Original instructions
SIRe Competent Air Curtains
Water
With quick guide
SIReAC
SE .... 2
GB .... 21
DE .... 40
FR .... 59
ES .... 78
IT
NL .... 116
NO .... 135
PL .... 154
RU .... 173
.... 97
For wiring diagram, please see last pages
GB
SIRe Competent Air Curtains Water
Quick guide/start up
Wiring diagrams
Check that all constituent parts are present
(see section Constituent parts).
The wiring diagrams are in a separate section
at the end of this manual.
When external PC board Base SIReB1X is
used, wiring between the PC board base and
the unit must be done. Please see separate
manual for SIReB1X.
Advice about location
PC board HUB SIReC1X is installed close to
the unit.
Control unit SIReUA1 has an integrated
room temperature sensor and is installed so
that it is easily accessible to the user. RJ12
(6p/6c) modular cables, which are available in
different lengths, are used to connect the PC
board and the control unit. Longer cables are
available as options. Maximum cable lengths
see section Options.
To prevent unauthorised people from accessing the Control unit it can instead be placed
in another area and an external room sensor,
SIReRTX (option), can be installed in the premises to sense the correct temperature.
Enter ID/Operation without control unit
The control system can control one or more
units in parallel (max 9). Each unit must get
a unique ID number (1-9) which is set in the
ID selector of the PC board. E.g. Unit 1: ID=1,
unit 2: ID=3
If the external control for some reason has
not been installed the unit can still be run
temporarily. The ID selector is then set to
mode 0 see the image below.
The function is half speed and heating is on.
When the ID number must be changed the
unit must be disconnected from power.
Connect the system
3
4
5
3
6
In PC board Base SIReB1(X) the unit is
7
2
connected further with RJ12 (6p/6c) modular
1
8
cable if several units are to be connected in
9
0
parallel.
If an external room temperature sensor
Each unit should have
SIReRTX is used it is connected using modular a unique ID on its
SIReB1X card.
cable RJ11 (4p/4c) on HUB SIReC1X.
The actuator for water control is connected to
SIReB1(X) and door switch SIReDC (a closed
contact when the door is open) is connected to
the terminal block on PC board HUB SIReC1X.
Control board Base SIReB1(X) in/at the unit
and control unit SIReUA1 are connected by
PC board HUB SIReC1X with RJ12 (6p/6c)
modular cables, after the other units are
powered up.
For fixed installation requirements, remove
the supplied cable and plug. Perform the installation in accordance with applicable regulations.
4
5
6
2
7
1
8
0
9
To run the unit
temporarily without
external control select
mode 0.
21
GB
SIRe Competent Air Curtains Water
Start up
System supplied with power. At the first start
up, the start-up wizard is run and the basic
settings are made. Fan and heating steps
are tested through the test program. Then a
status window is displayed.
At the first start up alarm and error codes
can occur, these will usually be reset without
actions.
Start-up wizard
1
Start-up wizard
5
Set language
English
Start-up wizard
Function test
Start test
Skip test
Screen function test
2
Start-up wizard
Start-up wizard
Set temp. unit
Fan step 1-5
Heating step off-1
°C
°F
3
Start-up wizard
6
Set date
2011-05-28
Function test
Test completed
Restart test
YYYY-MM-DD
4
Start-up wizard
Set time
14:07
24h format
Checking system...
22
Start-up wizard
7
Start-up wizard
Start-up finished
Proceed
Restart wizard
SIRe Competent Air Curtains Water
GB
Contents
Quick guide/start up
Advice about location Connect the system Wiring diagrams
Enter ID/Operation without control unit
Start up
21
21
21
21
22
Constituent parts
SIReAC24
Option25
Water control - valve kit 26
Operating modes
Door that is opened and closed
Doors that are always or often left open for longer periods
Function description of current stage
27
27
28
Control unit SIReUA1
Overview30
Statuswindow30
Main menu
Current settings
31
Temperature settings
31
Fan control
31
Summer/Winter31
System on/off
31
Installer menu
31
Installer menu
Installer status screen
Week program
Fan settings
Heating settings
Filter guard settings (not for electric)
External control (BMS)
General settings
Service menu
32
32
33
33
34
34
35
35
Alarm and error codes
Displaying alarm and error codes
Reset alarm
Overheat protection
Power failure
Frost protection function
36
36
36
36
36
Wiring diagrams, see last pages
23
GB
SIRe Competent Air Curtains Water
Constituent parts
SIReAC
Integrated in the air curtain
PE N L
SUPPLY 230V
X5
C2
SIReUA1,
control unit
Competent and
Advanced
Wall unit
cover
X4
C1
X3
ROOM
ACTUATOR
230V
SIReIT, internal
temperature
sensor
SIReB1,
integrated PC
Board Base
SIReDC,
door contact
SIReC1X,
PC board HUB Competent
SIReCC,
modular cable
Dimensions constituent parts
Type
Description
SIReUA1
SIReB1
SIReIT
SIReC1X
SIReDC
SIReCC603
SIReCC605
Control unit Competent and Advanced
Integrated PC board Base
Internal temperature sensor
PC Board HUB Competent
Magnetic door contact
Modular cable RJ12 (6/6)
Modular cable RJ12 (6/6)
24
HxWxD
[mm]
120x70x35
L
[m]
1
202x139x50
3
5
GB
SIRe Competent Air Curtains Water
Option
SIReRTX, external
room temperature
sensor
SIReUR, kit
for recessed
installation
SIReCJ4,
joint piece
SIReCJ6, joint
piece
Type
RSK-no.
E-no.
Description
SIReRTX
SIReUR*
SIReCJ4
SIReCJ6
SIReCC603
SIReCC605
SIReCC610
SIReCC615
SIReCC403
SIReCC405
SIReCC410
SIReCC415
673 09 22
673 09 21
87 510 12
87 510 11
673 09 23
673 09 24
673 09 25
673 09 26
673 09 27
673 09 28
673 09 29
673 09 30
87 510 13
87 510 14
87 510 15
87 510 16
87 510 17
87 510 18
87 510 19
87 510 20
External room temperature sensor
Kit for recessed installation
Joint piece for two pcs. RJ11 (4/4)
Joint piece for two pcs. RJ12 (6/6)
Modular cable RJ12 (6/6)
Modular cable RJ12(6/6)
Modular cable RJ12 (6/6)
Modular cable RJ12 (6/6)
Modular cable RJ11 (4/4)
Modular cable RJ11 (4/4)
Modular cable RJ11 (4/4)
Modular cable RJ11 (4/4)
SIReCC,
modular cable
HxWxD
[mm]
70x33x23
114x70x50
L
[m]
3
5
10
15
3
5
10
15
*) See separate manual.
Max. cable lenghts
• Modular cabel RJ12 (6p/6c) between SIReUB1 and SIReB1(X): max 50 m.
• Modular cable RJ12 (6p/6c) between SIReC1X and SIReB1(X): max 10 m
• Modular cabel RJ12 (6p/6c) between two SIReB1(X): max 50 m.
• Modular cabel RJ11 (4p/4c) to room sensor SIReRTX: max 20 m.
Total cable length permitted in the system is a maximum of 300 m.
25
GB
SIRe Competent Air Curtains Water
Water control - valve kit
SD230
VOS
TBVC
BPV10
AV
Water control - option
SD230
VOSP
TBVCMP
BPV10
AV
VAT, adjustment tool for
valve package.
VOT
SD230
TRVS
Type
RSK-no.
Description
Connection
VOS15LF
VOS15NF
VOS20
VOS25
VOSP15LF
VOSP15NF
VOSP20
VOSP25
VOT15
VOT20
VOT25
VAT
673 09 35
673 09 36
673 09 37
673 09 38
673 09 43
673 09 44
673 09 45
673 09 46
On/off
On/off
On/off
On/off
Pressure independent
Pressure independent
Pressure independent
Pressure independent
Three way valve and actuator on/off
Three way valve and actuator on/off
Three way valve and actuator on/off
Adjustment tool for valve package
DN15
DN15
DN20
DN25
DN15
DN15
DN20
DN25
DN15
DN20
DN25
26
482 98 30
SIRe Competent Air Curtains Water
Operating modes
Door that is opened and closed
The control function notes whether the door
is open or closed as standard, this mode is
default set and is called Fixed flexible (the
setting is under Installer menu > Fan settings
> Door mode).
