ALARM
80
81
82
83
84
85
86
87
54
55
56
64
65
33
34
48
49
7
8
16
17
18
19
20
32
4
5
6
0
1
2
3
Entry/Exit
Perimeter
Night Interior
Away Interior
Double Entry Delay
Quadruple Entry Delay
Latching Perimeter
Latching Night Interior
Latching Away Interior
Panic
Police Emergency
Duress
Tamper
Latching Tamper
Fire
Fire Emergency
Gas Alarm
Auxiliary Emergency
Trouble
Freeze
Water
Fire Tamper
Auxiliary
Keyswitch Input
Programmable Energy Saver Module
Outdoor Temperature
Temperature
Temperature Alarm
Humidity
Extended Range Outdoor Temperature
Extended Range Temperature
Extended Range Temperature Alarm
Page 39
LATCHING ZONE TYPES
When any device (other then FIRE or GAS) is connected to SWITCH 12V or a Switched Power Output, the zone must be configured as one of the LATCHING ZONE TYPES (latching perimeter, latching night interior, latching away interior, and latching tamper). LATCHING ZONE TYPES ignore the status of that zone during power cycles.
Used primarily when the FIRE ALARM VERIFICATION feature is being used or if more than one area is being protected. This type will ignore the status of LATCHING ZONES (i.e. Glassbreak Detectors) when the power is switched to reset devices.
DESCRIPTION OF ZONE TYPES
ENTRY/EXIT
ENTRY/EXIT ZONE types are intended for doors. ENTRY/EXIT ZONES are armed in security modes DAY, NIGHT, AWAY, and VACATION. In DAY and AWAY modes, there is an entry delay (defined by ENTRY DELAY) on ENTRY/EXIT ZONES to allow you to get into the house and turn off the alarm before it sounds. In NIGHT & DAY INSTANT mode, there is no entry delay, so that the alarm sounds immediately if someone opens a door.
There are two special types of ENTRY/EXIT ZONES for use with garage doors, or doors that are far away from the control console. They are called DOUBLE ENTRY DELAY and QUADRUPLE ENTRY DELAY zones. These zones have double or quadruple the ENTRY DELAY to give you additional time to reach the console to disarm the system upon returning. Only the
ENTRY DELAY is extended on these zone types. The EXIT DELAY is not extended.
If an ENTRY/EXIT ZONE is tripped first, all other zones will are delayed.
PERIMETER and LATCHING PERIMETER
PERIMETER ZONE types are intended for windows and exterior doors not requiring an entry delay. All PERIMETER ZONES are armed in security modes DAY, NIGHT, AWAY, and VACATION. There is not an entry delay on a perimeter zones. If a window or door on this zone is opened while the security system is in DAY, NIGHT, AWAY or VACATION mode, the alarm will sound immediately. LATCHING PERIMETER ZONES ignore the status of that zone during power cycles.
NIGHT INTERIOR and LATCHING NIGHT INTERIOR
NIGHT INTERIOR ZONES are intended for motion detectors in areas where no one should be while you are sleeping in your home. For example, if you have a two-story home and sleep upstairs, your downstairs motion detector(s) should be on a NIGHT
INTERIOR ZONE.
NIGHT INTERIOR ZONES are armed in security modes NIGHT, VACATION, and AWAY only. There is no delay on a
NIGHT INTERIOR ZONE. Night interior zones are NOT armed in DAY or DAY INSTANT mode, so that you may move about freely in your home when the security system is in DAY or DAY INSTANT mode, while still having the windows and doors protected. LATCHING NIGHT INTERIOR ZONES ignore the status of that zone during power cycles.
AWAY INTERIOR and LATCHING AWAY INTERIOR
AWAY INTERIOR ZONES are for areas of your home where no one should be while you are away. In the previous example, your upstairs motion detector(s) should be on an AWAY INTERIOR ZONE. AWAY INTERIOR ZONES are armed only when the security mode is AWAY. LATCHING AWAY INTERIOR ZONES ignore the status of that zone during power cycles.
PANIC, TAMPER, and LATCHING TAMPER
PANIC and TAMPER ZONES are for emergency pushbuttons and tamper switches. PANIC and TAMPER ZONES are always armed, even if the security mode is OFF. There are no delays on PANIC and TAMPER ZONES. An emergency dial out is activated after the DIAL OUT DELAY.
TAMPER ZONES should be used for items such as gun cabinets and liquor closets.
LATCHING TAMPER ZONES ignore the status of that zone during power cycles.
Page 40
POLICE EMERGENCY
This zone type activates the burglar alarm and sounder. An emergency dial out is activated after the DIAL OUT DELAY.
DURESS EMERGENCY (SILENT DIAL OUT)
If you wish to have a button in your home that activates a SILENT dial out, (no lights flashing and no sounder) it should be connected to a zone that is configured as a DURESS EMERGENCY. If this zone is accidentally tripped, you will not know that the Omni IIe is making a silent dial out, and hence won't know to stop it.
To stop a silent dial out once it has started, you must go to the console and press OFF then enter your code.
SUPERVISED FIRE
Any zone can be programmed as a SUPERVISED FIRE ZONE. In UL Listed Installations, all fire detectors must be configured as a SUPERVISED FIRE ZONE and connected as shown in this manual. When Zones 1-4 are configured as a SUPERVISED
FIRE ZONE, the corresponding Zone Jumpers (JP11-JP14) must be in the "SMK" (smoke) position.
FIRE EMERGENCY
This zone type activates the fire alarm for a normally closed (open for alarm) and open collector (short to ground for alarm) switches. It is not supervised as required for UL Listed Installations and shall NOT be used in such installations.
GAS
This GAS ZONE will generate an alarm, activate the sounder (on - off - on - long off), and make a dial out. This zone type requires an external 1000-ohm end-of-line resistor.
When Zones 1-4 are configured as a GAS ZONE, the corresponding Zone
Jumpers (JP11-JP14) must be in the "SMK" (smoke) position.
AUXILIARY EMERGENCY
This AUXILIARY EMERGENCY ZONE type will generate an alarm (console beeper - no sirens) and make an emergency dial out when the zone is violated. An emergency dial out is activated after the DIAL OUT DELAY.
TROUBLE
This zone type can be used to monitor the status of an external device, such as the battery status of a wireless security receiver. It can also used to record events in the event log (i.e. driveway activation, opening of a gate, etc.) without setting off the alarm.
When the zone is tripped, the zone name will be displayed on the display as "NOT RDY". The alarm is not activated, regardless of the security mode. The trouble is logged in the event log. The digital communicator (if used) will report the alarm code for the zone. The voice dialer will not be activated.
FREEZE
This FREEZE ALARM ZONE type will generate an alarm (console beeper, no sirens) and make an emergency dial out.
WATER
This WATER ALARM ZONE type will generate an alarm (console beeper, no sirens) and make an emergency dial out.
FIRE TAMPER
This zone type is used to monitor the wiring to bells and sirens (other than those connected to the Horn Output). The zone will report trouble if an open, short, or other wiring problem is detected in the supervised bell circuit. This zone will make a digital dial out when violated. Connect a wire from the Fire Tamper zone (+) to an output configured as a Sounder.
Page 41
AUXILIARY
A zone defined as AUXILIARY is ignored for security. It is used to activate macros or to conditionalize programs. This is the default setting for all zones. Zones that are not in use should be configured as AUXILIARY.
KEYSWITCH INPUT
This zone is used to arm AWAY and Disarm the Omni IIe security system using a toggle (to ground) keyswitch or keypad.
PROGRAMMABLE ENERGY SAVER MODULE
This zone type is for use with the Programmable Energy Saver Modules (PESM). It converts the Zone and the corresponding
Output to operate the PESM. Only Zones 9-16 can be programmed as a PESM.
OUTDOOR TEMPERATURE AND ER OUTDOOR TEMPERATURE
Use this zone type for Outdoor Temperature Sensors. The outdoor temperature can be displayed on the console, spoken over the telephone, or displayed on an LEVITON Communicating Thermostat.
TEMPERATURE AND EXTENDED RANGE TERMPERATURE
The general-purpose TEMPERATURE ZONE type is typically used to monitor indoor temperatures and control devices. It sets the zone secure/not ready for program conditionals and event button activation.
If FREEZE ALARM is enabled, it reports a potential freeze condition if the temperature falls below 40 o
.
TEMPERATURE ALARM AND EXTENDED RANGE TEMPERATURE ALARM
The TEMPERATURE ALARM ZONE type will generate an alarm (console beeper, no sirens) and dial out if the temperature goes above the high setpoint or drops below the low setpoint.
HUMIDITY
The HUMIDITY ZONE type is used to monitor indoor and outdoor humidity levels from 0 to 100 percent using the Model
31A00-2 Indoor/Outdoor Temperature and Humidity Sensor. It sets the zone secure/not ready state for program conditionals and event button activation programs.
