INSTALLATION GUIDE
CURRENT MONITORING
TM
H535NS
TM
535NS
Enclosed Relay
Installer’s Specifications
Sensor Power
Induced from the monitored conductor
Amperage Range
0.25 to 15 A
Frequency Range
50-60 Hz
Operating Temperature Range
-15° to 50°C (5° to 122°F)
Operating Humidity Range
10-90%, noncondensing
Wire to Relay Contacts
Use 12 AWG (3.3 mm2) wire or larger*
Relay Switching Capacity at 120 VAC
1 HP
Relay Switching Capacity at 277 VAC
1.5 HP
Relay Output
SPDT, 15 Amps
Relay Coil
24 VAC/DC; 36 mA nom.
Terminal Block Torque
Relay control terminals: 3.5 in-lb (0.4 N-m)
All other terminals: 12 in-lb (1.35 N-m)
Agency Approvals
UL508, Installation Category III
DANGER
* For current loads up to 10 A, use 75°C rated wire insulation. For loads greater than 10 A, use
90°C rated wire insulation.
The product design provides for basic insulation only.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
•
•
•
•
quick install
1. Disconnect power sources prior to installation.
2. Remove the sensor lid. Wire the command relay connections and relay controls to
the base.
3. This device has four wiring options, detailed on page 2-3 of this installation guide.
Choose the option appropriate to the application and follow instructions.
operation
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
The H535NS is an enclosed switching relay that is connected in series between the
power source and the motor device. It operates at amperage loads up to a maximum
of 15A, and the relay controls the on/off functioning of the motor. The H535NS
requires no additional power source for operation.
dimensions
CL
Wire
Opening
1.16"
(30 mm)
4.25"
(108 mm)
Wire
Opening
Wire
Opening
CL
CL
2.13"
(55 mm)
1.16"
(30 mm)
4.25"
(108 mm)
Z202807-0D
PAGE 1
1.53"
(39 mm)
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
H535NS
TM
Wiring board
4. Select one of the following mounting configurations (a, b, c, or d) to match your
installation.
1
1. Line current terminals:
Common
Normally Open
Normally Closed
2. 24 VAC/DC Relay
2
a.) duplex box:
Mounting slot
Connect line voltage wires
to line current terminals
Line Voltage
Wires
installation
Mounting hole
Prior to installation, disconnect and lock out all power sources.
1. Open the device. Set aside the lid and the bag of hardware enclosed.
Wire the 12 AWG lines from the controller through the back of the device, to
the line current terminals. Tighten line current terminal blocks to 12 in-lb
(1.35 N-m) torque.
Use the base as a template for mounting to the wall using the mounting hole
and slot shown.
b.) 4S junction box:
Mounting hole
INC.
VERIS INDUSTRIES,
OREGON USA
PORTLAND,
TOLL FREE USA 1.800.354.8556
TEL USA 1.503.598.4564
FAX USA 1.503.598.4664
RS
OC
SO
SP
SC
540NS
!
CAUTION: Consult instructions
prior to installation
Line Voltage
Wires
STATUS OUTPUT: [email protected]/DC
RELAY COIL: 24VAC/DC; 16mA nom.
RELAY OUTPUT: 16(8)[email protected]; 3/4 HP
2. Wire the 24 AC/DC relay control through the top hole of the device. Use only copper
conductors for command relay inputs. Tighten terminal blocks to 3.5 in-lb (0.4
N-m) torque. See Specifications for wire insulation requirements.
Status Output & Relay Coil
(Low Voltage Wires Only)
Connect line voltage wires
to line current terminals
Mounting hole
Wire the 12 AWG lines from the controller through the back of the device, to
the line current terminals. Tighten line current terminal blocks to 12 in-lb
(1.35 N-m) torque.
Use the base as a template for mounting to the wall using the mounting holes
shown.
24VAC/DC Relay Control
3. Wire the line current from the controller to the Common terminal. Wire the second
line to either the N. O. terminal or the N. C. terminal. The device is shown here as
wired to the N.O. block. Tighten line current terminal blocks to 12 in-lb (1.35 N-m)
torque.
Common
N.O. block
N.C. block
Z202807-0D
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
H535NS
TM
wiring example
c.) surface mounting:
Connect line voltage wires
to line current terminals
C
N.C.
N.O.
Line Voltage
Wires
Wire the 12 AWG lines from the controller through the side of the device, onto
the line current terminals. Tighten line current terminal blocks to 12 in-lb
(1.35 N-m) torque.
d.) nipple mount to another enclosure:
1. Relay Contacts: Wire the H535NS in series with the motor using these terminals.
Choose from N.O. or N.C.
2. Relay: Enables actuation of the circuit by a control system
Insert the conduit nuts (provided) into the slots in the side hole of the device
for additional weight support.
3. Relay Coil Terminal Blocks: Wire the output signal from the control panel to
actuate the relay. 24 VAC/DC; 36 mA nominal
4. Relay Status LED: For positive indication of energized coil.
CAUTION!
Connect line voltage wires
to line current terminals
ENCLOSURE
Line voltage wires
Nipple to existing enclosure
(conduit nipple fitting not
provided)
Do not rely on status indicators to determine whether or not the relay contacts are
connected to a power source. Doing so may result in injury or death from electrical
shock.
If the connections to the unit are made through more than one metallic conduit, bond
the conduits to prevent the hazard of electric shock. A bonding plate is available (Veris
part AH10).
Wire the 12 AWG lines from the controller through the side of the device,
from the enclosure to the line current terminals. Tighten line current terminal
blocks to 12 in-lb (1.35 N-m) torque.
5. Use the knockout seal to cover any unused holes in the housing. Attach the cover,
securing with the screws provided.
NOTE: If a conduit is used, connect the conduit to the mounting hub before connecting it to the
device. Be sure to support the H535NS housing when nipple-mounted to another enclosure, or the
unit may shift on opening, potentially causing undue stress on the wiring and the terminals.
Z202807-0D
PAGE 3
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]s.com