Installation_C1200_e_recent
C1200 Servo Drives
Installation Guide
Eine Deutsche Version kann unter http://www.linmot.com bezogen werden!
Please visit http://www.linmot.com to check for the latest version of this document!
This document applies to the following drives:
C1250-PL-XC-xS
C1250-EC-XC-xS
C1250-SE-XC-xS
C1250-PN-XC-xS
C1250-IP-XC-xS
C1250-SC-XC-xS
ATTENTION: The connectors have to be ordered separately and are
not included with the drive!
DC01-C1200/X4/X30
DC01-C1200/X4/X30/X33
Drive Connector Set for C1200-0S
Drive Connector Set for C1200-1S
0150-????
0150-????
C1200 Installation Guide
Preliminary
© 2013 NTI AG
This work is protected by copyright.
Under the copyright laws, this publication may not be reproduced or transmitted in any form, electronic or mechanical, including
photocopying, recording, microfilm, storing in an information retrieval system, not even for didactical use, or translating, in whole or in
part, without the prior written consent of NTI AG.
LinMot® is a registered trademark of NTI AG.
The information in this documentation reflects the stage of development at the time of press and is therefore without obligation.
NTI AG reserves itself the right to make changes at any time and without notice to reflect further technical advance or product
improvement.
Document version 5.2a / FM, June 2013
Page 2/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
Table of Content
1 Important Safety Instructions.........................................................................................4
2 System Overview.............................................................................................................6
3 Interfaces..........................................................................................................................7
4 Functionality and Interfaces...........................................................................................8
5 Software............................................................................................................................8
6 Power Supply and Grounding........................................................................................9
7 Description of the connectors / Interfaces..................................................................10
7.1 X1..............................................................................................................................10
7.2 X2..............................................................................................................................10
7.3 X3..............................................................................................................................11
7.4 X4 .............................................................................................................................12
7.5 X9..............................................................................................................................12
7.6 X13............................................................................................................................13
7.7 X17 - X18..................................................................................................................13
7.8 X19............................................................................................................................14
7.9 X33 ...........................................................................................................................14
7.10 S1 - S2....................................................................................................................14
7.11 S5............................................................................................................................15
7.12 LEDs.......................................................................................................................15
7.13 RT BUS LEDs.........................................................................................................15
8 Error Codes....................................................................................................................16
9 Safety Wiring..................................................................................................................17
10 Physical Dimensions...................................................................................................18
11 Power Supply Requirements......................................................................................19
12 Regeneration of Power................................................................................................19
13 Ordering Information...................................................................................................20
14 International Certifications.........................................................................................20
15 Declaration of Conformity CE-Marking......................................................................21
16 Contact Addresses......................................................................................................22
NTI AG / LinMot®
www.LinMot.com
Page 3/22
C1200 Installation Guide
Preliminary
1 Important Safety Instructions
For your personal safety
Disregarding the following safety measures can lead to severe injury to persons and
damage to material:
•
•
•
•
•
•
•
•
•
•
•
Only use the product as directed.
Never commission the product in the event of visible damage.
Never commission the product before assembly has been completed.
Do not carry out any technical changes on the product.
Only use the accessories approved for the product.
Only use original spare parts from LinMot.
Observe all regulations for the prevention of accidents, directives and laws applicable on site.
Transport, installation, commissioning and maintenance work must only be carried out by qualified
personnel.
• Observe IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC report 664 or
DIN VDE 0110 and all national regulations for the prevention of accidents.
• According to the basic safety information, qualified, skilled personnel are persons who are
familiar with the assembly, installation, commissioning, and operation of the product and who
have the qualifications necessary for their occupation.
Observe all specifications in this documentation.
• This is the condition for safe and trouble−free operation and the achievement of the specified
product features.
• The procedural notes and circuit details described in this documentation are only proposals.
It is up to the user to check whether they can be transferred to the particular applications.
NTI AG / LinMot does not accept any liability for the suitability of the procedures and circuit
proposals described.
LinMot servo drives and the accessory components can include live and moving parts (depending on
their type of protection) during operation. Surfaces can be hot.
• Non−authorized removal of the required cover, inappropriate use, incorrect installation or
operation create the risk of severe injury to persons or damage to material assets.
• For more information, please see the documentation.
High amounts of energy are produced in the drive. Therefore it is required to wear personal
protective equipment (body protection, headgear, eye protection, hand guard).
Application as directed
•
•
•
•
drives are components which are designed for installation in electrical systems or machines. They
are not to be used as domestic appliances, but only for industrial purposes according to EN
61000−3−2.