Open door
Indicates OP on the installer status screen.
The fan speed runs at high speed which is
set under Main menu > Fan speed > Max fan
speed.
Normally it is requested that heat is engaged
when the door is opened. The set point value
(Room temp. day) is then increased with
the fixed set point value difference that can
be changed under Installer menu> Settings
heating > Open door setp. diff., factory setting
3.0 K. The set point is set under Main Menu
> Temperature settings > Room temp. day.
If week program is used the night time set
point value is set under Main menu > Temp.
settings > Room temperature night. The room
temperature is regulated using the integrated
room temperature sensor or the external
room temperature sensor, SIReRTX (option).
Closed door
Indicated CL on the installer status screen.
When heating demand the fan speed runs
at low speed which is set under Main menu
> Fan speed > Speed closed door. Heating is
regulated to Room temp. Day which is set
under Main Menu > Temperature settings >
Room temp. day.
If week program is used the night time set
point value is regulated against the Room
temperature is set under Main menu > Temp.
settings > Room temperature night. The room
temperature is regulated using the integrated
room temperature sensor or the external
room temperature sensor, SIReRTX (option).
GB
When the door is closed - over run
When the door has been closed, high speed
mode remains during the fixed time that is
set under Installer menu > Settings fan >
Door over run > High speed over run and at
low speed during a fixed time under Installer
menu > Settings fan> Door over run > Low
speed over run, on the condition that it is
sufficiently warm in the premises, otherwise
the fans run until the desired temperature has
been reached.
When the door is closed, the set point value
shifts from room temperature + fixed set point
value difference for open door to Room temp.
day/night.
Over run is factory set so that the over run
times are controlled according to how often
the door is opened (Auto mode under Installer menu > Settings fan > Over run door >
Over run mode).
Doors that are always or often left open for
longer periods
If a door is always, or often, left open it is
possible to use a function called CURRENT
STAGE instead. The fan and heating steps
increase/decrease 6 or 9 steps (depending on
the type of unit) and are only controlled by
the room temperature. Actual Current stage
is shown in the status screen.
The function current stage is activated in
two ways:
Door that are always open
For a door that is always open, door mode
Fixed open > can be selected under >Settings
fan> Door mode.
Doors that are often open for longer
periods
For a door that is often open Auto can be
selected under Installer menu > Settings
fan > Door mode. In Auto mode, the control
automatically switches between Flexible and
Open modes depending on how often the
door has been open (when the door has been
open for longer than 300 seconds the function
changes from Flexible to Open).
27
GB
SIRe Competent Air Curtains Water
Function description of current stage
The task of the Current stage function is to
balance the room climate when a door is
always open by using the right combination of
fan and heating step.
In open mode, the room temperature is
read every 60 seconds (during the first 6
cycles, and then every 5 minutes and at each
reading any Current stage adjustments are
made, i.e. fan control and supplied output
adjusted.
Winter
When winter mode is selected under Main
Menu > Summer / Winter.
•If the room temperature is more than 3
degrees below the current settings, the
current stage increases by 2 steps.
•If the room temperature is between 1 and
3 degrees below the current settings, the
current stage increases by 1 step.
•If the room temperature is more than 2
degrees above the current setting, the
current stage decreases by 1 step.
Summer
When summer mode is selected under Main
Menu > Summer/Winter, heating is blocked.
• If the room temperature is more than
2 degrees below the current settings, the
current stage increases by 1 step.
•If the room temperature is between 1 and
2 degrees below the current settings, the
current stage decreases by 1 step.
•If the room temperature is more than 2
degrees greater than the Current settings,
current stage increases by 1 step.
•If the room temperature is between 1 and 2
degrees above current settings, the current
stage decreases by 1 step.
If fan control has been max. limited under
Main Menu > Fan control> High speed limit,
all current stages will be used but the fan will
be limited to the current setting.
See the table on the next page.
