Specification Sheet T8 Parallel Program Rapid Start Lamp Operation escent Ballast Project:

Specification Sheet T8 Parallel Program Rapid Start Lamp Operation escent Ballast Project:
EP4/32PPRS/MV/SC/HE
Specification Sheet
Electronic Fluorescent Ballast
7/21/2014
Project:
4 Lamp
Standard Ballast Factor
Multi-volt
High Efficiency
Catalog#:
Approved by:
T8 Parallel Program Rapid Start Lamp Operation
Lamp Type
F32T8*
F32T8/ES/30
F32T8/ES/28
F32T8/ES/25
F25T8
F17T8
F40T8
No. Of
Lamps
Lamp
Watts
Line
Voltage
Ballast
Factor
Input
Watts
Input
Current
(amps)
Power
Factor
THD
Ballast
Efficacy
Factor
4
4
3
3
4
4
3
3
4
4
3
3
4
4
3
3
4
4
3
3
4
4
3
3
3
3
32
32
32
32
30
30
30
30
28
28
28
28
25
25
25
25
25
25
25
25
17
17
17
17
40
40
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
0.86
0.86
0.92
0.93
0.83
0.84
0.88
0.89
0.85
0.86
0.92
0.93
0.89
0.89
0.94
0.94
0.84
0.85
0.90
0.90
0.87
0.89
0.94
0.94
0.88
0.89
114
114
95
95
104
104
86
86
100
100
83
83
93
93
76
76
88
88
74
74
63
63
53
53
111
111
0.95
0.42
0.79
0.35
0.87
0.38
0.72
0.32
0.84
0.37
0.70
0.31
0.77
0.34
0.64
0.28
0.74
0.33
0.62
0.28
0.52
0.24
0.45
0.21
0.93
0.41
0.99
0.98
0.99
0.98
0.99
0.98
0.99
0.98
0.99
0.98
0.99
0.97
0.99
0.98
0.99
0.98
0.99
0.98
0.98
0.97
0.98
0.97
0.98
0.95
0.99
0.98
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<12%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<12%
<10%
<12%
<10%
<15%
<10%
<10%
0.75
0.76
0.97
0.99
0.80
0.80
1.03
1.03
0.85
0.86
1.11
1.12
0.96
0.96
1.23
1.24
0.96
0.97
1.21
1.21
1.39
1.41
1.77
1.78
0.80
0.80
* Primary Lamp Design
Wiring Diagram
Ballast Specifications
Four Lamp Operation
• Ballast shall have a five-year warranty
BLUE/WHITE
BLACK
• Ballast shall be UL certified
BLUE/WHITE
WHITE
RED/WHITE
• Ballast shall be sound rated Class A
RED/WHITE
BALLAST
BLUE
• Ballast shall be Class P Type 1 Outdoor
BLUE
• Ballast shall have a Lamp Current Crest Factor of <1.7
RED
YELLOW
RED
YELLOW
• Ballast shall meet ANSI Standards C62.41 Cat. A
• Ballast shall comply with the limits of FCC Part 18 Class A Non-Consumer
• Ballast shall have a lamp operating frequency greater than 40kHz
LAMP
• Ballast shall have a 0oF minimum lamp starting temperature for primary lamp
LAMP
• Ballast shall be Program Rapid Start
LAMP
• Ballast shall be Parallel Lamp Operation
LAMP
• Ballast shall have minimum Power Factor of 98% for primary Lamp operation
• Ballast shall operate within +/- 10% of the ballast specified line voltage at 60 Hz
Three Lamp Operation
(cap unused red leads)
• Ballast shall have a maximum case hot spot temperature of 75 Celsius
Side Ballast View
Dimensions
Bottom Ballast View
H
W
0.31
M
L
W
L: 9.5”
W: 1.65”
H: 1.18”
M: 8.9”
BLACK
WHITE
BALLAST
YELLOW
YELLOW
LAMP
LAMP
LAMP
• Specifications are subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
BLUE/WHITE
BLUE/WHITE
RED/WHITE
RED/WHITE
BLUE
BLUE
RED