Exit Signs Catalogue
Introducing new Pictogram Exit Signs
To harmonize with existing international standards (ISO 7010 and ISO 3864-1), the National
Building Code of Canada (NBC) released at the end of 2010 introduces a major change to
emergency lighting signage. The new NBC replaces the traditional EXIT, SORTIE legend using
letters and chevrons with a Pictogram (the running man) and, when needed, a large directional
arrow.
The colors of the Pictogram legend are green and bright white instead of the red letters and
opaque background (white, black, etc.) of the EXIT, SORTIE signs. The entire Pictogram legend
surface (both colors) must be illuminated in normal and emergency lighting modes.
The Pictogram legend has three main configurations: “left from here,” “straight from here,” and
“right from here”.
Other orientations of the arrow are allowed in increments of 45 degrees. Unlike the EXIT,
SORTIE legend, the Pictogram legend cannot use peel-off arrows, since the “left” and “right”
legends do not use a common running man.
With the new Pictogram signs, there is no legend with two arrows (left and right). Double
arrow configurations require two signs.
Following the NBC modifications, the Canadian Standards Association revised the main
standard for emergency lighting: CSA22.2 No.141-10. The CSA revision includes two annexes
dedicated to the tests and performance of the EXIT/SORTIE and Pictogram signs. Equipment
manufacturers can offer both types of signage during the transition period.
Provincial building codes may adopt the NBC as is or with modifications. A special dispensation
may be requested to use the Pictogram signs before local codes have been approved. These
dispensations may or may not be granted by the local authority having jurisdiction. The local
building authority should be contacted to determine which signs should be used.
Table of content
RA Series
Extruded Aluminum Pictogram Exit Sign
RS Series
All-Metal Pictogram Exit Sign
RN Series
NEMA-4X Rated Pictogram Exit Sign
RH Series
LED Pictogram Exit Sign for Hazardous Locations
RDE Series
Die-Cast Aluminum Pictogram Edge-Lit Exit Sign
RAE Series
Aluminum Slim Edge-Lit Sign
RAC Series
Extruded Aluminum Combination Unit
RSC Series
5
6
7
8
10
11
12
Steel Combination Unit
RNC Series
NEMA 4X Certified Combination Unit
RHC Series
Combination Unit for Hazardous Locations
3
4
13
14
www.readylite.com
Project/Location:
RA Series
Contractor:
Extruded Aluminum
Pictogram Exit Sign
Date:
Prepared by:
Versatile, smooth finish, pictogram exit signage
Features
Typical Specification
Supply and install the Ready-Lite® RA Series pictogram exit signs. The equipment shall operate with universal 2-wire AC
input voltage of 120 to 347VAC at less than 2.5 Watts and universal 2-wire DC input voltage from 6 to 24VDC at less than
1.5 Watts for single and double face signs. The equipment shall be suitable for wall, end, or ceiling mount. The housing shall
be constructed of rugged extruded aluminum and have a maximum depth of 2-1/2”. The faceplate(s) shall be constructed of
extruded Aluminum and shall incorporate a protective clear poly-carbonate panel. Each face plate shall come standard with
two legend films for pictogram and direction selection. The light source shall be white light-emitting diodes (LED) and shall
provide even illumination in normal and emergency operation. The pictogram exit sign in a Self-Powered configuration shall
use a sealed Nickel-Cadmium battery of 2.4V nominal voltage and shall stay illuminated during emergency operation for at
least two hours upon AC failure.
• Durable extruded, one-piece Aluminum housing
and face plates
•White LED light source
• Supplied standard with two pictogram films per
face, for direction selection
• Meets or exceeds CSA 22.2 No.141-10 standard
for pictogram exit signs
• Universal AC input: two-wire 120 to 347VAC;
standard DC input: two-wire 6 to 24VDC
The pictogram exit sign shall meet or exceed the CSA 22.2 No.141-10 standard.
• Energy efficient – consumes less than 2.5 Watts in
AC or DC-remote mode
• Self-Powered model gives standard two hours of
back-up lighting
The equipment shall be Ready-lite® Model:
.
Dimensions
• Universal mounting – end, wall or ceiling
• Easy access to wiring entry for all mounting options
• Comes standard with the Ready-lite® EZ2 canopy
for quick and easy installation
Wire Guards
460.0079-RL
Wall mount
460.0027-RL
End mount
460.0028-RL
Ceiling mount
Power Consumption
Model
AC Specs
DC Specs
AC-only
120 to 347VAC
Less than 2.5 W
-
-
AC/DC standard
120 to 347VAC
Less than 2.5 W
6 to 24VDC
Less than 1.5 W
AC/Special DC
120 to 347VAC
Less than 2.5 W
36, 48, 120VDC
Less than 2.5 W
Two-wire 120V AC/DC
120VAC
Less than 2.5 W
120VDC
Less than 2.5 W
Self-Powered
120 to 347VAC
Less than 3 W
Ni-Cd battery
Min. two hours
Ordering Information
Series
RA= extruded aluminum
pictogram exit sign
Faces / Mounting
Colour
1= single face universal mount
2= double face universal mount
W= factory white
B= black
G= grey
A= brushed aluminum
Other colours available
Voltage
Options
U= 120 to 347 VAC; 6 to 24 VDC
SP= 120 to 347 VAC; Self-Powered / 2 hours
U00= 120 to 347 VAC only
U36= 120 to 347 VAC; 36 VDC
U48= 120 to 347 VAC; 48 VDC
U120= 120 to 347 VAC; 120 VDC
2120= 2-wire 120 VAC/VDC
TP= tamper proof screws
VR= vandal-resistant shield and tamper-proof screws
990.0119-RL= tamper-proof bit*
Example: ra1wutp
*One bit per order. Sold separately.