28
SIRe Competent Air Curtains Water
GB
Table - Current stage for units with 5 fan controls Current
stage
0
1
2
3
4
5
6
7
8
Fan
Heating
0
1
2
2
3
3
4
5
5
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
Table - Current stage for units with 3 fan controls
Current
stage
0
1
2
3
4
5
Fan
Heating
0
1
2
2
3
3
OFF
OFF
OFF
ON
ON
ON
29
GB
SIRe Competent Air Curtains Water
Control unit SIReUA1
Overview
IN
19.0
°C
Statuswindow
DOOR
Back arrow
CL
Forward arrow
Rotary dial
Fan speed step
Heating step
Week program
Day
Alarm Red led
AV Week program
Out of operation
Run signal
Green led
Explanations
Statuswindow
The display shows the prevailing room
temperature, fan and heating step, door status
and day/night mode or Off when the week
program is used.
Forward arrow
Confirm selection and proceed.
Rotary dial
Scroll between alternatives
Back arrow
Go back.
After three minutes the control unit goes back
to displaying the status window.
30
Week program
Night
Statuswindow
Press forward arrow to enter the main menu.
GB
SIRe Competent Air Curtains Water
Main menu
Current settings
Summer/Winter
Displays set room temp, high speed limit,
Speed closed door, Summer / Winter and
week program status.
To permit or block heating. Heating is
permitted in winter mode. Summer mode is
displayed with a crossed out heating symbol
in the status window.
Main menu
Current settings
Current settings
Temperature settings
Fan control
Room temp. day
Room temp. night
High speed limit
Speed closed door
Summer/Winter
Week program
20°C
18°C
Step 5
Step 1
Winter
No program
Temperature settings
Set the desired room temperatures to apply
for day respectively night mode, when the
door is closed (room temperature night is
used for week program/night reduction).
At open door these set point values automatically increase with a set point differential
that can be set under Installer menu > Heat
settings> Open door setp. diff. (Factory setting 3.0 K).
Main menu
Current settings
Temperature settings
Fan control
Main menu>Temperature
settings
Room temp. day
Room temp. night
Factory setting
Room temp. day: 20°C (5 – 35°C)
Room temp. night: 18°C (0 – 20°C)
Main menu
Main menu>Summer/Winter
Fan control
Summer/Winter
System on/off
Summer/Winter
Winter
•
Factory setting
Summer/Winter:
Winter (Summer - heat off)
System on/off
Switch the whole unit off manually. In Off the
display goes out; as soon as a button is pushed
the display lights and shows System on/off. To
activate the unit again select On.
The unit’s safety functions are still active
when the system is switched off, which means
that the fan can continue to run for a moment
after mode Off has been selected.
Main menu
Main menu>System on/off
Summer/Winter
System on/off
Installer menu
System on/off
ON
•
Fan control
Installer menu
Possibility of setting high speed mode at an
open door and what speed should apply with
a closed door (3 or 5 steps depending on the
unit).
Main menu
The installer menu is at the bottom of the
main menu, this is password protected. See
Installer menu in this manual.
Temperature settings
Fan control
Summer/Winter
Main menu>Installer menu
Summer/Winter
System on/off
Enter password
Installer menu
Main menu>Fan control
Main menu>Fan control
High speed limit
Speed closed door
High speed limit
•
Main menu
0 0 0 0
(See manual)
Step 5
Main menu>Fan control
Main menu>Fan control
High speed limit
Speed closed door
Speed closed door
•
Step 1
Factory setting
High speed limit: 3 resp. 5 (1-3, resp. 1-5)
Speed closed door: 1 (Off-3, resp. Off-4)
31
GB
SIRe Competent Air Curtains Water
Installer menu
To enter the Installer menu, code 1932 is
entered. Select the digits using the rotary dial
and confirm using the forward arrow.
To check which days a certain program is
active, select a week day by pressing the
forward arrow, the program is marked and
those days that the program is used will be
underlined, switch between the programs for
a particular day using the rotary wheel.
Main menu
Main menu>Installer menu
Check program
Summer/Winter
System on/off
Enter password
Mon Tue Wed Thu Fri
Installer menu
0 0 0 0
(See manual)
Installer status screen
Check the settings. The installer status screen
consists of three pages with settings, scroll
using the rotary dial.
>Installer menu
>Installer status screen
Installer status screen
Week program
Fan settings
Functionality mode
Door mode
Current stage
Over run mode
Program
Sat Sun
08:00 Day (1)
18:00 Night (2)
Comp.
