Bettis Q Integrated Control Modules QC41, QC42, QC43

Bettis Q Integrated Control Modules QC41, QC42, QC43
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 1 of 11
Date:
April 2015
Q-Series
Integrated Control modules
QC41, QC42 and QC43
Features:
- Basic actuator functions for:
- Spring return applications, or
- Double acting applications or,
- Double acting Fail in Last Position applications.
APPROVED
- Suitable for all Bettis Q-Series actuator sizes.
- Available as "Weather Proof" for indoors or outdoors
use and "Explosion Proof" for areas with a potential
explosion hazard.
- The robust aluminum alloy enclosure (IP66 /
NEMA4X rated), protects the IPT system, pneumatic
components, the feedback switches and terminals and
makes it suitable for indoor and outdoor use.
- The Explosion Proof version is available with ATEX /
IECEx Ex d approval for use in Zone 1, 2, 21 and 22
and/or FM / CSA Explosion proof approval for use in
Class I, Division 1.
- Various feedback switch options available.
- Non-Intrusive switch point adjustment of the feedback
switches. Allows to adjust switch points without
opening the Control Module.
- Lockable Control Module cover.
- All the control and feedback connections can be wired
through one single entry to the Control Module.
- One larger entry (3/4"NPT) is available for larger multicore cables on imperial units.
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 2 of 11
Date:
April 2015
Description:
Q-Series
Electrical safety requirements:
These Bettis Q-Series conventionally wired control modules
are the next step for the integrated concept of valve
automation.
Next to the components for feedback switches, also all
the pneumatic control components are located inside one
module housing.
Its compact and robust construction incorporates basic
control and feedback functionality and is suitable for indoor
and outdoor use.
These modules are available with ATEX and IECEx
certification for use in Zone 1, 2, 21 and 22, and additionally
FM and CSA certified for use in Class I, Division 1.
Use
Altitude
: In- and outdoor.
: Operating full power available up to 2000 meter (6000 feet).
Maximum relative
: 80% for temperatures up to 31°C
humidity (87.8°F) decreasing linearly to 50% relative humidity at 40°C (104°F).
Mains supply
: Up to ±10% of nominal voltage
fluctuation
Over voltage category : II
Pollution degree
: 2
(3 when the cover remains closed)
Construction:
The Control Module is mounted at the side of the basic
actuator housing. Inside, wiring terminals are available for
connecting control and feedback signals. Two cable entries
are available.
The pilot valves inside the control module are used to send
the actuator to its open or closed position. One pneumatic
connection is available to feed the control module.
General specifications:
Material housing:
Operating media:
Pneumatic entry:
Electrical connections:
Cable entries:
Enclosure:
Switch points:
- Adjustable range:
Finish:
Temperature range:
Dimensions:
Aluminium alloy
Air or inert gasses, filtered at 50µm
Metric units: G1/4"
Imperial units:1/4”NPT
Pilot valve(s): 6 pole terminal strip.
Switches:
6 pole terminal strip.
Metric units: 2x M20x1.5
Imperial units:1/2” and 3/4"NPT
Rated IP66 - NEMA4X
Factory set at 15° before each end
of travel (open and closed position).
Between -3° to 15° and +75° to
+93° of the end position.
Chromated, polyurethane based
coating.
Depends on the switches inside
the module and or Hazardous Area
approvals (See section "Position
feedback"
Metric:1.603.08
Imperial/UNC:1.603.09
DIN 3337:
1.603.10
Terminal
compartment
Control Module
Type Label
Option: 1 or 2
speed control
throttles
Lockable
Module cover
Pneumatic connections:
1/4”BSP or 1/4”NPT
Electrical entries:
3/4”NPT
or M20
Option: Additional Local
Manual Control for “Fail in
Last Position”
Option: Local Manual
Control
1/2”NPT
or M20
Switch
terminals
Pilot valve
terminals
Control module overview
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Non-Intrusive switch
point adjustment
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 3 of 11
Date:
April 2015
Q-Series
Pneumatic control
Pneumatic control variations
The Control Module contains all the necessary pneumatic
components to control the actuator and control the
incoming and outgoing airflow. Pneumatically the modules
are available for three applications:
1 Spring return or
2 Double acting or
3 Double Acting - "Fail-in-Last-Position".
To achieve these functions, each Control Module can be
fitted with one or two pilot valves depending on the required
functionality:
Pilot valve 1
Cable range:
0.2 - 2.5mm2 or
30-12AWG
One default pilot valve and wiring connections
1 One pilot valve is default and suitable for normal
operation of double acting or spring return actuators
2 Two pilot valves are required to achieve a "Fail-in-LastPosition" functionality on double acting actuators.
Pilot valve 1
Table 1: Pilot valve specifications
Module
Voltages
Power
QC41
24VDC (±10%)
1W
Frequency
NA
QC42
115 VAC (±10%)
3VA
50/60Hz
QC43
230 VAC (±10%)
3VA
50/60Hz
Pilot valve 2
Cable range:
0.2 - 2.5mm2 or
30-12AWG
FILP = Fail in Last Position
Wiring diagram shown, is applicable for actuators with assembly code “CW”.