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
4
Project/Location:
Contractor:
RS Series
Date:
All-Metal Pictogram Exit Sign
Prepared by:
Labour-saving, Steel pictogram exit sign
Features
Typical Specification
Supply and install the Ready-lite® RS Series pictogram exit signs. The equipment shall operate with universal 2-wire AC
input voltage of 120 to 347VAC at less than 2.5 Watts and universal 2-wire DC input voltage from 6 to 24VDC at 1 Watt
consumption for single and double face signs. The sign shall be suitable for wall, end, or ceiling mount. The frame and back
plate shall each be of a one-piece steel construction. The faceplate(s) shall be constructed of robust clear
poly-carbonate panels with an opaque border coloured factory-white. Each face plate shall come standard with two legend
films for pictogram and directional indicators. The light source shall be white light-emitting diodes (LED) and shall provide
even illumination in normal and emergency operation. The pictogram exit sign in a Self-Powered configuration shall use a
sealed Nickel-Cadmium battery of 2.4V nominal voltage and shall stay illuminated during emergency operation for at least
two hours upon AC failure.
• Metal construction using Canadian cold-rolled steel
• Based on a modular design, this product comes
pre-assembled for quick, easy installation
• Long-life white LED light source
• Supplied standard with two pictogram films per
face, for direction selection
• Meets or exceeds CSA 22.2 No.141-10 standard
for pictogram exit signs
The exit sign shall meet or exceed the requirements of CSA 22.2 No.141-10 standard.
The equipment shall be Ready-lite® Model:
•Two-wire universal AC input: 120 to 347VAC; twowire standard DC input: 6 to 24VDC
.
• Energy efficient – consumes less than 2.5 Watts in
AC mode and only 1W in DC-remote
Dimensions
• Self-Powered model delivers standard two hours of
back-up lighting
• Universal mounting – end, wall or ceiling
• Easy access to wiring entry for all mounting options
• Canopy mounting system designed specifically for
ease of installation
Wire Guards
460.0079-RL
Wall mount
460.0027-RL
End mount
460.0028-RL
Ceiling mount
Power Consumption
Model
AC Specs
DC Specs
AC-only
120 to 347VAC
Less than 2.5 W
-
-
AC/DC standard
120 to 347VAC
Less than 2.5 W
6 to 24VDC
Less than 1.5 W
AC/Special DC
120 to 347VAC
Less than 2.5 W
36, 48, 120VDC
Less than 2.5 W
Two-wire 120V AC/DC
120VAC
Less than 2.5 W
120VDC
Less than 2.5 W
Self-Powered
120 to 347VAC
Less than 3 W
Ni-Cd battery
Min. two hours
Ordering Information
Series
RS= pictogram steel exit sign
Faces/Mounting
1= single face universal mounting
2= d ouble face universal mounting
Voltage
Colour
U= 120 to 347 VAC; 6 to 24 VDC
SP= 120 to 347 VAC; Self-Powered / 2 hours
U00= 120 to 347 VAC only
U36= 120 to 347 VAC; 36 VDC
U48= 120 to 347 VAC; 48 VDC
U120= 120 to 347 VAC; 120 VDC
2120= 2-wire 120 VAC/VDC
Example: RS1UWVR
W= factory white
B= black
G= grey
Other colours available
Options
TP= tamper proof screws
VR= v andal-resistant shield and tamper proof screws
990.0119-RL= tamper proof bit*
*One bit per order. Sold separately.
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
5
Project/Location:
RN Series
Contractor:
NEMA-4X Rated Pictogram Exit Sign
Date:
All-climate, harsh environment
pictogram exit signage
Prepared by:
Features
Typical Specification
Supply and install the Ready-Lite® RN Series pictogram exit signs. The equipment shall be certified for NEMA-4X and
designed specifically for high abuse areas, wet location, and cold weather applications. The equipment frame shall be of
industrial grade polyvinyl chloride with a gasket around lenses and canopy. The faceplate(s) shall be constructed of heavyduty vandal-resistant polycarbonate and feature an even illuminated legend. Each face plate shall come standard with two
legend films for pictogram and direction selection. The light source shall be white light-emitting diodes (LED). The pictogram
exit sign shall operate with universal 2-wire AC input voltage of 120 to 347VAC at less than 2.5 Watts and universal
2-wire DC input voltage from 6 to 24VDC at less than 1 Watt for single and double face signs. The Self-Powered model
shall include a concealed green pilot light and magnet-sensitive test switch, shall use a sealed Nickel-Cadmium battery of
2.4V nominal voltage and shall stay illuminated during emergency operation for at least two hours upon AC failure. When
specified, the Self-Powered model shall include self-diagnostic functions: it shall execute automatic tests for 5 minutes
every 30 days, 30 minutes every 60 days and two hours annually. When a fault is detected, the bi-colour pilot light shall turn
from green to red and flash following a particular code. The code description shall be visible on a label next to the pilot light
to identify the failure type: battery, charger circuitry, or LED lamps.