Flexible
2°C
FF
Auto
002 FF
FF
AC11
To add program step, select New program
step. Confirm your selection with the forward
arrow. Select Day, Night or Off (if the unit
should not be in operation), set the time
for switch on and then for which days the
program applies, then go to End to finish.
>Installer menu>Week
program
Week program on/off
New program step
Check program
New program step 7/16
Mode
Day
00:00
Tue 10:45
Mon Tue Wed Thu Fri
Tue 10:45
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
Week program
End
Sat Sun
Tue 10:45
A new program step does not replace a set
time for Day for example, but you can instead
select to change a program step.
To change a program step, select Change
program.
Make settings for week program.
>Installer menu
Installer status screen
Week program
Fan settings
A basic program is pre-entered in SIRe.
Mon-Fri Day from 08:00, Night from 18:00
Sat Day from 10:00, Night from 16:00
Sun Day from 11:00:00, Night from 14:00
>Installer menu>Week
program
Check program
Change program
Remove program
Change program
Mon Tue Wed Thu Fri
1. 08:00
2. 18:00
3. 10:00
4. 16:00
Day
Night
Day
Night
00:00
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
Tue 10:45
Sat Sun
Tue 10:45
To check which program is set for a particular
day, select Check program and then switch
between the days using the rotary dial.
>Installer menu>Week
program
New program step
Check program
Change program
Check program
Mon Tue Wed Thu Fri
08:00 Day (1)
18:00 Night (2)
Sat Sun
Mon Tue Wed Thu Fri
End
Tue 10:45
The program steps that should not apply
are removed in Remove program. One or all
program steps can be removed in the menu.
To return to the factory set basic program,
select Reset all.
>Installer menu>Week
program
Check program
Change program
Remove program
32
Sat Sun
Remove program
Remove single
Remove all
Reset all
GB
SIRe Competent Air Curtains Water
Week program is activated by selecting On,
under Week program on/off. In On-mode,
a sun, moon or Off in the Status window
appears to indicate day, night respectively
Off-function.
>Installer menu>Week
program
>Installer menu>Week program
Week program on/off
New program step
Check program
Week program on/off
ON
•
Fan settings
Make settings for fan mode (see also
Operating modes section).
>Installer menu
Week program
Fan settings
Heating settings
Door over run
Settings for overrun.
Factory setting
Over run mode:
High speed over run:
Low speed over run:
Auto (Set time)
30 s (0 – 180 s)
120 s (0 – 300 s)
Door mode
There are three different door modes to
choose from; Auto, Fixed flexible and Fixed
open.
>Installer menu>Fan settings
>Installer menu>Fan settings
Door over run
Door mode
Door mode
Fixed flexible
•
In Fixed flexible mode, the control function
notes whether the door is open or closed.
In Fixed open mode the door is considered
always open and is only controlled according
to Current stage. In Auto mode, the control
automatically switches between Fixed flexible
and Fixed open modes depending on how
often the door has been open.
>Installer menu>Fan settings
Door over run
Door mode
>Installer menu>Fan
settings>Door over run
>Installer menu>Fan
settings>Door over run
Over run mode
High speed over run
Low speed over run
Over run mode
Auto
•
In over run mode Auto, SIRe controls the over
run time depending on how frequently the
door is opened between openings, according
to fixed preset values, according to the table.
Time between
opening [s]
t < 60
60 < t < 300
t > 300
High speed over
run [s]
30
10
0
Low speed over
run [s]
90
300
180
Over run mode Fixed time is selected is one
wants fixed over run times, the times can be
changed during High speed over run and Low
speed over run.
>Installer menu>Fan
settings>Door over run
Over run mode
High speed over run
Low speed over run
>Installer menu>Fan
settings>Door over run
Factory setting
Door mode:
Auto)
Fixed flexible (Fixed open/
Heating settings
Make settings for heating.
>Installer menu
Fan settings
Heating settings
Filter guard settings
Open door setp. diff.
Set by how much the set point value (Room
temp. day/night) is to increase when the door
is open.
>Installer menu>Heating
settings
>Installer menu>Heating
settings
Open door setp. diff.
Sensor calibration
Control range limit
•
Open door setp. diff.
