Moottorilähtöjen valintakäsikirja 2009 (5 Mt)

Moottorilähtöjen valintakäsikirja 2009 (5 Mt)
Load Feeder
SIRIUS Configuration
Selection data for Fuseless Load Feeders
Configuration Manual • 10/2009
Industrial Controls
Answers for industry.
Load feeders
Configuring SIRIUS
Introduction
1
General Information
2
Selection tables 400 V AC
3
Selection tables 440 V AC
4
Selection tables 480 V AC
5
Selection tables 500 V AC
6
Selection tables 550 V AC
7
Selection tables 690 V AC
8
Installation guidelines
9
Configuration Manual
Service and support
10/2009
A8E56203880002-01
10
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation for the specific task, in particular its warning notices and
safety instructions. Qualified personnel are those who, based on their training and experience, are capable of
identifying risks and avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be adhered to. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
Ordernumber: 3ZX1012-0RA21-0AC0
Ⓟ 11/2009
Copyright © Siemens AG 2009
Technical data subject to change
Table of contents
1
Introduction................................................................................................................................................ 7
2
General Information ................................................................................................................................... 9
3
Selection tables 400 V AC ....................................................................................................................... 17
4
5
6
3.1
Motor starter protector / circuit breaker + contactor.....................................................................17
3.2
Motor starter protector + contactor + 3RU11 thermal overload relay ..........................................27
3.3
Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload
relay .............................................................................................................................................33
3.4
Motor starter protector / circuit breaker + contactor + 3RB21 solid-state overload relay ............44
3.5
3.5.1
Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 /
3RB22/3RB23 solid-state overload relay.....................................................................................46
CLASS 30, types of coordination 2 and 1, short-circuit breaking capacity Iq ≥ 100 kA ..............56
3.6
Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7.............................58
3.7
Motor starter protector + solid-state contactor.............................................................................62
3.8
Motor starter protector + solid-state reversing contactor .............................................................64
3.9
Motor starter protector + star(wye)-delta starting + 3RU11 thermal overload relay ....................65
3.10
Motor starter protector / circuit breaker + star(wye)-delta starting + 3RB20/3RB21 solidstate overload relay......................................................................................................................67
3.11
Motor starter protector / circuit breaker + star(wye)-delta starting + SIMOCODE pro 3UF7
/ 3RB22/3RB23 solid-state overload relay...................................................................................69
3.12
Motor starter protector / circuit breaker + 3RW30/3RW40 soft starter ........................................71
3.13
Motor starter protector / circuit breaker + 3RW44 soft starter .....................................................73
Selection tables 440 V AC ....................................................................................................................... 75
4.1
Motor starter protector + contactor ..............................................................................................75
4.2
Motor starter protector + contactor + 3RU11 thermal overload relay ..........................................77
4.3
Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay........................78
4.4
Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay...............................................................................................................................80
Selection tables 480 V AC ....................................................................................................................... 83
5.1
Motor starter protector + contactor ..............................................................................................83
5.2
Motor starter protector + contactor + 3RU11 thermal overload relay ..........................................85
5.3
Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay........................86
5.4
Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay...............................................................................................................................88
Selection tables 500 V AC ....................................................................................................................... 91
6.1
Motor starter protector / circuit breaker + contactor.....................................................................91
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
5
Table of contents
7
8
9
10
6
6.2
Motor starter protector + contactor + 3RU11 thermal overload relay ......................................... 97
6.3
Motor starter protector / circuit breaker + contactor + 3RB20/3RB21 solid-state overload
relay........................................................................................................................................... 101
6.4
Motor starter protector / circuit breaker + contactor + 3RB21 solid-state overload relay ......... 106