NOTE ON TEMPERATURE AND HUMIDITY ZONE TYPES
Outdoor temperature, temperature, and temperature alarm zone types all have HEAT (LOW) and COOL (HIGH) setpoints. The zone is "Not Ready" when the temperature is above the high setpoint or below the low setpoint. The zone is "Secure" when the temperature is between the setpoints. Setting a setpoint to 0 disables the setpoint.
Except for a type 83 and 87, the alarm is not activated. The zone "Not Ready" or "Secure" status is used to activate button programs and program conditionals.
Page 42
SETUP DIGITAL COMMUNICATOR
To setup the Digital Communicator, from the Installer Setup menu, select the 3 (DCM) key.
FIRST PHONE NUMBER, FIRST ACCOUNT NUMBER
The first item in the DIGITAL COMMUNICATOR category is the FIRST PHONE NUMBER. Enter the FIRST PHONE
NUMBER on the keypad. This enables the Digital Communicator.
You can cause a 2-second pause during dialing by pressing the DAY key.
To prevent a call waiting line from interfering with the dial out, you may use the call waiting cancel sequence at the beginning of the number. The call waiting sequence is typically ' * 7 0 T ' (T = pause); however this may vary depending on your region.
If you are using the call waiting sequence, only use it on the “FIRST PHONE NUMBER”; do not use it on the “SECOND
PHONE NUMBER”.
FIRST PHONE NUMBER:
-
↓
To disable the digital communicator, enter a single "-" for the FIRST and SECOND PHONE NUMBER by pressing the OFF key, then ' # '. Phone number may be up to 24 digits long.
Press the down arrow () to advance to the FIRST ACCT NUMBER:
FIRST ACCT NUMBER: 0000
0-FFFF ↕
Enter the 4 digit account number (3 digits if using 3/1 format) and press ' # '. To enter the digits B-F, first press the OFF key, then press the 1-5 key respectively (i.e. 1B11 = 1 OFF 1 1 1 #).
NOTE: You must enter 4 digits for the account number if you are using 4/2 format (i.e. 0123), and 3 digits if using 3/1 (i.e. 123).
SECOND PHONE NUMBER, SECOND ACCOUNT NUMBER
Enter these if used.
Note: do not use the call waiting sequence on the “SECOND PHONE NUMBER”.
SECOND PHONE NUMBER:
- ↕
SECOND ACCT NUMBER: 0000
0-9999 ↕
COMMUNICATOR TYPE
This item is used to select the transmitting parameters of the digital communicator. The Omni IIe can transmit in FAST 2300 Hz
(20 PPS) mode, in SLOW 1400 Hz (10 PPS) 3/1 format, and in Contact ID.
COMMUNICATOR TYPE: 2
0=2300 1=1400 2=ID ↕
The default setting is 2 = ID (Contact ID). If you need to transmit to a 4/2 or 3/1 receiver, select the proper handshaking frequency (2300 Hz or 1400 Hz) and press ' # '.
Page 43
TWO-WAY AUDIO
If a Two-Way Audio Module is being used, this item enables hands free audio communication between your customer's premises and the central station.
After the transmission of the alarm to the central station, the operator can talk and listen to people and sounds at the premises.
TWO-WAY AUDIO: 0
0=NO 1=YES ↕
If a Two-Way Audio Module is part of the system, select the 1 (YES) key to enable this feature.
REPORT OPEN/CLOSE
The communicator can be setup to send an opening and a closing report by user code. Whenever the system is disarmed the communicator will send an opening report to the central station. When the system is armed, the communicator will send a closing report to the central station.
REPORT OPEN/CLOSE: 0
0=NO 1=YES ↕
To enable the communicator to send opening and closing reports to the central station, select the 1 (YES) key.
REPORT BYPASS / RESTORE
This item is used to enable/disable reporting to the central station when a zone is bypassed or restored when using Contact ID.
The communicator can be configured to send bypass/restore signals to the central station when using Contact ID. Whenever a zone is bypassed, the communicator will send a zone bypassed report to the central station. When a zone is restored, the communicator will send a zone restored report to the central station.
REPORT BYPASS/REST: 1
0=NO 1=YES ↕
To disable the communicator from sending bypass and restore reports to the central station, select the 0 (NO) key.
AUTOMATIC TEST TIME
The communicator CAN be setup to automatically send a test code to the central station on a periodic basis. AUTOMATIC
TEST TIME is used to set the time and days of the week of the test, and the TEST CODE specifies the code that will be transmitted for the test.
AUTOMATIC TEST TIME:
-- NEVER #=CHNG↕
To disable the automatic test, press the ' # ' key and then 0 for Never, and ' # '.
TEST CODE: 98
0-FF ↕
ALARM CODES (4/2 and 3/1 Formats)
Press the down arrow () to advance to the next ZONE ALARM CODE. Press the up arrow () to go to the previous ZONE
ALARM CODE. To change an alarm code, enter two digits for 4/2 format, or one digit when using 3/1 format, then press the ' # ' key.
Enter the 2 digit alarm code (1 digits if using 3/1 format) and press ' # '. To enter the digits B-F, first press the OFF key, then press the 1-5 key respectively (i.e. B1 = OFF 1 1 # and CB = OFF 2 OFF 1 #).
Page 44
The various alarm codes are sent when the indicated alarm zone is tripped. Each alarm code must be two digits long for 4/2 format (01-FF), 1 digit for 3/1 format (1-F).
To disable the digital communicator for a specific zone, set the alarm code to 0 or 00. The digital dialer will not report when this zone is tripped.
THROUGH
ZONE 1 ALARM CODE: 01
0-FF ↕
USER 16 CLOSE CODE: 76
0-FF
↑
SETUP AREAS
To configure the system for multiple areas, from the Installer Setup menu, press the 4 (AREA) key. The number of areas must be specified. Also, consoles, zones, units, thermostats, and buttons must be assigned to areas. By default, one area is configured.
The display prompts for the number of areas that will be used:
NUMBER OF AREAS: 1
1-2
If you choose 2, the Setup Areas menu is displayed:
SETUP AREAS
1=CTRL 2=ZONES 3=BTTN
↓
4=CONS 5=TEMP 8=MSG
SETUP AREAS: CONTROL
↑
To assign control units to specific areas, from the Setup Areas menu, press the 1 (CTRL) key.
Units can be setup so that they can be activated from specific areas or from all areas.
Units for an entire X-10 House Code can be assigned to specific areas. Units 65-72 (voltage outputs) may be assigned individually to specified areas. Units 73-128 (flags) can be assigned to specific areas in groups of eight.
UNITS 1-16 AREAS:
1 2 0=CLR
↓
UNITS 17-32 AREAS:
1 2 0=CLR ↕
UNITS 33-48 AREAS:
1 2 0=CLR ↕
UNITS 49-64 AREAS:
1 2 0=CLR ↕
UNITS 65 AREAS:
1 2 0=CLR ↕
UNITS 66 AREAS:
1 2 0=CLR ↕
UNITS 67 AREAS:
Page 45
1 2 0=CLR ↕
UNITS 68 AREAS:
1 2 0=CLR ↕
Page 46
UNITS 69 AREAS:
1 2 0=CLR ↕
UNITS 70 AREAS:
1 2 0=CLR ↕
UNITS 71 AREAS:
1 2 0=CLR ↕
UNITS 72 AREAS:
1 2 0=CLR ↕
UNITS 73-80 AREAS:
1 2 0=CLR ↕
UNITS 81-88 AREAS:
1 2 0=CLR ↕
UNITS 89-96 AREAS:
1 2 0=CLR ↕
UNITS 97-104 AREAS:
1 2 0=CLR ↕
UNITS 105-112 AREAS:
1 2 0=CLR ↕
UNITS 113-120 AREAS:
1 2 0=CLR ↕
UNITS 121-128 AREAS:
1 2 0=CLR
SETUP AREAS: ZONES
↑
To assign zones to areas, from the Setup Areas menu, press 2 (ZONE). Each zone must be assigned to one and only one area.
ZONE 1 AREA: 1
1-2
↓
THROUGH
ZONE 48 AREA 1
1-2
↑
SETUP AREAS: BUTTONS
To assign groups of macro buttons to specific areas, from the Setup Areas menu, press the 3 (BTTN) key.
Buttons can be setup so that they can only be activated from a particular area or from any area. Buttons are assigned to areas in groups of eight.
BUTTONS 1-8 AREAS:
1 2 0=CLR
↓
BUTTONS 9-16 AREAS:
1 2 0=CLR ↕
Page 47
BUTTONS 17-24 AREAS:
1 2 0=CLR ↕
BUTTONS 25-32 AREAS:
1 2 0=CLR ↕
Page 48
BUTTONS 33-40 AREAS:
1 2 0=CLR ↕
BUTTONS 41-48 AREAS:
1 2 0=CLR ↕
BUTTONS 49-56 AREAS:
1 2 0=CLR ↕
BUTTONS 57-64 AREAS:
1 2 0=CLR
SETUP AREAS: CONSOLES
↑
To assign consoles to areas, from the Setup Areas menu, press the 4 (CONS) key.