3.0 K
Factory setting
Set point value difference open door: 3.0 K (0
K – -10 K)
Over run mode
Fixed time
•
33
GB
SIRe Competent Air Curtains Water
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for example +2K gives an increase of the
displayed value of 2 degrees).
>Installer menu>Heating
settings>Sensor calibration
>Installer menu>Heating
settings
Open door setp. diff.
Sensor calibration
Control range limit
Room temp. sensor
Outdoor temp. sensor
>Installer menu>Heating
settings>Sensor calibration
Room temp. sensor
•
0.0 K
Factory setting
Room temperature sensor: 0.0 K (-10 K – 10
K)
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35°C.
Filter timer on/off
Filter alarm is activated by selecting On,
under Filter timer on/off.
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
Last filter change
Factory setting
Filter timer on/off: Off (On)
Last filter change
To check the number of run time hours since
the last filter replacement, select Last filter
change. The time is reset when the filter
alarm is reset. If the time is to be reset before
the alarm has gone, switch the filter timer on
and off.
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
>Installer menu>Filter guard
settings
Last filter change
0h
Last filter change
>Installer menu>Heating
settings
Open door setp. diff.
Sensor calibration
>Installer menu>Heating
settings
Control range limit
•
35°C
Control range limit
Factory setting
Control range limit temperature: 35°C (5 –
35°C)
Filter guard settings (not for electric)
Filter alarm alarms when the set fixed run
time has been exceeded.
External control (BMS)
BMS functions can be activated under
External control.
Activate External on/off (5-30V AC/DC from
BMS) or 0-10V fan control by selecting On
under the respective one. See diagram on
next page and Connecting external control.
>Installer menu
>Installer menu>External
control
Heating settings
Filter guard settings
External control
>Installer menu
Filter timer setting
Under Filter timer setting, set the desired run
time to between 50 and 9950 hours.
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
Last filter change
>Installer menu>Filter guard
settings
Filter timer setting
•
1500 h
Factory setting
Filter timer setting: 1500 h (50 - 9950 h)
34
Filter guard settings
External control
General settings
External on/off
0-10V fan control
>Installer menu>External
control
External on/off
0-10V fan control
SIRe Competent Air Curtains Water
GB
8,4
5
7,0
4
5,6
3
4,2
2
2,8
1
1
7,4
6,0
4,6
3,2
2
8,8
3
4
5
6
7
8
9
10
11
[V]
Diagram: Fan step at incoming 0-10V DC voltage level, 5 step
7,2
3
5,0
2
7,6
2,8
1
5,4
1
2
3,2
3
4
5
6
7
8
9
10
11
[V]
Diagram: Fan step for incoming 0-10V DC voltage level, 3-step.
General settings
Possibility of making general settings that are
also in the Start-up wizard and execute user
reset.
Function test
To test the fan and heating steps, run the
function test.
>Installer menu
External control
General settings
Support menu
>Installer menu>General
settings
Change the date, time, language and
temperature unit.
>Installer menu>General
settings
Set date
Set time
Set language
Function test
Start test
Skip test
>Installer menu>General
settings
Fan step 1-5
Heating step off-1
>Installer menu>General
settings
User reset
User reset (Room temp. day resp. night, high
speed limit, speed closed door, door, Summer
/ Winter) to factory setting.
Function test
Test completed
Restart test
Service menu
>Installer menu>General
settings
Function test
User reset
>Installer menu>User reset
Execute user reset?
No
Yes
The service menu is password protected and
is used for support in contact with Frico or
authorised installer.
35
GB
SIRe Competent Air Curtains Water
Alarm and error codes
SIRe has different alarms and error codes for
safe and problem free operation.
If alarms or error codes have been indicated
these must be reset in order to return to
normal operation, for example activating the
heating again. Fan mode is active even when,
for example, the over heating alarm has been
indicated.
The alarm remains in the control unit’s display. If the unit overheats twice within an
hour, the alarm must be reset before the heating can be engaged again, the fan operates
until the alarm is reset.
Note! In event of repeated alarms and over
heating alarms, carry out a thorough check
and if the fault cause cannot be found contact
authorised service person or Frico.