6.5
Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 /
3RB22/3RB23 solid-state overload relay .................................................................................. 108
6.6
Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7.......................... 115
6.7
Motor starter protector + star(wye)-delta starting + 3RU11 thermal overload relay ................. 117
6.8
Motor starter protector / circuit breaker + star(wye)-delta starting + 3RB20/3RB21 solidstate overload relay................................................................................................................... 119
6.9
Motor starter protector / circuit breaker + star(wye)-delta starting + SIMOCODE pro 3UF7
/ 3RB22/3RB23 solid-state overload relay ................................................................................ 121
Selection tables 550 V AC ..................................................................................................................... 123
7.1
Motor starter protector + contactor + 3RB20/3RB21 solid-state overload relay ....................... 123
7.2
Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay............................................................................................................................ 125
Selection tables 690 V AC ..................................................................................................................... 127
8.1
Motor starter protector + contactor............................................................................................ 127
8.2
Motor starter protector + contactor + 3RU11 thermal overload relay ....................................... 129
8.3
Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay ..................... 131
8.4
Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay............................................................................................................................ 134
Installation guidelines ............................................................................................................................ 137
9.1
Installation guidelines for all voltages ....................................................................................... 137
9.2
Installation guidelines for combinations: 3RV1. 5 ... 3RV1. 8 ................................................... 139
9.3
Installation guidelines for 400/440/480/500 V AC..................................................................... 140
9.4
Installation guidelines for 690 V AC .......................................................................................... 142
Service and support............................................................................................................................... 145
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
1
Introduction
SIRIUS – the Modular System Family for the Switching, Protecting and Starting of Motors
In order to simplify the configuration of load feeders, the SIRIUS modular system offers
standard components that are optimally coordinated and are easy to combine. Just 7 sizes
cover the entire performance range up to 250 kW. The individual switching devices can be
easily assembled to form complete load feeders, either using link modules or by mounting
directly.
SIRIUS motor starter protectors
3RV10 11 (S00)
3RV10 21 (S0)
SENTRON circuit breakers
3RV10 31 (S2)
3RV10 41 (S3)
VL250/3VL3
VL400 (3VL4)
VL630 (3VL5)
3RT10 3 (S2)
3RT1. 4 (S3)
3RT1. 5 (S6)
3RT1. 6 (S10)
3RT1. 7 (S12)
3RB20 36 (S2)
3RB20 46 (S3)
3RB20 56 (S6)
3RB20 66 (S10/S12)
SIRIUS contactors/magnetic motor controllers
3RT10 1 (S00)
3RT10 2 (S0)1)
SIRIUS overload relays
3RB20 16 (S00)
3RB20 26 (S0)
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
7
Introduction
SIRIUS motor starter protectors
SENTRON circuit breakers
SIRIUS soft starters
3RW30 1 (S00)
3RW40 2 (S0)
3RW40 3 (S2)
3RW40 4 (S3)
3RW40 5 (S6)
3RW40 7 (S10/S12)
We recommend the use of solid-state contactors/solid-state reversing contactors for high
switching frequencies.
1)
Highlights
8
•
Load feeders:
Easy to implement up to 250 kW / 400 V from standard devices
•
Modular design:
Everything fits together and can be combined
•
Variants and sizes:
Economical and flexible thanks to 7 compact sizes
•
Accessories:
Optimum variance with uniform accessories
•
Type of construction:
Space-saving design with small device width and butt-mounting
type of construction up to 60 °C
•
Design:
Fast start-up, short setting-up times and simple wiring
•
Communication:
Connection to AS-Interface and PROFIBUS DP supported
•
Maintenance:
Extremely durable, low maintenance and reliable
•
Approvals:
Global approvals and certifications, such as UL, CSA, CCC,
shipbuilding ...
•
Mounting:
Permanently secure mounting, screw or snap fitting
•
Spring-type connection:
Quick and secure connection, vibration-proof and maintenancefree
•
Environment:
Environment-friendly production and materials, recycling capability,
low power loss
•
Design:
Clear-cut, ergonomic design (winner of the iF Product Design
Award)
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
General Information
2
General criteria for the selection of devices
The motor starter protectors, contactors, solid-state switching devices, soft starters and
overload relays in the following tables are all specified in their basic versions, i.e. (in
particular) without accessories. It goes without saying that accessories such as auxiliary
switches, auxiliary trip units etc. can be used at any time.
The contactors listed have a rated control supply voltage Us of 230 V AC, 50 Hz. Versions
with other voltages can also be used.