When drives are installed into machines, commissioning (i.e. starting of the operation as directed) is
prohibited until it is proven that the machine complies with the regulations of the EC Directive
98/37/EC (Machinery Directive); EN 60204 must be observed.
Commissioning (i.e. starting of the operation as directed) is only allowed when there is compliance
with the EMC Directive (2004/108/EC).
The technical data and supply conditions can be obtained from the nameplate and the
documentation. They must be strictly observed.
Transport, storage
•
•
Please observe the notes on transport, storage, and appropriate handling.
Observe the climatic conditions according to the technical data.
Page 4/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
Installation
•
•
•
•
The drives must be installed and cooled according to the instructions given in the corresponding
documentation.
The ambient air must not exceed degree of pollution 2 according to EN 61800−5−1.
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and
do not change any insulation distances during transport or handling. Do not touch any electronic
components and contacts.
drives contain electrostatic sensitive devices which can easily be damaged by inappropriate
handling. Do not damage or destroy any electrical components since this might endanger your
health!
Electrical connection
•
•
When working on live drives, observe the applicable national regulations for the prevention of
accidents.
The electrical installation must be carried out according to the appropriate regulations (e.g. cable
cross−sections, fuses, PE connection). Additional information can be obtained from the
documentation.
• This product can cause high-frequency interferences in non industrial environments
which can require measures for interference suppression.
Operation
•
•
If necessary, systems including drives must be equipped with additional monitoring and protection
devices according to the valid safety regulations (e.g. law on technical equipment, regulations for the
prevention of accidents). The drives can be adapted to your application. Please observe the
corresponding information given in the documentation.
After the drive has been disconnected from the supply voltage, all live components and power
connections must not be touched immediately because capacitors can still be charged. Please
observe the corresponding stickers on the drive. All protection covers and doors must be shut during
operation.
Protection of persons
• Before working on the drive, check that no voltage is applied to the power terminals:
• The power terminals Ph1+, Ph1-, Ph2+, Ph2- and PWR+ remain live for at
least 5 minutes after disconnecting from the power supplies.
•
The heat sink of the drive has an operating temperature of > 80 °C: Contact with the
heat sink results in burns.
NTI AG / LinMot®
www.LinMot.com
Page 5/22
C1200 Installation Guide
Preliminary
2 System Overview
Typical Servo System C12x0-XX: Servo Drive, Motor and Power Supply.
Page 6/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
3
C1200 Installation Guide
Interfaces
C12x0-xx-xx-xS-xxx
NTI AG / LinMot®
www.LinMot.com
Page 7/22
C1200 Installation Guide
Preliminary
C1250-PN-XC-0S
C1250-SC-XC-0S
C1250-IP-XC-0S
C1250-EC-XC-0S
C1250-SE-XC-0S
C1230-DP-XC-0S
C1200-GP-XC-0S
C1250-PL-XC-1S
C1250-PN-XC-1S
C1250-SC-XC-1S
C1250-IP-XC-1S
C1250-EC-XC-1S
C1250-SE-XC-1S
C1230-DP-XC-1S
C1200-GP-XC-1S
Supply Voltage
Motor Supply 72VDC (24..85VDC)
Logic Supply 24VDC (22...26VDC)
Motor Phase Current (preliminary)
25A peak
Controllable Motors
LinMot P01…(Motor Link P)
Selected motors (contact support)
Command Interface
POWERLINK
PROFINET
SERCOS III
ETHERNET IP
LinUDP
ETHERCAT
SERCOS over ETHERCAT
PROFIBUS-DP
Programmable Motion Profiles (Curves)
Up to 100 Motion Profiles
Programmable Command Table
Command Table with up to 255 entries
External Position Sensor
Incremental (RS422 up to 25 M counts/s)
Absolute (BiSS)
Configuration Interface
RS232
Integrated Safety Functions (-1S Option)
STO (2 Safety Relays)
C1250-PL-XC-0S
4 Functionality and Interfaces
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
5 Software
The configuration software LinMot-Talk is free of charge and can be downloaded
from the LinMot homepage.
Page 8/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
6 Power Supply and Grounding
In order to assure a safe and error free operation, and to avoid severe
damage to system components, all system components must be well
grounded to protective earth PE. This includes both LinMot and all
other control system components on the same ground bus.
The leakage current to earth (PE) is >3.5 mA. According to EN 50178 a
fixed installation is required and a double PE connection is required.
