- Industrial & lab equipment
- Electrical equipment & supplies
- Batteries & accessories
- Rechargeable batteries
- Alpha
- AlphaCell XTV
- User Guide
- 36 Pages
Alpha AlphaCell XTV User guide
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
AlphaCell XTV Battery
User Guide
Effective: September 2014
Safety Information
Alpha considers customer safety and satisfaction its most important priority. To reduce the risk of injury or death and to ensure continual safe operation of this product, certain information is presented differently in this manual. Alpha tries to adhere to ANSI Z535 and encourages special attention and care to information presented in the following manner.
The following symbols describe how that information is presented in this document:
WARNING! HAZARD
WARNING provides safety information to reduce the risk of INJURY OR DEATH to the technician or user and CATASTROPHIC PROPERTY DAMAGE. The nature of the hazard will be indicated by one or more of the following three icons.
WARNING! ELECTRICAL HAZARD
ELECTRICAL HAZARD WARNING provides electrical safety information to PREVENT
INJURY OR DEATH to the technician or user.
WARNING! FUMES HAZARD
FUMES HAZARD WARNING provides fumes safety information to PREVENT INJURY OR
DEATH to the technician or user.
WARNING! FIRE HAZARD
FIRE HAZARD WARNING provides flammability safety information to PREVENT INJURY OR
DEATH to the technician or user.
There may be multiple warnings associated with the call out. Example:
WARNING! ELECTRICAL & FIRE HAZARD
This WARNING provides safety information for both Electrical AND Fire Hazards
CAUTION!
CAUTION provides safety information intended to PREVENT DAMAGE to material or equipment.
NOTE:
NOTE provides additional information to help complete a specific task or procedure.
ATTENTION:
ATTENTION provides specific regulatory/code requirements that may affect the placement of equipment, installation procedures, or maintenance guidelines.
Read the entire manual and review all the drawings and illustrations contained in this manual before proceeding. If there is any question regarding the safe installation or operation of the product or its components, contact Alpha Technologies or the nearest Alpha representative. Save this document for future reference.
AlphaCell
TM
XTV Battery User Guide
Storage, Maintenance and Deployment
745-680-B13-001, Rev. B
Effective Date: September 2014
© 2014 by Alpha Technologies, Inc.
Disclaimer
Images contained in this manual are for illustrative purposes only. These images may not match your installation.
Operator is cautioned to review the drawings and illustrations contained in this manual before proceeding. If there are questions regarding the safe operation of this powering system, please contact Alpha Technologies or your nearest Alpha representative.
Alpha shall not be held liable for any damage or injury involving its enclosures, power supplies, generators, batteries or other hardware if used or operated in any manner or subject to any condition not consistent with its intended purpose or is installed or operated in an unapproved manner or improperly maintained.
Contact Information
Sales information and customer service in USA
(7AM to 5PM, Pacific Time):
Complete technical support in USA
(7AM to 5PM, Pacific Time or 24/7 emergency support):
Sales information and technical support in Canada:
Website:
1 800 322 5742
1 800 863 3364
1 888 462 7487 www.alpha.com
4
Contents
Safety Information ................................................................................................................................................ 2
AlphaCell XTV Battery Safety Notes .................................................................................................................... 6
Electrical Safety ............................................................................................................................................ 6
Chemical Hazards ......................................................................................................................................... 6
Mechanical Safety ......................................................................................................................................... 7
Battery Maintenance Guidelines........................................................................................................................... 7
Recycling and Disposal Instructions ..................................................................................................................... 8
Transportation Information ................................................................................................................................... 8
Important Storage Practices ................................................................................................................................. 9
1.0 Introduction ................................................................................................................................................. 10
1.1 Description ........................................................................................................................................... 10
1.2 Operating Conditions ........................................................................................................................... 12
1.3 Capacity ............................................................................................................................................... 12
1.3.1 Ratings ...................................................................................................................................... 13
2.0 Preparing for Maintenance. ......................................................................................................................... 17
2.1 Required Tools and Equipment ............................................................................................................ 17
2.2 Inspection of Cabinet ........................................................................................................................... 17
2.3 Pad Undermining ................................................................................................................................. 18
2.4 Inspection of Indicator Lamps .............................................................................................................. 18
2.5 Ground Integrity ................................................................................................................................... 18
2.6 Surge Suppression/SPI Alt Box ........................................................................................................... 18
2.7 Inspect All Wiring and Power Supply ................................................................................................... 18
2.8 Remove all Dirt, Dust and Debris from the Cabinet ............................................................................. 18
3.0 Battery Maintenance Procedure .................................................................................................................. 19
3.1 Battery Visual Inspection ..................................................................................................................... 19
3.2 Power Supply Charger Evaluation ....................................................................................................... 19
3.3 Battery Test Evaluation Using Float Voltage ........................................................................................ 20
3.4 Battery Test Evaluation Using Conductance Reading ......................................................................... 20
3.5 Battery Test Evaluation using Power Supply Self-Test ........................................................................ 21
3.6 Battery Redeployment Procedure Using 24-hour Open Circuit Voltage Test ...................................... 21
3.3 PM Certification Report ........................................................................................................................ 23
3.4 Battery Evaluation Procedures for AlphaCell™ XTV ........................................................................... 25
4.0 Battery Float Charging ................................................................................................................................ 26
5.0 Troubleshooting .......................................................................................................................................... 27
6.0 Battery Specifications by Model Number .................................................................................................... 30
7.0 Warranty and Return Information ................................................................................................................ 31
7.1 AlphaCell XTV Limited Warranty ......................................................................................................... 31
7.2 Battery Maintenance Report for Return Authorizations ....................................................................... 33
745-680-B13-001, Rev. B (09/2014)
Figures
Storage Time vs. Temperature Graph ................................................................................................... 9
Fig. 1-1, Series String Configuration of Batteries ................................................................................ 10
Fig. 1-2, 36Vdc Parallel Battery Strings ................................................................................................11
Fig. 1-3, Terminal Stack (Fused and Unfused) .....................................................................................11
Fig. 1-4, Estimated Available Capacity vs. Battery Temperature ......................................................... 12
Fig. 3-1, Flow Chart for Battery Refurbishment Plan ........................................................................... 22
Fig. 3-2, PCM Certification Report ....................................................................................................... 23
Fig. 3-3, PCM Certification Report, Part 2 ........................................................................................... 24
Tables
Table 1-1, AlphaCell 100XTV Rating ................................................................................................... 13
Table 1-2, AlphaCell 150XTV Rating ................................................................................................... 14
Table 1-3, AlphaCell 195XTV Rating ................................................................................................... 15
Table 1-4, AlphaCell 240XTV Rating ................................................................................................... 16
Table 3-1, Battery Test Evaluation Using Float Voltage ....................................................................... 20
Table 3-2, Conductance Values, Healthy vs. Suspect Batteries .......................................................... 25
Table 4-1, Recommended Charge Settings ......................................................................................... 26
Table 5-1, Troubleshooting .................................................................................................................. 27
Table 6-1, Battery Specifications, AlphaCell XTV Models ................................................................... 30
Table 7-1, Warranty Periods for AlphaCell XTV Batteries ................................................................... 32
745-680-B13-001, Rev. B (09/2014) 5
6
AlphaCell XTV Battery Safety Notes
Review the drawings and illustrations contained in this manual before proceeding. If there are any questions regarding the safe installation or operation of the system, contact Alpha Technologies or the nearest Alpha representative. Save this document for future reference.
To reduce the risk of injury or death, and to ensure the continued safe operation of this product, the following symbols have been placed throughout this manual. Where these symbols appear, use extra care and attention.
WARNING! HAZARD
Any liquid emissions from a valve-regulated lead-acid (VRLA) battery contains dilute sulfuric acid, which is harmful to the skin and eyes. Emissions are electrolytic and are electrically conductive and corrosive.
WARNING! ELECTRICAL HAZARD
Lead-acid batteries contain dangerous voltages, currents, and corrosive material. Battery installation, maintenance, service, and replacement must only be performed by authorized personnel.
Alpha highly recommends fusing in single and parallel string configurations.
Electrical Safety
Lethal voltages are present within the power supply and electrical enclosures. Never assume that an electrical connection or conductor is not energized. Check circuits with a volt meter prior to any installation or removal procedure.
• Observe circuit polarities.
• Always work with another technician when working under hazardous conditions.
• Ensure no liquids or wet clothes contact internal components.
• Hazardous, electrically live parts exist inside uninterruptable power supplies (UPS), and are energized from the batteries even when the AC input power is disconnected.
• Use an insulated blanket to cover exposed portions of the battery system when performing extended maintenance that could result in personal or equipment contact with the energized conductors.
• Certain types of rectifier circuits used in charging the battery may not include a line isolating transformer. In these cases, extreme caution should be used when maintaining and collecting data on the battery system.