• NEMA-4X Certified
• NSF compliant for food processing
• Polymeric enclosure is fully gasketed around lens
and canopy to secure against water leaks
• Sealed, heavy-duty, vandal-resistant polycarbonate
face plate
• Suitable for cold-weather: -40°C for AC/DC and
-20°C for Self-Powered models (option: -CW)
•Tamper-resistant, concealed test switch with
magnetic action
•White LED light source
The pictogram exit sign shall meet or exceed the CSA 22.2 No.141-10 standard.
• Supplied standard with two pictogram films per
face, for direction selection
The equipment shall be Ready-Lite® Model:
• Meets or exceeds CSA 22.2 No.141-10 standard
for pictogram exit signs
.
Dimensions
• Universal AC input: two-wire 120 to 347VAC;
Standard DC input: two-wire 6 to 24VDC
• Energy efficient – consumes less than 2.5 Watts in
AC or DC-remote mode
• Self-Powered models deliver two hours of back-up
lighting
®
NEMA-4X
Wire Guards
460.0079-RL
Wall mount
460.0027-RL
End mount
460.0028-RL
Ceiling mount
Power Consumption
Model
AC Specs
DC Specs
AC-only
120 to 347VAC
Less than 2.5 W
-
-
A C/DC standard
120 to 347VAC
Less than 2.5 W
6 to 24VDC
Less than 1 W
AC/Special DC
120 to 347VAC
Less than 2.5 W
36, 48, 120VDC
Less than 2.5 W
Two-wire 120V AC/DC
120VAC
Less than 2.5 W
120VDC
Less than 2.5 W
Self-Powered
120 to 347VAC
Less than 3 W
Ni-Cad battery
Min. two hours
Self diagnostics
120 / 347VAC
Less than 3.5 W
Ni-Cad battery
Min. two hours
Ordering Information
Series
Faces / Mounting
Colour
Voltage
Options
RN= NEMA-4X &
NSF pictogram
exit sign
1= single face universal mounting
2= double face universal mounting
W= factory white
B= black
SP= 120 to 347 VAC; Self-Powered / 2 hours
SPD= 120/347 VAC; Self-Powered / 2 hours c/w non-audible diagnostic
SPD2= 120/ 277VAC; Self-Powered / 2 hours c/w non-audible diagnostic
U= universal 120 to 347 VAC; 6 to 24 VDC
U00= 120 to 347 VAC only
U36= 120 to 347 VAC; 36 VDC
U48= 120 to 347 VAC; 48 VDC
U120= 120 to 347 VAC; 120 VDC
2120= 2-wire 120 VAC/VDC
CW= cold-weather (-20°C for spwrd, -40°C for AC/DC)
FA= fire alarm-activated flasher (AD model only)
FB= flasher / buzzer in emergency mode (AD model only)
NEX= NEXUS® system interface*
NEXRF= wireless NEXUS® system interface*
Example: RN1BUCW
*Note: some options are not available with NEXUS® system
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
6
RH Series
Project/Location:
LED Pictogram Exit Sign for
Hazardous Locations:
Contractor:
Date:
Class I Zone 2 Groups: IIA, IIB and IIC
Class I Division 2 Groups: A, B, C and D
Prepared by:
Typical Specification
Features
Supply and install the Ready-lite® RH Series of pictogram exit signs. The equipment shall be certified for Hazardous
Locations: Class I Division 2 Groups A, B, C and D with a temperature code T6 (Maximum 85ºC). The equipment frame shall
be of industrial grade polyvinyl chloride with a gasket around lenses and canopy. The faceplate(s) shall be constructed of
heavy-duty vandal-resistant polycarbonate and feature an even illuminated pictogram legend. Each face plate shall come
standard with two legend films for pictogram and direction selection. The light source shall be long-life white light-emitting
diodes (LED). The pictogram exit sign shall operate with universal 2-wire AC input voltage of 120 to 347VAC at less than 2.5
Watts and universal 2-wire DC input voltage from 6 to 24VDC at less than 1 Watt for single and double face signs. The SelfPowered model shall include a concealed pilot light and magnet-sensitive test switch, shall use a sealed Nickel-Cadmium
battery of 2.4V nominal voltage and shall stay illuminated during emergency operation for at least two hours upon AC
failure. The Self-Powered model shall include self-diagnostics functions: it shall execute automatic tests for 5 minutes every
30 days, 30 minutes every 60 days and two hours annually. When a fault is detected, the bi-colour pilot light shall turn from
green to red and flash following a particular code. The code description shall be visible on a label next to the pilot light to
identify the failure type: battery, charger circuitry, or LED lamps.
• Compliant Class I Division 2, Groups A, B, C and D
as per CSA C22.2 No.137-M1981
• Class I Zone 2 Groups IIA, IIB, IIC
•Temperature Code T6 (maximum +85°C) as per
Canadian Electrical Code, Part I and CSA C22.2
No.137-M1981
• High-impact thermo-plastic frame with built-in
gasket to secure against liquid leaks
• Sealed, heavy-duty, vandal-resistant polycarbonate
face plate(s)
• Concealed pilot light and test switch with magnetic
action
The pictogram exit sign shall meet or exceed the CSA 22.2 No.141-10 standard.
The equipment shall be Ready-lite® Model:
• Long-life white LED light source
.
