Catalogue Sheet: ESLT Series

Catalogue Sheet: ESLT Series
Project/Location:
Contractor:
ESLT Series
Date:
Prepared by:
6, 12, 24V T-Bar Unit
TYPICAL SPECIFICATIONS
Fully recessed units for T-Bar mounting
in suspended ceilings.
Supply and install a complete emergency lighting system as
described herein and shown on the drawings.
The Emergi-Lite® Smart Diagnostic Micro controller board shall
supply the rated load for a minimum of a 30 minutes to 87.5% of the
rated battery voltage. The unit shall be rated 120V or 347V, 60 Hz and
be CSA listed. The unit shall have an output of
V.
The charger shall be fully computer tested and its charge voltage
factory set to ± 1% tolerance. Chargers with field-adjusted
potentiometers are not acceptable. A pulse-type charger shall be
employed to promote long battery life and reduce the potential for
grid corrosion. The charger shall provide a continuous high charge
to recharge the battery and when the battery is at full capacity, the
charger will shut off. Periodically the charger shall provide a pulse of
energy to keep the battery topped off. The charger shall be current
limited, temperature compensated, short-circuit proof and reverse
polarity protected. The unit shall be furnished with an electronic
lockout circuit, which will connect the battery when the AC circuit
is activated, and an electronic brownout circuit, which will activate
the emergency lights when utility power dips below 75% of nominal
voltage. A low voltage battery protection circuit shall be provided
and will disconnect the battery from the fused output circuit at
the end of discharge. The unit shall self-test for 1 minute every 30
days, 10 minutes every 6 months and 30 minutes every 12 months.
The unit shall be capable of full recharge in compliance with a CSA
specifications. The unit shall be furnished with a sealed dust tight
relay, a test switch and seven diagnostic LED indicator lights to
continuously monitor the status of the unit: Battery Failure, Battery
Disconnected, Charger Failure, Lamp Failure, Service Alarm, AC
“ON”, Charger High Rate. The unit shall be T-bar mounted and come
complete with tool-less emergency lighting heads requiring no tools
to adjust or aim.
The unit shall be Emergi-Lite® model:
.
The ESLT Series battery units are designed for T-bar ceiling
grid installation. This slim-line, unobtrusive unit is ideally suited
for any commercial location where there is limited wall space
and where the greater directional flexibility of ceiling-mounted
heads is needed to provide greater light distribution.
FEATURES
• Rugged steel cabinet with corrosion-resistant undercoating.
• Battery and charger are concealed above the ceiling level
in the unit cabinet
• Removable panel provides easy access to battery and
circuitry
• Test switch and LED indicators are mounted on the visible
bottom panel
• Units mount quickly and easily in standard 2’ x 2’ or 2’ x 4’
grids without any additional hardware
• Solid-state pulse-type charger – current-limited,
temperature-compensated, short-circuit proof and
reverse-polarity protected
• Unit comes standard with electronic lockout and brownout
circuits
• Sealed dust-proof transfer relay, test switch and LED
indicator lights
• Long-life, maintenance-free lead acid battery
• NEXUS® compatible (for more information on NEXUS®,
please consult your sales representative)
REPLACEMENT LAMPS
•C
SA C22.2 No. 141 certified
CABINET
DIMENSIONS
A
B
C
D
E
F
Large
Cabinet
23 3/4”
7 1/4”
7 1/8”
10 5/8”
5 5/8”
13”
(60.3 cm) (18.4 cm) (18.1 cm) (27.0 cm) (14.3cm) (33.0 cm)
Small
Cabinet
7 1/4”
4 5/8”
10 5/8”
23 3/4”
(60.3 cm) (18.4 cm) (11.7 cm) (27.0 cm)
3 1/4”
(8.3 cm)
13”
(33.0 cm)
DIMENSIONS
ORDERING CODE
LAMP TYPE
VOLTAGE/WATTAGE
570.0016-E
Mini tungsten
6V-9W
570.0025-E
Mini tungsten
12V-9W
570.0045-E
Mini tungsten
24V-9W
580.0104-E
MR16, LED
12V-5W
580.0093-E
MR16, LED
12V-4W
580.0097-E
MR16, LED
6V-4W
580.0098-E
MR16, LED
24V-4W
580.0100-E
MR16, LED
24V-6W
580.0106-E
MR16, LED
12V-6W
For the complete list, please see the lamp chart on pages 156 to 158
Dimensions are approximate and subject to change.