Chemical Hazards
To avoid injury:
• Servicing and connection of batteries shall be performed by, or under the direct supervision of, personnel knowledgeable of batteries and their required safety precautions.
• Always wear eye protection, rubber gloves, and a protective vest when working near batteries. To avoid battery contact, remove all metallic objects, such as rings or watches.
• Batteries produce explosive gases. Keep all open flames and sparks away from batteries.
• Use tools with insulated handles, do not rest any tools on top of batteries.
• Batteries contain or emit chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. Battery post terminals and related accessories contain lead and lead compounds. Wash hands after handling (California Proposition 65).
• If any battery emission contacts the skin, wash immediately and thoroughly with water. Follow your company’s approved chemical exposure procedures.
745-680-B13-001, Rev. B (09/2014)
• Neutralize any spilled battery emission with the special solution contained in an approved spill kit, or with a solution of 1 pound (454g) sodium bicarbonate in 1 gallon (3.8L) of water. Report a chemical spill using your company’s spill reporting structure and seek medical attention if necessary.
• Always replace batteries with those of an identical type and rating (match conductance, voltages, and date codes
as specified in this document).
• Never install old or untested batteries.
• Prior to handling the batteries, touch a grounded metal object to dissipate any static charge that may have developed on your body.
• Use special caution when connecting or adjusting battery cabling. An improperly connected or unconnected battery cable can make contact with an unintended surface that can result in arcing, fire, or possible explosion.
• A battery showing signs of cracking, leaking, or swelling should be replaced immediately by authorized personnel using a battery of identical type and rating.
Mechanical Safety
Keep hands and tools clear of fans.
• Fans are thermostatically controlled and will turn on automatically.
• Power supplies can reach extreme temperatures under load.
• Use caution around sheet metal components, especially sharp edges.
• Depending on the model, batteries can weigh anywhere from 25 to 100 pounds (11kg to 45kg). Exercise care when handling and moving batteries. Use proper handling equipment.
Battery Maintenance Guidelines
For optimal performance, inspect batteries every 6 months for:
Signs of battery cracking, leaking or swelling. The battery should be replaced immediately by authorized personnel using a battery of the identical type and rating (match conductance, voltages, and date codes as specified in this document).
Signs of battery cable damage. Battery cable should be replaced immediately by authorized personnel using replacement parts specified by vendor.
Loose battery connection hardware. Refer to documentation for the correct torque and connection hardware for the application.
• Do not attempt to remove the vents (valves) from the AlphaCell XTV battery or add water. This is a safety hazard and voids the warranty.
• Apply NO-OX grease on all exposed connections.
• When necessary, clean up any spilled electrolyte in accordance with all federal, state, and local regulations or codes.
• Follow approved storage instructions.
• Always replace batteries with those of an identical type and rating. Never install untested batteries.
• Do not charge batteries in a sealed container. Each individual battery should have at least 1/2 inch of space between it and all surrounding surfaces to allow for convection cooling.
• All battery compartments must have adequate ventilation to prevent an accumulation of potentially dangerous gas.
Never place batteries in a sealed enclosure. Extreme caution should be used when maintaining and collecting data on the battery system.
745-680-B13-001, Rev. B (09/2014) 7
8
Recycling and Disposal Instructions
• Spent or damaged batteries are considered environmentally unsafe as they contain lead and dilute sulfuric acid. They should not be "thrown away" with common refuse.
• Always recycle used batteries in accordance with federal, state, provincial, and local regulations. The Alpha Group provides recycling services. Call 1-800-863-3930, visit www.alpha.com/BatteryRecycling, or contact your local Alpha representative.
Transportation Information
All AlphaCell XTV batteries are identified as “Battery, Electric Storage, Wet, Nonspillable” when transported by air, sea or by land transportation. The battery(s) must be identified as above on the Bill of Lading and properly packaged with their terminals protected from short circuit. NA or UN numbers do not apply. AlphaCell XTV battery(s) warning label identifies each battery as NONSPILLABLE.
AlphaCell XTV sealed lead-acid batteries are classified as “Nonspillable” for the purpose of transportation by DOT, and
IATA/ICAO as result of passing the Vibration and Pressure Differential Test described in DOT [49 CFR 173.159(f)] and
IATA/ICAO [Special Provision A67]. AlphaCell XTV sealed lead-acid batteries can be safely transported on deck, or under deck stored on either a passenger or cargo vessel as result of passing the Vibration and Pressure Differential Tests as described in the IMDG regulations (Special Article 238).
To transport these batteries as “Nonspillable,” the terminals must be protected from short circuit and the battery must be securely packaged to withstand normal shipping conditions. AlphaCell XTV Batteries packed accordingly are considered unregulated and require no additional special packaging or handling.
For all modes of transportation, each battery and outer package is labeled “NON-SPILLABLE” per 49 CFR 173.159(f).
If repackaging batteries or including batteries as a component of another product, the outer packaging must be labeled
“NON-SPILLABLE” per 49 CFR 173.159(f).
745-680-B13-001, Rev. B (09/2014)
Important Storage Practices
During storage please note:
• All lead acid batteries experience self-discharge while in open circuit storage. This causes circuit voltage and capacity to decrease.
• The self-discharge rate is related to ambient temperature. The lower the temperature, the lower the discharge rate.
Batteries should be stored in a clean, ventilated, and dry location with an ambient temperature of 32°F to 77°F (0°C to
25°C).
• It is important to track open circuit voltage which is related to the density of the electrolyte. If the open circuit voltage is lower than 12.6V or the batteries have been stored beyond the limits shown in the Storage Time vs. Temperature graph below, the batteries should be charged to avoid damage caused by self-discharge.
• Recharge at 14.4V for 12 hours prior to battery reaching 12.6Vdc.
• All batteries should be fully charged before storage. Record the storage date and next supplemental charge date in a maintenance record and on the battery.
• Upon battery deployment, verify all batteries within each string measure in the range of +/- 0.3Vdc of the string average while in "float" charger mode.
NOTE:
The product warranty could be voided if the batteries are not stored and recharged in accordance with these guidelines.
AlphaCell XTV Storage Time vs.Temperature
100% 13.00
12.95
95%
90%
12.90
12.85
85%
80%
75%
70%
0 2 4 6 8 10 12 14
Storage Time (Months)
16 18 20 22
12.80
12.75
12.70
12.65
24
12.60
Storage Time vs. Temperature Graph
745-680-B13-001, Rev. B (09/2014) 9
1.0 Introduction ......................................................... 10
1.1 Description ...............................................................................................................................11
1.2 Operating Conditions .............................................................................................................. 12
1.3 Capacity .................................................................................................................................. 12
1.3.1 Ratings ...................................................................................................................... 13
AlphaCell 100XTV ............................................................................................................................... 13
AlphaCell 150XTV ............................................................................................................................... 14
AlphaCell 195XTV ............................................................................................................................... 15
AlphaCell 240XTV ............................................................................................................................... 16
2.1 Required Tools and Equipment .............................................................................................. 17
3.0 Periodic Maintenance Tasks and Schedule ........................................................... 18
3.1 Monthly Remote Status Monitoring ........................................................................................ 18
3.2 Quarterly Preventive Maintenance ......................................................................................... 19
3.0 Periodic Maintenance Tasks and Schedule ........................................................... 20
3.3 PM Certification Report .......................................................................................................... 20
3.0 Periodic Maintenance Tasks and Schedule ........................................................... 22
3.4 Battery Evaluation procedures for AlphaCell™ XTV .............................................................. 22
Battery System Float Charging Voltage .................................................................................. 23
5.0 Troubleshooting ................................................................ 24
5.0 Troubleshooting ................................................................ 26
7.0 Warranty and Return Information ............................................ 28
7.1 AlphaCell XTV Limited Warranty .................................................................................................. 28
7.0 Warranty and Return Information ............................................ 30
7.2 Battery Maintenance Report for Return Authorizations .......................................................... 30
10
1.0 Introduction
The purpose of this guide is to provide the user with the necessary information to maintain batteries in storage and deploy batteries in Alpha Powering systems, as well as perform battery testing, install replacements and recycling.
This manual guides you through periodic maintenance checks and troubleshooting of the AlphaCell XTV Extreme
Temperature AGM battery.
Adherence to the procedures and practices detailed in this guide will not only insure the battery operates per specifications, but also provides the proper backup for the Alpha Powering system in which it is installed.
To achieve these goals, this guide will address the following topics:
• The storage and maintenance of new battery inventory.
• Deployment of AlphaCell XTV batteries into Alpha Power systems.
• Proper preventative maintenance practices for AlphaCell XTV batteries.
• Replacement and recycling of AlphaCell XTV batteries.
• Warehousing, testing, and redeployment of reuseable AlphaCell XTV batteries.
• How to keep proper maintenance records for troubleshooting and/or Warranty claims.
1.1 Description
The AlphaCell XTV battery is a lead acid battery that facilitates an oxygen recombination cycle.