• Supplied standard with two pictogram films per
face, for direction selection
Dimensions
• Meets or exceeds CSA 22.2 No.141-10 standard
for pictogram exit signs
• Universal AC input: two-wire 120 to 347VAC;
standard DC input: two-wire 6 to 24VDC
4
• Energy efficient – consumes less than 2.5 Watts in
AC or DC-remote mode
[11.0cm]
43/8” [11.1cm]
3/8”
• Self-Powered models come standard with
self-diagnostics functions and deliver two hours of
back-up legend illumination
21/4” [5.7cm]
91/4” [23.4cm]
• Suitable for cold-weather: -40°C for AC/DC and
-20°C for Self-Powered models (option: -CW)
®
131/4” [33.6cm]
31/2” [8.9cm]
Power Consumption
Model
AC Specs
DC Specs
AC-only
120 to 347VAC
Less than 2.5 W
-
-
AC/DC standard
120 to 347VAC
Less than 2.5 W
6 to 24VDC
Less than 1 W
AC/Special DC
120 to 347VAC
Less than 2.5 W
36, 48, 120VDC
Less than 2.5 W
Two-wire 120V AC/DC
120VAC
Less than 2.5 W
120VDC
Less than 2.5 W
Self-diagnostics
120 / 347VAC
Less than 3.5 W
Ni-Cd battery
Min. two hours
Ordering Information
Series
RH= CL.I Div.2 pictogram
exit sign
Faces*
1= single face
2= d ouble face
*Ceiling or wall mount only.
Housing Colour
G= grey
Voltage
SPD= 120/347 VAC; Self-Powered / 2 hours c/w non-audible diagnostic
SPD2= 120/ 277VAC; Self-Powered / 2 hours c/w non-audible diagnostic
U= universal 120 to 347 VAC; 6 to 24 VDC
U00= 120 to 347 VAC only
U36= 120 to 347 VAC; 36 VDC
U48= 120 to 347 VAC; 48 VDC
U120= 120 to 347 VAC; 120 VDC
2120= 2-wire 120 VAC/VDC
Example: RH1GU
Options
CW= c old-weather (-20°C for spwrd, -40°C for AC/DC)
FA= fi re alarm-activated flasher (AD model only)
FB= fl asher / buzzer in emergency mode (AD model only)
NEX= NEXUS® system interface*
*Note: some options are not available with NEXUS® system
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
7
Project/Location:
RDE Series
Contractor:
Date:
Die-Cast Aluminum Pictogram
Edge-Lit Exit Sign
Features
Prepared by:
Typical Specification
Supply and install the Ready-lite® RDE Series of die-cast pictogram edge-lit signs.
• Listed CSA 22.2 No.141-10
• Self-Powered models provide minimum 90 minutes
of emergency lighting
• Die-cast Aluminum construction
• Modular design offers great choice of architectural
profiles
• Universal die-cast back-box for surface or semirecessed mounting on ceilings or walls
• LED strip module can be rotated in the unit for
either wall or ceiling mount
• Flat die-cast trim plate and galvanized steel backbox for recessed ceiling mount
• Clear acrylic panel with pictogram legend
• Comes standard with double-face panels for use in
single-face and double-face applications
•White LED light source
• Universal AC input: two-wire 120 to 347VAC;
universal DC input: two-wire 6 to 24VDC
When specified for surface mount, the unit shall come standard with a trim plate, trim ring, back box and canopy made
of die-cast aluminum with _____ finish. The trim plate shall have a _____ profile and allow for wall- or ceiling-mount
installation. The trim ring shall allow for semi-recessed installation in walls or ceilings with cavity. The canopy shall allow for
wall, end, or ceiling mount.
When specified for recessed ceiling-mount, the unit shall come standard with a flat trim plate of die-cast aluminum with
_____ finish, a back box of galvanized steel, and a hardware kit for back box installation between ceiling joists. The back
box shall be provided with conduit knock-outs at the top, back and end.
All edge-lit units shall have the trim plate snap and lock in the housing with torsion spring retainers, thereby eliminating
any visible screws or hardware. The legend shall be printed on a clear acrylic panel. The panel shall come standard with
double-face legend, for single-face and double-face applications. The light source shall be long-life white light-emitting
diodes (LED) and shall provide even illumination in normal and emergency operation. The edge-lit sign shall operate with
universal 2-wire AC input voltage of 120 to 347VAC at less than 2.5 Watts and universal 2-wire DC input voltage from 6 to
24VDC at less than 2.5 Watts. The edge-lit sign in a Self-Powered configuration shall use a sealed Nickel-Cadmium battery
of 2.4V nominal voltage and shall stay illuminated during emergency operation for at least 90 minutes upon AC failure.
When specified, the Self-Powered unit shall include non-audible self-diagnostics functions, managed by a micro-controller:
it shall execute automatic tests for 5 minutes every 30 days, 30 minutes every 60 days and two hours annually. When a
fault is detected a red flashing LED shall identify the failure type: battery, charger circuitry, or LED lamps.
The edge-lit sign shall be listed CSA 22.2 No.141-10.
• Energy efficient – consumes less than 2.5 Watts in
AC and DC-remote modes
The equipment shall be Ready-lite® Model: _____________________ .
Power Consumption
Model
AC Specs
DC Specs
AC-only
120 to 347VAC
Less than 2.5W
-
-
AC/DC standard
120 to 347VAC
Less than 2.5W
6 to 24VDC
Less than 2.5W
Self-Powered
120 to 347VAC
Less than 3.5W
Nickel-Cadmium battery
Minimum 90 minutes
Self-Powered diagnostic
120/347VAC
Less than 3.5W
Nickel-Cadmium battery
Minimum 90 minutes
Ordering Information
Series
RDE= die-cast edge-lit pictogram exit sign
Faces / Arrow
(Universal Mounting)
2= universal two-face, no arrow
A= universal two-face, arrow left-right
Colour
Trim
A= brushed aluminum
B= black
C= chrome
P= polished brass
W= factory white
Z= bronze
A= angular
C= circular
F= flat (fully recessed)
Example: RDE2wadc
Voltage
AC= AC only, 120 to 347VAC
DC=120 to 347VAC, 6 to 24VDC
SP= Self-Powered, 120 to 347VAC
SD= Self-Powered with non-audible diagnostic, 120/347VAC
SD2= Self-Powered with non-audible diagnostic, 120/277VAC
U48= 120 to 347VAC, 48VDC
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
8
Project/Location:
Contractor:
Date:
Prepared by:
RDE Series
Die-Cast Aluminum Pictogram
Edge-Lit Exit Sign
Dimensions
9
Project/Location:
Contractor:
RAE Series
Date:
Prepared by:
Aluminum Slim Edge-Lit Sign
Features
Typical Specification
• Extruded acrylic panel with pictogram legend
Supply and install the Ready-lite® RAE Series of slim-profile pictogram edge-lit exit signs. The unit shall operate with
universal 2-wire AC input voltage of 120 to 347VAC at less than 3 Watts and universal 2-wire DC input voltage from 6 to
24VDC at less than 2.5 Watts for single and double face legends. The housing assembly shall be constructed of extruded
aluminum with textured finish and _____ colour. The canopy shall be of die-cast aluminum and allow for wall, end, or
ceiling mount. The legend shall be printed on a pure-acrylic panel. The panel shall come standard with double-face legend.
The light source shall be long-life white light-emitting diodes (LED) and shall provide even illumination in normal and
emergency operation. The pictogram edge-lit exit sign in a Self-Powered configuration shall use a sealed Nickel-Cadmium
battery of 2.4V nominal voltage and shall stay illuminated during emergency operation for at least two hours upon AC
failure.
• Comes standard with double-face panels for use in
single-face and double-face applications
The pictogram edge-lit exit sign shall meet or exceed the CSA 22.2 No.141-10 standard.
• Long-life white LED light source
The equipment shall be Ready-lite® Model:
• Meets or exceeds CSA 22.2 No.141-10 standard
for pictogram exit signs
Dimensions
• Slim-profile extruded Aluminum housing
• Low-profile EZ2 die-cast Aluminum canopy
• Universal surface mounting – wall, ceiling or end
mount
• Click-to-open housing door allows easy access to
the panel and electrical wiring
.
• Universal AC input: two-wire 120 to 347VAC;
standard DC input: two-wire 6 to 24VDC
• Energy efficient – consumes less than 3 Watts in
AC or DC-remote mode
• Self-Powered models provide minimum two hours
of emergency lighting
Power Consumption
Model
AC Specs
DC Specs
AC-only
120 to 347VAC
Less than 3W
-
-
AC/DC standard
120 to 347VAC
Less than 3W
6 to 24VDC
Less than 2.5W
AC/48VDC
120 to 347VAC
Less than 3W
48VDC
2W
AC/120VDC
120 to 347VAC
Less than 3W
120VDC
4.7W
Two-wire 120V AC/DC
120VAC
Less than 3.5W
120VDC
Less than 3.5W
Self-Powered
120 to 347VAC
Less than 4W
Nickel-Cadmium battery
Minimum two hours
Ordering Information
Series
RAE= extruded aluminum pictogram edge-lit exit sign
Faces / Arrow
(Universal Mounting)
Colour
2= universal two-face, no arrow
A= universal two-face, arrow left or right
TA= textured aluminum
OW= off-white
Example: RAE2OWDC
Voltage
AC= 120 to 347VAC Only
DC= 120 to 347VAC; 6 to 24VDC
SP= 120 to 347VAC; Self-Powered / 2 hours
U48= 120 to 347VAC; 48VDC
U120= 120 to 347VAC; 120VDC
2120= 2-wire 120VAC/VDC
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
10
Project/Location:
Contractor:
RAC Series
Date:
Prepared by:
Extruded Aluminum Combination Unit
Typical Specification
Supply and install Ready-lite® RAC Series combination of unit equipment and pictogram exit sign. The unit shall be
suitable for universal mounting: wall, end, or ceiling. The unit shall include a power pack made of steel and a legend housing
including a one-piece extruded aluminum frame. The legend housing shall have a maximum depth of 2-1/2”. The face
plate(s) shall be of extruded Aluminum and shall incorporate a protective clear polycarbonate panel. Each face plate shall
come standard with two legend films for pictogram and direction selection. The light source shall be white light-emitting
diodes (LED) and shall provide even illumination in normal and emergency operation. The power pack shall be complete
unit equipment with battery charger and rechargeable battery. The battery shall be maintenance-free, sealed Lead-Calcium.
In case of AC power failure the equipment shall provide minimum 30 minutes of emergency lighting. The rated DC power
available for emergency lights shall be 27 Watts or up to 80 Watts, as specified. The emergency heads shall require no tools
to adjust and aim. The heads shall be made of durable thermoplastic construction and include 4-watt MR16 LED lights or as
otherwise specified.
Units with “self-diagnostics option” shall include a micro-controller circuit to monitor all the critical functions of the
equipment and execute periodical tests of: one minute every 30 days, 10 minutes every 6 months and 30 minutes every 12
months. In case of equipment malfunction, an LED-based diagnostic display shall generate a service alarm and indicate the
cause of failure: battery, charger circuit, emergency lamps or exit sign lamps.
The equipment shall meet or exceed the requirements of CSA 22.2 No.141-10 standard.
The equipment shall be Ready-lite® Model:
Features
• Solid metal construction, painted factory white
• Universal mounting: end, wall or ceiling
• Meets or exceeds CSA 22.2 No.141-10 standard
for unit equipment and pictogram safety signs
• Legend illuminated by long-life white LED’s
• Comes standard with two pictogram films per face,
for direction selection
• Comes standard with two high-performance 4 Watt
MR16 LED lamps
•Twin 4-watt LED emergency lights provide 34 - 40
feet of egress illumination on a 6-foot wide path
• Sealed, maintenance-free Lead-Calcium battery
• Remote load capacity: 70 up to 350 feet of egress
illumination when using LED remote heads
.
Dimensions
®
Wire Guards
460.0081-RL
Wall mount
460.0060-RL
Ceiling mount
Power Consumption
Model
AC Specs
Pictogram module
RAC-627
RAC-640
RAC-672
RAC-1250
RAC-1280
30 min.
120/347VAC
Less than 1.5W
120/347VAC
0.15 / 0.05 Amp
120/347VAC
0.25 / 0.09 Amp
27
40
72
50
80
Emergency power available for lamps
1 hr.
1.5 hrs.
2 hrs.
16
23
42
29
46
11
16
30
21
32
9
13
24
16
27
4 hrs.
12
8
13
Ordering Information
Series
Faces / Mounting
Colour
RAC= Pictogram aluminum
combination unit
1= single face
2= double face universal
mounting
W= factory white
B= black
Power em. lights
627= 6V-27W
640= 6V-40W
672= 6V-72W
1250= 12V-50W
1280= 12V-80W
Heads
Head style and power
Blank= no heads
1= one head
2= two heads
EXAMPLE: RAC1W6272LD1
Blank= no heads
LD1= MR16 LED 6V-4W
LD7= MR16 LED 12V-4W
MI= MR16 halogen 6V-6W
MJ= MR16 halogen 6V-10W
MK= MR16 halogen 12V-12W
MA= MR16 halogen 12V-20W
RQ8= mini-halogen, 8W
RQ12= mini-halogen, 12W
RT9= mini-tungsten, 9W
Options
AD= auto-diagnostics, audible*
ADN= auto-diagnostics, non-audible*
D3= time delay 15 minutes**
TP= tamper-proof screws***
U2= 120/277VAC input
NEX= NEXUS® system interface
NEXRF= wireless NEXUS® system interface
* Not available with 6V 72W
** Time delay only with auto-diagnostics
*** Bit ordered separately: 990.0119-RL
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
11
Project/Location:
Contractor:
RSC Series
Date:
Prepared by:
Steel Combination Unit
Features
Typical Specification
Supply and install Ready-lite® RSC Series combination of unit equipment and pictogram exit sign. The unit shall be
made of solid steel sheet metal and be suitable for universal mounting: wall, end, or ceiling. The legend housing shall have
a maximum depth of 2-1/8”. The legend face plate(s) shall be constructed of robust clear polycarbonate panel(s) with
an opaque border coloured factory-white. Each face plate shall come standard with two legend films for pictogram and
direction selection. The light source shall be white light-emitting diodes (LED) and shall provide even illumination in normal
and emergency operation. The power pack shall include one circuit board with test switch and pilot light for battery charger
and legend LED driver. The unit shall include one 6-volt, maintenance-free, sealed Lead-Calcium battery and shall provide
minimum 30 minutes of emergency lighting upon AC power failure. The electrical power available for emergency lights shall
be 28 Watts or up to 72 Watts, as specified. The emergency heads shall require no tools to adjust and aim. The heads shall
be made of durable thermoplastic construction and include 6 Volt 4 Watt MR16 LED lights or as otherwise specified.
• Universal mounting: end, wall or ceiling
• Meets or exceeds CSA 22.2 No.141-10 standard
for unit equipment and pictogram exit signs
• Legend illuminated by long-life white LED’s
• Comes standard with two pictogram films, for
direction selection
• Comes standard with two high-performance
4 Watts MR16 LED lamps
• 4 Watts LED emergency lights provide 34 feet of
egress illumination on a 6-foot wide path
The equipment shall meet or exceed the requirements of CSA 22.2 No.141-10 standard.
The equipment shall be Ready-lite® Model:
• Sealed, maintenance-free, 6 Volt Lead-Calcium
battery
• Remote load capacity: 80 up to 270 feet of egress
illumination when using LED remote heads
.
Dimensions
®
Wire Guards
460.0081-RL
Wall mount
460.0060-RL
Ceiling mount
Power Consumption
Model
AC Specs
Pictogram module
120/347VAC
30 min.
Less than 1.5W
RSC28
RSC44
120/347VAC
0.13 / 0.05 Amp
RSC72
Emergency power available for lamps
1 hr.
1.5 hrs.
2 hrs.
4 hrs.
-
-
-
-
-
28
16
12
9
-
44
26
18
15
7
72
42
30
24
12
Ordering Information
Series
RSC= pictogram steel
combo exit sign
Power em. lights
28= 6V-28W
44= 6V-44W
72= 6V-72W
Colour
W= factory white
B= black
Heads
Head style and power
Blank= no head
1= one head
2= two heads
Blank= no head
LD1= MR16 LED 6V-4W
RQ8= mini-halogen, 8W
RQ12= mini-halogen, 12W
RT9= mini-tungsten, 9W
MI= MR16 halogen 6V-6W
MJ= MR16 halogen 6V-10W
Options
DF= double-face sign
D3= time delay (15 minutes)
TP= tamper-proof screws*
U2= 120/277VAC input
NEX= NEXUS® system interface**
NEXRF= wireless NEXUS® system interface**
* Bit ordered separately: 990.0119-RL
** Max. 44W; consult your sales representative
Example: rsc28w2rt9
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
12
Project/Location:
Contractor:
RNC
Date:
Prepared by:
NEMA 4X Certified Combination Unit
Typical Specification
Supply and install Ready-lite® RNC Series combination of unit equipment and pictogram exit sign. Designed specifically
for the industrial environment, the equipment frame shall be of industrial grade polyvinyl chloride with gaskets around both
sides of the frame contour. The back plate shall be made of 1/8-inch thick aluminum sheet and shall include knock-outs for
installation on an electrical box. The faceplate(s) shall be constructed of heavy-duty vandal-resistant clear polycarbonate and
feature a uniformly illuminated pictogram legend. Each face plate shall come standard with two legend films for pictogram
and direction selection. The light source shall be long-life white light-emitting diodes (LED). The unit shall have attached a
lower compartment containing two emergency heads with adjustable swivels and long-life MR-16 LED lamps of ___ V and
___ W. The heads shall be installed on a shield housing made of rigid thermoplastic and shall be protected by a shockabsorbent, clear polycarbonate cover.
The standard AC input voltage shall be 120/347VAC. The unit shall be equipped with a magnetic test switch and a LED
pilot light protected by the clear face plate. The unit shall perform self-diagnostics functions managed by a micro-controller
and shall automatically self-test for one minute every 30 days, 10 minutes in the 6th month and 30 minutes annually.
When a fault is detected, the bi-colour pilot light shall turn from green to red and flash following a particular code. The code
description shall be displayed on a label next to the pilot light to identify the failure type: battery, charger circuitry, LED lights
for the signage, or emergency lights.
The combination unit shall meet or exceed the standard CSA C22.2 No.141.
The equipment shall be Ready-lite® Model:
Features
• Certified NEMA-4X for wall or ceiling mount
• Certified NSF for use in food processing areas
• Meets or exceeds CSA 22.2 No.141-10 standard
for pictogram exit signs
• Polyvinyl chloride frame, with built-in gasket to
prevent water infiltration
• Sealed, vandal-resistant faceplate of polycarbonate
• Legend illuminated by long-life white LED’s
• Comes standard with two pictogram films per face,
for direction selection
•Two high-performance MR16 LED lamps shielded
by a clear polycarbonate cover
• 4-Watt LED emergency lights provide 30 - 36 feet
of egress illumination on a 6-foot wide path
• Sealed, maintenance-free Lead-Calcium or NickelCadmium batteries
.
Dimensions
• Remote load capacity: covers with 4 Watt LED lights
100 feet up to 230 feet of egress illumination
• Comes standard with self-diagnostics
• Cold-weather option: -40°C with only 14W extra
power consumption
®
NEMA-4X
Power Consumption
Model
AC Specs
Pictogram sign module
RNC-6L36
RNC-6L36-CW
RNC-6N36
RNC-6N36-CW
RNC-12N60
30 min.
Emergency power available for lamps
1 hr.
1.5 hrs.
2 hrs.
4 hrs.
120/347VAC
Less than 2.5W
-
-
-
-
-
120/347VAC
0.10 / 0.03 Amp
0.25 / 0.08 Amp
0.10 / 0.03 Amp
0.25 / 0.08 Amp
0.18 / 0.06 Amp
36
36
36
36
60
21
21
30
30
40
15
15
20
20
30
12
12
16
16
20
8
8
10
Ordering Information
Series
RNC= NEMA-4X
& NSF
pictogram exit
combo unit
Faces / Mounting*
Housing colour
1= single face
2= double face
B= black
W= factory white
Battery type and power
Head style and power
Options
6L36= 6V-36W Lead-Calcium
6N36= 6V-36W Nickel-Cadmium
12N60= 12V-60W Nickel-Cadmium
Blank= No head
LD1= 2 x MR16 LED 6V-4W
LD7= 2 x MR16 LED 12V-4W
MI= 2 x MR16 halogen 6V-6W
MJ= 2 x MR16 halogen 6V-10W
MK= 2 x MR16 halogen 12V-12W
Blank= auto-diagnostics, non-audible (standard)
AD= auto-diagnostics, audible
CW= c old-weather -40°C to +25°C only with 6 Volt single-face units
D3= time delay (15 minutes)
FA= fire alarm activated flasher
FL= flasher (AC power failure)
FB= flasher/buzzer (AC power failure)
U2= 120/277VAC input
NEX= NEXUS® system interface*
NEXRF= wireless NEXUS® system interface*
*Universal mounting
*Some options are not available with NEXUS®.