e
a
b
d
f
c
108
Project/Location:
Contractor:
ESLT Series
Date:
Prepared by:
6, 12, 24V T-Bar Unit
POWER CONSUMPTION AND UNIT RATING
MODEL
WATTAGE CAPACITY
AC SPECS
1H30
2H00
06ESLT36
0.10/0.04 A
36
21
15
12
6
06ESLT72
0.22/0.08 A
72
42
30
24
12
06ESLT108
0.22/0.08 A
108
63
45
36
18
06ESLT180
0.22/0.08 A
180
105
75
60
30
12ESLT36
0.09/0.03 A
36
21
15
12
6
0.15/0.06 A
72
42
30
24
12
12ESLT100
0.34/0.12 A
100
58
42
33
17
12ESLT144
0.40/0.14 A
144
84
60
48
24
12ESLT216
0.41/0.14 A
200
117
83
67
33
24ESLT144
0.55/0.20 A
144
84
60
48
24
24ESLT288
0.67/0.23 A
288
168
120
96
48
12ESLT72
120/347VAC
30MIN
1H00
4H00
ORDERING INFORMATION
SERIES CAPACITY
COLOUR
06ESLT= 36= 36W
6V
72= 72W
108= 108W
180= 180W
Blank= f actory
white
lack
BK= b
12ESLT= 36= 36W
12V
72= 72W
100= 100W
144= 144W
216= 216W
24ESLT= 144= 144W
24V
288= 288W
VOLTAGE
OPTIONS
U= auto-diagnostics*
Blank=
uto-diagnostics, non120/347VAC input UN= a
audible*
-2= 277VAC input
NEX= NEXUS® system
interface*
NEXRF= wireless NEXUS®
system interface*
A= ammeter
V= voltmeter
CT= cab-tire
D= time delay
FB6= 6 cct. fuse panel
LW= twist-lock plug***
P= light activated test switch
T= lamp disconnect
(programmable)
TB= DC terminal block
TBAC= AC terminal block
TBACDC= AC/DC terminal
block
X2= remote test receiver**
* Minimum lamp load required: 20%
of unit capacity
# OF HEADS
/0= no heads
/1= one head
/2= two heads
/3= three
heads
HEAD STYLE LAMP WATTAGE
Blank= large tungsten, 6V, 12V, 24V-9W, wedge
base
LA= MR16 LED, 6V-4W
LG= MR16 LED, 12V-4W
LI= MR16 LED, 12V-5W
LJ= MR16 LED, 12V-6W
LL= MR16 LED, 24V-4W
LM= MR16 LED, 24V-6W
150LA= deco head, MR16 LED, 6V-4W*
150LG= deco head, MR16 LED, 12V-4W*
150LI= deco head, MR16 LED, 12V-5W*
150LJ= deco head, MR16 LED, 12V-6W*
150LL= deco head, MR16 LED, 24V-4W*
MI= MR16 halogen, 6V-6W
MJ= MR16 halogen, 6V-10W
MK= MR16 halogen, 12V-12W
MA= MR16 halogen, 12V-20W
MS= MR16 halogen, 24V-12W
150MG= deco head, MR16 halogen, 12V-20W*
150MB= deco head, MR16 halogen, 12V-35W*
150MC= deco head, MR16 halogen, 12V-50W*
150MS= deco head, MR16 halogen, 24V-12W*
150MD= deco head, MR16 halogen, 24V-20W*
150ME= deco head, MR16 halogen, 24V-35W*
150MF= deco head, MR16 halogen, 24V-50W*
­-18= large tungsten, 12V, 24V-18W, wedge base
­-25= large tungsten, 6V, 12V, 24V-25W, DCB
M= mini tungsten, 6V, 12V, 24V-9W, wedge base
M18= mini tungsten, 12V, 24V-18W, wedge base
MQ= mini halogen, 6V, 12V-8W, bi-pin
MQ12= mini halogen, 6V, 12V, 24V-12W, bi-pin
Q8= large halogen, 6V, 12V- 8W, bi-pin
Q12= large halogen, 6V, 12V-12W, bi-pin
Q20= large halogen, 6V, 12V, 24V-20W, bi-pin
Q55= large halogen, 12V-55W, H3
Q70= large halogen, 24V-70W, H3
S= large tungsten, 6V, 12V-8W, sealed beam
S18= large tungsten, 6V, 12V-18W, sealed beam
S25= large tungsten, 6V, 12V-25W, sealed beam
H= large halogen, 6V, 12V-8W, sealed beam
H12= large halogen, 6V, 12V-12W, sealed beam
H20= large halogen, 6V-20W, sealed beam
*N
ot all options available with the
NEXUS® system. Please consult
your sales representative.
** TX2= remote test transmitter
(sold seperately)
*Polar white or black cabinets only.
*** 120V is standard
EXAMPLE: 06ESLT108U/2MQ