For actuators with assembly code “CC” (reverse acting) the “Open” and
“Closed” pilot valve connections are also reversed.
Pneumatic cartridge
Pilot valve cartridge
Pilot valve
terminals
Two pilot valves and wiring connections for Fail in Last
Position
Pilot valve and pneumatic cartridge
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 4 of 11
Date:
April 2015
Pneumatic components
The pneumatic components inside the module consist
out of one or two pilot valves and a 3/2 spool valve or 5/2
bistable spool valve. The spool valves are pneumatically
operated by the pilot valves.
To assure trouble-free operation, the spool valves are
equipped with big ports. This enables a large air flow and
makes it less sensitive for contamination of the internals.
The large air flow also fast cycle times and enables it to be
utilized for the entire Bettis Q-Series actuator range.
Internal corrosion protection:
The spring return models have standard a built in “Breather”
function. During the spring stroke, the exhaust air from the
center chamber (A-Port) is first fed to the spring chamber
(B-port) preventing air from outside from being sucked into
the spring chamber. This reduces the possibility of internal
corrosion and maximizes the actuators’ working life.
Pneumatic options
Q-Series
Fail safe
(spring return)
A-port
B-port
Option: Throttle 1
3/2 Spool valve
Option: LMC
Ps
Ra
Pilot valve 1
Double acting
Speed Control
The Bettis Q-Series can be supplied with a Speed Control
option. One throttle is required for Spring Return actuators
and up to two for Double Acting actuators.
The speed control throttle controls the air flow in and out
of an air chamber and as such limits the speed of the
“Opening” and “Closing” stroke simultaneously.
Silencers and vents
A-port
B-port
Option:
Throttle 1
Option:
Throttle 2
5/2 Spool valve
Option: LMC
Rb
Ps
Ra
The exhaust ports Ra and Rb on the module are shipped
from the factory with transport protection.
The module can be equipped with either silencers or vents.
Pilot valve 1
Manual Control
For commissioning, emergency or maintenance purposes,
the Bettis Q-Series can be supplied with Manual Control
options. These options can operate the actuator when there
is air pressure available, but no control signal or power
supply.
- For normal operation the module should be fitted with
one Manual Control.
- For Double Acting with a Fail-in-Last-Position function,
two Manual Control can be fitted.
Double Acting
Fail in Last
Position
A-port
Option:
Throttle 1
Option:
Throttle 2
5/2 Spool valve
Maximum Flow rates of Q-Series modules
The maximum flow rates depends mainly on the flow rates
of the Bettis Q-Series modules. You can use Kv 0.33 (m3/h)
or Cv value of 0.28 (US gall/min 1Psi) for approximate
operating speed calculations.
B-port
Option: LMC 1
Option: LMC 2
Ps
Rb
Ra
Pilot valve 1
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Pilot valve 2
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 5 of 11
Date:
April 2015
Q-Series
Position feedback
Non-Intrusive switch point adjustment
The position feedback is achieved by switch cartridges in
the module. These cartridges contain switching elements
which sense the open or closed position and are pre
wired to the terminal strip. These easily exchangeable
switch cartridges are available with various mechanical or
proximity switching elements.
If required the switches can be adjusted without opening the
module. This, so called, Non-Intrusive switch adjustment is
located at the front of the module behind a locable (1) shield
(2). Two adjustment screws are available for adjusting the
Closed (3) and Open (4) position indication.
N WHEN E
NING N
PE
O WAR
!-
G
ER
IZED
DO NO
T
Switch cartridges
Terminal strip position
feedback switches
3
4
1
2
Switch cartridge
Switch cartridges
"Closed"
Switch point adjustment
"Open"
Switch point adjustment
Non-Intrusive switch point adjustment
Important:
- The above "Closed" and "Open" marked adjustment
screws will adjust the valve's "Closed" or "Open" switch
point, if the valve closes after a Clock Wise (CW) rotation.
