250 0399

250 0399
VFDS4X05-D230-PCM
Variable Frequency Drives
for 3-phase & single phase AC motors
Q U I C K
S T A R T
G U I D E
D I M E N S I O N S
6.980 [177]
C501
JMP504
1 2 3
TB501
4mA
ZERO
SET
JMP505
MIN
IC501
T501
MAX
IL501 JMP503
UV TRIP
RESTART
C502
IL504
ACCEL
ENABLE
BRAKE
IL501
IL502
COAST
POWER FAULT
JMP506
1-Phase Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .*115/230 VAC
1 or 3 -Phase Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .230 VAC
Maximum Horsepower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.5 HP
Maximum Continuous Output Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . † 5.0 AC
AC Amps In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 / 10 amps
AC Voltage Input Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115/230 VAC ± 10%
50/60 Hz single phase
Standard Carrier Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 KHz
Adjustable Braking Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 - 5 ADC
Adjustable Braking Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 - 10 Sec.
Adjustable Minimum Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 - 30 Hz
Output Frequency Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0 - 120 Hz
Adjustable Maximum Output Frequency Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 - 120 Hz
Acceleration Time Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 - 12 secs
Deceleration Time Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 - 12 secs
Analog Input Voltage Range
(S1 [-] to S2 [+]) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 - 5 VDC, 0 - 10 VDC, 4 - 20 mA
Input Impedance, S1 to S2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .~ 100K ohms
Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.5G max (20 - 50 Hz)
0.1G max (> 50 Hz)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 lbs
Ambient Operating Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10° - 40° C
0.188 [5]
* Jumper settings MUST match input line voltage. Application of 230 VAC line input when jumpers are set for 115 VAC will
result in severe damage to the drive.
DECEL
SLIP
COMP
J501
Q14
S P E C I F I C A T I O N S
† Derate current by 2% per degree if the operating temperature is above 40° C. Under no circumstances may the ambient
temperature exceed 55° C.
C501
BOOST
IL503
W I R I N G
Q13
R88
TORQUE
LIMIT
R89
INSTALL JUMPER
FOR 115VAC
D20
D21
R75
C503
D19
C502
C508
8.450 [214]
JMP504
INPUT SELECT
1-2 = VDC
2-3 = mA
R84
JMP505
RANGE SELECT
1 = 0 - 5 VDC
2 = 0 - 10 VDC
3 = 4 - 20 mA
FU5
SCR501
C38
C28
JMP502
R80
BRAKE
CURRENT
FU502
C504
D18
SCR502
BRAKE
TIME
230 VAC
R76
BR501
C35
9.750 [247]
C34
Q11
115 VAC
JMP501
L1
L2
U
V
TB502
W
230 VAC
1.450 [36]
115 VAC
JMP502
L1
L2
U
V
W
TB502
1
2
ALL DIMENSIONS IN INCHES [MILLIMETERS]
Maximum Height (C1 & C2): 3.30 [84]
WARNING
Ꮨ
Do not connect 230 VAC
line input when the drive is
set for 115 VAC input. This
will result in severe
damage to the motor and
drive, and can lead to
explosion and/or injury.
1
3-Phase
MOTOR
2
L1 L2
115/230 VAC
C O N N E C T I O N S
STEP #1
Skip this step if provided FWD/OFF/REV switch and speed potentiometer will be used.
Otherwise disconnect factory-wired connections from the FWD/OFF/REV switch and speed
potentiometer. Connect the enable/disable switch, direction switch, and speed
potentiometer or signal input to TB501 on the TOP board using 20 - 24 AWG wire as shown
below.
STEP #4
Configure jumpers JMP501 and JMP502 on the bottom board for 115 or 230 VAC Power
Input. A jumper must be installed on JMP501 for 115 VAC input. No jumper is necessary
on JMP501 for 230 VAC input.
STEP #5
Connect motor leads of a 3-phase motor to U, V, and W (TB502 on BOTTOM board) using 14 - 16
AWG wire as shown in the figure below.
STEP #6
Connect 115 or 230 VAC power input using 12 AWG wire. Include a start/stop switch as shown in the
figure below.
STEP #2
Configure jumpers JMP504 and JMP505 on the top board for the appropriate signal input.
1
2
3
JMP504
1
2
JMP504 (on top board)
Pins 1 & 2 for Voltage Input, or using a speed pot.
Pins 2 & 3 for Current Input
3
JMP505 (on top board)
1 for 0 - 5 VDC Voltage Input, or using a speed pot
2 for 0 - 10 VDC Voltage Input
3 for 4 - 20 mA Current Input
JMP505
STEP #3
Configure jumpers JMP503 on the bottom board and JMP506 on the top board.
JMP503
1
2
3
JMP503 (on bottom board)
Pins 1 & 2 to Trip
Pins 2 & 3 to Restart
UV TRIP
RESTART
TRIP: Drive has a low voltage fault & must
be manually re-enabled to restart.
RESTART: Drive has a low voltage fault &
will momentarily stop then auto-restart
when input voltage returns to minimum level.
1
2
3
BRAKE
COAST
JMP506
JMP506 (on top board)
Pins 1 & 2 to Brake
Pins 2 & 3 to Coast
NOTE
This connection may be
internal to the motor (2 wire
leads). If not, you must
make the connection yourself.
WARNING!
DO NOT use a
direction switch
with
this set-up!
AUXILLARY
WINDING
WITHOUT
CAP
MOTOR
WINDING
MOTOR
WINDING
M I N A R I K D R I V E S
w w w . m i n a r i k d r i v e s . c o m
14300 De La Tour Drive, South Beloit, IL 61080;
Phone: (800) MINARIK (646-2745); Fax: (815) 624-6960
Document Number: 250-0399, Revision 0; Printed in the U.S.A. - June 2005
Copyright 2005 by Minarik Corporation - All rights reserved. No part of this document may be reproduced or transmitted in any form without written permission from
Minarik Corporation. The information and technical data in this document are subject to change without notice. Minarik Corporation and its Divisions make no
warranty of any kind with respect to this material, including, but not limited to, the implied warranties of its merchantability and fitness for a given purpose. Minarik
Corproation and its Divisions assume no responsibility for any errors that may appear in this document and make no commitment to update or to keep current the
information in this document. mvd092503