KZMb
--------------------------------------------------------
INSTALLATION – WIRING
Figure 1. Maximum operationg temperature.
Figure 4. Installation with CLA size 500 demand one meter
duct between CLA and KZM.
Figure 5. KZM may only be installed with the pressure sensor
in vertical position.
Figure 2.
Figure 3. Installation with sound attenuator without inner
baffles.
Figure 6. Rectanglular KZM are only alowed for damper blade axel in horizontal position.
Table 1.
Size L L1
160 472 1470
200 472 1470
250 472 1470
315 472 1470
400 552 1550
500 649 see fig.
Registered design. The company reserves the right to make design changes without prior notice.
www.swegon.com - 24 October, 2006
1
KZMb
----------------------------------------------------------------
INSTALLATION
Figure 7. KZM for control of mixing box.
Figure 8. Min. straight duct after sound attenuator with beffles. A = 3 x Thickness of the baffle.
Figure 9. Installation area requirements.
2 www.swegon.com - 24 October, 2006
WIRING
Power supply 24 V AC (±10%). max 6 A fuse, wire area 1.5
mm
2
.
Wire for KSP min. 0,75 mm
2
and max. 0.75 m length to KZM.
Wire between 0 and M (dot dashed) is not necessary if the products are connected to the same transformer.
The usw eith mixing box BLB is only valid then set up for erimix system.
Figure 10.
Figure 11. Wiring graph.
Key to figures 10 and 11
1.
KZM
2.
Pressure sensor KSP
3.
Controllerr KCP
4.
Connection for Hand terminal KOP
5.
Actuator ASM115SF901
6.
7.
8.
Flow sensor
Pressure sensor
Mixing boxx BLB
9.
Actuator for mixing box BLB, NMA
10.
Temperature prob www.swegon.com - 24 October, 2006