- If the valve closes after a Counter Clock Wise (CCW)
rotation, the "Closed" marked adjustment screw will adjust
the "Open" switch point. Similar, the "Open" marked
adjustment screw will adjust the "Closed" switch point.
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 6 of 11
Date:
April 2015
Q-Series
Mechanical switches
2-Wire Proximity switches
Specification
Description
Specification
Description
Option code
M
Option code
N
Option code
G (gold contacts)
Type
2-wire inductive, normally closed
Type
Mechanical
Voltage
8 VDC nominal
Voltage
M: 277 VAC or 250VDC (maximum)
Output
Unswitched , > 3 mA
Temperature range
Switched , < 1 mA
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
DIN EN 60947-5-6 (NAMUR)
Table 2: Mechanical switches
Table 4: 2-wire NAMUR proximity switches
G: 125 VAC or 30VDC (maximum)
Contacts
Temperature range
NO and NC
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
Table 3: Maximum currents
Switch voltage
M type switch
G type switch
125 VAC
10 A (3 A1)
0.1 A 2
250 VAC
10 A (3 A1)
-
30 VDC
0.5 A
0.1 A 2
125 VDC
0.5 A
-
250 VDC
0.25 A
-
Note:
1. The mechanical (M-type) switches are rated for 3 A with
inductive load.
2 The mechanical (G-type) switches have gold contacts.
For applications where the benefits of gold contacts are
required, the maximum current is 1 A.
3. For applications below -20°C (-4°F), the base actuator
must be equipped with Low temperature seals.
Compliant to
Table 5: 2-Wire 230V proximity switches
Specification
Description
Option code
H
20...250VAC / 10...300VDC
(50...60 Hz AC)
Maximum
100 mA
Voltage
Current
Peak
Leakage
Temperature range
Note:
1 For applications below -20°C (-4°F), the base actuator
must be equipped with Low temperature seals.
Wiring diagram:
Wiring diagram:
- 2-Wire NAMUR proximity switches
- 2-Wire 115V proximity switches
- M = Mechanical
- G = Mechanical, gold contacts
1 L- 2
Open
0,9A (20ms / 0,5Hz),
< 1.7 mA
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
Close
Cable range : 0.2 - 2.5mm2 or 30-12AWG
Wiring diagram is shown in the actuators mid-stroke position.
Wiring diagram for mechanical switches
L+ 3
4 L- 5
2
2
1
1
Open
L+ 6
Close
Cable range : 0.2 - 2.5mm or 30-12AWG
2
Wiring diagram for 2-Wire proximity switches
Important:
- The above "Closed" and "Open" marked adjustment terminals will indicate the valve's "Closed" or "Open" switch
point, if the valve closes after a Clock Wise (CW) rotation.
- If the valve closes after a Counter Clock Wise (CCW) rotation, the "Closed" marked adjustment terminals will indicate
the "Open" switch point. Similar, the "Open" marked adjustment terminals will indicate the "Closed" switch point.
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 7 of 11
Date:
April 2015
Q-Series
3-Wire Proximity switches
Table 4: 3-wire proximity switches
Specification
Description
Option code
O, V3 PNP
Option code
C, V3 NPN
Function
Make
Voltage
10 - 30V
Current
100 mA maximum
Off-state current
0 ... 0.5 mA typical
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
Temperature range
Note:
1 For applications below -20°C (-4°F), the base actuator
must be equipped with Low temperature seals.
Wiring diagram:
3-Wire proximity "O" type switches PNP
L-
2
1
L+
3
L-
5
4
3
4
1
L+
6
L+
6
3
4
1
PNP
Open
Close
Wiring diagram:
3-Wire proximity "C" type switches NPN
L-
2
1
L+
3
3
4
1
L-
5
4
3
4
1
NPN
Open
Close
Cable range : 0.2 - 2.5mm2 or 30-12AWG
Wiring diagram for 3-Wire proximity switches
Important:
- The above "Closed" and "Open" marked adjustment terminals will indicate the valve's "Closed" or "Open" switch
point, if the valve closes after a Clock Wise (CW) rotation.
- If the valve closes after a Counter Clock Wise (CCW) rotation, the "Closed" marked adjustment terminals will indicate
the "Open" switch point. Similar, the "Open" marked adjustment terminals will indicate the "Closed" switch point.