The 3RU11 thermal overload relay and the 3RB20/3RB21 solid-state overload relays can
generally be directly mounted onto the contactor. Exceptions are specified in the footnotes of
the respective tables. The 3RB22 / 3RB23 solid-state overload relay and the SIMOCODE
pro 3UF7 motor protection and control device are essentially used for stand-alone
installation. In their basic version, these devices are specified with a rated control supply
voltage of 230 V AC. No sizes are specified for the "Molded-Case Circuit Breakers" (MCCB)
as for SIRIUS.
Mounting the combinations
When mounting the devices, specific arcing spaces must be maintained so that short-circuits
can be cleared safely and reliably. The appropriate installation guidelines are listed
separately for 400/440/480/500/550 V AC and 690 V AC starting on page 72. ((Siehe auchLink))
The technical data of the individual devices must be taken into account when selecting a
device.
400/440/480/500/550/690 V AC
The subsequent tables are structured according to mains voltages of
400 / 440 / 480 / 500 / 550 / 690 V AC for grounded networks (at 50 and 60 Hz) generally
found in IEC regions. With a few exceptions, tests are carried out with a test voltage which
lies 10% above these values (further details can be found in the test reports). Thus, the
specified combinations can also be used for other networks as long as their maximum
voltage does not exceed the test voltage. This means, for instance, the combinations for
400 V can also be used for 415 V networks that have a line supply tolerance of +5%.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
9
General Information
Ambient conditions
A maximum ambient temperature of 60 °C applies to all electromechanical controlgear, and
40 °C to soft starters and solid-state contactors. Higher temperatures are possible with
derating. For details refer to Catalog LV1 T or contact Technical Assistance.
A maximum installation height of 2000 m applies to electromechanical controlgear, and
1000 m to soft starters and solid-state contactors.
Greater installation heights are also possible with derating. For details refer to Catalog
LV1 T.
Trip classes
CLASS 5, CLASS 10, CLASS 20, CLASS 30 and CLASS 40
Trip classes, according to IEC 60947-4-1, define the time intervals within which the
protection equipment (overload release of a motor starter protector or overload relay) must
trip from the cold state, for a symmetrical, three-phase load with a 7.2-fold set current Ie.
The tripping times are as follows:
● CLASS 5 and CLASS 10 between 2 s and 10 s,
● CLASS 20 between 4 s and 20 s,
● CLASS 30 between 9 s and 30 s,
● CLASS 40 between 30 s and 40 s.
120
100
min
50
20
10
CLASS 30
25
20
s
Tripping time
5
2
1
50
20
10
5
15
10
CLASS 5
2
0,6
1
5
2
10x e
Tripping current (mean values)
In practice, devices with trip CLASS 5 and CLASS 10 are generally used. These devices are
designed for standard applications. CLASS 5 and CLASS 10 are often referred to as normal
starting.
Combinations for CLASS 20, CLASS 30 and CLASS 40 are available for applications where
a higher starting current is required for a prolonged period. In this case, using standard
devices of CLASS 5 and CLASS 10 would result in unwanted tripping. CLASS 20, CLASS 30
and CLASS 40 are also known as heavy starting devices. Large fan motors are an example
of this type of application.
As well as the overload protection devices, the contactors and short-circuit protection
devices must also be designed for these long starting times. This is why combinations acc.
to CLASS 5 and CLASS 10 are generally more cost-effective. CLASS 20, CLASS 30 and
CLASS 40 are only generally used if genuinely necessitated by the application.
10
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
General Information
Type of coordination 1 or 2
When selecting the combinations, in many cases, either coordination type 1 or 2 can be
selected. According to IEC 60947-4-1, the coordination type defines the permissible degree
of damage for a device following a short-circuit.
•
Type of coordination "1"1):
After a short-circuit, it is permissible for the starter to be inoperative, in particular, damage to the contactor, solid-state
switching devices and overload relay is permissible.
•
Type of coordination "2"1):
The starter is still operative. There must be no signs of damage to the devices, with the exception of slightly welded
contactor contacts if these can be easily separated again without any noticeable deformation.
1)
Combinations are color coded according to the respective type of coordination as shown above.
In both cases, the short-circuit is reliably and safely cleared. Combinations of coordination
type 2 are therefore of a higher quality and are rapidly available for reuse after a short-circuit.
In the case of solid-state switching devices, the same applies as for type of coordination 2,
that the short-circuit is cleared without any damage to the power semiconductors.
Combinations of coordination type 1 are generally the more favorably priced solution.
Combinations of coordination type 2 automatically fulfill the requirements of coordination
type 1.
Tests
All of the specified combinations are tested in compliance with IEC 60947-4-1.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
11
General Information
With or without overload relay
In addition to the combinations comprising a motor starter protector (for motor protection)
and contactor, combinations are also available with circuit breaker (for starter protection),
contactor and overload relay.
In the first case, the motor starter protector assumes the dual function of overload protection
and short-circuit protection, while in the second case, the circuit breaker assumes only the
short-circuit protection function and the overload relay the overload protection function. The
tripping behavior of both solutions under overload and short-circuit conditions is technically
comparable.
For fuseless load feeders with solid-state overload relay, and for higher trip classes, CLASS
20, CLASS 30 and CLASS 40 in particular, a starter circuit breaker is often used instead of a
motor starter protector. This is due to the following: from the point of view of thermal
destruction limits, starter circuit breakers are generally designed for CLASS 10 motor starts.
The current measurement of solid-state overload relays usually moves into saturation
upwards of a 10-fold rated current, so that the intrinsic protection of the motor starter
protector is no longer guaranteed for higher trip classes. In order to ensure thermal intrinsic
protection, it is advisable to use a motor starter protector that protects itself over the overload
release. The motor-protective circuit breaker is selected so that the point at which the
characteristic curve of the overload relay intersects with the a-tripping characteristic of the
motor-protective circuit breaker is more than 10 x the set current. This ensures that, in the
case of motor faults, such as overload or blocking, the overload relay always trips and not
the motor starter protector.
In this situation, combinations with motor starter protector and contactor offer the most costeffective solution. However, combinations with overload relays offer distinct advantages for
certain applications:
● Using 3RB20 / 3RB21 and 3RB22 / 3RB23 solid-state overload relays, or even
SIMOCODE pro 3UF7, enables users to achieve not only trip classes CLASS 5 and
CLASS 10, but also solutions for heavy starting, such as CLASS 20, CLASS 30 and
CLASS 40.
● Using solid-state overload relays offers a wide setting range of 1:4 or 1:10. This offers
advantages during configuration (e.g. if the exact motor current is not known) and
enables us to reduce the number of variants required.
● Overload and short-circuit protection are carried out separately and can also be signaled
separately. Alternatively, the 3RV19 21-1M signaling block can be used for the 3RV
motor starter protector instead of the overload relay. This also supports the separate
signaling of overloads and short-circuits.
● Setting of the overload relay to "Automatic Reset" can also save a walk to the control
cabinet in the case of overload tripping, as a manual reset in the control cabinet is not
required. Alternatively, this function can also be implemented with the "3RV11 motor
starter protector with overload relay function". These devices can be used in the motor
starter protector + contactor tables instead of the 3RV10 motor starter protector.
12
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
General Information
Star(wye)(Y)-delta function(Δ) starting
In order to keep the current peaks in the line supply as low as possible, contactor assembly
are frequently used as star(wye)-delta starters to start three-phase motors. However, to
make worthwhile use of YΔ starting, a low load torque is required during starting. Only then
can the motor approximately reach its rated speed in the Y stage before switching to
Δ operation.
An overload relay should be used for motor overload protection. Normally, this is located
directly in the motor feeder cable U1, V1, W1, as shown in the circuit diagram. Using this
arrangement, the overload protection is effective in both the Y and Δ circuit. The overload
relay should be set for 58% of the rated motor current.
L1
L2
L3
Q1
>
>
1
3
5
2
4
6
135
K2
246
F1
W1
W2
V1 M V2
U1 3~ U2
Circuit diagram main circuit for
135
K3
246
NSB0_01770
K1
N
>
circuit
A YΔ timing relay is required for switching from the Y to the Δ circuit. These timing relays are
specifically designed for these types of applications and ensure safe, reliable switchover.