Power failure
Displaying alarm and error codes
In event of alarm or error the alarm/error
code is shown in the status window. In event
of alarm/error code the unit it applies to is
displayed.
See Table - Alarms and Table – Error codes.
Reset alarm
Note! Before resetting, check that the fault is
rectified and there is nothing to prevent the
unit from being recommissioned!
When the fault is rectified, the alarm is
reset by pressing the forward arrow and selecting Reset alarm and then confirm. If several
units give an alarm at the same time, the fact
that there are several alarms is indicated, but
only one is shown in the display. By resetting
that alarm the next alarm can be read.
At the first start up alarm and error codes
can occur, these can usually be reset without
action.
Overheat protection
Only applies to units with internal sensor.
The over heating protection is intended to
restrict the exhaust temperature to +40 °C.
At +40 °C the actuator for heat supply will
close. Actuator will open again if the internal
temperature drops below +35 °C. If the
temperature continues to rise despite this, for
example because of a faulty valve/actuator,
the fan will start to spin at +46 °C to keep the
temperature down. At the same time there
is an over heating alarm (Table - Alarm). At
internal temperatures of +50 °C the fan runs
at maximum speed.
If the unit cools, the heat is engaged again.
36
Note that in case of power failure the time
settings need to be checked, if the time is not
set correctly week program will be affected.
Frost protection function
Only applies to units with internal sensor.
The frost protection function is intended to
prevent the water coil from freezing.
If the internal temperature falls below +5 °C
frost protection alarm A3 is given, the valve
actuator opens and the fan stops.
Note! In event of repeated alarms, overheating alarms and frost protection alarms, carry
out a thorough check and if the fault cause
cannot be found contact authorised installer
or Frico.
SIRe Competent Air Curtains Water
GB
Table - Alarm
Alarm
A1 Motor alarm
Cause
Thermal switch has deployed. One
or several motors have overheated.
(Only units with withdrawn thermal
switches.)
A2 Over heating alarm The temperature in the unit has
exceeded the alarm limit for
overheating.
(Only applies to units with
internal unit temperature.)
Action
Check that nothing is obstructing the
unit’s air intake and exhaust. When the
overheated motor has cooled the thermal
switch shuts again and the alarm can be
reset. At repeated alarms, check the motors,
replace damaged motors.
Check that nothing is obstructing the unit’s
air intake and exhaust, the function of the
internal temperature sensor.
A3 Frost protection
alarm
The temperature in the unit has
fallen below the alarm limit for frost
protection. (Only applies to units
with internal unit temperature.)
Make sure that the ambient temperature
where the unit is installed exceeds +5°C.
Check the flow temperature, the flow of hot
water and the function of the actuator and
valve. In event of an alarm there a risk that
the battery is damaged, check carefully for
leakage and replace the battery if damaged.
A4 Filter alarm
Fixed run time before the filter
alarm has been reached.
Replace or clean the filter, adjust any alarm
time based on how dirty the filter was and
reset the alarm.
External alarm input on SIReC1X
has been activated.
Check the external alarm.
A5 Ext. alarm
37
GB
SIRe Competent Air Curtains Water
Table - Error codes
Error code
Cause
Action
E1
Communication
SIReB1(X) has no contact
with SIReC1X.
Check connection between the
boards. Replace any modular
cables.
E2
ID Error
Two or more SIReB1(X) have the
same ID-number.
Interrupt the current and select
different ID numbers for all
SIReB1(X) in the system.
E3
ID Error
One or more SIReB1(X) do not
have programs.
Contact Frico for support.
E4
Room sensor error
Fault on or missing external
room sensor SIReRTX connected
to SIReB1(X).
Always disconnect the power
when connecting or disconnecting
sensors. Check connection of the
sensor.
E8
Internal sensor faults
Fault on or missing internal sensor
in the unit.
(Only applies to units with internal
unit temperature.)
Check connection of the sensor. If
there is no sensor, contact Frico for
support.
E10
ID Error
Two or more SIReB1(X) in the
system have different programs.
Contact Frico for support.
E12
Room sensor error
Error in or missing external room
sensor SIReRTX connected to
SIReC1X.
Always disconnect the power
when connecting or disconnecting
sensors. Check connection of the
sensor.
E20
Communication
Control unit SIReUA1 has no
contact with SIReC1X.