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 8 of 11
Date:
April 2015
Q-Series
Control Module Options
QC41, QC42 and QC43
Local Manual Control
Speed Control
Description
Description
For commissioning, emergency or maintenance purposes,
the Bettis Q-Series can be supplied with one or two
Manual Control options. These can operate the pilot
valve(s) inside the module and as such operate the
actuator, when there is air pressure available, but no
control signal or power supply.
The Bettis Q-Series can be supplied with a Speed Control
option. One throttle is required for Spring Return actuators
and up to two for Double Acting actuators.
The speed control throttle controls the air flow in and
out of an air chamber and as such limits the speed of
the “Opening” and “Closing” stroke simultaneously. This
throttle consists of :
1 Nut cover
2 Main throttle with set screw.
Notes:
- One Local Manual Control is required for normal
operation of Double acting or Spring return actuators.
- For Double acting actuator with a Fail-in-last position
function, a second Local Manual Control can be
mounted.
- These options can be ordered together with the Control
Module or as a kit to be mounted later.
- For option ordering codes, see page 7
Note:
- For Spring Return actuators with one speed control
throttle, it is not possible to set both the stroke cycle
times to an equal time.
- Four Double Acting actuators it is possible to mount two
speed control throttles.
- The actual stroke cycle times depend on the actual load
on the actuator during the different strokes.
Spring Return:
Top entry only.
Double Acting:
Bottom and/or top entries.
Location for 2nd
Local Manual Control
Lock
45°
Default location of
Local Manual Control
Unlock
On
1
Off
Local Manual Control option
Speed control options
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
2
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 9 of 11
Date:
April 2015
Q-Series
Hazardous area specifications
Modules QC41, QC42 and QC43
Below specification are applicable for QC41, QC42 and QC43 modules with a hazardous area approval.
Hazardous area product marking;
FM hazardous or Classified Location:
IECEx hazardous or Classified Location:
APPROVED
Ex d IIB+H2 T4/T6 Gb
Ex t IIIC T80°C Db
IECEx DEK 15.0034X
CL I, II, III, DIV 1
Groups BCDEFG, T4/T6, Type 4X/6
CL l, ZN 1, IIB+H2, T4/T6
CSA hazardous or Classified Location:
ATEX hazardous or Classified Location:
Class I, II, III, DIV 1
Groups CDEFG, T4/T6, Type 4X/6
Ex d IIB+H2 T4/T6
DIP A21 TA 80°C
1180
II 2G Ex db IIB+H2 T4/T6
II 2D Ex tb IIIC T80°C
DEKRA 15ATEX0055X
Notes:
1 Each control module is marked with the applicable ambient temperature marking.
2 Metric control modules are marked with ATEX and IECEx markings.
3 Imperial control modules are marked with ATEX, IECEx, FM and CSA markings.
Temperature rating
Table 7: Temperature rating for use in areas with a potential explosion hazard.
Configuration
Module type
Switch cartridge
QC41 (24VDC)
QC42, QC43 (115 or 230VAC)
QC42, QC43 (115 or 230VAC)
Notes:
M, G
O, C, N, H
Temperature (°C)
Pneumatic
Max. Power
Min.
Max.
Max.
action
dissipation
ambient
ambient
Surface
S,D,F
3.6W (2
-25°C (-13°F)
+60
+80
T6/T4
S,D
3.6W (2
-25°C (-13°F)
+60
+80
T6/T4
F
7.2W (3
-25°C (-13°F)
+60
+80
T6/T4
1 1x or 2x 24VDC pilot valves, or 1x 115/230 VAC
pilot valve
2 2x 115 or 230 VAC pilot valves
Switch cartridge
M = Mechanical switches
G = Mechanical switches (gold contacts)
C = 3 wire PNP proximity switch
O = 3 wire NPN proximity switch
N = 2 wire proximity switch
H = 2 wire proximity switch
Pneumatic action
S = Spring Return (Single acting).
D = Double acting.
F = Double acting (Fail in Last Position)
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Class
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 10 of 11
Date:
April 2015
Q-Series
Corrosion protection Bettis Q-Series
Modules QC41, QC42 and QC43
Description
Technical data base actuator
The corrosion protection system of Bettis Q-Series
actuators consist of the following treatments or materials:
Finish:
Polyurethane powder coating
Thickness:
80 to 160 micrometer (3.1 to 6.2 mils).
Salt spray test: 1000 hours (ASTM B117)
Color:Yellow
Materials:
Housing:
Anodized aluminium alloy
Pistons:Chromatized
Pinion: High grade aluminum alloy,
hard anodized
Fasteners: Stainless steel or coated
alloy steel.