The respective timing relays are listed in the Catalog LV 1 "Low-Voltage Controls". The
specified combinations are designed for a starting time of 10 seconds in Y operation. In
order to prevent damage to the Y contactor in the event of a motor blockage, operation
should switch to Δ mode within a maximum of 10 seconds.
In the tables, circuit breakers are used for starter combinations (without overload releases).
However, 3RV10 motor starter protectors with the same rated current can also be used for
motor protection instead. In this case, the rated motor current of the motor starter protector
must be set to the maximum value. This prevents a simultaneous tripping of the motor starter
protector and overload relay.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
13
General Information
Soft starting with soft starters
What is the basic principle of a soft starter?
Soft starters limit the starting current and starting torque. This reliably prevents mechanical
stress and mains voltage dips. The motor voltage is reduced using phase control and is
increased from an adjustable starting voltage up to the mains voltage within a specific ramp
time. Soft starting and stopping reduces the stress on connected equipment, thus ensuring
prolonged smooth and trouble-free production.
Motor voltage
Motor current
Direct Wyestarting delta
Soft
starter
Motor torque
M Direct
Direct
starting
starting
100%
58%
M Wye-
Wyedelta
Ramp
time
Time
delta
MN
Rotat. M Soft
speed starter
Soft
starter
N
nN
L1
U L1-L3
L2
Rotat.
speed
NSB0_01999
nN
L3
UL1-L3
G1
2SHUDWLQJDQJOH
M
3~
3ULQFLSOHRIWKHRSHUDWLQJDQJOH
RIWKHPDLQVYROWDJHIRU
VROLGVWDWHHOHPHQWVLQVRIW
VWDUWHUV
● 3RW30 soft starters for the soft starting of three-phase asynchronous motors for simple
applications
– performance range: up to 55 kW at 400 V (75 hp at 460 V)
● 3RW40 soft starters with integrated functions; solid-state motor overload and intrinsic
device protection and adjustable current limiting
– performance range: up to 250 kW at 400 V (300 hp at 460 V)
● The 3RW44 solid-state soft starters offer the following:
– soft starting and stopping
– solid-state motor overload and intrinsic device protection
– adjustable current limiting
– numerous functions for higher-level requirements
– performance range:
up to 710 kW at 400 V in standard circuit
up to 1200 kW at 400 V (1700 hp at 460 V) in
in the inside-delta circuit
Further information can be found in the Internet at:
SIRIUS soft starters (http://www.siemens.de/sanftstarter)
For optimum configurations, we recommend using the selection and simulation program
"Win-Soft Starter".
Order or download at:
Demonstration software (http://www.siemens.de/lowvoltage/demosoftware)
(Order No.: E20001-D1020-P302-V2-7400)
14
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
General Information
Load feeders with soft starters
Soft starters can also be used to prevent current peaks in the line supply instead of the
star(wye)-delta starting combinations. Three versions of these soft starters are available:
● 3RW30
● 3RW40
● 3RW44
The 3RW4 soft starters come as standard with an integrated solid-state overload relay. This
means that, in fuseless combinations, a motor starter protector is only required for shortcircuit protection. In the case of 3RW30 soft starters, the motor starter protector must also
cover the overload protection.
3RB22 / 23 overload relays and SIMOCODE pro
The modular, solid-state overload relays with external power supply type 3RB22 / 23 for
high-feature applications up to 630 A have been designed for inverse-time delayed
protection of loads with normal and heavy starting against excessive temperature rises due
to overload, phase unbalance or phase failure.
SIMOCODE pro is a flexible, modular motor management system for motors with constant
speeds in the low-voltage performance range. It provides the intelligent, communicationcapable interface between the higher-level automation system and the motor feeder.