Each console must be assigned to one and only one area. A console may be set to global, which allows it to access areas other than its assigned area through security arming and the "go to" function.
THROUGH
CONSOLE 1 AREA: 1
1-2
↓
CONSOLE 1 GLOBAL: 1
0=NO 1=YES ↕
CONSOLE 8 AREA: 1
1-2 ↕
CONSOLE 8 GLOBAL: 1
0=NO 1=YES ↑
SET-UP AREAS: THERMOSTATS
To assign thermostats to specific areas, from the Set-up Areas menu, press the 5 (TEMP) key.
Thermostats can be set up so that they can only be controlled from a specific area or from all areas. PESMs and Temperature
Sensors can only be controlled from a single area, as specified in SETUP AREAS.
THROUGH
THERMOSTAT 1 AREAS:
1 2 0=CLR
↓
THERMOSTAT 4 AREAS:
1 2 0=CLR
↑
SETUP AREAS: MESSAGES
To assign messages to specific areas, from the Setup Areas menu, press the 8 (MSG) key.
Messages can be setup so that they can be displayed in a specific area or in all areas.
MESSAGES 1-8 AREAS:
1 2 0=CLR
↓
Page 49
MESSAGES 9-16 AREAS:
1 2 0=CLR ↕
Page 50
MESSAGES 17-24 AREAS:
1 2 0=CLR ↕
MESSAGES 25-32 AREAS:
1 2 0=CLR ↕
MESSAGES 33-40 AREAS:
1 2 0=CLR ↕
MESSAGES 41-48 AREAS:
1 2 0=CLR ↕
MESSAGES 49-56 AREAS:
1 2 0=CLR ↕
MESSAGES 57-64 AREAS:
1 2 0=CLR
↑
SETUP TEMPERATURES
To configure temperatures from the Installer Setup Menu, press the 5 (Temp) key.
TEMPERATURE DISPLAY
This allows you to choose between Fahrenheit and Celsius temperature format.
TEMPERATURE DISPLAY: 1
1=FAHRENHEIT 2=CELSIUS
↓
THERMOSTAT TYPE
If LEVITON thermostats are part of the system, this item specifies the thermostat type for each thermostat (this enables the thermostat). If thermostats are used, they must be configured to the applicable thermostat type. When any THERMOSTAT
TYPE is changed from the default setting of "Not Used", Zone 16 and Output 8 is automatically configured for thermostats.
There is no need to change the ZONE TYPE for Zone 16 or OUTPUT TYPE for Output 8.
For thermostat types, the current setting is shown on the bottom line.
THERMOSTAT 1 TYPE: 0
NOT USED #=CHNG ↕
THROUGH
THERMOSTAT 4 TYPE: 0
NOT USED #=CHNG
↑
To enable or change a thermostat type, press the ' # ' key. Use the arrow keys to scroll through the list of thermostat types, then press ' # ' to select a new type
.
The display shows:
SELECT TYPE: 1
AUTO HEAT/COOL
↓
Page 51
TYPE
AUTO HEAT/COOL
HEAT/COOL
NUMBER
HEAT ONLY
COOL ONLY
SETPOINT ONLY
Z-WAVE THERMOSTAT NODE ID
1
2
3
4
5
DESCRIPTION
Automatic changeover heat and cool thermostat
Manual changeover heat and cool thermostat
Heating only thermostat
Cooling only thermostat
Setpoint only thermostat
If Z-Wave Thermostats are part of the system, the Node ID for the thermostat must be associated (mapped) with the specified thermostat address in the Omni IIe controller.
TSTAT 1 NODE ID: 0
0-232 ↕
THROUGH
TSTAT 4 NODE ID: 0
0-232 ↑
Enter the Node ID (0-232) for each Z-Wave thermostat followed by the ' # ' key.
Enter 0 if there is no node associated to the specified thermostat.
SETUP MISCELLANEOUS
To configure the miscellaneous Installer Setup items, from the Installer Setup menu, press the 6 (MISC) key.
INSTALLER CODE
The Installer code allows the installer access to the Installer Setup menu. The Installer code should be changed and not given to the customer. The Installer code cannot be used for remote phone access.
INSTALLER CODE:
0000-9999 0000=DISABLE
The default setting for the Installer code is 1 1 1 1.
↓
NOTE:
Remember this Installer code and do not disable. There is no way to reset or retrieve the code! If the code is forgotten or disabled, the Omni IIe controller must be sent back to the factory. Call for an RA#.
ENABLE PC ACCESS
This enables or disables the PC ACCESS feature. Factory default is enabled.
ENABLE PC ACCESS: 1
0=NO 1=YES ↕
Page 52
PC ACCESS CODE
This code allows dealers to put an access code in the system that is separate from the customer's Master code and the Installer code. Dealers can use the PC Access code to access the system by PC. The PC Access code cannot arm and disarm the system.
The PC Access code is NOT programmed from the factory. To use it, set it to any code other than 0000. To disable the PC
Access code, enter 0000 for the code.
NOTE: This item must be enabled (by entering a code) if PC Access is will be used.
PC ACCESS CODE:
0000-9999 0000=DISABLE↕
CALL BACK PHONE NUMBER
In response to a request for remote PC ACCESS using the PC ACCESS code, the system will hang up and dial this number back immediately. To program the CALLBACK PHONE NUMBER, enter the number then press ' # '. To remove the CALLBACK
PHONE NUMBER, press the OFF key to enter a single "-", then press ' # '.
CALL BACK PHONE NUMBER:
- ↕
OUTSIDE SIREN DELAY
If an output is configured as an "Exterior Sounder", when the alarm is "tripped", the interior sounder is turned on first. After the
OUTSIDE SIREN DELAY, the outside sounder is turned on.
This feature helps reduce annoying false alarms by signaling inside the premises first. The outside siren delay is set to 15 seconds at the factory. You may change it to any value from 0 to 60 seconds. If you want the outside sounder to turn on immediately when the alarm is activated, set the delay to 0. We recommend a minimum time of 15 seconds.
DIAL OUT DELAY: 15
0-60 SECONDS ↕
DIAL OUT DELAY
The DIAL OUT DELAY is the number of seconds that the Omni IIe waits before making an emergency dial out, AFTER the alarm is "tripped" (activated by burglar or fire) to preclude an accidental activation of the alarm from calling in a false alarm.
This delay is set at the factory to 30 seconds.
Note: The DIAL OUT DELAY may be disabled for each individual zone (See – Zone Options).
ALARM RESET TIME
DIAL OUT DELAY: 30
15-45 SECONDS ↕
The Alarm Reset Time is the time it takes before the alarm system resets itself after the alarm is tripped.
ALARM RESET TIME: 6
6-30 MINUTES ↕
To change the alarm reset time, enter a new time between 6-30 minutes, then press the ' # ' key.
The default setting is 6 minutes.
Page 53
ARMING CONFIRMATION
The Arming Confirmation is a quick pulse (squawk) given by the outside siren when the alarm system is armed into a security mode and the EXIT DELAY is expired.
ARMING CONFIRMATION: 0
0=NO 1=YES ↕
To enable the arming confirmation feature, press the 1 (YES) key, then press the ' # ' key. The default setting is 0 (NO) disabled.
FIRE ALARM VERIFICATION
This unit is equipped with a FIRE ALARM VERIFICATION feature. When enabled, if a zone configured as a FIRE (Type 32) or a GAS (Type 34) is activated, the system will cycle SWITCH 12V and Switched Power Outputs off for 10 seconds. The
SWITCH 12V power output will then be restored, and 5 seconds later, the zones will be monitored again. If the zone is activated again within a 2-minute window, the fire alarm will be activated. If not, no fire alarm will be indicated.
VERIFY FIRE ALARMS: 0
0=NO 1=YES ↕
This feature is turned OFF by factory default.
If VERIFY FIRE ALARMS is turned ON:
1) Any device (other than FIRE or GAS) connected to a SWITCH 12V Output (i.e. Glassbreak Detectors), must be connected to a zone configured as a LATCHING ZONE TYPE.
2) The following notice is required by UL:
WARNING
This unit includes an alarm verification feature that will result in a delay of the system fire alarm signal from the initiating circuit. The total delay (Omni IIe controller plus detector delay) shall not exceed 60 seconds. No other initiating devices shall be connected to these circuits unless approved by the local authority having jurisdiction.
Zone Control Detector Total Delay
Circuit Unit Delay Model/Delay
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
SUPERVISE INT SNDR
This enables or disables supervision of the Interior Horn Output, which monitors the wiring to the connected sirens. Factory default is disabled.
SUPERVISE INT SNDR: 0
0=NO 1=YES ↕
SUPERVISE EXT SNDR
This enables or disables supervision of the Exterior Horn Output, which monitors the wiring to the connected sirens. Factory default is disabled.