A 12V battery is made up of six 2V cells internally connected to provide 12 volts.
The battery system is a group of 12V batteries connected in a series string to provide a higher voltage system. In Fig. 1-1, three of the nominal 12V batteries are connected in series to provide an 18 cell system with a nominal voltage of 36V, and four of the nominal 12V batteries are connected in series to provide a 24 cell system with a nominal voltage of 48V.
to power supply
: red
(+), black
(-)
3A 2A 1A to power supply
: red
(+), black
(-)
4A 3A 2A 1A
( inline fuse recommended
) inline fuse
( recommended
)
36V String 48V String
Fig. 1-1, Series String Configuration of Batteries
You can connect multiple strings of batteries in parallel. This provides a system whose capacity equals the sum capacity of all the strings. For example, in Fig. 1-2, two 36V 110Ah capacity strings are connected in parallel to provide a nominal
36V at 220Ah.
745-680-B13-001, Rev. B (09/2014)
1.0 Introduction .
WARNING!
Alpha highly recommends fusing in single and parallel string configurations.
to power supply
: red
(+), black
(-)
3A 2A 1A upper tray inline fuse
( recommended
)
3B 2B 1B inline fuse
( recommended
)
[Front]
Fig. 1-2, 36Vdc Parallel Battery Strings lower tray
Battery Cable
M6 x 20mm Bolt (Supplied
With 150XTV, 195XTV, and 240XTV Battery)
OR
M6 x 12mm Bolt (Supplied
With 100XTV Battery)
Split Washer
Flat Washer
Battery Sense
Cable or PTS
Spacer
Battery Terminal
Fig. 1-3, Terminal Stack (Fused and Unfused)
1/4-20 Nut
Split Washer
Flat Washer
Battery Cable
Flat Washer
3/4" (19mm) x 1/4-20 Bolt
Fuse
745-680-B13-001, Rev. B (09/2014) 11
1.0 Introduction
1.2 Operating Conditions
AlphaCell XTV batteries are valve regulated and virtually sealed, and do not give off perceptible amounts of gas under normal operating conditions.
• Acceptable ambient operating temperature: -40°F to 140°F (-40°C to 60°C)
• Ideal ambient operating temperature: 68°F to 77°F (20°C to 25°C)
• Ambient humidity: ≤ 95%
1.3 Capacity
The actual capacity is related to the utilization ratio of the active positive and negative materials within the battery. The utilization ratio is influenced by the depth of discharge, the structure of the battery, and the manufacturing technology.
During normal usage, the factors that influence the actual capacity are discharge rate, depth of discharge, end voltage, and temperature.
• The higher the discharge rate, the lower the available capacity.
• As batteries get colder, the available capacity is reduced. This is related to the kinetics of the electrochemical reactions and the resistivity of the electrolyte (See Fig. 1-4).
NOTE:
Although the battery can be operated at temperatures below -4°F (-20°C), the capacity and ability to discharge will be dramatically decreased.
12
Fig. 1-4, Estimated Available Capacity vs. Battery Temperature
NOTE:
When operating batteries at extreme cold temperatures (-40°C/-40°F) it is recommended to properly size battery strings to the expected load. In these conditions, single strings of 100XTV, 150XTV, 195XTV, 240XTV are not recommended at output CATV loads above 10, 12, 15 and 18AMP respectively for 90VAC without the addition of battery heater mats. Contact your Alpha Sales representative for battery heater mat information.
745-680-B13-001, Rev. B (09/2014)
1.3.1 Ratings
AlphaCell 100XTV
Capacity in Ampere Hours (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
29.8
29.3
35.1
34.8
40
39.7
42.8
42.5
45
44.8
1.75V
1.80V
1.85V
28
26.3
23.1
34
32.5
30.3
39.4
38.1
36.2
42
41
39.2
44.2
43.4
41.6
Constant Current Discharge in Amperes (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
119
117
70.1
69.5
40
39.7
28.5
28.3
22.5
22.4
1.75V
1.80V
1.85V
112
105
92.5
67.9
64.9
60.6
39.4
38.1
36.2
28
27.3
26.1
22.1
21.7
20.8
Constant Power Discharge Watts/Cell (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
213.8
211.3
130
128.3
76.3
75.7
55.2
55
43.5
43.3
1.75V
1.80V
1.85V
203.5
191.2
171.7
126.8
122.3
114.7
75.2
73.8
69.8
54.5
53.5
51.5
43.2
42.5
40.8
3hr
16.1
16
15.8
15.4
14.8
3hr
48.3
48
47.4
46.2
44.4
3hr
31.2
31
30.8
30.3
29.2
5hr
52.5
52
51.5
50.5
48.4
5hr
20.3
20.2
20
19.7
19.2
Table 1-1, AlphaCell 100XTV Rating
5hr
10.5
10.4
10.3
10.1
9.7
8hr
6.83
6.74
6.7
6.54
6.28
1.0 Introduction
8hr 10hr
54.64 55.5
53.92 54.8
53.6
54.1
52.32 53.1
50.24 50.9
10hr
5.55
5.48
5.41
5.31
5.09
8hr 10hr 20hr
13.37 10.93
5.73
13.28 10.85
5.7
13.12 10.7
5.65
12.95 10.57
5.57
12.47 10.18
5.38
20hr
2.8
2.79
2.75
2.73
2.64
20hr
56
55.8
55
54.6
52.8
.
745-680-B13-001, Rev. B (09/2014) 13
14
1.0 Introduction
AlphaCell 150XTV
Capacity in Ampere Hours (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
37.8
37
45.7
45.4
54.2
53.8
59.7
59.3
62.6
62.2
1.75V
1.80V
1.85V
35.5
32
28
44.1
41.8
38.9
53
51.3
48.3
58.4
57
54.3
61.2
59.8
57
Constant Current Discharge in Amperes (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
1.75V
1.80V
1.85V
151
148
142
128
112
91.4
90.8
88.1
83.5
77.7
54.2
53.8
53
51.3
48.3
39.8
39.5
38.9
38
36.2
31.3
31.1
30.6
29.9
28.5
Constant Power Discharge Watts/Cell (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
269.7
266
171
169
104.2
77
103.5
76.5
61
60.5
1.75V
1.80V
1.85V
252.8
232.8
207
166
158.5
149.7
102.3
99
93.3
75.7
74
70.7
60.2
58.7
55.8
3hr 5hr
66 71
65.7
70.5
64.8
69.5
63.6
68
60.3
65
3hr 5hr
22 14.2
21.9
14.1
21.6
13.9
21.2
13.6
20.1
13
3hr 5hr
43.3
28.2
43 28
42.7
27.8
41.8
27.5
40.3
26.3
Table 1-2, AlphaCell 150XTV Rating
8hr 10hr
75.36 77.5
75.04 77.3
74.16 76.5
72.96 75.3
69.76 72.3
8hr 10hr
9.42
7.75
9.38
7.73
9.27
7.65
9.12
7.53
8.72
7.23
8hr 10hr 20hr
18.5
15.43
8.2
18.33 15.42
8.17
18.17 15.3
18 14.97
8.08
7.97
17.67 14.48
7.65
20hr
82.2
81.6
80
79.2
76.2
20hr
4.11
4.08
4
3.96
3.81
745-680-B13-001, Rev. B (09/2014)
