H609
CURRENT MONITORING
INSTALLATION GUIDE
TM
609
Split-Core Current Switch, Adjustable Trip Point
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
CONTACTOR
Insulated Conductor ONLY
DDC CONTROLLER
DI
Installer’s Specifications
Amperage Range
External Supply Voltage
1.25-50 A Continuous
Induced from monitored conductor
Frequency 50/60 Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range
Hysteresis
Status Output Ratings
Terminal Block Max. Wire Size
Terminal Block Torque (nom.)
Insulation Class
Agency Approvals
10-90% RH non-condensing
10% typical
N.O. 0.2 A@120 VAC/DC
14 AWG
4 in-lbs (0.45 N-m)
600 VAC RMS (UL)
UL508, E150462
The unit design provides for basic insulation only.
INSTALLATION
Disconnect and lock out power to the enclosure containing the conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow the monitored conductor to pass through the center window when it is installed and that will keep the product at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
3. Wire the output connections between the sensor and the controller (solid-state contact).
4. Snap the sensor over the wire to be monitored and clip the assembly to the mounting bracket.
5. Calibrate the sensor (see page 2) with the load running normally.
6. Secure enclosure and reconnect power.
DIMENSIONS
Removable Mounting Bracket
2.1"
(54 mm)
0.6"
(16 mm)
0.5"
(13 mm)
0.7"
(18 mm)
1.2"
(31 mm)
2.5" *
(64 mm)
2.1"
(54 mm)
Fan
1.0" *
(26 mm)
Motor
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x) 2.9"
(74 mm)
3.5"
(89 mm)
Z201761-0D PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 01121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
H609
TM
OPERATION
The H609 is a current-sensitive switching device that monitors current (amperage) in the conductor passing through it. A change in the conductor’s amperage that crosses the adjustable switch threshold plus the hysteresis value causes the resistance of the FET status output to change state, similar to the action of a mechanical switch.
In this model, the setpoint is adjustable through the action of a twenty (20) turn potentiometer (see the CALIBRATION section). The status output is suitable for connection to building controllers or other appropriate data acquisition equipment operating at up to 120 volts. The H609 requires no external power supply to generate its output.
INSTALLATION GUIDE
CALIBRATION
Before beginning calibration, establish normal load conditions.
OK!
OK!
A
Then choose either A or B below.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be combined with wrapping (see below) to add range for a low current load on a high current source.
240A > 50A (Sensor max.)
A. To monitor under-current (belt loss, coupling shear, status)
!
OK!
STATUS
OK!
A
1. Turn setpoint screw clockwise until Status Open
LED turns ON.
Status
Open Setpoint
STOP
2. Slowly turn the screw counter-clockwise until the Status Closed LED just turns ON.
Setpoint
Status
Closed
STOP
+
Setpoint
1/4
3.Turn the screw an additional 1/4 turn counter-clockwise for operational margin.
300A: 5A
B. To monitor over-current (mechanical problems, seized impeller)
Portla nd, Oregon
97223
1-800-354-
8556
®
Hawkeye H68xx-5A CT
4A
!
OK!
A
STATUS
OK!
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases the current measured by the transducer.
< 1.25 A (Sensor Min.)
0.5A
4x
Hawkeye
556
®
1. Turn setpoint screw counter-clockwise until Status
Closed LED turns on.
Setpoint
STOP
2. Slowly turn the setpoint screw clockwise until the Status Open LED just turns on.
Status
Open Setpoint
STOP
+
Setpoint
1/4
3. Turn the setpoint screw an additional 1/4 turn clockwise for operational margin.
TROUBLESHOOTING
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (<120V)
• Check for amperage in monitored conductor (> 1.25A)
• Assure that sensor core mating surfaces are clean and that the core clamp is completely closed
Setpoint screw has no stops
The setpoint screw has a slip-clutch at both ends of its travel to avoid damage. Twenty turns CCW will reset the sensor to be most sensitive. Repeat calibration above.
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
Z201761-0D PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 01121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.