A configuration with 3RB22 / 23 overload relays and with SIMOCODE pro requires in each
case a basic unit, a connection cable and a current measuring module. The MLFBs of the
current measuring modules are listed in the tables. Details of the basic units and connection
cables are given in the following:
3RB22 / 23
● Basic unit (= evaluation module)
– Monostable, screw: 3RB22 83-4AA1
– Bistable, screw: 3RB23 83-4AA1
– Monostable, spring-loaded: 3RB22 83-4AC1
– Bistable, spring-loaded: 3RB23 83-4AC1
● Connection cable
– 0.1 m (S00-S3): 3RB29 87-2B
– 0.5 m (S00-S12): 3RB29 87-2D
● For other accessories for 3RB22 / 23 overload relays see Catalog LV 1 Chapter 5.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
15
General Information
SIMOCODE pro
● SIMOCODE pro C, Basic Unit 1
PROFIBUS DP interface, 12 Mbit/s, RS485 4I / 3O freely assignable, input for thermistor
connection, monostable relay outputs
– 24 V DC: 3UF7 000-1AB00-0
– 110 ... 240 V AC / DC: 3UF7 000-1AU00-0
● SIMOCODE pro V, Basic Unit 2
PROFIBUS DP interface, 12 Mbit/s, RS485 4I / 3O freely assignable, input for thermistor
connection, monostable relay outputs, can be expanded by expansion modules
– 24 V DC: 3UF7 010-1AB00-0
– 110 ... 240 V AC / DC: 3UF7 010-1AU00-0
● Connection cable
– 0.1 m, flat: 3UF7 931-0AA00-0
– 0.3 m, flat: 3UF7 935-0AA00-0
– 0.5 m, flat: 3UF7 932-0AA00-0
– 0.5 m, round: 3UF7 932-0BA00-0
– 1.0 m, round: 3UF7 937-0BA00-0
– 2.5 m, round: 3UF7 933-0BA00-0
● For other accessories and software for SIMOCODE pro see Catalog LV 1 Chapter 7.
16
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
3
Selection tables 400 V AC
3.1
Motor starter protector / circuit breaker + contactor
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq = 50 kA / 80 kA
$&9
Standard three-phase
motor
4-pole at 400 V AC1
Motor starter
protector / circuit
breaker
Contactor2
P
Setting range
Overload
release
Motor
Motor starter
current
protector /
(guide value) circuit breaker
kW
A
A
Order No.
Order No.
0,06
0,2
0,14 ... 0,20
3RV10 11-0BA10
3RT10 15-1AP01
S00/S00
50
0,06
0,2
0,18 ... 0,25
3RV10 11-0CA10
3RT10 15-1AP01
S00/S00
50
0,09
0,3
0,22 ... 0,32
3RV10 11-0DA10
3RT10 15-1AP01
S00/S00
50
0,09
0,3
0,28 ... 0,40
3RV10 11-0EA10
3RT10 15-1AP01
S00/S00
50
0,12
0,4
0,35 ... 0,50
3RV10 11-0FA10
3RT10 15-1AP01
S00/S00
50
0,18
0,6
0,45 ... 0,63
3RV10 11-0GA10
3RT10 15-1AP01
S00/S00
50
0,25
0,85
0,55 ... 0,80
3RV10 11-0HA10
3RT10 15-1AP01
S00/S00
50
0,25
0,85
0,70 ... 1,00
3RV10 11-0JA10
3RT10 15-1AP01
S00/S00
50
0,37
1,1
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
50
0,55
1,5
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
50
0,75
1,9
1,40 ... 2,00
3RV10 11-1BA10
3RT10 15-1AP01
S00/S00
50
0,75
1,9
1,80 ... 2,50
3RV10 11-1CA10
3RT10 15-1AP01
S00/S00
50
1,1
2,7
2,20 ... 3,20
3RV10 11-1DA10
3RT10 15-1AP01
S00/S00
50
1,5
3,6
2,80 ... 4,00
3RV10 11-1EA10
3RT10 15-1AP01
S00/S00
50
1,5
3,6
3,50 ... 5,00
3RV10 11-1FA10
3RT10 15-1AP01
S00/S00
50
2,2
5,0
4,50 ... 6,30
3RV10 11-1GA10
3RT10 15-1AP01
S00/S00
50
3
6,5
5,50 ... 8,00
3RV10 11-1HA10
3RT10 15-1AP01
S00/S00
50
Standard
output
Size
Short-circuit
breaking
capacity
Iq
I
kA
4
8,5
7,00 ... 10,0
3RV10 11-1JA10
3RT10 16-1AP01
S00/S00
50
5,5
11,5
9,00 ... 12,0
3RV10 11-1KA10
3RT10 17-1AP01
S00/S00
50
7,5
15,5
11,0 ... 16,0
3RV10 21-4AA10
3RT10 25-1AP00
S0/S0
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
17
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
Standard three-phase
motor
4-pole at 400 V AC1
Motor starter
protector / circuit
breaker
Contactor2
P
Setting range
Overload
release
Motor
Motor starter
current
protector /
(guide value) circuit breaker
kW
A
A
Order No.
