eco Sensors_ds_en_v03

eco Sensors_ds_en_v03
Energy Intelligence Solutions
eco Sensors
Energy Management Software
eco Sensors software has been developed to work with ATEN’s new generation of PE series green energy
power distribution units (PDUs) to effectively increase the efficiency of data center power usage. With the use
of dynamic Rack Cooling Index (RCI) and Return Temperature Index (RTI) by zone, eco Sensors software, in
conjunction with sensor-enabled eco PDUs, gives you the means to assess, diagnose and estimate how much
energy you can save. Following the suggestions generated by the sensor-enabled system allows you to optimize
energy usage to save energy without harming your IT equipment’s reliability. The eco Sensors utility provides
single portal, single login, secure, centralized, access, administration and management of up to 1000 PE devices
over the network – local and worldwide – anywhere and anytime.
Because eco Sensors offers a single, integrated window-based application program to manage all your devices,
users no longer need to learn the interface for each individual device or remember every device’s IP addresses,
making system management easier and more efficient.
By consolidating the management of your PE devices, eco sensors allows every PE device to be accessed and
controlled by means of a single interface. All outlets in different PE devices are integrated into a single tree
view, making eco sensors ideal for the power management of large data centers and branch office,with servers
located in several remote locations within the same intranet.
eco Sensors is able to automatically discover all PE devices within the same intranet and has the ability to
monitor/manage these devices. This software provides monitoring/managing of PE device outlet power ON/OFF/
Reboot, sequential ON/OFF of outlet, current / kWH / environmental monitoring at PDU/outlet level, name of
outlet, current / kWH / environment sensor threshold setting/alert, circuit breaker status monitoring etc. through
SNMP. Threshold exceed alert through System log / SMTP.
*eco Sensors is designed to work with NRGence™ PDUs, and is bundled with all PE series packages.
1
Energy Intelligence Solutions
Features
Power Distribution
• Automatic discovery of all PE devices within the same intranet
• Remote real-time power measurement and monitoring
• PDU level current / voltage / power dissipation / power consumption
• Outlet ON / OFF / Recycle status
• Second window to monitor data center status including PUE, RTI, RCI, Power, Carbon Footprint and rack status
• Remote real-time power outlet management*
• Power outlet ON / OFF / Cycle switching by outlet or user-defined group
• Power outlet ON / OFF / Cycle switching with pre-defined schedule
• User-defined outlet level delays for sequential power up
• Current / Voltage / Power Dissipation / Power Consumption threshold level setting
• User access assignment for every outlet
• Name assignment to individual outlets
• Remote real-time environment sensor monitoring
• Temperature / Temperature + Humidity reading / Temperature + Differential Pressure
• Temperature and Humidity threshold level setting
• Plotting/Monitoring of all PE devices
• Add data center server racks
• Add PE devices for each server rack
• Manage device/device outlet status for each plot
• Offers essential data center indices including Rack Intake Temperature, Rack Exhaust Temperature, Rack Equipment Temperature
Difference, RCI ( Rack Cooling Index ), RTI ( Return Temperature Index ), RHI ( Rack Humidity Index ), RPI ( Rack Pressure Index ), RAI
( Rack Airflow Index )
• Power analysis report for optimizing data center energy management – including power usage, power load, power cost, CO2 cost,
power capacity and trend
• Exceed threshold alert through SMTP and System log
• 10240 line event log
• System log provision
• Two-level password security
• Strong security features include password protection and advanced encryption technologies – 128 bit SSL
*Not all functions are supported by all eco PDU PE models. Please see www.aten.com for more details.
Benefits
2
Remote Monitoring
eco Sensors enables IT administrators to easily monitor the real-time power
measurement and environment monitoring information from a remote console.
With Threshold Monitor function, overall threshold monitoring information can be
displayed on a Dashboard for easy viewing.
Power Analysis Report
eco Sensors offers comprehensive power analysis reports which can be separated
by departments and locations. Displays trend charts in real-time or according to
day, month, season or year, grasping the power consumption needs for each of
the four seasons. By knowing actual power consumption trends, you can allocate
power resources without waste and prevent wasted power capacity.
Optimum Data Center
Energy Management
When used in conjunction with Sensor-enabled eco PDUs, eco Sensors Energy
Management Software provides administrators with a real time Rack Cooling
Index® and dynamic power analysis to protect IT equipment from excess heat or
insufficient power capacity.
Energy Intelligence Solutions
eco Sensors keeps a record of transactions that take place on its installation,
and stores up to 128 events at one time. The Event log function also provides a
powerful array of filters and functions that allow administrators to view and export
the log file data, as well as be informed by email of specified events as they occur.
Event Log Support
Hardware Requirements
Operating System
CPU
Display
Memory
Disk
Network
Windows XP/ Windows Server 2003 and later
2.0 GHz Dual Core
Larger than 1024x768
2GB
300GB
10/100/1000 Mbp Ethernet
System Parameters
Max PDU number
1000
Data Center Layout
Max Rack Number
Max Zone Number
Power Report Data
Real Time Dashboard Data
45 x 30
500
20
3 years
1 hour
Temperature Sensor
Differential
Pressure
Sensor
IT Office
IT Office
eco PDU
Sensor Probes
Server Storage
ATEN International Co., Ltd.
3
3F., No.125, Sec. 2, Datong Rd., Sijhih District., New Taipei City 221, Taiwan
Phone: 886-2-8692-6789 Fax: 886-2-8692-6767 www.aten.com E-mail: [email protected]
Printed 09/2012 V2.0
© Copyright 2012 ATEN® International Co., Ltd.
ATEN and the ATEN logo are trademarks of ATEN International Co., Ltd.
All rights reserved. All other trademarks are the property of their
respective owners.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement