Energy lntelligence PDU for Data Centers
E nergy lntelligence PDU for Data Centers
2013
Our Vision
“Simply Better Connections” has always been at the heart of the ATEN brand. It means providing innovative solutions for
you to make better connections, efficiently and seamlessly, to the information and people that you value. As a result, ATEN
connects you to the world, anytime and anywhere, by providing technologies that enable you to share and to care. ATEN
makes professional and personal life easier, simpler, and better connected.
About ATEN
ATEN, established in 1979, is specialized in connectivity and management solutions in accessing and sharing technologies.
ATEN consolidates all of its products and services under one brand – ATEN, in order to provide an efficient and consistent
service standard. The ATEN brand consists of innovative solutions applied to connectivity, professional audio/video, and
green energy, for consumers, small/home offices (SOHO), small to medium sized businesses (SMB), and enterprise customers.
ATEN’s Energy Intelligence PDUs for Data Centers
At ATEN we are committed to offering real solutions for data centers, to this end, ATEN’s Green Energy solutions offer the
latest in energy intelligence. Our solutions for data centers begin with a wide range of eco PDUs, developed to support
ISO50001, that take intelligence to the next level by providing real-time energy management, control, and energy-saving
efficiency by allowing you to easily upgrade current IT resources quickly and cost effectively.
As PDU experts we have developed a variety of standardized and modularized rack PDUs in both 1U and 0U types to suit
most data centers. As PDU experts we understand that some data centers have requirements that can’t be met effectively
with “off the shelf models”, therefore we also offer customers a BTC “Build to Configuration” service to construct PDUs
according to their individual requirements, effectively providing the ideal power solution.
ATEN’s dedicated PDU team offer professional solutions in developing energy efficiency. Only with accurate measurements
and accurate data can data centers develop effective strategies and employ effective technologies for energy reduction.
ATEN delivers and we care about our customers. We are committed to the best customer support in the industry.
PDU Comparison
Features
1U PE6
PE6108
PE6208
1U
1U PE8
PE8108
PE8208
1U
Outlet
8
8
Remote Power Control
V
V
PDU Level
Outlet, PDU
Level
V
V
Model
Rack Space
Metering Capability
Environment Monitoring
eco Sensors Support
Proactive Overload
Protection
Critical Load Outlet
V
V
V
PE1/PE2
PE1216/PE2220
PE1324/PE2340
0U
16/20
24/40
Bank Via
EC1000
EC2004
Via EC1000
EC2004
PE5
PE5220s
PE5340s
0U
PE6
PE6216
PE6324
0U
PE7
PE7214
PE7328
0U
PE8
PE8216
PE8324
0U
PE9
PE9222
PE9330
0U
20/40
16/24
14/28
16/24
22/30
V
V
V
Bank, PDU
Level
Bank, PDU
Level
Outlet,
Outlet, Bank,
Outlet, Bank,
Bank, PDU
PDU Level
PDU Level
Level
V
V
V
V
V
V
V
V
V
V
V
V
V
EC1000/EC2004
PE1216/PE1324
PE2220/PE2340
PE1216
PE1324
• 16 Outlets
• 0U
• 24 Outlets
• 0U
Energy PDU PE1216/PE1324/PE2220/PE2340
The Energy PDU contains 16/24/20/40 AC outlets and is available in various IEC or NEMA socket configurations. It features a space-saving
0U design that allows it to be mounted vertically on the outside of the rack, resulting in a more efficient use of server room space.
• Space saving 0U rack mount design
• IEC or NEMA outlet models
Energy Box EC1000/EC2004
NRGence™ Energy Box is an intelligent 1U (0U vertical hook also available) power monitor unit which can monitor the current from 4
Energy PDUs and 4 temperature, humidity, or differential pressure sensors. It is a standalone Over IP monitor box that can be controlled
by Web UI or eco Sensors software. Conveniently deploying Energy Boxes in your rack, connected to Energy PDUs, allows all current
information from the PDUs to be collated and displayed on the Energy Box for easy viewing and monitoring.
• 4 Energy Sensor ports for Energy PDU current monitoring ( 0A to 32A per port )
• 4 Environment Sensor ports for temperature, humidity and differential pressure
monitoring
• Space saving 0U/1U rack mount design
• Remote real-time current management and monitoring
• Current threshold level setting provision
• Name assignment to individual PDU
• Wide Management Option Range
• Remote management via IP network with Web Brower, eco Sensors software
or 3rd party SNMP manager
• Exceed threshold alert through
• Local: audio alarm and LED light blinking
• Remote: SMTP/SNMP trap/Syslog
Function
Inlet
Current
Monitor
Environment
Monitor
LAN
EC1000
Power Adapter DC 5V (1.8m)
4 x Energy Sensor Connection
port
4 x Environment Sensor
Connection port
1 x RJ-45 Female with LEDs
100–240V; 50/60Hz; 0A to 32A
(per port)
LED Display Resolution 0.1A
Accuracy: ±[email protected] ~ 1A, ±1%@
>1A
Monitoring
Range
Setup
EC2004
Power Adapter DC 5V (1.8m)
2xCurrent+2xCurrent/Voltage
Energy Sensor Connection Port
4xEnvironment Sensor
Connection Port
1xRJ-45 Female with LEDs
100–240V; 50/60Hz; 0A to 32A
(per port)
LED Display Resolution 0.1A
Accuracy: ±[email protected] ~ 1A, ±1%@
>1A
Model
Rack
Space
Input
Voltage
Derated
AMP
Max
AMP
Input Plug
# of Bank
Outlet
Outlet
Control
Meter
PE1216A
0U
100-120V
16A
20A
NEMA5-20P
1x20A
16xNEMA5-15R
None
Bank x 1
FCC, cTUVus, TUV-PSE
PE1216B
0U
100-240V
16A
20A
NEMA6-20P
1x20A
16xIEC 320 C13
None
Bank x 1
FCC, cTUVus, TUV-PSE
PE1216G
0U
100-240V
16A
16A
IEC C20
1x16A
16xIEC 320 C13
None
Bank x 1
CE, TUV-CB, TUV, C-Tick, GOST
PE1324B
0U
100-240V
24A
30A
NEMAL6-30P
2x15A
24xIEC 320 C13
None
Bank x 2
FCC, cTUVus, TUV-PSE
PE1324G
0U
100-240V
32A
32A
IEC60309 32A
2x16A
24xIEC 320 C13
None
Bank x 2
CE, TUV-CB, TUV, C-Tick, GOST
PE2220A
0U
100-120V
16A
20A
NEMA5-20P
1x20A
20xNEMA5-15R
None
Bank x 1
CE-LVD, TUV-CB, Others by request
None
Bank x 1
FCC, TUV-CB, Others by Reuest
None
Bank x 1
CE-LVD, TUV-CB, Others by request
None
Bank x 2
FCC, TUV-CB, Others by Reuest
None
Bank x 2
CE-LVD, TUV-CB, Others by request
PE2220B
0U
100-240V
16A
20A
NEMA6-20P
1x20A
PE2220G
0U
100-240V
16A
16A
IEC C20
1x16A
PE2340B
0U
100-240V
24A
30A
NEMAL6-30P
2x15A
PE2340G
0U
100-240V
24A
32A
IEC60309 32A
1x16A
The specification and pictures are subject to change without notice.
10xDuplex Receptacles
IEC320 C13
10xDuplex Receptacles
IEC320 C13
20xDuplex Receptacles
IEC320 C13
20xDuplex Receptacles
IEC320 C13
Certification
PE6108/PE6208
PE8108/PE8208
PE6108
PE8108
PE6208
PE8208
• 8 Outlets
• 1U
• 8 Outlets
• 1U
• 8 Outlets
• 1U
Power Distribution
•
•
•
•
Space saving rack mount design with rear mounting
IEC or NEMA outlet models
3 x 7 segment front panel LED shows Current / IP Address
Remote users can monitor outlet status via web pages on their
browsers
• Safe shutdown support
• Separate power for the unit's own power and its power outlets – the
user interface is still accessible even when an overload condition trips
the devices' circuit breakers
Remote Access
• Remote power control via TCP/IP and a built in 10/100 Ethernet port
• Network Protocols: TCP/IP, PPP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP,
NTP, DNS, auto sense, Ping
• eco PDU Power Management software – eco Sensors
• Supports SNMP Manager V1, V2 & V3
Operation
• Remote power outlet control (On, Off, Power Cycle) by individual
outlets
• Supports multiple power control methods – Wake on LAN, System
After AC Back, Kill the Power
• Power-on sequencing - users can set the power on sequence and
delay time for each outlet to allow equipment to be turned on in the
proper order
• Easy setup and operation via a browser-based user interface
• Multibrowser support (IE, Firefox, Chrome, Safari)
• RTC support to keep the timer running during times of no power
• Supports up to 8 user and 1 administrator accounts
• Proactive overload protection(POP) – automatically powers off the
last outlet that caused the current overload Patent Pending!(PE8 only)
• 8 Outlets
• 1U
• Real-time current, voltage, and kWH displayed in a browsed-based UI
for monitoring at the PDU level
• Environment monitoring – supports external temperature /
temperature & humidity sensors for rack temperature and humidity
monitoring
• Current, voltage, power dissipation, energy consumption,
temperature, and humidity threshold level setting
• Naming support for outlets
• User outlet access assignment on an outlet-by-outlet basis
• Event logging and syslog support
• Supports Management Information Base (MIB) files for SNMP
• Upgradeable firmware
• Multilanguage support
Security
• Two-level password security
• Strong security features include strong password protection and
advanced encryption technologies – 128 bit SSL
• Remote authentication support: RADIUS
Management
• Power status measurement at PDU level or PDU level (PE8108/PE8208)
• LED indicators for current and IP address at the PDU device level
Model
Rack
Space
Input Voltage
Derated
AMP
Max
AMP
Input Plug
# of
Bank
PE6108A
1U
100-120V
12A
15A
NEMA5-15P
1x15A
8xNEMA5-15R
Yes
Bank x 1 FCC, UL, PSE
PE6108B
1U
100-240V
12A
15A
NEMA6-15P
1x15A
8xNEMA6-15R
Yes
Bank x 1 FCC, UL, PSE
PE6108G
1U
100-240V
10A
10A
IEC C14
1x10A
8xIEC 320 C13
Yes
Bank x 1 CE, TUV-CB, TUV, C-Tick, GOST
PE6208A
1U
100-120V
16A
20A
NEMA5-20P
1x20A
8xNEMA5-20R
Yes
Bank x 1 FCC, UL, PSE
PE6208B
1U
100-240V
16A
20A
NEMA6-20P
1x20A
7xIEC 320 C13+1xIEC 320 C19
Yes
Bank x 1 FCC, UL, PSE
PE6208G
1U
100-240V
16A
16A
IEC C20
1x16A
7xIEC 320 C13+1xIEC 320 C19
Yes
Bank x 1 CE, TUV-CB, TUV, C-Tick, GOST
PE8108A
1U
100-120V
12A
15A
NEMA5-15P
1x15A
8xNEMA5-15R
Yes
Outlet
FCC, UL, PSE
PE8108B
1U
100-240V
12A
15A
NEMA6-15P
1x15A
8xNEMA6-15R
Yes
Outlet
FCC, UL, PSE
PE8108G
1U
100-240V
10A
10A
IEC C14
1x10A
8xIEC 320 C13
Yes
Outlet
CE, TUV-CB, TUV, C-Tick, GOST
PE8208A
1U
100-120V
16A
20A
NEMA5-20P
1x20A
8xNEMA5-20R
Yes
Outlet
FCC, UL, PSE
PE8208B
1U
100-240V
16A
20A
NEMA6-20P
1x20A
7xIEC 320 C13+1xIEC 320 C19
Yes
Outlet
FCC, UL, PSE
PE8208G
1U
100-240V
16A
16A
IEC C20
1x16A
7xIEC 320 C13+1xIEC 320 C19
Yes
Outlet
CE, TUV-CB, TUV, C-Tick, GOST
The specification and pictures are subject to change without notice.
Outlet
Outlet
Control
Meter
Certification
PE5220s/PE5340s
PE6216/PE6324
PE5220s
PE6216
PE5340s
PE6324
• 20 Outlets
• 0U
• 16 Outlets
• 0U
• 24 Outlets
• 0U
• 40 Outlets
• 0U
Power Distribution
• Space saving rack mount design with rear mounting
• IEC or NEMA outlet models
• 3 x 7-segment front panel LED shows Current / IP Address for PDU /
Bank
• Remote users can monitor PDU/Bank status via web pages on their
browsers
• Safe shutdown support
• Separate power for the unit's own power and its power outlets - the
user interface is still accessible even when an overload condition trips
the devices' circuit breaker
Remote Access
* Remote power control via TCP/IP and a built in 10/100 Ethernet port
• Network Protocols: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP, NTP,
DNS, auto sense, Ping
• eco PDU Power Management software – eco Sensors
• Supports SNMP Manager V1, V2 & V3
• Real-time aggregate current, voltage, and power and power
dissipation displayed in a browser-based UI for monitoring at the PDU
level (PE5216/PE6216) and at the bank level (PE5324/PE6324)
• Environment monitoring – supports external temperature / humidity /
Differential Pressure sensors for rack environment monitoring
• Current and voltage threshold setting
• Naming support for outlets
* User outlet access assignment on an outlet-by-outlet basis
• Event logging and syslog support
• Upgradeable firmware
• Multilanguage support: English, Traditional Chinese, Simplified
Chinese, Japanese, German, Italian, Spanish, French, Russian
Security
• Two-level password security
• Strong security features include strong password protection and
advanced encryption technologies – 128 bit SSL
• Remote authentication support: RADIUS
Operation
* Remote power outlet control (On, Off, Power Cycle) by individual
outlets
* Supports multiple power control methods – Wake on LAN, System
After AC Back, Kill the Power
* Power-on sequencing – users can set the power on sequence and
delay time for each port to allow equipment to be turned on in the
proper order
• Easy setup and operation via a browser-based user interface
• Multibrowser support (IE, Mozilla, Firefox, Chrome, Safari, Opera,
Netscape)
• RTC support to keep the timer running during times of no power.
• Up to 8 user accounts and 1 administrator account.
Management
• Power status measurement at the PDU/Bank level
• LED indicators for current and IP address at the PDU device and/or
Bank levels
*Features supported by PE6216/PE6324 only
Model
Rack
Space
Input
Voltage
Derated
AMP
Max
AMP
Input Plug
# of
Bank
Outlet
Outlet
Control
PE5220sA
0U
100-120V
16A
20A
NEMA5-20P
1x20A
20xNEMA5-15R
None
Meter
Certification
Bank x 1 FCC, TUV-CB, Others by request
PE5220sB
0U
100-240V
16A
20A
NEMA6-20P
1x20A
20xIEC 320 C13
None
Bank x 1 FCC, TUV-CB, Others by request
PE5220sG
0U
100-240V
16A
16A
IEC C20
1x16A
20xIEC 320 C13
None
Bank x 1 CE, TUV-CB, Others by request
PE5340sB
0U
100-240V
24A
30A
NEMAL6-30P
2x15A
40xIEC 320 C13
None
Bank x 2 FCC, TUV-CB, Others by request
PE5340sG
0U
100-240V
32A
32A
IEC60309 32A
2x16A
40xIEC 320 C13
None
Bank x 2 CE, TUV-CB, Others by request
PE6216A
0U
100-120V
16A
20A
NEMA5-20P
1x20A 14xNEMA5-15R+2xNEMA5-20R
Yes
Bank x 1 FCC, cTUVus, TUV-PSE
PE6216B
0U
100-240V
16A
20A
NEMA6-20P
1x20A 14xIEC 320 C13+2xIEC 320 C19
Yes
Bank x 1 FCC, cTUVus, TUV-PSE
PE6216G
0U
100-240V
16A
16A
IEC C20
1x16A 14xIEC 320 C13+2xIEC 320 C19
Yes
Bank x 1 CE, TUV-CB, TUV, C-Tick, GOST
PE6324B
0U
100-240V
24A
30A
NEMAL6-30P
2x15A 21xIEC 320 C13+3xIEC 320 C19
Yes
Bank x 2 FCC, cTUVus, TUV-PSE
PE6324G
0U
100-240V
32A
32A
IEC60309 32A
2x16A 21xIEC 320 C13+3xIEC 320 C19
Yes
Bank x 2 CE, TUV-CB, TUV, C-Tick, GOST
The specification and pictures are subject to change without notice.
PE7214/PE7328
PE8216/PE8324
PE9222/PE9330
PE7214
PE8216
PE9222
PE7328
PE8324
PE9330
• 14 Outlets
• 0U
• 28 Outlets
• 0U
Power Distribution
• Space saving rack mount design
• IEC or NEMA outlet models
• Remote users can monitor outlet status via web pages on their
browsers
• Safe shutdown support
• Separate power for the unit's own power and its power outlets – the
user interface is still accessible even when an overload condition trips
the devices' circuit breakers
•
•
•
•
•
•
• 16 Outlets
• 0U
• 24 Outlets
• 0U
• 22 Outlets
• 0U
• 30 Outlets
• 0U
User outlet access assignment on an outlet-by-outlet basis
Event logging and syslog support
Supports Management Information Base (MIB) files for SNMP
Upgradeable firmware
Multi-language support
Proactive overload protection(POP) – automatically powers off the
last outlet that caused the current overload Patent Pending! (PE8/PE9
only)
Security
Remote Access
• Remote power control via TCP/IP and a built in 10/100 Ethernet port
• Network Interfaces: TCP/IP, PPP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP,
NTP, DNS, auto sense, Ping
• eco PDU Power Management software – eco Sensors
• Supports SNMP Manager V1, V2 & V3
• Two-level / Three-level password security
• Strong security features include strong password protection and
advanced encryption technologies – 128 bit SSL
• Remote authentication support: RADIUS
Operation
• Remote power outlet control (On, Off, Power Cycle) by individual
outlets and outlet groups
• Supports multiple power control methods – Wake on LAN, System
After AC Back, Kill the Power
• Power-on sequencing - users can set the power on sequence and
delay time for each outlet to allow equipment to be turned on in the
proper order
• Easy setup and operation via a browser-based user interface
• Multibrowser support (IE, Firefox, Chrome, Safari)
• RTC support to keep the timer running during times of no power
• Supports up to 8 user and 1 administrator accounts
• Critical load outlet – keeps power always on for critical load devices
( PE9 only )
Management
• Power status measurement at PDU and outlet levels
• Current, voltage, power dissipation, and energy consumption
displayed in a browser based UI for monitoring at the outlet, group,
PDU levels
• Environment monitoring – supports external temperature /
temperature & humidity sensors for rack temperature and humidity
monitoring
• Current, voltage, power dissipation, energy consumption,
temperature, and humidity threshold level setting
• Naming support for outlets and outlet groups
*PE7 Outlet is always on.
Model
Rack
Space
Input
Voltage
Derated
AMP
Max
AMP
Input Plug
# of
Bank
Outlet
Outlet
Control
Meter
PE7214B
0U
100-240V
16A
20A
NEMA6-20P
1x20A
12xIEC 320 C13+2xIEC 320 C19
None
Outlet
Certification
FCC, cTUVus, TUV-PSE
PE7214G
0U
100-240V
16A
16A
IEC C20
1x16A
12xIEC 320 C13+2xIEC 320 C19
None
Outlet
CE-LVD, TUV-CB, Others by request
PE7328B
0U
100-240V
24A
30A
NEMAL6-30P
2x15A
24xIEC 320 C13+4xIEC 320 C19
None
Outlet
FCC, cTUVus, TUV-PSE
PE7328G
0U
100-240V
32A
32A
IEC60309 32A
2x16A
24xIEC 320 C13+4xIEC 320 C19
None
Outlet
CE-LVD, TUV-CB, Others by request
PE8216B
0U
100-240V
16A
20A
NEMA6-20P
1x20A
14xIEC 320 C13+2xIEC 320 C19
Yes
Outlet
FCC, cTUVus, TUV-PSE
PE8216G
0U
100-240V
16A
16A
IEC C20
1x16A
14xIEC 320 C13+2xIEC 320 C19
Yes
Outlet
CE, TUV-CB, TUV, C-Tick, GOST
PE8324B
0U
100-240V
24A
30A
NEMAL6-30P
2x15A
21xIEC 320 C13+3xIEC 320 C19
Yes
Outlet
FCC, cTUVus, TUV-PSE
PE8324G
0U
100-240V
32A
32A
IEC60309 32A
2x16A
21xIEC 320 C13+3xIEC 320 C19
Yes
Outlet
CE, TUV-CB, TUV, C-Tick, GOST
PE9222B
0U
100-240V
16A
20A
NEMA6-20P
1x20A
19xIEC 320 C13+3xIEC 320 C19
Mix
Outlet
FCC, TUV-CB, Others by request
PE9222G
0U
100-240V
16A
16A
IEC C20
1x16A
19xIEC 320 C13+3xIEC 320 C19
Mix
Outlet
CE, TUV-CB, Others by request
PE9330B
0U
100-240V
24A
30A
NEMAL6-30P
2x15A
26xIEC 320 C13+4xIEC 320 C19
Mix
Outlet
FCC, TUV-CB, Others by request
PE9330G
0U
100-240V
32A
32A
IEC60309 32A
2x16A
26xIEC 320 C13+4xIEC 320 C19
Mix
Outlet
CE, TUV-CB, Others by request
The specification and pictures are subject to change without notice.
Energy & DCIM Management Software
eco Sensors
eco Sensors software has been developed to work with NRGence™ power distribution units (PDUs) to effectively increase the efficiency
of data center power usage. With the use of dynamic Rack Cooling Index (RCI) and Return Temperature Index (RTI) by zone, eco Sensors
software, in conjunction with sensor-enabled eco PDUs, gives you the means to assess, diagnose and estimate how much energy you can
save. Following the suggestions generated by the sensor-enabled system allows you to optimize energy usage to save energy without
harming your IT equipment’s reliability.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Automatic discovery of all PE devices within the same intranet
Remote real-time power measurement and monitoring
PDU level current / voltage / power dissipation / power consumption
Outlet ON / OFF / Recycle status
Remote real-time power outlet management*
Power outlet ON / OFF / Cycle switching by outlet
User-defined outlet level delays for sequential power up
Current / Voltage / Power Dissipation / Power Consumption threshold level setting
User access assignment for every outlet
Name assignment to individual outlets
Remote real-time environment sensor monitoring
Temperature / Temperature + Humidity reading / Temperature + Differential Pressure
Temperature and Humidity threshold level setting
Plotting/Monitoring of all PE devices
Add data center server racks
Add PE devices for each server rack
Manage device/device outlet status for each plot
Offers essential data center indices including RCI( Rack Cooling Index ), RTI ( Return Temperature Index ), RHI ( Rack Humidity Index ),
RPI ( Rack Pressure Index ), RAI ( Rack Airflow Index )
Power analysis report for optimizing data center energy management – including power usage, power load, power cost, CO2 cost,
power capacity and trend
Exceed threshold alert through SMTP and System log
10240 line event log
System log provision
Two-level password security
* Not all functions are supported by all NRGence™ PDU. Please see www.aten.com for more details.
Setup
Temperature Sensor
Normal
1
Unreachable
2
3
Warning
4
5
15
20
6
Critical
7
8
9
1
5
10
Differential
Pressure
Sensor
A
1
5
10
25
Internet/
LAN
IT Office
Report Title: Sales Department IT Power Analysis
Daily Report: 2011/1/1 – 2011/5/5 by Bill Li
IT Office
IT Power Load Chart
IT Power Usage Chart
kWH
kWH
- Sales 3
6
6
4
4
- Sales 2
2
Sales
2
- Sales 1
1/1 2/2 3/3 4/4 5/5
1/1 2/2 3/3 4/4 5/5
IT Inventory List in Report
No.
eco PDU Sensor Probes
Server Storage
Hardware Requirement
Name Peak Watts
Peak
CO2e/Hrs
Yearly Power Cost
Yearly CO2e Cost
Location
01
Web Server
3
1.8 kg
1200
600
L25
02
Log Server
6
3.6 kg
3600
1800
L27
System Parameter
Operating System
Windows XP / Windows Server 2003 and later
Max PDU number
1000
CPU
2.0 GHz Dual Core
Data Center Layout
45x30
Display
Larger than 1024x768
Max Rack Number
500
Memory
2GB
Max Zone Number
20
Disk
300GB
Power Report Data
3 years
Network
10/100/1000 Mbp Ethernet
Real Time Dashboard Data
1 hours
Optional Accessories
Mounting Kit
Environment Sensors
Part No.
Sensor
Accuracy
EA1140
Temperature
1°C
EA1240
Temperature / Humidity
1°C , 3%RH
EA1340
Differential Pressure /
Temperature
1°C , 10 Pa
EA1440
Photo Door Sensor
EA1441
Inductive Proximity Door
Sensor
Slide Rail Kit (2X-016G)
Button Mount Kit (2X-017G)
• Side Mount Installation
Cable Holders
Part No.
Description
2X-EA07
Lok-U-Plug Cable Holder
(10 pcs per pack) Patent Pending!
2X-EA08
Lok-U-Plug Installation Tool
(4 pcs per pack)
• Button Mount Installation
• Lok-U-Plug Installation
Corporate Headquarters
ATEN International Co., Ltd.
3F., No.125, Sec. 2, Datong Rd., Sijhih District.,
New Taipei City 221, Taiwan
Phone: +886-2-8692-6789 Fax: +886-2-8692-6767
www.aten.com E-mail: [email protected]
U.S.A. Subsidiaries:
Japan Subsidiary :
ATEN Technology Inc.
19641 DaVinci, Foothill Ranch, CA 92610, U.S.A
Phone: +1-949-428-1111 Fax: +1-949-428-1100
www.aten-usa.com E-mail: [email protected]
ATEN Japan Co., Ltd.
ATEN Bldg. 8-4, Minami-senjyu 3-chome, Arakawa-ku,
Tokyo 116-0003 Japan
Phone: +81-3-5615-5810 Fax: +81-3-3891-3810
www.atenjapan.jp E-mail: [email protected]
ATEN New Jersey Inc.
Korea Subsidiary :
China Subsidiary :
ATEN Korea.,Ltd.
ATEN China Co., Ltd.
155 Pierce Street, Somerset, NJ 08873, U.S.A
Phone: +1-732-356-1703 Fax: +1-732-356-1639
www.aten-usa.com E-mail: [email protected]
B-303, Gabeul Great Valley, 60-5, Gasan-dong,
Geumcheon-gu, Seoul, Korea; 153-801
Phone: +82-2-467-6789 Fax: +82-2-467-9876
www.aten.co.kr E-mail: [email protected]
18/F, Tower A, Horizon International Tower,
No.6, Zhichun Road,
Haidian District, Beijing, China 100088
Phone: +86-10-5255-0110 Fax: +86-10-8296-1318
www.aten.com.cn E-mail: [email protected]
Belgium Subsidiary :
U.K. Subsidiary :
Taiwan Subsidiary :
ATEN Infotech N.V.
ATEN U.K. Limited
Atech Peripherals, Inc.
Mijnwerkerslaan 34, 3550 Heusden-Zolder, Belgium
Phone: +32-11-531543 Fax: +32-11-531544
www.aten.eu E-mail: [email protected]
229 Berwick Avenue, Slough, SL1 4QT, U.K.
Phone: +44-1753-539-121 Fax: +44-1753-215-253
www.aten.co.uk E-mail: [email protected]
6F., No.133, Sec. 2, Datong Rd., Sijhih District.,
New Taipei City 221, Taiwan
Phone: +886-2-8692-6969 Fax: +886-2-8692-6926
www.aten.com.tw E-mail: [email protected]
®
© Copyright 2012 ATEN International Co., Ltd.