One PE connection is on X30, the second one is an M5 bolt on top of
the housing.
Each system component should be tied directly to the ground bus (star
pattern), rather than daisy chaining from component to component.
(LinMot motors are properly grounded through their power cables when
connected to LinMot drives.)
NTI AG / LinMot®
www.LinMot.com
Page 9/22
C1200 Installation Guide
Preliminary
7 Description of the connectors / Interfaces
7.1 X1
X1
Motor Phases
PWR+
PGND
Motor Supply: 72VDC nominal, 24...85VDC
Absolute max. Rating: 72VDC +20%.
External Fuse: 16AT / min. 100VDC
If motor supply voltage exceeds 90VDC, the drive will go into error state.
–
Use 60/75°C copper conductors only
–
Conductor Cross-Section 2.5mm2 (AWG14) max Length 4m
7.2 X2
X2
Motor Phases
LinMot Motor:
PH1+
Motor Phase 1+
red
PH1-
Motor Phase 1-
pink
PH2+
Motor Phase 2+
blue
PH2-
Motor Phase 2-
grey
PE/SCRN
Protective Earth / Shield
- Use 60/75°C copper conductors only
- Conductor cross-section: 0.5 – 2.5mm2 (depends on Motor current) / AWG 21 -14
Page 10/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
7.3 X3
X3
Motor Sensor
LinMot Motor:
1
2
3
4
5
6
7
8
9
case
DSUB-9 (f)
Do not connect
Do not connect
+5VDC
Sensor Sine
Temp In
Do not connect
Do not connect
AGND
Sensor Cosine
Shield
Note:
Use +5V (X3.3) and AGND (X3.8) only for motor internal hall sensor supply (max. 100mA).
Cable length < 30m.
Caution:
Do NOT connect AGND (X3.8) to ground or earth!
NTI AG / LinMot®
www.LinMot.com
Page 11/22
C1200 Installation Guide
Preliminary
7.4 X4
X4
Logig Supply / IO Connection
11
10
9
8
7
6
5
4
3
2
1
Spring cage
connector
AnInAnIn+
AnIn
In
In
In
In
Out
Out
+24VDC
GND
Inputs (X4.5 .. X4.8):
Outputs (X4.3 & X4.4):
Analog inputs:
X4.11
X4.10
X4.9
X4.8
X4.7
X4.6
X4.5
X4.4
X4.3
Supply
Supply
Configurable Analog Input differential (with X4.10)
Configurable Analog Input differential (with X4.11)
Configurable Analog Input single ended
Configurable Input
Configurable Input
Configurable Input
Configurable Input
Configurable Output
Configurable Output
Logic Supply 22-26 VDC
Ground
24V / 5mA (Low Level: –0.5 to 5VDC, High Level: 15 to 30VDC)
24V / max.100mA, Peak 370mA (will shut down if exceeded)
12 bit A/D converted.
Supply 24V / type. 500mA / max. 2.5A (if all outputs “on” with max. load.)
- Use 60/75°C copper conductors only
- Conductor cross-section max. 1.5mm2
- Stripping length: 10mm
CAUTION: For continued protection against risk of fire, replace only with same type and rating of fuse.
7.5 X9
X9
PROFIBUS DP (only available on E1230-DP-UC)
1
2
3
4
5
6
7
8
9
case
DSUB-9 (f)
Page 12/22
Not connected
Not connected
RxD/TxD-P
CNTR-P
GND
+5V
Not connected
RxD/TxD-N
Not connected
Shield
(isolated)
(isolated)
Max. Baud rate: 12Mbaud
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
7.6 X13
X13
External Position Sensor Differential Hall Switches
ABZ with Hall Switches
1
+5V DC
9
2
A+
A-
10
3
B+
B-
11
4
Z+
Z-
12
5
Encoder Alarm
GND
13
6
U+
U-
14
7
V+
V-
15
8
case
DSUB-15 (f)
W+
WShield
Position Encoder Inputs (RS422):
Max. counting frequency: 25 Mcounts/s with quadrature decoding, 40ns edge separation
Differential Hall Switch Inputs (RS422):
Input Frequency: <1kHz
Enc. Alarm In:
5V / 1mA
Sensor Supply:
5VDC max 100mA
7.7 X17 - X18
X17 - X18
RealTime Ethernet 10/100 Mbit/s
X17 RT ETH In
Specification depends on RT-Bus Type. Please refer to according documentation.