1.0 Introduction .
AlphaCell 195XTV
Capacity in Ampere Hours (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
47
46
57
56.5
67.2
66.7
73.1
72.5
76.8
76
1.75V
1.80V
1.85V
43.3
39.3
34.5
55
52.2
48.5
65.5
63
59.1
71.6
69.5
65.7
75.2
73
69.2
Constant Current Discharge in Amperes (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
1.75V
1.80V
1.85V
188
184
173
157
138
114
113
110
104.3
96.9
67.2
66.7
65.5
63
59.1
48.7
48.3
47.7
46.3
43.8
38.4
38
37.6
36.5
34.6
Constant Power Discharge Watts/Cell (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
338.2
331.2
214.3
212.3
129.2
94.5
128.5
94
74.5
74.2
1.75V
1.80V
1.85V
313.3
287.8
257.7
207.5
198.7
187.5
126.8
122.5
115.8
92.8
90.8
86.5
73.3
71.5
68.7
3hr 5hr
82.2
87.5
81.9
87
80.7
86.5
78.3
84
75.6
80.5
3hr 5hr
27.4
17.5
27.3
17.4
26.9
17.3
26.1
16.8
25.2
16.1
3hr 5hr
53.5
35
53.2
34.8
52.7
34.5
51.3
33.8
49.5
32.3
Table 1-3, AlphaCell 195XTV Rating
8hr 10hr
92 94.7
91.2
94.5
90.4
93.8
89.6
91.6
85.6
88.2
8hr 10hr
11.5
11.4
11.3
9.47
9.45
9.38
11.2
9.16
10.7
8.82
8hr 10hr 20hr
22.83 18.83
9.93
22.67 18.67
9.88
22.5
18.5
9.83
22.17 18.33
9.68
21.5
17.5
9.32
20hr
100.4
100.2
100
96.8
92.6
20hr
5.02
5.01
5
4.84
4.63
745-680-B13-001, Rev. B (09/2014) 15
16
1.0 Introduction
AlphaCell 240XTV
Capacity in Ampere Hours (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
1.75V
1.80V
1.85V
57.8
56.6
52.8
47.9
41.5
68.5
68.0
66.0
62.4
57.9
83.8
83.4
81.7
78.1
72.5
84.6
84.0
82.5
79.6
74.6
93.1
92.1
91
88.2
83.3
Constant Current Discharge in Amperes (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
1.70V
231.4
226.3
137.1
136.1
83.8
83.4
56.4
56.0
46.6
46
1.75V
1.80V
1.85V
211
191.6
41.5
132.0
124.9
115.8
81.7
78.1
72.5
55.0
53.1
49.7
45.5
44.1
41.6
Constant Power Discharge Watts/Cell (77°F/25°C)
End Voltage/
Time
15min 30min 60min 90min 2hr
1.67V
410.8
256.4
147.3
107.8
89.6
1.70V
1.75V
1.80V
1.85V
402.3
382.4
348.8
311.6
255.2
247.8
238.8
223.9
158.5
155.3
149.0
139.2
107.5
105.6
101.9
96.3
89.4
88.0
85.5
81.2
3hr 5hr 8hr 10hr 20hr
97.9
101.0
105.6 107.0
112.4
97.6
100.0
104.8 106.0
112.2
96.3
99.0
104.0 105.0
112
93.4
96.0
89.6
92.4
102.4 103.0
108.5
97.5
99.3
104.9
3hr 5hr
32.6
20.2
32.5
20.0
32.1
19.8
31.1
19.2
29.9
18.5
3hr 5hr
63.7
39.9
63.5
39.6
62.9
39.1
61.1
38.6
59.0
36.9
Table 1-4, AlphaCell 240XTV Rating
8hr 10hr
13.2
10.7
13.1
10.6
13.0
10.5
12.8
10.3
12.19 9.95
8hr 10hr
26.0
21.0
25.9
20.9
25.7
20.7
25.2
20.5
24.5
19.9
20hr
5.62
5.61
5.60
5.43
5.24
20hr
11.30
11.2
11.2
11.0
10.5
745-680-B13-001, Rev. B (09/2014)
2.0 Preparing for Maintenance .
Each site must be physically inspected every 12 months, at minimum. Measurement of electrolyte specific gravity, as well as adding water to individual battery cells, is not necessary. All batteries in the string should be numbered to facilitate recording and analysis of data unique to each unit.
Notify anyone affected by the intended maintenance or troubleshooting activity. This should include but not be limited to anyone responsible for the status monitoring equipment at the Central Office head-end or Network Operations Center.
2.1 Required Tools and Equipment
Prior to beginning maintenance, ensure that all recommended tools and equipment, including safety equipment, is available and functional.
The following is a list of the recommended equipment:
• True RMS digital voltmeter
• Conductance meter
• Infrared temperature sensor
• Socket wrenches, insulated
• Box end wrenches, insulated
• Torque wrenches calibrated inch/lbs
• Rubber gloves
• Full face shield
• Safety glasses
• Plastic apron
• Hard hat
• Portable eyewash
• Spill kit, including sodium bicarbonate solution
• Fire extinguisher
• NO-OX corrosion inhibitor
• Paper towels and/or rags
• Plastic soft bristle brush
• Spare battery terminal hardware and cables
2.2 Inspection of Cabinet
Upon arrival, the technician will do a visual inspection of the cabinet at the site location. This will consist of an inspection of the door, latches, hinges, lights and other indicators, and overall condition of the system.
1. Inspect power supply cabinet security and condition.
2. Inspect cabinet for integrity (securely mounted, service meter and conduit integrity, etc.)
3. Inspect cabinet for unwanted critters (i.e., rodents, poisonous spiders, poisonous snakes, fire ants, etc.)
4. Do a visual inspection for any sign of corrosion.
5. Verify the cabinet door opens and closes properly.
6. Check all locks and hinges for proper operation and lubricate if necessary.
7. Determine if the battery tray is operating properly by verifying it slides in and out without sticking.
8. If there is brush surrounding the enclosure, remove any overgrowth.
745-680-B13-001, Rev. B (09/2014) 17
2.0 Preparing for Maintenance
18
9. Identify if enclosure is located in a designated flood plain.
10. For overhead applications, note the distance from the bottom of the power supply to the ground.
2.3 Pad Undermining
1. For ground-level applications, inspect the soil surrounding the enclosure. Verify that the soil has not eroded away from the enclosure causing the cabinet to lean.
2. Report any issues to the supervisor.
2.4 Inspection of Indicator Lamps
1. Locate any installed indicator lamps and verify indicators are functioning correctly.
2. Replace defective lamps.
2.5 Ground Integrity
1. Inspect the ground rod and ensure it complies and meets NEC, NESC or local authority having jurisdiction.
2. Inspect the ground wire cable clamps and enclosure ground lug and make sure the connection is secure.
3. Verify the ground/bond wire is #6 AWG at a minimum.
4. Verify tight connections at both ends of the ground/bond wire. Appropriate bolts or clamps should be used and all bonds should be clean and free of corrosion.
2.6 Surge Suppression/SPI Alt Box
1. Inspect the surge suppressor and replace if needed. If the LED indicator is not illuminated for the LAP, it will need to be replaced.
2. Verify the SPI/Alt Box is tight, along with the coaxial connection, ensuring that the power supply and sheath of coax is grounded. Make sure the Alt Box is not loose and is secured properly to the coax cable at the back of the cabinet.
3. Visually inspect the SPI/Alt Box wires to verify they are in good working condition with the Anderson connectors.
• Burnt or melted wires or Anderson Connectors are an indication of bad wires.
• Anderson Connectors may show signs of discoloration. This is an indication that they need to be replaced.
2.7 Inspect All Wiring and Power Supply
1. Inspect the breakers and receptacles and verify they are functioning properly.
• Inspect breaker to ensure proper size for power supply, and if it is a single pole breaker, the breaker must be of a high magnetic type.
• Examine the AC output on both sides of the receptacle. Replace if cracked.
2. Do not test the power supply standby functionality until after the batteries have been tested. Verify the battery breaker is in working condition and the unit will go into standby mode.
3. Verify the display on the Inverter Module is functioning. Replace the display if it does not appear.
4. Visually inspect the battery cables for secure connections and any evidence of corrosion.
5. Record any active alarms.
2.8 Remove all Dirt, Dust and Debris from the Cabinet
To clean the enclosure, it is recommended to use a vacuum, leaf blower or damp rag. Once the cabinet inspection is complete, proceed to check the batteries.
745-680-B13-001, Rev. B (09/2014)
3.0 Battery Maintenance Procedure
As part of a comprehensive Preventative Maintenance program, a technician must verify that all system batteries are operating correctly. When performing service and maintenance on batteries, always follow recommended safety practices and wear personal protective equipment. It is recommended to perform battery maintenance checks when the ambient temperature is between 32°F (0°C) and 100°F (38°C). It is recommended to follow each of the steps listed below to ensure batteries have been tested properly.
3.1 Battery Visual Inspection
1. Verify the batteries that make up a single string are of the same make and model. Any string consisting of a mixture of makes or models should be completely replaced.
2. Verify battery date codes do not exceed agreed upon age.
3. Physically inspect the batteries. The technician should look for leaking, cracking, swelling, discoloration and/or excessive terminal corrosion.
Suspect batteries should be removed immediately by switching off the battery breaker, disconnecting the battery and removing it from the enclosure. Any battery suspected of leaking should be placed in a plastic bag, the bag tied close, and then placed in a second bag. The bagged battery should then be placed into a cardboard box for safe transport to the designated battery collection location.
The same double-bag procedure should be used for all contaminated cleaning rags at the end of the shift. Batteries should be transported in their shipping cartons or with the terminals protected to prevent short circuits.
4. Using a baking soda and water, clean any corrosion or excessive dirt from the battery itself and the battery tray.
Neutralize any suspect surfaces until all bubbling/foaming from the baking soda itself.
5. If the corrosion is confined to the battery terminal itself (battery is not suspected of leaking), a plastic bristle brush and/or Scotchbrite-style pad may be required to remove corrosion from the battery terminals and battery cables. It is recommended to replace any hardware or cables where the corrosion has pitted or removed significant amounts of the cable lug plating.
6. Inspect battery terminals for proper hardware stack – note that the main battery cable should be next to the battery terminal itself, and that locking hardware is present. Verify the battery terminal hardware is torqued to proper specification.
7. Slide batteries apart to maximize space between batteries to ensure proper air circulation. A ½” of space is recommended, however, a minimum of a ¼” space is required.