SUPERVISE EXT SNDR: 0
Page 54
0=NO 1=YES ↕
ENABLE EMERGENCY KEYS
This enables or disables the functionality of the emergency keys on the console keypad. Factory default is enabled. Select the 1
(YES) key to enable the emergency keys. Select the 2 (NO) key to disable the emergency keys.
TIME DISPLAY
ENABLE EMERG KEYS: 1
0=NO 1=YES ↕
This allows you to choose between AM/PM and 24-HOUR time format.
DATE DISPLAY
TIME DISPLAY: 1
1=AM/PM 2=24HR ↕
This allows you to choose between MONTH/DAY and DAY/MONTH date format.
DATE DISPLAY: 1
1=MMDD 2=DDMM ↕
AC POWER FREQUENCY
Set this to the appropriate AC Powerline Frequency.
DEAD LINE DETECT
AC POWER FREQUENCY: 1
1=60HZ 2=50HZ ↕
NOTE: To disable Omni IIe from detecting a dead line, set this item to '0'; otherwise adjust only under direction of LEVITON.
This item adjusts the threshold that is used to determine when the phone line goes dead.
OFF HOOK DETECT
DEAD LINE DETECT: 8
0-15 0=DISABLE ↕
NOTE: Adjust only under direction of LEVITON.
This item adjusts the threshold that is used to determine when the phone line is going off hook.
OFF HOOK DETECT: 69
20-250 ↕
PICKUP AFTER HANGUP
This item is used to disable Omni IIe from picking up the phone line after the called party hangs up the line.
PICKUP AFTER HANGUP: 1
0=NO 1=YES ↕
Currently, after the called party or the called party's answering machine hangs up the phone line, Omni IIe picks up the line and make its "Beep". If you wish to turn the Pickup After Hangup OFF, press 0 then ' # '. To turn it back On, press 1 then ' # '.
The default setting for Pickup After Hangup is Yes.
Page 55
CLOCK ADJUSTMENT
If the clock on an Omni IIe is running faster or slower than the actual time, you can have the Omni IIe automatically compensate up to 29 seconds per day. The Omni IIe will add or subtract the selected amount of time daily.
CLOCK ADJUSTMENT: 30
1-59=-29 TO +29 SEC/DAY↕
Enter 1-29 to subtract 1-29 seconds. Enter 31-59 to add 1-29 seconds. Enter 30 for no adjustment to the clock.
The default setting is 30.
MODEL AND SOFTWARE VERSION
Next, the model number and software version for the system is displayed:
LEVITON OMNI IIe
S/W VERSION 2.11 ↕
RESET SYSTEM EEPROM
Select the 1 (YES) key to reset the EEPROM. All programs, names, and setup items will be reset. All system RAM will also be initialized and the system will restart. This option, if effect, allows the system to be restored to factory fresh configuration.
RESET SYSTEM EEPROM? 0
0=NO 1=YES ↕
RESET SYSTEM RAM
Select the 1 (YES) key to cause all of the system RAM to be reinitialized. The time, date, and event log will be cleared. Other volatile memory locations will also be reinitialized. The system RAM should only be reset if the system is acting strangely and memory corruption is suspected. Resetting the system RAM will not reset any setup items stored in EEPROM.
RESET SYSTEM RAM? 0
0=NO 1=YES ↕
ETHERNET MAC ADDRESS
The Ethernet MAC Address, short for Media Access Control address, is the hardware address that uniquely identifies Omni IIe when connected to a network.
ETHERNET MAC ADDRESS
FF-FF-FF-FF-FF-FF
↑
Page 56
SETUP EXPANSION
To configure each Expansion Module that is installed on the system, from the Installer Setup menu, press the 7 (EXP) key.
Expansion Modules include Hardwire Zone Expanders, ALC Interface Modules, and Serial Interface Modules.
MODULE 1 TYPE
The Module Type defines the function of each expansion module on the controller. Module 1 is the module with the “ADDR” jumper set to 1. Set the module type from the list below. Press ' # ' to change the module type, then use the arrow keys to select the proper module type, then press ' # ' to enter.
MODULE 1 TYPE 1
NOT USED #=CHNG
↓
For example, when configuring the module for a Hardwire Expander and if the jumper on the Hardwire Expander is set to 1, set
“Module 1” Type to “1” (HARDWIRE EXPNDR).
MODULE TYPES NUMBER
NOT USED
HARDWIRE EXPNDR
0
1
ALC
OMNI-LINK
PRO-LINK
UPB
RADIO RA
CENTRALITE
VIZIA RF Z-WAVE
LEVITON HI-FI
Notes:
2
3
4
5
6
9
10
11
DESCRIPTION
No module is installed
Model 10A06 Hardwire Expander installed
ALC Interface Module is installed
Model 10A17 Serial Interface using the Omni-Link protocol
Model 10A17 Serial Interface using the Pro-Link protocol
Model 10A17 Serial Interface using the UPB protocol
Model 10A17 Serial Interface using the RadioRA protocol
Model 10A17 Serial Interface using the CentraLite protocol
Model 10A17 Serial Interface using the Z-Wave protocol
Model 10A17 Serial Interface using the LEVITON Hi-Fi protocol
1. Only 2 Model 10A06 Hardwire Expander Modules can be installed.
2. Only 2 ALC Interface Modules can be installed.
3. Only 1 Serial Interface Module can be installed.
MODULE 2 TYPE - MODULE 4 TYPE
Module 2 is the module with the jumper set to 2, and so on. Set each module type from the list of “Module Types”.
SERIAL 1 RATE
"Serial 1 Rate" selects the baud rate used for the first built-in serial interface (J1 Serial) on the Omni IIe controller. Select the baud rate for the first built-in serial interface from the list. Use the arrow keys to select the baud rate then press the ' # ' key.
BAUD RATE NUMBER
75 baud
150 baud
300 baud
600 baud
1200 baud
2400 baud
4800 baud
9600 baud
4
5
6
1
2
3
7
8 (default)
Page 57
SERIAL 1 FUNCTION
The "Serial 1 Function" selects the communication protocol used for the first built-in serial interface (J1 Serial) on the Omni IIe controller. Select the function for the first built-in serial interface from the list. Use the arrow keys to select the function then press the ' # ' key.
FUNCTION TYPES
OMNI-LINK
NUMBER
3
DESCRIPTION
Serial communication using the Omni-Link protocol
PRO-LINK
UPB
RADIO RA
CENTRALITE
VIZIA RF Z-WAVE
LEVITON HI-FI
4
5
6
9
10
11
Serial communication using the Pro-Link protocol
Serial communication using the UPB protocol
Serial communication using the RadioRA protocol
Serial communication using the CentraLite protocol
Serial communication using the Z-Wave protocol
Serial communication using the LEVITON Hi-Fi protocol
SERIAL 2 - SERIAL 5 RATE
"Serial 2 Rate" - “Serial 5 Rate" selects the baud rate used for the second, third, fourth, and fifth built-in serial interface ports (J2
Serial - J5 Serial, respectively) on the Omni IIe controller. Select the baud rate for the built-in serial interface from the list.
SERIAL 2 FUNCTION
The "Serial 2 Function" selects the communication protocol used for the second built-in serial interface ports (J2 Serial) on the
Omni IIe controller. Select the function for the built-in serial interface from the list.
SERIAL 3 FUNCTION
The “Serial 3 Function” by default is set to UPB to utilize HLC Lighting. When using HLC, plug the LEVITON Powerline
Interface Module (PIM) into the third built-in serial interface (J3 Serial) on the Omni IIe controller. To change the “Serial 3
Function”, select the function for the built-in serial interface from the list.
SERIAL 4 - SERIAL 5 FUNCTION
The "Serial 4 Function" and "Serial 5 Function" selects the communication protocol used for the built-in serial interface ports (J4
Serial and J5 Serial, respectively) on the Omni IIe controller. Select the function for the built-in serial interface from the list.
SERIAL 6 RATE
"Serial 6 Rate" selects the baud rate used when a Serial Interface Module is added to the Omni IIe system. If a Serial Interface
Module is installed, select its baud rate then press the ' # ' key.
Page 58
SETUP ZONE OPTIONS
Zone options are parameters that define the way that a zone functions. There are global zone options that affect all zones and there are individual zone options that affect how each individual zone functions.
To configure zone options, from the Installer Setup menu, press the 8 (ZOPT) key.
SWINGER SHUTDOWN NUMBER
Swinger Shutdown is a false alarm prevention feature that counts the number of alarms caused by a specific zone. After a certain number of alarms caused by the same zone within the same arming period, the controller will then shutdown that zone for the remainder of that arming period.
The "Swinger Shutdown Number" is the number of times that a zone may cause an alarm during the same arming period before it is shutdown.
SWINGER SHUTDOWN NUM: 1
1-2
↓
When enabled, if the Swinger Shutdown zone is violated (causes an alarm) 1 or 2 times (according to the “Swinger Shutdown
Number”) within the same arming period, the controller will then shutdown and ignore that zone for the remainder of that arming period.
The default setting is 1.
CROSS ZONE WINDOW
Cross Zoning is a feature that enforces redundant detection of devices such that two or more zones must trip within a defined period to cause an alarm. This feature is typically used when multiple devices are used to cover the same general area.
The "Cross Zone Number" is the number of seconds in which a second zone must trip after a zone configured as “Cross Zoning” has been tripped in order to cause an alarm.
CROSS ZONE NUMBER: 60
15-240 SECONDS ↕
The default setting is 60 seconds.
ZONE 1 OPTIONS – ZONE 48 OPTIONS
Each zone has individual zone options that may be configured for Cross Zoning, Swinger Shutdown, and Dial Out Delay.
ZONE 1 OPTIONS: 4
0-7 ↕
THROUGH
ZONE 48 OPTIONS: 4
0-7
↑
Enter a single value to configure the individual zone options for each zone according to the table below:
Zone Options Table
Zone Options Value
Cross Zoning
Swinger Shutdown
Dial Out Delay
0
No
No
No
1
Yes
No
No
2
No
Yes
No
3
Yes
Yes
No
4
No
No
Yes
5
Yes
No
Yes
The default value for Zone 1 Options – Zone 48 Options is 4. See the highlighted area of Zone Options Table.
Page 59
6
No
Yes
Yes
7
Yes
Yes
Yes
SIA CP-01 COMPLIANCE
This control complies with the SIA CP-01 Control Panel Standard - Features for False Alarm Reduction.
CP-01 is a standard sponsored by the Security Industry Association (SIA) designed with features for security systems and associated arming and disarming devices intended to reduce the incidence of false alarms.
PROGRAMMABLE FEATURES
SHIPPING DEFAULTS AND RECOMMENDED PROGRAMMING
FEATURE
CP-01
PAR. #
REQUIREMENT RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
4.2.2.1 60 seconds 60 seconds Exit Time
(Exit Delay)
Progress Annunciation - Disable
(Audible Exit Delay)
Exit Time Restart
Unvacated Premises
Entry Delay
4.2.2.2
4.2.2.3
4.2.2.5
4.2.3.1
4.2.5.1
Required
(programmable)
Allowed
Required Option
Required Option
(except for remote arm)
Required
(programmable)
Required Option
For full or auto arming: 45-180 seconds
Individual consoles may be disabled
For re-entry during exit delay
If no exit after full arm
30-60 seconds
May be disabled by zone
Enabled on all consoles
Enabled
Enabled
30 seconds
Enabled
Enabled on all consoles
Enabled
Enabled
At least 30 seconds**
Enabled (all zones) Abort Window for Non-Fire Zones
(Dial Out Delay – Zone Option)
Abort Window Time
(Dial Out Delay)
Abort annunciation
(Alarm Aborted)
Cancel Window
(Alarm Reset Time)
Cancel annunciation
(Alarm Canceled)
Duress Feature
(Duress Code)
Cross Zoning
(Cross Zoning – Zone Option)
Programmable Cross Zoning Time
(Cross Zone Window)
Swinger Shutdown
(Swinger Shutdown Number)
Swinger Shutdown Disable
(Swinger Shutdown – Zone Option)
Fire Alarm Verification
Call Waiting Cancel
4.2.5.1
4.2.5.1.2
4.2.5.4
4.2.5.4.1
4.2.6.1 &
4.2.6.2
4.3.1
4.3.1
4.3.2
4.3.2
4.3.3
4.5
Required Option
Required Option
Required
Required Option
Allowed Option
Required Option
Allowed
Required
(programmable)
Allowed
Required Option
Required Option
15-45 seconds
Display that alarm was aborted
6-30 minutes
Display that alarm was canceled
No duplicates with other user codes Disabled
May be enabled by zone
15-120 seconds
For all non-fire zones, shut down at
1 or 2 trips
For non-police response zones
Depends on Sensors
Depends on user phone line
30 seconds
Enabled
6 minutes
Enabled
Disabled
15 seconds
One trip
Enabled
Disabled
Disabled
At least 15 seconds**
No programming option
At least 6 minutes
No programming option
Disabled
Enabled and two (or more) zones programmed
Time based on walk path in protected area
One trip
Enabled (all zones)
Enabled unless sensor can self verify
Enabled if user has call waiting
* Programmable at installation may be subordinate to other UL requirements for the intended application.
** Combined Entry Delay and Abort Window (Dial Out Delay) should not exceed 1 minute.
Minimum Equipment Requirements for a CP-01 Compliant Installation:
Quantity Description Applicable Model Numbers
1
1 -8
Omni IIe Controller
Omni Console
Model 20A00-50, 20A00-51, 20A00-52, 20A00-53
Model 33A00-1, 33A00-4
Page 60
OMNI IIe SPECIFICATIONS
Size: Controller: 13 W x 13 H x 4.5 D
Console: 4.6 W x 4.5 H x 1.2 D
Weight: Controller: approx. 10 lb.
Console: approx. 0.5 lb.
Operating 32 - 122 degrees F (0 - 50 degrees C)
Ranges: 10 - 95 % relative humidity, non-condensing
Power: 120 VAC, 60 Hz, 60 watts
Transformer: 24 VAC, 1.67 amps, 40 VA
Battery: Rechargeable Lead-Acid, 12 volts, 7 amp-hour
Device Fuse: Polyfuse: 1.35 A
Horns Fuse: Polyfuse: 1.35 A
Battery Fuse: Polyfuse: 4.00 A
Polyfuses are permanent fuses that do not need replacement.
Nominal Voltage: 10 - 13.7 VDC, 0.5 V max. peak to peak ripple
Low Voltage Cut Out: approx. 9 VDC
Typical Current Consumption at Nominal Voltage:
Controller: 135 mA
Console: backlight off - 35 mA; backlight on - 100 mA
Controller Maximum Group Current Outputs:
Devices: AUX 12 VDC, SWITCH 12 VDC, CONSOLE, and OUTPUTS 1 - 8: 1 A
Horn: INT HORN and EXT HORN: 1 A
Controller Maximum Individual Current Outputs:
Devices: (Do not exceed 1 A total)
AUX 12 VDC 1 A
SWITCH 12 VDC 1 A
CONSOLE 1 A
OUTPUTS 1 - 8 100 mA
For 24-Hour Battery Standby Time, the following must be observed: (See Figure 18)
Controller Maximum Group Current Outputs (applies to residential and commercial):
Devices: AUX 12 VDC, SWITCH 12 VDC, CONSOLE, and OUTPUTS 1 - 8: 250mA
Horn: INT HORN and EXT HORN: 300mA
Page 61
UNDERWRITER'S LABORATORIES (UL) INSTALLATION REQUIREMENTS
The Omni IIe control units (20A00-50, -51, and -52) are suitable for household burglar and fire applications. Refer to UL1641 for installation requirements. Model 20A00-51 is also suitable for use in Commercial Burglar Alarm Applications, Central Station, Local and Police Connect.
Refer to UL 681 for Installation Requirements.
1. The line carrier (X-10) operation is considered supplementary. Operation of the line carrier devices was not investigated by UL.
2. For those zones programmed as PANIC, DURESS or POLICE EMERGENCY, the initiating device shall be a UL Listed Hold Up Device switch.
3. Connections to phone circuit must be made via the supplied cable and RJ31X Jack as shown under RJ31X JACK CONNECTIONS in this manual.
4. For connection of smoke detectors to the controller, refer to requirements under FIRE ZONE HOOKUP and FIRE ZONE CONNECTIONS diagrams in this manual.
5. The controller must be configured for 24 hour Standby Time as shown under 24 HR STANDBY CONNECTIONS diagram in this manual. Maximum current ratings for 24 hours must be observed.
6. Recognized energy limited cable shall be employed, 22 AWG minimum for all connections.
7. The audible signal appliance shall be the Listed Wheelock Model MT-12/24-R Multitone Signal, rated 10.5 - 15.6 VDC, 95 dB(A) with 2 reflecting planes.
The audible signal shall be mounted indoors in a central location. The audible signal appliance can be connected to either the "INT HORN" or "EXT
HORN" circuits. In the case of the latter, the OUTSIDE SIREN DELAY shall be set to 0 seconds.
8. For Residential Applications, the Model 10A01-1 Enclosure shall be used.
9. For Commercial Applications, the Model 10A02-2 Commercial Enclosure shall be used.
10. For Commercial Applications, Listed Ademco AB12 Bell and housing to be used.
11. If the remote arm/disarm switch is used, it shall be the Listed Ademco Model 9789.
12. Operation of the controls with the Programmable Energy Saver Module was not conducted by UL.
13. Operation of the Model 12A00 Wireless Receiver was not verified by UL.
14. Operation of the Two-Way Audio Module was not verified by UL.
15. RS-232 and RS-485 communications were not verified by UL.
16. Refer to the Omni IIe Owner's Manual (Document No. 20R00-50) for programming requirements in UL Listed Installations.
17. For the monitoring of burglar alarm initiating devices, the zone type shall provide an audible output (i.e., not DURESS).
18. The Omni controller must be connected (when employed) to listed carbon monoxide gas detectors (i.e. Sentrol -Model 240-CO).
19. All connections to energy sensors and modules must be done to listed Class 2 circuits only.
20. The Omni IIe must be used in Residential Applications that are under a single ownership.
When used in UL Listed Installations, the following items apply:
1. The "High Security Mode" must be ON.
2. The "Enable Auto Bypass" feature must be OFF.
3. The "Zone Resistors" must be YES.
4. The "Supervise Int Horn" must be YES.
5. The ENTRY DELAY SHALL NOT EXCEED 45 SECONDS for Residential Applications; 60 seconds for Commercial Applications.
6. The EXIT DELAY shall not exceed 60 seconds.
7. Double Delay and Quad Delay zone types shall not be used.
8. The BEEP ON TROUBLE feature must be ON.
9. For Residential Applications the sounding device may be mounted indoors. If, however, the sounding device is connected to the "EXT HORN" terminals of the Omni IIe, then the OUTSIDE SIREN DELAY shall be set to 0.
10. The DIAL OUT DELAY shall not exceed 30 seconds.
11. The SWINGER SHUTDOWN feature for each zone must be NO.
12. The CROSS ZONING feature for each zone must be NO.
13. The EXIT TIME RESTART feature must be NO.
Installer: NAME: __________________________________ NUMBER: _______________________________
Page 62
24-HOUR STANDBY BATTERY CAPACITY
Maximum current ratings for 24-hours:
Aux 12 VDC, Switch 12 VDC, Console, and Outputs 1-8: 250 mA
Interior Horn and Exterior Horn: 350 mA
RED
BLACK
3M, P/N 952
SNAP CONNECTOR
OVER WIRE
BLACK WIRE TO -
RED WIRE TO +
12"
12"
BATTERY
12V 7AH
BATTERY
12V 7AH
FIGURE 18 - 24-HOUR STANDBY CONNECTIONS
Page 63
SMOKE DETECTOR INSTALLATION GUIDELINES
1. Ceiling mounted smoke detectors should be located in the center of the room or hall, or not less than 4 inches from any wall.
When the detector is mounted on a wall, the top of the detector should be 4 to 12 inches from the ceiling.
2. Do not install smoke detectors where normal ambient temperatures are above 100 deg. F (37.8 deg. C) or below 40 deg. F (4 deg. C). Also, do not locate the detector in front of air conditioners, heating registers, or other locations where normal air circulation will keep smoke form entering the detector.
3. Additional information on Household Fire Warning is available at nominal cost from: The National Fire Protection
Association, Battery March Park, Quincy, MA. 02269. Request Standard No. NFPA 72. Contact your home Insurance
Company for a possible reduction of your insurance premium.
4. A smoke detector should be located between the sleeping area and the rest of the family living unit.
5. In family living units with more than one sleeping area, a smoke detector should be provided to protect each sleeping area.
6. A smoke detector should be located on each story (Refer to the diagrams below).
7. For complete details on proper location and installation of smoke detectors, refer to the instructions supplied with the smoke detector.
Page 64
APPENDIX A – CONTACT ID REPORTING FORMAT
ZONE TYPE
Entry/exit (also Double & Quad)
Perimeter (also Latching)
Night Interior (also Latching)
Away Interior (also Latching)
Panic
Police Emergency
Silent Duress
Tamper (also Latching)
Fire
Fire Emergency
Gas
Auxiliary Emergency
Trouble
Freeze
Water
Auxiliary
Fire tamper
Temperature Alarm
EVENT
Zone bypass/restore
Fire zone bypass/restore
Automatic communicator test
Cancel
User disarm/arm
Programmed disarm/arm
PC Access disarm/arm
Quick arm
Keyswitch disarm/arm
Recent closing
Exit error
SYSTEM TROUBLE
Battery low
Fuse
AC power failure
Phone line dead
Digital communicator
Fire tamper
137
110
110
151
150
330
159
154 none
321
152
TRIP TROUBLE DESCRIPTION
134
131
370
370
Entry/exit burglary
Perimeter burglary
132
132
120
120
122
370
370
375
Interior burglary
Interior burglary
Panic alarm
375 Panic alarm
375 Silent panic
370 Tamper burglary
373 Fire alarm
373 Fire alarm
373 Gas alarm
370 24 hour non-burglary
330 System peripheral trouble
370 Low temperature alarm
370 Water leakage
370 Auxiliary trouble
321 Bell/siren #1 trouble
370 Refrigeration alarm
CODE DESCRIPTION
570 Zone bypass/restore
571 Fire bypass/restore
602 Periodic test
406 Cancel
401 Open/close by user
403 Automatic open/close
407 Remote open/close
408 Closing-quick arm
409 Keyswitch open/close
459 Recent closing
374 Exit error
CODE DESCRIPTION
302 Low system battery
312 Power supply overcurrent
301 AC power loss
351 Phone line #1 trouble
350 Communication failure
321 Bell/siren #1 trouble
Page 65
APPENDIX B - DIGITAL COMMUNICATOR CODE SHEET
INFORMATION FOR CENTRAL STATION
Date: _________________________
Subscriber Name: ______________________________________________________________________
Address 1: ______________________________________________________________________
Address 2: ______________________________________________________________________
City, State, Zip: ____________________________________________
Home #: _______________________ Work #: _________________
Password: ________________________________________________
Installer Name: ______________________________________________________________________
Address 1: ______________________________________________________________________
Address 2: ______________________________________________________________________
City, State, Zip: ____________________________________________
Phone #: _______________________ Beeper #: ________________
Subscriber's Notification List:
1. Name:
Phone #:
__________________________________________________
__________________________________________________
Relationship: __________________________________________________
2. Name: __________________________________________________
Phone #: __________________________________________________
Relationship: __________________________________________________
3. Name: __________________________________________________
Phone #: __________________________________________________
Relationship: __________________________________________________
Subscriber Equipment:
Home Automation, Inc. - Omni IIe
Notes: __________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
_________________________________________________________________________________________
First Phone #: ____________________________________________
First Account #: ____________________________________________
Second (Backup) Phone #: __________________________________
Second (Backup) Account #: __________________________________
Communicator Type (Contact ID, 1400 Hz, or 2300 Hz): ____________________
TWO-WAY AUDIO: _______ YES _______ NO
REPORT OPEN/CLOSE: _______ YES _______ NO
24 HOUR TEST: _______ YES _______ NO TEST TIME: ________________________
Page 66
CODE
98
21
22
23
24
17
18
19
20
25
26
27
15
16
13
14
09
10
11
12
05
06
07
08
03
04
01
02
ZONE
TEST CODE
ZONE 1:
ZONE 10:
ZONE 11:
ZONE 12:
ZONE 13:
ZONE 14:
ZONE 15:
ZONE 16:
ZONE 2:
ZONE 3:
ZONE 4:
ZONE 5:
ZONE 6:
ZONE 7:
ZONE 8:
ZONE 9:
ZONE 17:
ZONE 18:
ZONE 19:
ZONE 20:
ZONE 21:
ZONE 22:
ZONE 23:
ZONE 24:
ZONE 25:
ZONE 26:
ZONE 27:
DESCRIPTION
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
ACTION TO TAKE
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
Page 67
CODE
28
82
83
84
C0
81
BC
BD
BE
BF
85
86
87
B8
B9
BB
B3
B4
B5
B6
B7
32
B0
B1
B2
29
30
31
ZONE
ZONE 28:
ZONE 29:
ZONE 30:
ZONE 31:
ZONE 32:
ZONE 33:
ZONE 34:
ZONE 35:
ZONE 36:
ZONE 37:
ZONE 38:
ZONE 39:
ZONE 40:
ZONE 41:
ZONE 42:
ZONE 43:
ZONE 44:
ZONE 45:
ZONE 46:
ZONE 47:
ZONE 48:
FREEZE ALARM
FIRE EMERG
POLICE EMERG
AUX EMERG
DURESS
BATTERY LOW
FIRE ZONE
TROUBLE
DESCRIPTION
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
Page 68
ACTION TO TAKE
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
CODE
99
54
55
52
53
48
49
50
51
44
45
46
47
42
43
40
41
65
66
67
68
69
63
64
61
62
56
60
ZONE
CANCEL CODE
OTHER OPEN
USER 1 OPEN
USER 2 OPEN
USER 3 OPEN
USER 4 OPEN
USER 5 OPEN
USER 6 OPEN
USER 7 OPEN
USER 8 OPEN
USER 9 OPEN
USER 10 OPEN
USER 11 OPEN
USER 12 OPEN
USER 13 OPEN
USER 14 OPEN
USER 15 OPEN
USER 16 OPEN
OTHER CLOSE
USER 1 CLOSE
USER 2 CLOSE
USER 3 CLOSE
USER 5 CLOSE
USER 5 CLOSE
USER 6 CLOSE
USER 7 CLOSE
USER 8 CLOSE
USER 9 CLOSE
DESCRIPTION
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
ACTION TO TAKE
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
Page 69
CODE
70
71
72
73
74
75
76
ZONE
USER 10 CLOSE
USER 11 CLOSE
USER 12 CLOSE
USER 13 CLOSE
USER 14 CLOSE
USER 15 CLOSE
USER 16 CLOSE
DESCRIPTION
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
ACTION TO TAKE
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
__________________________________
Page 70
APPENDIX C – FIRMWARE UPDATES
Description
The Omni IIe Version 3.2 firmware adds the following new features:
•
Support for Clipsal C-Bus Lighting Control
The Omni IIe Version 3.0 firmware adds the following new features:
•
Automatic cycling of switched power when the system is disarmed
•
UPB Transmit Count to increase reliability on a large UPB network
•
AC Fail Report Time to delay “AC Power Off” trouble report to the central station
•
Support for LEVITON Access Control
Note: Loading new screens into each OmniTouch touchscreen may be necessary to support new features in Version 3.0
Firmware. Ensure that each OmniTouch is running “Screens Version “9”. To check, press the “Setup” icon from the Home page.