X18 RT ETH Out
RJ-45
NTI AG / LinMot®
www.LinMot.com
Page 13/22
C1200 Installation Guide
Preliminary
7.8 X19
X19
System
1
2
3
4
5
6
7
8
case
RJ-45
(Do not connect)
(Do not connect)
RS232 Rx
GND
GND
RS232 Tx
(Do not connect)
(Do not connect)
Shield
Use Adapter cable AC01-RJ45/Df-2.5-RS1 (Art.-No. 0150-2143) for Configuration over RS232.
7.9 X33
X33
Safety Relays (only with the -1S option)
4/8
3/7
2/6
1/5
Spring cage connector
7.10
Ksr +
Ksr Ksr f+
Ksr f-
Safety Relay 1 / 2 Input positive
Safety Relay 1 / 2 Input negative
Safety Relay 1 / 2 feedback positive
Safety Relay 1 / 2 feedback negative
- Use 60/75°C copper conductors only
- Conductor cross-section max. 1.5mm2
- Stripping length: 10mm
- Never connect the safety relays to the logic supply of the drive!
S1 - S2
S1 - S2
Address Selectors
S1 (5..8)
Bus ID High (0 … F). Bit 5 is the LSB, bit 8 the MSB.
S2 (1..4)
Bus ID Low (0 … F). Bit 1 is the LSB, bit 4 the MSB.
The use of these switches depends on the type of fieldbus which is used. Please see the corresponding
manual for further information.
Page 14/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
7.11
S5
C1200 Installation Guide
S5
Bootstrap
S5
7.12
LEDs
LEDs
State Display
Green
Yellow
Yellow
Red
7.13
RT Bus LEDs
Bootstrap
24V Logic Supply OK
Motor Enabled / Error Code Low Nibble
Warning / Error Code High Nibble
Error
RT BUS LEDs
RT Bus State Display
Green
Red
OK
Error
The use of these LEDs depends on the type of fieldbus which is used. Please see the corresponding
manual for further information.
NTI AG / LinMot®
www.LinMot.com
Page 15/22
C1200 Installation Guide
Preliminary
8 Error Codes
Error Codes
Error
Warn
EN
Description
Off
Warning
Operation
Enabled
Normal Operation:
Warnings and operation enabled are displayed.
On
● ~2Hz
0..15 x
Error Code
High Nibble
● ~2Hz
0..15 x
Error Code
Low Nibble
Error:
The error code is shown by a blink code with “WARN” and “EN”.
The error byte is divided into low and high nibble (= 4 bit).
”WARN” and “EN” are blinking together.
The error can be acknowledged.
(e.g.: WARN blinks 3x, EN blinks 2x; Error Code = 32h)
● ~2Hz
● ~2Hz
0..15 x
Error Code
High Nibble
● ~2Hz
0..15 x
Error Code
Low Nibble
Fatal Error:
The error code is shown by a blink code with “WARN” and “EN”.
The error byte is divided into low and high nibble.
”WARN” and “EN” are blinking together.
Fatal errors can only be acknowledged by a reset or power cycle.
(e.g.: WARN blinks 3x, EN blinks 2x; Error Code = 32h)
● ~4Hz
● ~2Hz
0..15 x
Error Code
High Nibble
● ~2Hz
0..15 x
Error Code
Low Nibble
● ~0.5Hz
● ~0.5Hz
On
System Error:
Please reinstall firmware or contact support.
Signal Supply 24V too low:
The error and warn LEDs blink alternating if the signal supply +24V (X4.2) is
less than 18VDC.
The meaning of the error codes can be found in the
Usermanual_MotionCtrl_Software_SG5 and the user manual of the installed
interface software. These documents are provided together with LinMot-Talk
configuration software and can be downloaded from www.linmot.com.
Page 16/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
9 Safety Wiring
The C1200 drives with the -1S option have internal safety functions:
Two Safety relays Ksr in series, which support the supply voltage for the motor
drivers. There are also two feedback contacts for each relay.
To enable the -1S drives both relays have to be switched on.
Minimal wiring:
- Connect X33.8 and X33.4 to 24VDC (from safety)
- Connect X33.7 and X33.3 to GND (from safety)
Attention: Never connect X33.8 and X33.4 to the logic supply of X4!
If an overvoltage protection is needed, it must be provided externally and
sized according the safety circuit of the machine!
Attention: The drop out time of the relays is depending on the external circuitry!
Safety Relay Ksr
Nominal voltage
24 VDC
Min. pick-up voltage at 20°C
≤ 16.8V
Drop-out voltage at 20°C
≥ 2.4 V
Drop-out time (no protection circuit)
Typ. 3ms
Coil resistance at 20°C
2'100 Ω ± 10%
Type
EN 50205, type A
Contact lifetime
> 10'000'000
Manufacturer and type
Elesta relays / SIS112 24VDC
Drive Classification according EN ISO 13849-1 (safety of machinery) (preliminary)
Category
cat = 3
Performance Level
PL = d
Diagnostic Coverage
DC = high
Mean Time to hazardous failure of one channel
MTTFd = high
NTI AG / LinMot®
www.LinMot.com
Page 17/22
C1200 Installation Guide
Preliminary
10 Physical Dimensions
C1200 Series single axis drive
C12xx-xx-XC-0S
Width
mm (in)
Height
mm (in)
166 (6.54)
Height with fixings
mm (in)
206 (8.11)
Depth
mm (in)
Weight
g (lb)
Mounting
C12xx-xx-XC-1S
25.3 (1.0)
176 (6.93)
216 (8.5)
106 (4.17)
630 (1.4)
700 (1.54)
2 x M5
Case
IP
20
Storage Temperature
°C
-25…40
Transport Temperature
°C
-25…70
Operating Temperature
°C
0…40 at rated data
40...50 with power derating
Relative humidity
95% (non-condensing)
Pollution
IEC/EN
60664-1
Pollution degree 2
Site altitude
m amsl
to be defined
Shock resistance (16ms)
-1S option
3.5g
Vibration resistance (10-200Hz)
-1S option
1g
Max. Case Temperature
°C
Max. Power Dissipation
W
Mounting place
???
In the control cabinet
Mounting position
Distance between Drives
90
vertical
mm (in)
Without Power Derating:
20 (0.8) horizontal / 50 (2) vertical
With Power Derating:
5 (0.2) horizontal / 20 (0.8) vertical
Page 18/22
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
11 Power Supply Requirements
Motor Power Supply
The calculation of the needed power for the Motor supply is depending on the
application and the used motor. The nominal supply voltage is 72- 80 VDC. The
possible range is from 24 to 85VDC, for UL from 30 to 85 VDC.
ATTENTION:
The motor supply can rise up to 95 VDC when braking.
This means that everything connected to that power supply needs a
voltage rating of 100 VDC. (Additional capacitors, etc...). Due to high
braking voltage and sudden load variations of linear motor
applications,
only specially designed power supplies can be used.
Signal Power Supply
The logic supply needs a regulated power supply of a nominal voltage of 24 VDC.
The voltage must be between 22 and 26 VDC.
Current consumption:
min. 0.5A
(no load on the outputs)
typ. 1.5A
(all 10 outputs “on” with 100mA load and /Break with no load)
max. 2.5A
(all 10 outputs “on” with 100mA load and /Break with 1A load)
Do not connect the safety relays to the 24VDC Signal Supply!
Use a separate power supply for the safety circuit!
12 Regeneration of Power
Connect an additional capacitor to the motor power supply. It is recommended to
use a capacitor >= 10’000 μF
(install capacitor close to the drive supply!)
NTI AG / LinMot®
www.LinMot.com
Page 19/22
C1200 Installation Guide
Preliminary
13 Ordering Information
Item
Description
Art. Nr.
C1200-GP-XC-0S
GENERAL PURPOSE Drive (72V/25A)
0150-1882
C1230-DP-XC-0S
PROFIBUS DP Drive (72V/25A)
0150-2386
C1250-PL-XC-0S
POWERLINK Drive (72V/25A)
0150-1885
C1250-SE-XC-0S
SERCOS over ETHERCAT Drive (72V/25A)
0150-1897
C1250-IP-XC-0S
ETHERNET IP Drive (72V/25A)
0150-1886
C1250-EC-XC-0S
ETHERCAT Drive (72V/25A)
0150-1884
C1250-PN-XC-0S
PROFINET Drive (72V/25A)
0150-1888
C1250-SC-XC-0S
SERCOS III Drive (72V/25A)
0150-1887
C1200-GP-XC-1S
GENERAL PURPOSE Drive (72V/25A/STO)
0150-2344
C1230-DP-XC-1S
PROFIBUS DP Drive (72V/25A/STO)
0150-2387
C1250-PL-XC-1S
POWERLINK Drive (72V/25A/STO)
0150-2347
C1250-SE-XC-1S
SERCOS over ETHERCAT Drive (72V/25A/STO)
0150-2350
C1250-IP-XC-1S
ETHERNET IP Drive (72V/25A/STO)
0150-2346
C1250-EC-XC-1S
ETHERCAT Drive (72V/25A/STO)
0150-2345
C1250-PN-XC-1S
PROFINET Drive (72V/25A/STO)
0150-2348
C1250-SC-XC-1S
SERCOS III Drive (72V/25A/STO)
0150-2349
RS232 PC config. Cable 2.5m
For E1200 / E1400
0150-2143
ATTENTION: The connectors have to be ordered separately and are not
included with the drive!