8. Verify the RTS (Remote Temperature Sensor or PTS (Precision Temperature Sensor) is properly installed to provide the Power Supply with the battery temperature for proper temperature compensation for the battery charger. Refer to the power supply manual for proper installation procedure.
9. After battery testing is complete and if batteries are deemed good and serviceable, treat the battery posts with corrosion inhibitor.
3.2 Power Supply Charger Evaluation
1. Verify the correct battery model, number of strings and/or battery capacity was selected in the power supply settings.
2. Ensure power supply is in “Float” charger mode.
3. With the battery breaker on, measure the string voltage at the main positive and negative terminals of the battery string. Log the string voltage on maintenance report.
4. If the power supply charger is equipped with temperature compensation, note battery temperature from the power supply display and log this temperature on maintenance report.
745-680-B13-001, Rev. B (09/2014) 19
3.0 Battery Maintenance Procedure
5. Ensure float charge voltage for the string is within +/- 0.3mV of the temperature compensated charger voltage.
Example: For a 36 Volt / 3 battery string system
Nominal charger voltage at 77°F (25°C) = 40.5VDC
Temperature compensation = .005 Volts per °C per Cell.
Battery temperature = 15°C at time of inspection.
Nominal charger voltage calculation 25°C-15°C = 10 degrees x (.005 x 18 cells) =.9V + 40.5V = 41.4Vdc Charge
Voltage
3.3 Battery Test Evaluation Using Float Voltage
It is recommended to perform battery maintenance checks when the ambient temperature is between 32°F (0°C) and
100°F (38°C).
1. With the battery breaker on and after confirming the Power Supply charger is in Float mode and outputting the proper charge voltage above, measure each individual battery’s float voltage within the string and log into the maintenance log.
2. Battery Float Voltage readings are temperature dependent. Use the following table to determine suspect batteries.
3. Turn off battery breaker prior to replacing batteries. Do not perform self-test on known bad batteries.
4. Although float voltage evaluation is a good indication of a battery approaching end-of-life, further evaluation of the battery via conductance and self-test is required to determine if replacement is required. Proceed to step 4.4.
Temperature
32°F / 0°C
54.5°F / 12.5°C
77°F / 25°C
88.5°F / 31.5°C
100°F / 38°C
Battery OK
>13.6 Vdc
>13.4 Vdc
>13.1 Vdc
>13.0 Vdc
>12.8 Vdc
Battery Suspect
≤13.6 Vdc
≤13.4 Vdc
≤13.1 Vdc
≤13.0 Vdc
≤12.8 Vdc
Table 3-1, Battery Test Evaluation Using Float Voltage
Replacement Candidate
<13.0 Vdc
<12.8 Vdc
<12.5 Vdc
<12.4 Vdc
<12.2 Vdc
20
3.4 Battery Test Evaluation Using Conductance Reading
Conductance values are expressed with Siemens (mhos) values. These values are directly affected by temperature.
As a general rule of thumb, for every 2°F drop in temperature below 77°F, the Siemens reading should be adjusted up by 0.7%.
1. Turn the battery breaker off.
2. Allow the batteries to sit idle for one minute to stabilize.
3. Following the conductance meter manufacturer’s instructions, perform a conductance test on each battery (using
Midtronics meter or similar). Log the voltage and conductance readings in the maintenance log. Measure and record the battery temperature in the maintenance log. Temperature compensate the measured values and record in the maintenance log. It is recommended to replace a battery when conductance readings are 40% of the initial or published value for a new battery.
Example: Battery temperature: 67°F, Measured conductance value: 880 S
Compensated Reading: (1+(((77-67)/2)*0.007))*880 = 911
745-680-B13-001, Rev. B (09/2014)
3.0 Battery Maintenance Procedure .
4. Assuming that a battery has an initial (or new published value) Siemens reading of 1000 mhos, follow the guidelines suggested below:
• For readings below 400 mhos, replace the battery.
• For readings between 400-800 mhos, it is considered a marginal reading and it requires a 10-minute self-test as outlined in Section 5.5 below.
3.5 Battery Test Evaluation using Power Supply Self-Test
1. Initiate a 10-minute self-test via the front panel display of the power supply if this feature is supported.
2. Record the readings of the individual battery voltages in the 9th minute of the self-test. (It is important to measure all of the individual battery voltages before the self-test completes to ensure you get an accurate voltage reading while under load and before entering a charging state.)
3. If any battery voltage falls below 10.8 Volts, then that battery should be replaced if it is less than 2 years old. If it is greater than 2 years old then the string replacement is recommended. See Section 4.6 for possible redeployment procedures of potentially good batteries.
This concludes the field battery maintenance portion of the procedure.
3.6 Battery Redeployment Procedure Using 24-hour Open Circuit Voltage Test
(performed in the warehouse on batteries removed from the field but under consideration for redeployment)
Battery strings that fail the self-test may have batteries that are still healthy enough for redeployment. “Good batteries” can be redeployed if they are grouped with other “Good batteries” of the same make and model with like date codes, voltages and conductance readings when redeployed. Batteries should be redeployed within 60 days of removal.
1. After returning batteries to the warehouse, recharge at 14.40V for 12 hours.
2. Remove from charger and let stand open circuit for 24 hours. Measure the battery voltages and log. Any battery measuring below 12.60V should be recycled.
3. Any battery above 12.60V is a candidate for redeployment. Proceed to flow chart below.
745-680-B13-001, Rev. B (09/2014) 21
22
3.0 Battery Maintenance Procedure
Battery
Refurbishment
Plan
Batteries returned from site. Measure and document 24 hour Open Circuit
Voltage (OCV).
( Must occur within 24 hours of removal from charger)
No
Measure
Conductance
Properly recycle batteries per EPA requirements
No
Yes
Measure
Battery
Voltage
Yes
Sort Batteries per
Conductance &
Voltage
Does battery meet the minimum conductance values per Section 3.4?
Does battery meet the minimum of
12.6 Volts for the 24 hour OCV?
Group re-deployable batteries as indicated for future deployment as strings
Group 1 - Voltage 12.6 to 12.9 and conductance 600 to 900 mhos.
Group 2 - Voltage 12.6 to 12.9 and conductance 900 to 1200 mhos.
Group 3 - Voltage 12.9 to 13.2+ and conductance 600 to 900 mhos.
Group 4 - Voltage 12.9 to 13.2+ and conductance 900 to 1200 mhos.
Manufacture date codes should be within
18 months for batteries in string
Batteries stored in warehouses for extended periods of time refer to “Important
Storage Practices” on page 9.
Fig. 3-1, Flow Chart for Battery Refurbishment Plan
745-680-B13-001, Rev. B (09/2014)
3.0 Battery Maintenance Procedure .
3.3 PM Certification Report
Follow this sample when filling out the maintenance log (following page).
Site Data
Latitude
Hub
Region
Longitude
City
System
SAMPLE
Date
State /
Province
Node
Time
Site ID: SAMPLE
Transformer #
Zip Code
Country
Project ID
Business
Service
Street(s)
Transponder Data
CM Mac
Address
CM IP
Address
Trap 1
Utility Account #
SNR
Transponder
Type
Trap 2
CER
Utility Company
Utility Meter #
Transmit
Power
T3
Timeouts
Pole #
Powering
A Node
Trap 4
Receive
Power
T4
Timeouts
Alpha MIB 1
Frequency
Alpha MIB 2
Modulation
Frequency Modulation
Power Supply Data
Make-Model
Firmware
Version
PIM/DOC
Installed
Power
Supply #
PowerSupplyEvents
Number Time
PS1
Battery Data
Self-Test
Verified
Battery # Battery Manufacturer
Total
Run Days
Output VAC
AC Input Voltage (VAC)
Self-Test
Start Time
Date Code
(MMYY)
ID #
Alpha MIB 3
UPSTREAM
Lock
DOWNSTREAM
Lock
Event Log
Cleared
120V Or
240V?
Output Voltage (VAC)
Channel ID
Channel ID
Voltage No
Load (VDC)
Self-Test
Finish Time
Voltage Under Load (VDC)
After 9 Minute Self-Test
Alpha MIB 4
Symbol Rate
Symbol Rate
Self-Test
Interval (days)
Primary (1)
Output Current (A)
Secondary (2 - If Present)
Battery Temperature
(°F / °C)
BS Conductance (mhos)
Meter Reading Corrected 77°F
A1
A2
Logic Card
Firmware
Version
SNMP TRAPS
Trap 3
A3
A4
Battery
Separator Present
B1
B2
B3
B4
Battery
Separator Present
String A Total
String B Total
String A Fused
String B Fused
Charger
Mode
Float (V/C)
Charger
Current
Temp Comp
(mV)
CHARGER INFO
Accept (V/C)
Charger
Current Limit
Fig. 3-2, PCM Certification Report
745-680-B13-001, Rev. B (09/2014) 23
3.0 Battery Maintenance Procedure
As-Found Local Power Supply Alarms
Alarm Major/ Minor
Work Items Performed On Site
Work Item
Tech Notes/ Actions Taken Cleared On Site
Inspection
Item To Check
Check For Pad Undermining
ACI Installed & Functioning
Generator Accessibility
Co-Locate With Vault
Control Switch Installed
Enclosure Make-Model
Internal Breaker
Yes/No
Item To Check
Check Wire Harness And Connectors
Tamper Installed And Functioning
Battery Hardware Properly Tightened
Pad Value
Tap Installed
Yes/No
Mat Type
Enclosure Exterior Maintenance Checklist
Item To Check Yes/No
Clean Dust/Dirt From Enclosure Inside
LRI Installed & Functioning
PS Co-Locate With Node
U-Guard On Ground Wire
Security Bar Present
Enclosure Condition
Service Entrance
UG Or Aerial
Interior Systems Maintenance Checklist
Item To Check Yes/No
Clean And NO-OX Batteries
AC TVSS Installed And Functioning
Coax TVSS Present
Cable Sim Value
Drop Installed
Battery Heater Mat Types & Quantities
Quantity Mat Type
Item To Check
Enclosure Hardware Tightened
Enclosure Snow Shield
Dual Utility Switch Present
PS Metered
Lock Present
Enclosure Depth (cm)
Receptacle Type
Item To Check
Site Grounded Properly
AlphaGuard Installed And Functioning
Battery Temperature Probe Present
Ground Current
Generator Cord Present
Yes/No
Yes/No
Quantity
Quantity Part Number(s)
24
Technician Info
Open Items For
Repeat Visit
Initial X-Tractor & Form Time (minutes)
Last Name
Additional Form Time (minutes)
First Name
PM Service Technician
Contact #
Fig. 3-3, PCM Certification Report, Part 2
Technician #
745-680-B13-001, Rev. B (09/2014)
3.0 Battery Maintenance Procedure
3.4 Battery Evaluation Procedures for AlphaCell™ XTV
.
To help identify batteries approaching end of life in an operating power system, Evaluation Procedure 1 should be performed at each maintenance interval. For batteries not installed in an operating power system, Evaluation Procedure 2 may be performed. For accuracy, tests must be performed on fully charged batteries.
A battery failing any of the following combined tests is defined as a faulty battery. The battery will be replaced under the terms of the warranty if within the defined warranty period.
Evaluation Procedure 1
Conductance/Impedance Test – Measure the conductance of each battery. Any battery that possesses a conductance that is
50% less than the initial reading taken at the point of install can be considered suspect of being below 70% capacity and should be evaluated further. The battery temperature must be approximately the same each time this reading is taken (see Table 3-2 below). Use temperature compensation feature when using Midtronics meter.
AND
Float Voltage Test – Measure the float voltage of each battery in the string that is on float charge. Any battery in the string measured at 13.2 volts or less is a suspect battery and should be further evaluated with the steps below. Any battery below 12.6 volts should be replaced. The 13.2 and 12.6 voltage values are based on a 77ËšF (25ËšC) temperature. Adjust the voltage for higher or lower temperatures by 0.0168 volts per battery per degree Fahrenheit. The higher the temperature above 77ËšF (25ËšC) the lower the voltage will have to be adjusted and vice-versa for temperature below 77ËšF (25ËšC). (i.e.: at a temp of 89ËšF (32ËšC) would have a corresponding float voltage of 13.0 volts).
Evaluation Procedure 2
Conductance/Impedance Test – Measure the conductance of each battery. Any battery that possesses a conductance that is
50% less than the initial reading taken at the point of install can be considered suspect of being below 70% capacity and should be evaluated further. The battery temperature must be approximately the same each time this reading is taken (see Table 3-2 below). Use the temperature compensation feature when using Midtronics meter.
AND
24 Hour Open Circuit Test – Measure the open circuit voltage of the suspected battery 24 hours after the battery has come off of float charge. Care must be taken to ensure that the battery is at full state of charge when it is disconnected from the power supply. The battery should exhibit a voltage about 12.60V. A battery below this voltage should be replaced. A fully charged battery below 12.6 volts is below 70% capacity, but a battery above 12.6 volts is not necessarily above 70% in capacity. Batteries that have been sitting for extended periods should be recharged after 6 months or when they reach 12.8 volts (75% capacity), which ever comes first depending on the storage temperature.
NOTE:
To maintain consistent test results, ensure the same Midtronics conductance tester is used for each test cycle.
100XTV 150XTV 195XTV 240XTV Midtronics Conductance
Models 3200/CELLTRON CTE-1200 AT
Approximate Conductance Values (mhos)
Healthy Battery @ 77°F (25°C)
700-800 900-1100 1050-1250 1250-1550
Suspect Battery @ 77°F (25°C) in mhos 300 400 450 500
Table 3-2, Conductance Values, Healthy vs. Suspect Batteries
745-680-B13-001, Rev. B (09/2014) 25
26
4.0 Battery Float Charging .
Battery System Float Charging Voltage
Encountering temperature extremes
When you encounter temperature extremes, temperature compensate the float charging voltage. The temperature compensation coefficient is -0.0018 V/C per °F (-0.0033 V/C per °C).
For example if the normal battery temperature is 90°F (13° above 77°F) you should reduce the average float charging voltage by 0.0234 V/C (13° x -0.0018 V/C per °F) from 2.25 to 2.23 V/C.
If the battery operates at cold temperatures, (60°F, 17° below 77°F, for example), you can increase the charging voltage to improve recharging time.
For example, increase the charging voltage range by -17° x -0.0018 V/C per degree or 0.031 V/C.
Under or overcharging
If the battery is undercharged for a period of time during which there are multiple discharges, the battery does not fully recharge after each discharge and provides progressively lower capacity.
Excessive overcharging causes premature aging of the battery and loss of capacity, noted by excessive float current, corrosion of the plate grids, and gassing and drying of the limited amount of electrolyte.
Severe overcharging over extended periods of time can induce a thermal runaway condition. This requires replacing the battery system.
NOTE:
The following set points are recommended for AlphaCell XTV Batteries when used in an outdoor non-temperature controlled application.
AlphaCell TM XTV Batteries
Accept 2.35 V/C
Float
Temp Comp
2.25 V/C
-3.3mV/°C/C
Table 4-1, Recommended Charge Settings
745-680-B13-001, Rev. B (09/2014)
5.0 Troubleshooting .
Problem With
Capacity Test
Results
Visual Battery
Checks
Symptom
Reduced operating time at
77°F (25°C) with smooth voltage decline
Reduced operating time at
77°F (25°C) with steep voltage decline or voltage plateaus
Possible Causes
Normal life cycle
Individual low capacity cells
Possible Result
Eventual failure to support the load followed by potential for shorted cells.
Reversed cells during discharge.
Reversed cells will become very hot and will not fully recharge.
Corrective Actions
Replace battery system when at 70% of rated capacity or before.
Replace the isolated low capacity batteries.
Excessive initial voltage drop, even to the point of dropping load in the first several seconds.
•
•
•
•
•
Battery is extremely cold.
Cable gauge too small.
High resistance connections.
Battery is undersized.
Shorted cells.
• Excessive voltage drop.
• Cells will become hot, could develop thermal runaway; internal arcing could result in an explosion.
• Heat the battery.
• Run parallel cables or increase gauge of cables.
• Clean and reassemble connections.
• Add required parallel strings.
• Replace isolated units with shorts and evaluate entire string.
Replace damaged unit.
Cover or container crack
Cover or container explosion
Burned area on container
Permanently deformed
(swollen) container
Rotten egg odor
Melted grease at terminals
Handling or impact damage
Ignition of cell internal gasses due to external source, fusing, or internal conductive path or internal spark due to shorting. Potential exists for ill-maintained batteries or those left in service beyond useful life.
Cell dryout or ground fault.
Potential internal gas ignition.
•
•
Personal injury and equipment damage at time of explosion.
Failure to support load.
Crack in container wicking electrolyte to grounded rack/ tray. Ground fault.
Thermal runaway possible caused by high temperature environment, overcharging, excessively high recharge current, shorted cells, ground fault, or a combination of these.
Possible caused by high temperature environment, overcharging, excessively high recharge current, shorted cells, ground fault, or a combination of these.
Hot connections due to excessive resistance caused by loose connections, dirty contact surfaces or corrosion within connection.
Could result in
• personal hazard due to conductive path to rack.
• smoke or battery fire.
• thermal runaway.
Could result in the emission of hydrogen sulfide, detectable as a rotten egg odor, battery fire, and inability to support the load.
Odor is a product of thermal runaway.
• Excessive voltage drop perhaps leading to short operating time or damaged terminals.
• In extreme case could lead to melted terminal and ignition of the battery cover.
Replace damaged unit and evaluate balance of string.
Clear the ground fault and replace defective unit.
Evaluate balance of string.
Replace the battery system, and correct the items leading to the thermal runaway condition.
Replace the battery system and correct items leading to thermal runaway condition.
•
•
Clean and reassemble connection if damaged.
Replace batteries with damaged terminals.
Corrosion at terminals
Possibly electrolyte leaking from battery terminal seal attacking the interunit container.
Increased connection resistance and resulting increase in the connection heating and voltage drop at high rate discharge.
Disassemble connection, clean, coat connecting surfaces and terminal area seal with anti-oxidation grease, and reassemble the connection. If leakage about terminal area is obvious, the battery should be replaced.
Table 5-1, Troubleshooting
745-680-B13-001, Rev. B (09/2014) 27
28
5.0 Troubleshooting
Problem With
DC Voltage
Checks
Temperature
Checks
Float Charging
Current Checks
Battery
Impedance/
Conductance
Test
Symptom
System float voltage >
2.3V/C average 77°F
(25°C)
System float voltage <
2.25V/C average 77°F
(25°C)
High current recharge
Float current to string is zero.
Float current exceeds
3.0 milliamperes per ampere hour of rated capacity at 77°F(25°C) at float voltage.
Impedance / resistance increase by 50% from original values or conductance decline to
50% of the value when new.
Possible Causes
Charger output set incorrectly.
Charger output set incorrectly.
DC voltage measured between battery system output terminals and ground (rack/tray) or a ground fault indicated by automatic monitoring equipment.
Elevated room temperature
Damaged container allowing electrolyte to wick out to grounded surface
(rack/tray).
Elevated battery temp.
Lack of adequate air conditioning or ventilation.
• Elevated room temp.
• Inadequate cabinet ventilation.
• Discharge - charge cycle.
• High charging voltage.
• Shorted cells.
A battery or connection in series string is open.
Verify via the float voltage check or AC ripple voltage or impedance check of individual batteries.
• Batteries not fully recharged.
• Batteries above
77°F(25°C).
• Potentially shorted cells in battery.
• Depending on degree, battery entering or in thermal runaway.
• Battery discharged or battery conductive path, plate grid or active material, or electrolyte volume deterioration.
• Shorted cells.
• Open cells.
Possible Result
Overcharging causes excessive gassing and drying out of electrolyte, and contributes to potential thermal runaway.
Undercharging results in gradual loss of operating time and capacity with successive discharge cycles.
If persistent, an irreversible level of lead sulfate develops on the plates resulting in a permanent capacity loss.
Corrective Actions
Reset the charger output voltage to recommended value.
• Reset the charger output voltage to recommended value.
• Equalize battery system from 48 to 72 hours and perform capacity test. If capacity loss is permanent, replace the total battery system.
• Personnel shock hazard resulting in serious injury or electrocution.
• Potential burning of container at damaged area or battery fire.
Determine the source of ground fault and replace battery.
Reduced battery life.
• Reduced battery life.
• Reduced life and potential thermal runaway.
• Normal if not exceeding
18°F/10°C increase.
Normal if not exceeding
18°F/10°C increase over ambient.
• Failure to support load.
If an internal arc occurs during discharge, can ignite gasses internal to cell.
• If there is an open/loose connection in external conductive path, can damage termination under load.
• Not at 100% capacity.
• Conducive to thermal runaway.
• Thermal runaway results in eventual meltdown of battery and potential of hydrogen sulfide emissions and fire.
Cool room or accept reduced battery life.
• Improve room air conditioning.
• Improve cabinet ventilation.
• Limit recharge current.
• Limit recharge current.
• Reduce within specifications.
• Replace shorted cells and evaluate total string..
Replace battery with open cell or repair open/loose external connection.
Determine specific cause; take corrective action.
• Reduced operating time.
• Conducive to thermal runaway.
• Will not support load.
Charge and retest battery or replace as required.
Table 5-1, Troubleshooting, continued
745-680-B13-001, Rev. B (09/2014)
5.0 Troubleshooting .
Problem With
Connection
Hardware
Resistance /
Tightness Check
AC Ripple
Voltage Checks
Symptom Possible Causes Possible Result
Connection resistance increase
20% or more from original value.
• Repetitive cycles results in heating and cooling of connection, resulting in relaxation of torque, increase in connection resistance.
• Contamination within the connection results in corrosion and high terminal resistance.
• Loose connections result in heat damaged or melted terminals during high rate discharge.
• Excessive voltage drop during high rate discharge and resulting reduced operating time.
Connection hardware tightness is less than the specified "retorque" value.
AC ripple (p-p) voltage on system
>4% of the value of the DC float voltage
Individual battery in string exhibits AC ripple voltage twice that of other typical batteries in string.
Repetitive cycles results in heating and cooling of connection resulting in relaxation of torque and increase in connection resistance.
Loose connections result in heat damaged or melted terminals during high rate discharge.
Poor filtering of charger output.
Excessive AC ripple could cause the battery to cycle at the ripple frequency and result in heating and deterioration of the plate active material.
Battery with high AC ripple voltage has proportionately higher impedance. Evaluate for performance. Subject battery could have deteriorating conductive path or dry, shorted or open cell.
•
•
Reduced operating time.
Potential conditions could be conducive to thermal runaway.
Corrective Actions
• Retorque connection as required.
• Correct source of contamination, clean contact surface areas, grease contact surfaces with antioxidant grease, reassemble.
Retorque the connection as required.
Improve the charger output filtering.
Verify battery condition.
Replace as required.
Table 5-1, Troubleshooting, continued
745-680-B13-001, Rev. B (09/2014) 29
30
6.0 Battery Specifications by Model Number .
Specifications
Operating Temperature
Range (with Temperature
Compensation):
Storage Temperature:
AlphaCell 100XTV AlphaCell 150XTV AlphaCell 195XTV
-40 to 140°F / -40 to 60°C (Charger temp comp @ ±3.3mVpc per °C)
AlphaCell 240XTV
Self Discharge:
Voltage Per Unit:
14 to 104°F / -10 to 40°C
12V
14 to 104°F / -10 to 40°C
12V
14 to 104°F / -10 to 40°C
12V
14 to 104°F / -10 to 40°C
Battery can be stored up to 12 months at 77°F / 25°C. Higher temperatures during storage will require more frequent recharge.
12V
Float Charge Voltage:
Refresh/Boost Charging
Voltage:
Maximum AC Ripple
(Charger):
13.5 to 13.8Vdc average per 12V unit at 77°F / 25°C
14.4 to 15.0Vdc average per 12V unit at 77°F / 25°C
0.5% RMS or 1.5% of float recommended for best results. Maximum voltage allowed = 4% P/P
Terminal Type:
Terminal Hardware Torque:
Case Size:
Dimensions H x L x W (in/ mm):
Weight* (lb/kg):
Threaded alloy insert terminal to accept M6 x 12mm bolt
120in-lbs / 13.6NM
22NF
8.17 x 9.01 x 5.46 / 207 x 228 x 139
39 / 17.7
* Approximate ** Terminal hardware included with every battery
Threaded alloy insert terminal to accept M6 x 20mm bolt
120in-lbs / 13.6NM
24
8.44 x 10.85 x 6.65 / 214 x 276 x 169
56 / 25.4
120in-lbs / 13.6NM
27
8.43 x 12.71 x 6.67 / 214 x 323 x 169
67 / 30.5
120in-lbs / 13.6NM
31
8.57 x 13.50 x 6.71 / 218 x 343 x 170
75 / 34
AlphaCell 100XTV AlphaCell 150XTV AlphaCell 195XTV AlphaCell 240XTV Battery
Runtime Rating 25Amp
@ 77°F / 25°C to 1.75Vpc:
Ampere Hour Capacity 20Hr Rate
@ 77°F / 25°C to 1.75Vpc:
Maximum Discharge Current:
Short Circuit Current:
Impedance 60Hz (approx.):
Conductance Range Fully Charge
New Battery @ 77°F / 25°C:
100 minutes
56Ah
300 Amperes
1450 Amperes
0.005
700 - 800
150 minutes
80Ah
800 Amperes
1900 Amperes
0.0045
900 - 1100
195 minutes
100Ah
800 Amperes
2250 Amperes
0.0039
1050 - 1250
240 minutes
112Ah
850 Amperes
2650 Amperes
0.0034
1250 - 1550
Table 6-1, Battery Specifications, AlphaCell XTV Models
745-680-B13-001, Rev. B (09/2014)
7.0 Warranty and Return Information .
7.1 AlphaCell XTV Limited Warranty
Float Service Outdoor VRLA Batteries
This limited warranty applies only to the original purchaser (“User”) of the Product supplied under the Supply Agreement.
A Battery will be considered defective, and can be replaced, when it fails to deliver 70% of its rated capacity during stated warranty period provided that it has been used in accordance with the conditions listed below. Standard Warranty periods are outlined in Table
7-1.
When a defective battery is identified the User should promptly notify the manufacturer. Should the manufacturer confirm the Batteries to be defective they will replace the material found to be defective F.O.B. its Factory without charge except for freight.
CONDITIONS AND LIMITATIONS: (all claims are subject)
1) Warranty date is based on Ship Date code stamped on battery.
2) Warranty applies in accordance with Table 7-1.
3) The standard warranty shown in Table 7-1 applies to AlphaCell XTV Batteries used in Alpha enclosures in conjunction with Alpha
Power Supplies.
4) A baseline Two Year Warranty applies to AlphaCell XTV Batteries used in other applications not defined in item #3 shown above.
AlphaCell XTV batteries are not recommended for high cycling applications so please consult Alpha Applications Engineering for an alternative battery solution for high cycling applications. Extended warranties beyond two years may be available for unique enclosure/charger applications based on preapproval by Alpha Engineering. Consult your salesperson for details.
5) Each Battery must be of proper size, design and capacity for its application in order for the warranty to apply.
6) Each Battery must be charged, discharged, stored and serviced in accordance with the AlphaCell XTV owners manual and user's guide.
7) Warranty is void if Battery is subject to misuse, abuse or physical damage or if Battery becomes unserviceable due to fire, wreckage, freezing, or any act of God.
8) Battery must be used with a temperature compensation charger having characteristic charging curves (voltage and current) acceptable with standard manufacturer’s charging practices as outlined in the AlphaCell XTV owners manual and user's guide.
9) User agrees that the manufacturer’s representative shall have access to equipment furnished hereunder for purpose of inspection at reasonable hours and intervals in order for the warranty to apply.
10) All defective and replacement Batteries, if returned, become property of the manufacturer.
11) Field Batteries replaced through limited warranty terms and conditions will receive the balance of original warranty.
12) Standard AlphaCell XTV Warranty requires a minimum semiannual preventive maintenance schedule with records as outlined in the AlphaCell XTV owners manual and user's guide.
CLAIMS:
1) Contact original point of purchase for instructions on applicable warranty claim procedures.
2) Upon satisfactory proof of claim as determined by the manufacturer, the manufacturer shall repair or replace, at its option, any defective Battery based upon the purchase price, exclusive of freight and labor.
3) The manufacturer does not accept any product for return, credit or exchange unless expressly authorized by the manufacturer in writing and returned prepaid to its plant.
ALPHA SHALL NOT BE LIABLE FOR, AND USER SHALL INDEMNIFY AND SAVE ALPHA HARMLESS FROM ANY CLAIMS AND LIABILITIES
ARISING OUT OF THE USE, MAINTENANCE, TRANSPORTATION, OR INSTALLATION OF ANY EQUIPMENT WARRANTED HEREUNDER.
THE FOREGOING LIMITED WARRANTY IS IN LIEU OF ALL WARRANTIES EXPRESSED OR IMPLIED, INCLUDING ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. THE SOLE LIABILITY OF IS SET FORTH UNDER THE CLAIMS PARAGRAPH
ABOVE. SHALL NOT HAVE ANY LIABILITY FOR ANY SPECIAL INCIDENTAL INDIRECT OR CONSEQUENTIAL DAMAGES. THIS LIMITED
WARRANTY APPLIES ONLY TO THE ORIGINAL PURCHASER (USER) OF THE EQUIPMENT, AND IS NON-TRANSFERABLE.
745-680-B13-001, Rev. B (09/2014) 31
7.0 Warranty and Return Information
The table below indicates the warranty periods for AlphaCell XTV Batteries used with Alpha approved power supplies and enclosures.
Model
100XTV
Warranty USA/Canada
5 years
Warranty World Wide Stable Grid
4 years
150XTV
195XTV
5 years
5 years
4 years
4 years
240XTV 5 years 4 years
Contact Alpha Technologies at 1-800-322-5742 for excluded countries and cycling applications.
Table 7-1, Warranty Periods for AlphaCell XTV Batteries
32 745-680-B13-001, Rev. B (09/2014)
7.0 Warranty and Return Information .
7.2 Battery Maintenance Report for Return Authorizations
Contact your Alpha Customer Service representative for assistance in processing your AlphaCell XTV warranty claim.
Alpha Technical Support 1-800-863-3364
This form, in conjunction with Alpha's Battery Evaluation Procedure is intended as a method of collecting data critical to the efficient processing of your warranty battery claims. Record battery float voltage while the battery is still connected to the system. Record battery open circuit voltage (OCV) 24 hours following removal from the system. Describe the problem encountered with the battery as compared to the remaining batteries in the battery string. The ZRE# will be provided after you submit your request to Alpha for processing.
Customer Name/Company Name
Customer Address Line 1
Customer Address Line 2
Customer Phone
Customer Email
Battery Model
Initial
Install
Date
MFR. Date
Code (4-Digit
Code on Top
Label)
Battery
Temperature
(At Time of
Measurement)
Battery
Temperature
Evaluation Procedure 1
(Performed Live in Field)
Vdc in Float
(No Load)
Conductance
(MHOS)
OR
Evaluation Procedure 2
(Performed in Warehouse)
Vdc after 24-hr
OCV
Conductance
(MHOS)
745-680-B13-001, Rev. B (09/2014) 33
This page intentionally blank
This page intentionally blank
Alpha Technologies Inc.
3767 Alpha Way
Bellingham, WA 98226
United States
Tel: +1 360 647 2360
Fax: +1 360 671 4936
Alpha Technologies Europe Ltd.
Twyford House Thorley
Bishop’s Stortford
Hertfordshire, CM22 7PA
United Kingdom
Tel: +44 1279 501110
Fax: +44 1279 659870
Alpha Technologies
Suite 1903, Tower 1,
33 Canton Road, Kowloon
Hong Kong City, China
Phone: +852 2736 8663
Fax: +852 2199 7988
Alpha Technologies Ltd.
7700 Riverfront Gate
Burnaby, BC V5J 5M4
Canada
Tel: +1 604 436 5900
Fax: +1 604 436 1233
Toll Free: +1 800 667 8743
Alpha Technologies GmbH
Hansastrasse 8
D-91126
Schwabach, Germany
Tel: +49 9122 79889 0
Fax: +49 9122 79889 21
Alphatec Ltd.
339 St. Andrews St.
Suite 101 Andrea Chambers
P.O. Box 56468
3307 Limassol, Cyprus
Tel: +357 25 375 675
Fax: +357 25 359 595
Alpha TEK ooo
Khokhlovskiy Pereulok 16
Stroenie 1, Office 403
Moscow, 109028
Russia
Tel: +7 495 916 1854
Fax: +7 495 916 1349
Alphatec Baltic
S. Konarskio Street 49-201
Vilnius, LT-03123
Lithuania
Tel: +370 5 210 5291
Fax: +370 5 210 5292
Visit us at www.alpha.com
Due to continuing product development, Alpha Technologies reserves the right to change specifications without notice.
Copyright 2014 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies. 745-680-B13-001, Rev. B (09/2014)
advertisement
Related manuals
advertisement
Table of contents
- 2 Safety Information
- 6 AlphaCell XTV Battery Safety Notes
- 6 Electrical Safety
- 6 Chemical Hazards
- 7 Mechanical Safety
- 7 Battery Maintenance Guidelines
- 8 Recycling and Disposal Instructions
- 8 Transportation Information
- 9 Important Storage Practices
- 10 1.0 Introduction
- 10 1.1 Description
- 12 1.2 Operating Conditions
- 12 1.3 Capacity
- 13 1.3.1 Ratings
- 17 2.0 Preparing for Maintenance
- 17 2.1 Required Tools and Equipment
- 17 2.2 Inspection of Cabinet
- 18 2.3 Pad Undermining
- 18 2.4 Inspection of Indicator Lamps
- 18 2.5 Ground Integrity
- 18 2.6 Surge Suppression/SPI Alt Box
- 18 2.7 Inspect All Wiring and Power Supply
- 18 2.8 Remove all Dirt, Dust and Debris from the Cabinet
- 19 3.0 Battery Maintenance Procedure
- 19 3.1 Battery Visual Inspection
- 19 3.2 Power Supply Charger Evaluation
- 20 3.3 Battery Test Evaluation Using Float Voltage
- 20 3.4 Battery Test Evaluation Using Conductance Reading
- 21 3.5 Battery Test Evaluation using Power Supply Self-Test
- 21 3.6 Battery Redeployment Procedure Using 24-hour Open Circuit Voltage Test
- 23 3.3 PM Certification Report
- 25 3.4 Battery Evaluation Procedures for AlphaCellâ„¢ XTV
- 26 4.0 Battery Float Charging
- 27 5.0 Troubleshooting
- 30 6.0 Battery Specifications by Model Number
- 31 7.0 Warranty and Return Information
- 31 7.1 AlphaCell XTV Limited Warranty
- 33 7.2 Battery Maintenance Report for Return Authorizations