Next press the “Screen Setup” icon, followed by the “Next” button. The “Screens Version” should be displayed on the bottom left of the display. If the “Screens Version” is lower than “9” or if the text “Screens Version” is not displayed, the screens must be updated.
Configuring Clipsal C-Bus Lighting Groups
Each LEVITON lighting unit can be associated with a corresponding C-Bus lighting group. Omni IIe supports 64 C-Bus lighting groups. LEVITON unit 1 corresponds to C-Bus lighting group address 1; LEVITON unit 2 corresponds to C-Bus lighting group address 2; and so on. C-Bus group address 0 is not supported.
Configuring Serial Communications for Clipsal C-Bus and LEVITON Access Control
When connecting a Clipsal B-Bus lighting system or LEVITON Access Control Reader to a serial interface on the Omni IIe controller, the serial interface must be configured to the respective protocol.
Serial Module Setup
When connecting Clipsal C-Bus or LEVITON Access Control Readers to the LEVITON Model 10A17 Serial Interface Module, the “Module Type” must configured as follows:
From the Installer Setup menu, select the 7 (EXP) key.
The Module Type defines the function of each expansion module on the controller. Module 1 is the module with the ADDR jumper set to 1. Set the module type from the list below. Press ' # ' to change the module type, then use the arrow keys to select the proper module type, then press ' # ' to enter:
MODULE 1 TYPE 3
OMNI-LINK #=CHNG
↓
For LEVITON Access Control communications: set the Serial Interface Module to “18” (ACCESS CONTROL)
For Clipsal C-Bus communications: set the Serial Interface Module to “21” (CLIPSAL C-BUS)
Page 71
For example, when configuring the module to Access Control and if the jumper on the Serial Interface Module is set to 1, set
“Module 1” Type to “18” (ACCESS CONTROL). The Serial Interface Module is now set to use the LEVITON Access Control
Protocol.
NUMBER
DESCRIPTION
MODULE TYPES
NOT USED
HARDWIRE EXPNDR
ALC
0
1
2
No module is installed
Model 10A06 Hardwire Expander installed
ALC Interface Module is installed
OMNI-LINK
PRO-LINK
UPB
RADIO RA
CENTRALITE
VIZIA RF Z-WAVE
LEVITON HI-FI
ACCESS CONTROL
CLIPSAL C-BUS
Serial Function Setup
3
4
5
6
9
10
11
18
21
Model 10A17 Serial Interface using the Omni-Link protocol
Model 10A17 Serial Interface using the Pro-Link protocol
Model 10A17 Serial Interface using the UPB protocol
Model 10A17 Serial Interface using the RadioRA protocol
Model 10A17 Serial Interface using the CentraLite protocol
Model 10A17 Serial Interface using the Z-Wave protocol
Model 10A17 Serial Interface using the LEVITON Hi-Fi protocol
Model 10A17 Serial Interface using the LEVITON Access Control protocol
Model 10A17 Serial Interface using the Clipsal B-Bus protocol
When connecting Clipsal C-Bus or LEVITON Access Control Readers to one of the built-in serial ports (J1-J5 Serial) on the
Omni IIe, the "Serial Function" selects the communication protocol that is used.
FUNCTION TYPES NUMBER
DESCRIPTION
OMNI-LINK
PRO-LINK
UPB
RADIO RA
3
4
5
6
Serial communication using the Omni-Link protocol
Serial communication using the Pro-Link protocol
Serial communication using the UPB protocol
Serial communication using the RadioRA protocol
CENTRALITE
VIZIA RF Z-WAVE
LEVITON HI-FI
9
10
11
Serial communication using the CentraLite protocol
Serial communication using the Z-Wave protocol
Serial communication using the LEVITON Hi-Fi protocol
ACCESS CONTROL
CLIPSAL C-BUS
18
21
Serial communication using the LEVITON Access Control protocol
Serial communications using the Clipsal C-Bus protocol
For LEVITON Access Control communications: set the Serial Interface Module to “18” (ACCESS CONTROL)
For Clipsal C-Bus communications: set the Serial Interface Module to “21” (CLIPSAL C-BUS)
Serial 1 Function
Select the function for the built-in serial interface from the list. Use the arrow keys to select the function then press the ' # ' key.
Serial 2 - Serial 5 Function
The "Serial 2 Function" through "Serial 5 Function" selects the communication protocol used for the built-in serial interface ports
(J2 Serial – J5 Serial, respectively) on the Omni IIe controller. Select the function for the built-in serial interface from the list.
Automatic Cycling of Switched Power when the System is Disarmed
Whenever the Omni IIe security system is disarmed, the controller will cycle power to the SWITCH 12V or a Switched Power
Output to reset smoke detectors and other latching devices. In previous versions of controller firmware, the SWITCH 12V or
Switched Power Outputs were only cycled with the security system was armed.
This feature allows smoke detectors to be silenced and reset without having to arm the security system.
Page 72
UPB Transmit Count
The UPB Transmit Count is used to specify the number of UPB transmission attempts when UPB signals are sent from the Omni
IIe controller. The controller will also configure LEVITON UPB devices with this same number of attempts; hence, other UPB devices on the network will also transmit using the specified number of transmission attempts.
To change the UPB Transmit Count, from the Installer Setup menu, select the 1 (CTRL) key.
UPB TRANSMIT COUNT: 2
2-4 ↕
This setting is particularly useful in large installations where a Split Phase Repeater is connected on the UPB network.
Note: A higher setting will increase UPB reliability (particularly when a Split Phase Repeater is connected); however, may reduce performance (i.e. because of the additional UPB transmissions, it may reduce the speed in which devices are controlled).
AC Fail Report Time
The AC Fail Report Time is used to suspend the “AC Power Off” trouble report to the central station, until the power has been off for the specified amount of time. This is used to prevent the Omni IIe from calling and reporting of AC power failures when there are numerous AC power interruptions at the premises. An “AC Power Off” trouble is not generated until power has been off for 3 minutes. The AC Fail Report Time begins after the trouble has been generated (i.e. 3 minutes after the AC power goes off) and is reset every time power is restored.
To change the AC Fail Report Time, from the Installer Setup menu, select the 3 (DCM) key.
AC FAIL REPORT TIME: 60
0-240 MIN 0=DISABLE ↕
The AC Fail Report Time can be set from 1 to 240 minutes, or disabled (trouble will not be reported).
LEVITON Access Control
LEVITON Access Control allows you to access doors by opening an electric or magnetic lock, arm and disarm the security system, and achieve many home automation functions such as controlling lighting, energy management, surveillance, and audio.
The Access Control Reader is a 125 KHz high security, digitally encrypted, 26-bit proximity card reader. It has durable and scratch resistant polycarbonate housing and full epoxy potting which ensures successful operation even in harsh environments.
Omni IIe can have up to 4 LEVITON Access Control Readers connected.
Users can utilize either a standard credit card sized Access Control Card or the convenient Access Control Key Tag to access the system. Each card is attached to a user code in the controller which can be managed with several privileges. Users can be granted privileges based on time of day and day of week as well as any other desired events.
Reader Setup
Each Access Control Reader can easily be enrolled and configured using an LEVITON console or PC Access software. Access
Control Readers are configured and enrolled under Setup | Installer | Expansion.
Page 73
Enrolling Access Control Readers
When enrolling an Access Control Reader, the following configuration items are part of the enrollment process:
•
•
•
•
•
•
•
Area assignment
Link assignment (link to another Access Control Reader)
Unlock Time
Exit Time
Lock Type
Beeper (enable or disable)
Arming and disarming
Note: These items should be configured prior to enrolling the Access Control Reader.
To enroll Access Control Readers, from the Installer Setup menu, press the 7 (EXP) key. Use the down arrow key to scroll to the
“Reader Address” menu item.
READER 1 ADDRESS:
0.0.0.0 #=CFG ↕
Press the ' # ' (#=CFG) key to put the system into configuration mode. The display will show:
CONFIGURE READER 1
SWIPE CARD 3 TIMES
Go to the Access Control Reader to be enrolled and swipe any LEVITON Access Control Card or Key Tag 3 times in front of the reader:
READER 1 ADDRESS:
8.5.0.137 #=DEL ↕
Note: you have 3 minutes to complete the operation once the system is put into configuration mode. If an LEVITON Access
Control Card or Key Tag has not been swiped 3 times within the first 3 minutes, the controller will automatically exit configuration mode.
Deleting Access Control Readers
To delete an Access Control Reader that is enrolled in the system, scroll down to the particular “Reader Address” menu item, and then press the ' # ' (#=DEL) key.
READER 1 ADDRESS:
8.5.0.137 #=DEL ↕
You will first be prompted to confirm deletion:
DELETE READER 1?
0=NO 1=YES
Deleting an Access Control Reader will take it out of the system and it will not be valid any longer.
Area Assignment
When two Areas are configured, each Access Control Reader can be assigned to a specific Area on the controller. When used for security arming and disarming, the security mode of the Area where the Access Control Reader is assigned will be changed.
READER 1 AREA: 1
1-2 ↕
Page 74
Enter the Area for the selected Access Control Reader followed by the ' # ' key.
Page 75
Link Assignment
A Link Assignment is used when two Access Control Readers are used to control access to the same door (i.e. one reader on the inside and the other on the outside of the restricted door). This is useful when an Access Control Card or Key Tag is required to enter or exit through a restricted door.
Since the door lock is physically connected to a single Access Control Reader, the Link Assignment links the selected Access
Control Reader with a second Access Control Reader so that when a valid Access Control Card or Key Tag is presented at either
Access Control Reader, the door is unlocked. Furthermore, the controller will log which Access Control Reader was used to access the door (i.e. whether the user was entering or exiting the door).
READER 1 LINKED TO: 0
0-4 ↕
Enter the reader number of the Access Control Reader that will be linked to the selected reader, followed by the ' # ' key.
Notes:
•
Only two Access Control Readers can be linked together.
•
When a valid Access Control Card of Key Tag is presented at either linked Access Control Reader, the 9 LED indicators on both linked Access Control Readers will illuminate the color of the current security arming state for that area and will remain illuminated while the door is unlocked.
Unlock Time
The Unlock Time is the amount of time that the door remains unlocked when a valid Access Control Card or Key Tag is presented at the Access Control Reader. The Unlock Time can be between 1-60 seconds and is individually configured for each reader.
Note: When the door is unlocked due to a valid Access Control Card or Key Tag is presented, all 9 LED indicators will illuminate the color of the current security arming state for that area and will remain illuminated while the door is unlocked.
READER 1 UNLK TIME: 5
1-60 SECONDS ↕
Enter the Unlock Time (1-60 seconds) for the selected Access Control Reader, followed by the ' # ' key. The default time is 5 seconds.
Exit Time
The Exit Time is the amount of time that the door remains unlocked when the “Request to Exit” input is tripped. An optional device, such as a “Request to Exit” button which is mounted on the inside of the restricted door, is used to unlock the door without requiring a second Access Control Reader. The Exit Time can be between 1-60 seconds and is individually configured for each reader.
Note: When the door is unlocked due to pressing a “Request to Exit” button, none of the LED indicators will illuminate.
READER 1 EXIT TIME: 5
1-60 SECONDS ↕
Enter the Exit Time (1-60 seconds) for the selected Access Control Reader, followed by the ' # ' key. The default time is 5 seconds.
Page 76
Lock Type
The Lock Type specifies the type of door lock that is connected to the selected Access Control Reader. The Lock Type can be either be configured for a "Fail Secure" device (door is locked when power fails) or "Fail Safe" mode (door is unlocked when power fails).
READER 1 LOCK TYPE: 0
0=SECURE 1=SAFE ↕
Select 0 (Secure) when connecting a “Fail Secure” lock or select 1 (Safe) when connecting a “Fail Safe” lock, followed by the ' # ' key. The default setting is “Fail Secure”.
Reader Beeper
The Reader Beeper setting is used to enable and disable the beeper in the selected Access Control Reader. When the beeper is set to “Yes”, every time a valid Access Control Card or Key Tag is presented at the reader, the beeper will produce a single short beep. If the reader is used to arm or disarm the security system, the beeper will produce a single long beep.
When the beeper is set to “No”, the reader will not beep when a valid Access Control Card or Key Tag is presented at the reader or when the reader is used to arm or disarm the security system.
READER 1 BEEPER: 1
0=NO 1=YES ↕
To disable the beeper, select 0 (No) followed by the ' # ' key. To enable the beeper, select 1 (Yes) followed by the ' # ' key. The default setting for the beeper is enabled (Yes).
Reader Arm/Disarm
The Reader Arm/Disarm setting is used to enable or disable the reader for arming and disarming the security system in the respective area when a valid Access Control Card or Key Tag is presented at the selected Access Control Reader 3 times, each presentation within 5 seconds of the previous presentation of the card.
When Arm/Disarm is set to “Yes”, and a valid Access Control Card or Key Tag is presented at the reader 3 times, each presentation within 5 seconds of the previous presentation of the card, the Access Control Reader will produce a single long beep and the security system will:
(a) Arm to the Away mode (in the respective area) if the security system is currently disarmed, OR
(b) Disarm the security system (in the respective area) if the security system is currently armed in any security mode
When Arm/Disarm is set to “No”, the selected Access Control Reader can not be used to arm or disarm the security system.
READER 1 ARM/DISARM: 1
0=NO 1=YES ↕
To disable arming and disarming from the selected reader, select 0 (No) followed by the ' # ' key. To enable arming and disarming at the selected reader, select 1 (Yes) followed by the ' # ' key. The default setting for Reader Arm/Disarm is enabled
(Yes).
Page 77
FCC COMPLIANCE
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at
Leviton Manufacturing of Canada Ltd to the attention of the Quality
Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
LEVITON LIMITED WARRANTY
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that products manufactured by Leviton under the Leviton brand name (“Product”) will be free from defects in material and workmanship for the time periods indicated below, whichever is shorter: • OmniPro II and Lumina Pro: three (3) years from installation or 42 months from manufacture date.
• OmniLT, Omni IIe, and Lumina: two (2) years from installation or 30 months from manufacture date. • Thermostats, Accessories: two (2) years from installation or
30 months from manufacture date.
• Batteries: Rechargeable batteries in products are warranted for ninety (90) days from date of purchase. Note: Primary (non-rechargeable) batteries shipped in products are not warranted.
Products with Windows ®
Operating Systems: During the warranty period, Leviton will restore corrupted operating systems to factory default at no charge, provided that the product has been used as originally intended. Installation of non-Leviton software or modification of the operating system voids this warranty. Leviton’s obligation under this Limited Warranty is limited to the repair or replacement, at Leviton’s option, of Product that fails due to defect in material or workmanship. Leviton reserves the right to replace product under this Limited Warranty with new or remanufactured product. Leviton will not be responsible for labor costs of removal or reinstallation of Product.
The repaired or replaced product is then warranted under the terms of this Limited Warranty for the remainder of the Limited Warranty time period or ninety (90) days, whichever is longer. This Limited Warranty does not cover PC-based software products. Leviton is not responsible for conditions or applications beyond Leviton’s control. Leviton is
not responsible for issues related to improper installation, including failure to follow written Installation and operation instructions, normal wear and tear, catastrophe,
fault or negligence of the user or other problems external to the Product. To view complete warranty and instructions for returning product, please visit us at www.leviton.com.
COPYRIGHT AND TRADEMARK INFORMATION
This document and all its contents herein are subject to and protected by international copyright and other intellectual property rights and are the property of Leviton Manufacturing
Co., Inc, its subsidiaries, affiliates and/or licensors. © 2013 Leviton Manufacturing Co., Inc. All rights reserved.
Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the trademarks of their respective owners; such use is not meant to imply affiliation, sponsorship, or endorsement.
No part of this document may be reproduced, transmitted or transcribed without the express written permission of Leviton Manufacturing Co., Inc.
For Technical Assistance Call: 1-800-824-3005 (U.S.A. Only) www.leviton.com
PK-93404-10-B0-0A
AR2213
(20I00-50)
Advertisement
Key features
- Burglary and fire protection
- Supports various sensors and devices
- Control from console, mobile app or web interface
- Expandable to 48 zones
- SIA CP-01 compliant