14 International Certifications
Certifications
Europe
UR
Page 20/22
See chapter “15 Declaration of Conformity CE-Marking“
UL508C recognition pending
www.LinMot.com
NTI AG / LinMot®
Preliminary
C1200 Installation Guide
15 Declaration of Conformity CE-Marking
Manufacturer: NTI AG / LinMot ®
Haerdlistrasse 15
8957 Spreitenbach
Switzerland
Tel.:
+41 (0)56 419 91 91
Fax:
+41 (0)56 419 91 92
LinMot ® drives
Products:
Type
Art.-No.
Type
Art-No.
Type
Art.-No.
C1200-GP-XC-0S
C1250-IP-XC-0S
C1250-PN-XC-0S
C1200-GP-XC-1S
C1250-IP-XC-1S
C1250-PN-XC-1S
0150-1882
0150-1886
0150-1888
0150-2344
0150-2346
0150-2348
C1250-PL-XC-0S
C1230-DP-XC-0S
C1250-SC-XC-0S
C1250-PL-XC-1S
C1230-DP-XC-1S
C1250-SC-XC-1S
0150-1885
0150-2386
0150-1887
0150-2347
0150-2387
0150-2349
C1250-SE-XC-0S
C1250-EC-XC-0S
0150-1897
0150-1884
C1250-SE-XC-1S
C1250-EC-XC-1S
0150-2350
0150-2345
The product must be mounted and used in strict accordance with the installation instructions
contained within the installation guide, a copy of which may be obtained from NTI Ltd.
I declare that as the authorized representative, the above information in relation to the
supply/manufacture of this product is in conformity with the stated standards and other related
documents in compliance with the protection requirements of the Electromagnetic Compatibility
(EMC) Directive 2004/108/EC and Safety tests according to the 2006/95/EC harmonized standard
EN 50371: 2002.
Standards Complied with:
EN 61000-6-2: 2005
Immunity for industrial environments
EN 61000-4-2
Class B and FS
Electrostatic discharge immunity (ESD)
EN 61000-4-3
Class A and FS
Radiated electromagnetic field immunity
EN 61000-4-4
Class B and FS
Fast transients / burst immunity (EFT)
EN 61000-4-5
Class B and FS
Slow transients immunity (Surge)
EN 61000-4-6
Class A and FS
Conducted radio frequency immunity
EN 61000-4-8
Class A and FS
Power frequency magnetic field immunity
EN 61326-3-1
FS
EMC immunity (functional safety)
EN 61000-6-4: 2007
Emission for industrial environments
EN 55022
Class A
Stationary interference voltage AC mains
EN55022
Class A
Stat. Asym. Interference current on Telco lines
EN 55022
Class A
Radiated Emission
EN 61326-3-1:2008
Functional Safety
EN 50371
Human exposure to electromagnetic fields
EN 5022
Radio disturbance (IT equipment)
EN 5011
Radio disturbance (ISM)
CISPR 22: 2005
Radio disturbance (IT equipment)
Company: NTI Ltd.
Spreitenbach, June 25, 2013
----------------------------------------------------------R. Rohner / CEO NTI AG
NTI AG / LinMot®
www.LinMot.com
Page 21/22
C1200 Installation Guide
Preliminary
16 Contact Addresses
SWITZERLAND
USA
NTI AG
Haerdlistr. 15
CH-8957 Spreitenbach
Sales and Administration:
+41-(0)56-419 91 91
[email protected]
Tech. Support:
+41-(0)56-544 71 00
[email protected]
Tech. Support (Skype) :
skype:support.linmot
Fax:
Web:
+41-(0)56-419 91 92
http://www.linmot.com/
LinMot, Inc.
204 E. Morrissey Dr.
Elkhorn, WI 53121
Sales and Administration:
877-546-3270
262-743-2555
Tech. Support:
877-804-0718
262-743-1284
Fax:
800-463-8708
262-723-6688
E-Mail:
Web:
[email protected]
http://www.linmot-usa.com/
Please visit http://www.linmot.com/ to find the distributor closest to you.