Type plate: Stainless steel
1 Pretreatment
The actuator housings are anodized inside and outside, to
give them a durable and superb protection against wear
and corrosion.
2 De-greasing.
All aluminum parts are de-greased before the coating is
applied by washing with an alkaline solution to assure
the best bonding between the aluminum surface and the
coating.
3 Finish
3.1 Actuator
Polyurethane powder coating for exterior use.
The powder coating is applied cold using automatic
electrostatic spray equipment and is cured for about 10
minutes at minimum 200°C (392°F) offering excellent light
and weather resistance.
3.2 Module
Polyurethane coating for exterior use.
The coating offers excellent light and weather resistance.
Good chemical resistance against most bases, acids,
solvents, alkalis and oils at normal temperatures.
Excellent exterior mechanical durability.
Technical data Control Module
Finish:
2 Component with an epoxy primer and
polyurethane enamel top coating.
Thickness: 80 to 160 micrometer (3.1 to 6.2 mils).
Salt spray test: 1000 hours (ASTM B117)
Color: Yellow
Materials: Housing: Anodized aluminium alloy
Fasteners: Stainless steel or coated
alloy steel.
Type plate: Vinyl
Base
actuator
4 High grade & hard anodized aluminum pinion.
Module
Actuators with high grade & hard anodized aluminum
pinions, passed a 1000 hours salt spray test.
5 Stainless steel or coated steel parts.
External parts are stainless steel or coated alloy steel.
6 Corrosion protected springs on Spring Return
actuators
All the springs of spring return actuator are Deltatone®
or epoxy (black) coated to prevent the corrosion of the
springs and assure a long cycle life.
Stainless steel
Fasteners
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: BQ1.604.10 - Rev: 5, Page 11 of 11
Date:
April 2015
Q-Series
Control Module Configuration:
Modules QC41, QC42 and QC43
Sample code:
QC41 • UWPM S K 1 • 0040 INS 0 IP
Pneumatic exhaust
Manual Control
Speed control
Mounting Options
IPT Device size actuator
Language Code
Future Expansions Code
Action
Control module options
Protection method
Conduit connections
Control module
Control module
QC41
Control module with 24 VDC pilot valve
QC42
Control module with 115 VAC pilot valve
QC43
Control module with 230 VAC pilot valve
Connections
M
Metric
U
NPT
Protection method
WP
Weather Proof IP66/NEMA4X
P5
Flame- or Explosion proof approval (see note 1)
Control module options (position feedback)
M
Mechanical switch
G
Mechanical switch (Gold Plated)
O
3-wire prox. switch PNP
C
3-wire prox. switch NPN
N
2-wire prox. switch (NAMUR)
H
2-wire prox. switch (20-140 VAC/10-140 VDC)
Action
S
D
F
Single acting actuator
Double acting actuator
Double Acting - Fail-In-Last-Position
Future Expansions Code
K
Standard
Language Code
1
English
QC41 • UWPMSA1 • 0150INS0IP
- Control module with 24 VDC pilot valve
•
- Imperial unit with 1/2"NPT and 3/4"NPT
electrical entries and 1/4"NPT pneumatic
entry.
- Weather proof module (IP66/NEMA4x)
- Mechanical feedback switches
- Suitable for Spring Return actuators
•
- With IPT probe for Q150 size actuator
- Not installed to actuator (separate
Control module)
- No speed control option
- No manual control option
- With IP65/NEMA4 exhaust
IPT Device size for actuator:
0040
Q40 actuator
0065
Q65 actuator
0100
Q100 actuator
0150
Q150 actuator
0200
Q200 actuator
0350
Q350 actuator
0600
Q600 actuator
0950
Q950 actuator
1600
Q1600 actuator
0000
No IPT probe
Mounting Options
U
Uninstalled
I
Installed/Tested to actuator
Speed control
NS
No Speed Control
N1
Spring Return (1x throttle)
N2
Double acting (2x throttle)
Manual Control
0
No Manual Control
1
1x "Push&Lock", anodized aluminum
2
2x "Push&Lock", anodized aluminum
Pneumatic exhaust
IP
IP65/NEMA4 rated exhaust
IN
Non metalic exhaust / Check valve
ZZ
Special exhaust
Note: 1 Metric control modules are marked with ATEX and IECEx markings.
2 Imperial control modules are marked with ATEX, IECEx, FM and CSA markings.
3 The options below are all options available. Not all options apply to all configurations.
www.emersonprocess.com/bettis
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.emersonprocess.com/bettis or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement