Brultech | Greeneye Monitor | GreenEye Monitor

GreenEye Monitor
Commands
GreenEye Monitor
“Smart Energy Groups”
Setup Guide
For GEM model: All
Document Code: SEG
Ver 3.1
2013-09-25
©Copyright Brultech Research Inc. 2013
GreenEye Monitor
TABLE OF CONTENTS
Introduction .......................................................................................................................... 2
Create a SEG Account ............................................................................................................ 3
Steps.............................................................................................................................................................. 3
GEM Configuration ................................................................................................................ 6
Packet Setup ................................................................................................................................................. 6
Communication Setup ......................................................................................................... 10
Communication Setup (Ethernet Module) ................................................................................................. 10
Communication Setup (WiFi/Ethernet Module) ......................................................................................... 11
Communication Setup (WiFi Module) ........................................................................................................ 12
Communication Setup (Serial) .................................................................................................................... 13
Alternate Option ................................................................................................................................ 14
Final SmartEnergyGroups Configuration .............................................................................. 15
© Brultech Research Inc.
1
www.brultech.com
GreenEye Monitor
INTRODUCTION
Smart Energy Groups (www.smartenergygroups.com ) is a data hosting site compatible with the
GreenEye Monitor. Data may be forwarded to this site over the internet where SEG stores the data and
provides a means of viewing the data using customizable dashboard charts and gauges.
This manual describes the procedure for setting up a GEM system to post data directly to SEG. The three
main tasks required to accomplish this are:
1. Create a SEG account and obtain a “token”
2. Configure the GEM to send data to SEG
3. Connect to the SEG account to discover the GEM and name each channel
Once these three tasks have been performed, you may refer to the information on the SEG site and
create custom dashboards.
Please take note that at the time of this writing, the SEG site is a free service offered by Smart Energy
Groups. Please show them appreciation for their kindness.
© Brultech Research Inc.
2
www.brultech.com
GreenEye Monitor
CREATE A SEG ACCOUNT
STEPS
The first task required to allow the GEM to send data to SmartEnergyGroups.com is to go to their site
using any web browser and create an account.
Steps
1. In any web browser, navigate to “http://www.smartenergygroups.com/”.
2. Click the Join Us link in the top right.
3. Fill in the required fields.
4. Click the come and join us button. After joining an activation link will be sent to your email.
5. Log into your email and click the activation link.
6. Log into your newly created SEG account.
7. Select the My Things menu then click sites. (see Figure 1)
Figure 1
8. Click add a site in the My Sites section (Figure 2)
Figure 2
9. Fill in the information under add a site (Figure 3). The only required field is your site name,
although the address and postal code is helpful in determining the time zone automatically.
10. Click the Save button. A discovery process will begin (see Figure 4)
11. Click the button in the bottom right of the discovery box
© Brultech Research Inc.
3
www.brultech.com
GreenEye Monitor
Figure 3
Figure 4
12. Click the Edit icon in the top right as shown in Figure 5
Figure 5
© Brultech Research Inc.
4
www.brultech.com
GreenEye Monitor
13. The site token will be required during GEM configuration, leave the browser window open as
you’ll need to revisit it after configuring the GEM. Open a new window and go to the GEM
setup page.
Figure 6
.
© Brultech Research Inc.
5
www.brultech.com
GreenEye Monitor
GEM CONFIGURATION
At this point, it’s assumed that you already know how to make a connection to the GEM setup page. If
not, read one of the following setup manuals that is associated with our communication options:



GEM-SET-W (WiFi)
GEM-SET-E (Ethernet)
GEM-SET-WE (WiFi/Ethernet)
PACKET SETUP
1. Open a new browser window and navigate to the GEM’s setup page.
2. Click the Enter Setup Mode button. If password protection is enabled, you will have to input
your password before entering Setup Mode.
3. Click Packet Send from the top menu bar. (Figure 7)
Figure 7
4.
5.
6.
7.
Set the Primary Packet Format to “New SEG Format”. (Figure 7)
Set the Packet Send Interval to a value of 15 seconds or greater.
Set the Real Time Status to “ON”.
Click the Save button.
© Brultech Research Inc.
6
www.brultech.com
GreenEye Monitor
Figure 8
8. Click Data Post from the top menu bar. (see Figure 8)
9. Click the SmartEnergyGroups button. This will auto-populate the URL Address and URL
Extension fields, also it will enable the Node and Token text boxes.
10. Copy the site token that was found previously (Figure 6) in the other browser window. This can
be done by highlighting the text then right clicking the mouse and selecting Copy. Once copied,
delete the present contents of the Token box (Figure 8) and paste the token. Alternately, you
can manually enter the token. Make sure there are no leading or trailing spaces.
11. Enter a Node name of your choosing. The Node defines what the device is called, such as
“MyHouse”, “GEM1”, etc. The node name cannot contain spaces.
12. Click the Save button.
Further down the Packet Send setup page are groups of checkboxes which allows you to select which
channels will be sent to the SEG webhost. See Figure 9. It is preferable not to send unused channels to
avoid wasting memory space, bandwidth and improving performance. If you plan on adding one or more
unused channels in the future, this can easily be included at that time. SEG will discover the additional
channels and add them.
Note that there are two group boxes to select the desired channels. Complete each group one at a
time.
13. Select the channels from the CH1 to CH24 section that you want to send to SEG. (Figure 9)
14. Click Save to complete that section.
15. Select the channels from the CH25 to CH32, temperature and counter channels section that
you want to send to SEG. (Figure 9)
16. Click Save to complete that section.
© Brultech Research Inc.
7
www.brultech.com
GreenEye Monitor
Figure 9
At this point, you can view the packet to confirm everything is entered correctly.
17. Click the Show Packet button. The packet will be revealed and similar to that in Figure 10.
Figure 10
18. Click the Return link.
19. Click the Adv (advanced) menu button.
Figure 11
© Brultech Research Inc.
8
www.brultech.com
GreenEye Monitor
20. Click the Enable radio button for the Reset Wh On Post option
21. Click the Go button.
If the GEM has the “WiFi-only” option then skip the next step and proceed to “Communication Setup
(WiFi Module) Chapter”
22. Click Exit Setup. This step is important! Failure to do so will prevent the GEM from sending
packets for up to 15 minutes which is the time it takes for the GEM to auto-exit the setup
mode.
© Brultech Research Inc.
9
www.brultech.com
GreenEye Monitor
COMMUNICATION SETUP
COMMUNICATION SETUP (ETHERNET MODULE)
Figure 12
Open up the GEM Network Utility (Figure 12) available from www.brultech.com/software
Refer to Figure 12:
1. Select the Ethernet Only tab.
2. Click the Search button. A Device MAC Address should appear in the corresponding box on the
left (Figure 12).
3. Set the Remote Port value to “80”.
4. Click the DNS checkbox.
5. Set the Server(Domain) to “api.smartenergygroups.com“.
6. Set Ethernet Mode to “Mixed Mode”.
7. Set the Comm Setting to “Normal”.
8. Click the Save Settings button.
© Brultech Research Inc.
10
www.brultech.com
GreenEye Monitor
COMMUNICATION SETUP (WIFI/ETHERNET MODULE)
Figure 13
Refer to Figure 13:
1. Log into your WiFI/Ethernet module’s setup page.
2. Click on the Application Setting menu option.
3. Enter the following settings:
 Set the Mode to “Client”.
 Set the Protocol to “TCP”
 Set the Port to “80”
 Set the Server Address to “api.smartenergygroups.com”
 Click the Apply button.
4. Click on the Device Management menu option.
5. Click the Restart button.
The Restart button causes the settings to take effect and re-boots the communication module.
Once the GEM starts sending to SmartEnergyGroups.com, you will no longer be able to access the GEM
setup page unless you set the WiFi/Ethernet module back to Server mode and change the port number
to something other than 80 (Port 8000 is recommended).
© Brultech Research Inc.
11
www.brultech.com
GreenEye Monitor
COMMUNICATION SETUP (WIFI MODULE)
Figure 14
A GEM with the “WiFi Only” option is configured using the GEM Setup section.
Refer to Figure 14:
1.
2.
3.
4.
5.
Click the Network link from the menu.
Set the Remote Host to “api.smartenergygroups.com”.
Set the Remote Port to “80”.
Set the Remote IP to “0.0.0.0”.
Click the Save button and wait for the module to reboot
© Brultech Research Inc.
12
www.brultech.com
GreenEye Monitor
COMMUNICATION SETUP (SERIAL)
You can send to SmartEnergyGroups.com via the RS-232 port (or using an RS-232 to USB cable)if you
have a PC running 24/7.
We have a piece of software called the GEM Bridge available in our software section at
http://www.brultech.com/software which creates a connection between the PC’s Serial Port and a
TCP/IP connection on the network or internet. This allows the GEM to send packets over a network or
internet without the need of the “WiFi” or “Ethernet” option.
Figure 15
The bridge program is displayed in “Figure 15”.
1. Click Find COM Ports in the Serial Bridge section. A box will open listing all found ports.
2. Select the COM port associated with the GEM. The port number will be transferred to the port
box
3. Click Open. The port box should turn to green indicating a successful COM port connection
4. Set the TCP/IP Client to “api.smartenergygroups.com”.
5. Set the Port to “80”.
6. Click the Connect button.
© Brultech Research Inc.
13
www.brultech.com
GreenEye Monitor
The Port box will turn Green, and then Red after a packet is sent as the web server will disconnect from
the program after receiving the packet. The program will then reconnect until the next packet is sent.
Alternate Option
Another option is to use a 3rd party script like BTMon.py using a binary packet format. Visit
http://lancet.mit.edu/mwall/projects/power for more information on that script.
© Brultech Research Inc.
14
www.brultech.com
GreenEye Monitor
FINAL SMARTENERGYGROUPS CONFIGURATION
Now that you have the GEM configured, go back to the SmartEnergyGroups.com window.
1. Click the Discover button. Once you start the discovery process, wait for more than one minute
after the device is found before doing the next step
Figure 16
2. Click the finish the discovery button (Figure 16). This will cause your device to be initially setup.
(Figure 17)
Figure 17
© Brultech Research Inc.
15
www.brultech.com
GreenEye Monitor
3. Assign a name corresponding to each channel. For example “Main house panel” or
“Refrigerator”, etc. You should consult your “Channel Assignment” sheet which would have
been used during the GEM installation.
4. Select the desired options then click the Save button.
Refer to information provided on the SEG site to create custom Dashboards and take advantage of the
many options available.
© Brultech Research Inc.
16
www.brultech.com
GreenEye Monitor
TECHNICAL
PACKET INFORMATION
Power Information
For each of the 32 selected channels, the GEM sends Power (Watt) and Energy (Watt-Hour). Each packet
includes the “watt” value however the “watt-hour” value is included in the packet only once per minute.
This method improves accuracy and provides a high resolution load profile.
Watt
The watt value included in the packet is that of the most recent sample and not an average.
Watt-Hour
The watt-hour value included in the packet reflects the number of watt-hours used since the previous
packet send. This provides an accurate representation on energy consumption.
Voltage
The voltage value is included in every packet.
Temperature
The temperature value in the packet is that of the last sample.
Pulse Counter
The pulse count is an incremental value
© Brultech Research Inc.
17
www.brultech.com