Check the connection. Replace any
modular cables.
E21
Room sensor error
Error in the internal room sensor
in the control unit SIReUA1.
Check the connection between
SIReUA1 and SIReC1X. Replace any
modular cables. If the error is not
rectified SIReUA1 must be replaced.
E23
Soft ware error
Contact Frico for support.
38
GB
SIRe Competent Air Curtains Water
Connecting external control - including BMS functions
SIReC1X
COM 1
External on/off 5-30V AC/DC
External signal activates the unit.
Set parameter: >> Installer menu >
External control > External On/Off=
On
19 20
Alarm outgoing (BMS) (potentialfree switch, max 3A, 230V)
Outgoing alarm indication.
Always active.
Closed = buzzer alarm
Open = no alarm
17 18
Door switch (obligatory) (External
potential-free switch)
SIReDC indicates door status.
Potential-free switch from door
automatic or BMS can also be used.
Closed = door open
Open = door closed
1516
+ -
1112
+ -
External speed control 0-10V DC
Controls the fan speed in steps (see
diagram section External control
(BMS).
Set parameter: >> Installer menu
> External control > 0-10V Fan
control = On
9 10
External alarm IN (potential free
contact)
Input for external alarm. Closing
gives alarm.
7 8
External night reduction on/off
(potential-free switch)
Closes to activate the night
reduction function. Always active.
19 20
ALARM OUT (BMS)
ROOM
Door switch
15 161718
External ON/OFF
1112
+ -
Ext. speed ctrl. 0-10V DC IN
COM 2
External alarm IN
7 8 9 10
External night reduction
39
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
15 161718
EXTERNAL ON/OFF
5-30V AC/DC
1112
+ -
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
COM 1
COM 2
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
ROOM
X3
C1
X4
C2
Pot.
X5
Unit ID
SIReB1
230V~
PE N L
~
N L L
PE N L
SUPPLY 230V
ACTUATOR
230V
X3
ROOM
X4
C1
X5
C2
Wiring diagram - Competent
Internal PC Board Base
SD230
SIReC1X
7 8 9 10
ROOM
19 20
SIReRTX
(optional)
SIReDC
SIReUA1
SIRe Competent Air Curtains Water
C2
Pot.
X5
Unit ID
SIReB1X
C1
X4
ROOM
X3
~
N L L
L
230V~
PE N
SD230
For wiring of external PC board
base see separate manual for
SIReB1X
Wiring diagram - Competent
External PC Board Base
COM 1
COM 2
SIReC1X
7 8 9 10
15 161718
EXTERNAL ON/OFF
5-30V AC/DC
1112
+ -
ROOM
19 20
SIReDC
SIReRTX
(optional)
SIReUA1
SIRe Competent Air Curtains Water
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL RPM 0-10V DC IN
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
C2
Pot.
X5
Unit ID
SIReB1
C2
Pot.
X5
Unit ID
SIReB1
C2
Pot.
X5
Unit ID
SIReB1
C1
X4
C1
X4
C1
X4
X5
C2
ROOM
X3
ROOM
X3
ROOM
X3
X4
C1
PE N L
SUPPLY 230V
ACTUATOR
230V
~
N L L PE N L
ACTUATOR SUPPLY
~
N L L PE N L
ACTUATOR SUPPLY
~
N L L PE N L
ACTUATOR SUPPLY
X3
ROOM
SD230
SD230
SD230
Wiring diagram - Competent- parallel connection
COM 1
COM 2
SIReC1X
7 8 9 10
15 161718
EXTERNAL ON/OFF, 5-30V AC/DC
1112
ROOM
19 20
SIReUA1
SIReRTX
(optional)
SIRe Competent Air Curtains Water
ALARM OUT (BMS)
(potential free contact,max 3A, 230V)
EXTERNAL RPM 0-10V DC IN
DOOR CONTACT
(potential free contact)
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
Tel: +46 31 336 86 00
Fax: +46 31 26 28 25
[email protected]
www.frico.se
For latest updated information and information
about your local contact: www.frico.se
Art no: E4444, 2012-11-20 HH/ SÅ/ SÄ
Main office
Frico AB
Box 102
SE-433 22 Partille
Sweden