EXAMPLE: Rnc1b12n60old7
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
13
Project/Location:
Contractor:
RHC Series
Date:
Pictogram Combination Unit for
Hazardous locations
Features
Prepared by:
Typical Specification
Supply and install Ready-lite® RHC Series combination of unit equipment and pictogram sign. Designed specifically for
hazardous locations, the equipment frame shall be of industrial grade polyvinyl chloride with gaskets around both sides
of the frame contour. The back plate shall be made of 1/8-inch thick aluminum sheet and shall include knock-outs for
installation on an electrical box and four keyholes for alternative installation on a wall surface. The faceplate shall be
constructed of heavy-duty vandal-resistant clear polycarbonate and feature a uniformly illuminated pictogram legend.
The unit shall come standard with two legend films for pictogram and direction selection. The light source shall be long-life
white light-emitting diodes (LED). The unit shall have attached a lower compartment containing two emergency heads with
adjustable swivels and long-life MR16 LED lamps of ___ V and ___ W. The heads shall be installed on a shield housing
made of cast aluminum and protected by a shock-absorbent, clear polycarbonate cover.
• Certified Class I Division 2, Groups A, B, C and D as
per CSA C22.2 No.137-M1981
• Certified temperature Codes for several types of
emergency lamps
• Certified CSA C22.2 No.141-10
• Polyvinyl chloride frame, with built-in gasket to
prevent water infiltration
• Heavy-duty 1/8-inch thick aluminum back plate
with key-holes for wall-mount installation
The standard AC input voltage shall be 120/347VAC. The equipment shall be equipped with a magnetic test switch and one
LED pilot light protected by the clear face plate. The unit shall perform self-diagnostics functions managed by a microcontroller and shall automatically self-test for one minute every 30 days, 10 minutes in the 6th month and 30 minutes
annually. When a fault is detected, the bi-color pilot light shall turn from green to red and flash following a particular code.
The code description shall be displayed on a label next to the pilot light to identify the failure type: battery, charger circuitry,
LED lights for the signage, or emergency lights.
• Sealed, vandal-resistant faceplate of polycarbonate
• Legend illuminated by long-life white LEDs
• Comes standard with two pictogram films for
direction selection
The combination unit shall be approved CSA C22.2 No.141 and No.137-M1981 for Class I Division 2 Groups A, B, C and D.
•Two high-performance MR16 LED lamps shielded
by a clear polycarbonate cover
•Two 5W LED emergency lights provide up to 60 feet
of egress illumination on a 6-foot wide path
• Sealed, maintenance-free Lead-Calcium or
Nickel-Cadmium batteries
The combination unit shall be Ready-lite® model:
.
Dimensions
• Remote load capacity
•Comes standard with auto-diagnostics
•Includes an industrial-grade, die-cast Aluminum
electrical box
•Cold-weather option: -40°C (104°F) with only 14W
extra power consumption
• Nexus® interface option
Consult your sale representative
®
Power Consumption
Temperature Codes
Model
AC Specs
Emergency power available for heads
30 min.
1 hr.
1.5 hrs.
2 hrs.
Less than 2.5W
-
-
-
-
4 hrs.
-
0.10/0.03 Amp
36
21
15
12
-
Temperature
code
Maximum
4-5W MR16 LED
T4A
120°C
RHC-6L36-CW
10W MR16 Halogen
T3C
160°C
RHC-6N36
12W MR16 Halogen
T3A
180°C
RHC-6N36-CW
0.25/0.08 Amp
36
30
20
16
8
20W MR16 Halogen
T2D
215°C
RHC-12N60
0.18/0.06 Amp
60
40
30
20
10
Model
Pictogram sign module
120/347VAC
RHC-6L36
120/347VAC
0.25/0.08 Amp
36
21
15
12
-
0.10/0.03 Amp
36
30
20
16
8
Ordering Information
Series
RHC
Housing colour
G= grey
Battery type and power
6L36= 6V-36W Lead-Calcium
6N36= 6V-36W Nickel-Cadmium
12N60= 12V-60W Nickel-Cadmium
Head style and power
Blank= No head
LD1= 2 x MR16 LED 6V-4W
LD7= 2 x MR16 LED 12V-4W
LD9= 2 x MR16 LED 12V-5W
MJ= 2 x MR16 halogen 6V-10W
MK= 2 x MR16 halogen 12V-12W
MW= 2 x MR16 high-output 12V-20W
Options
Blank= auto-diagnostics, silent (standard)
AD= auto-diagnostics, audible
CW= cold-weather -40°C (104°F) (only 6V units)
D3= time delay (15 minutes)
U2= 120/277VAC input
NEX= NEXUS® wired*
NEXRF= NEXUS® wireless*
*Consult your sales representative
Example: rhcg12n60ld7
Unlike EXIT signs, the pictogram sign is not available in double arrow configuration.
14
Notes
www.readylite.com
All information and specifications contained in this catalogue are subject to change due to engineer design, errors and omissions.
Illustrations and diagrams within this catalogue may vary from actual products.