Order No.
7,5
15,5
14,0 ... 20,0
3RV10 21-4BA10
3RT10 25-1AP00
S0/S0
50
11
22
17,0 ... 22,0
3RV10 21-4CA10
3RT10 26-1AP00
S0/S0
50
11
22
20,0 ... 25,0
3RV10 21-4DA10
3RT10 26-1AP00
S0/S0
50
15
29
22,0 ... 32,0
3RV10 31-4EA10
3RT10 34-1AP00
S2/S2
50
18,5
35
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
50
22
41
36,0 ... 45,0
3RV10 31-4GA10
3RT10 36-1AP00
S2/S2
50
Standard
output
Size
Short-circuit
breaking
capacity
Iq
I
kA
22
41
40,0 ... 50,0
3RV10 31-4HA10
3RT10 36-1AP00
S2/S2
50
30
55
45,0 ... 63,0
3RV10 41-4JA10
3RT10 44-1AP00
S3/S3
50
30
55
45,0 ... 63,0
3RV10 42-4JA10
3RT10 44-1AP00
S3/S3
80
37
66
57,0 ... 75,0
3RV10 41-4KA10
3RT10 45-1AP00
S3/S3
50
37
66
57,0 ... 75,0
3RV10 42-4KA10
3RT10 45-1AP00
S3/S3
80
45
80
70,0 ... 90,0
3RV10 41-4LA10
3RT10 46-1AP00
S3/S3
50
45
80
70,0 ... 90,0
3RV10 42-4LA10
3RT10 46-1AP00
S3/S3
80
45
80
80,0 ... 100
3RV10 41-4MA10
3RT10 46-1AP00
S3/S3
50
45
80
80,0 ... 100
3RV10 42-4MA10
3RT10 46-1AP00
S3/S3
80
55
97
40,0 ... 100
3VL27 10-2SP333
3RT10 54-1AP36
–/S6
50
75
132
64,0 ... 160
3VL27 16-2SP33
3RT10 55-6AP36
–/S6
50
20-2SP363
90
160
80,0 ... 200
3VL37
110
195
80,0 ... 200
3VL37 20-2SP364
3RT10 56-6AP36
–/S6
50
3RT10 64-6AP36
–/S10
50
110
195
80,0 ... 200
3VL37 20-2SP364
3RT12 64-6AP56
–/S10V
50
132
230
100 ... 250
3VL37 25-2SP365
3RT10 65-6AP36
–/S10
50
132
230
100 ... 250
3VL37 25-2SP365
3RT12 65-6AP36
–/S10V
50
160
280
125 ... 315
3VL47 31-2SP36
3RT10 66-6AP36
–/S10
50
160
280
125 ... 315
3VL47 31-2SP36
3RT12 66-6AP36
–/S10V
50
200
350
200 ... 500
3VL57 50-2SP36
3RT10 75-6AP36
–/S12
50
200
350
200 ... 500
3VL57 50-2SP36
3RT12 75-6AP36
–/S12V
50
250
430
200 ... 500
3VL57 50-2SP36
3RT10 76-6AP36
–/S12
50
250
430
200 ... 500
3VL57 50-2SP36
3RT12 76-6AP36
–/S12V
50
1
2
3
4
5
18
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL27 16-2SP33 also possible.
Alternatively 3VL37 25-2SP36 also possible.
Alternatively 3VL47 31-2SP36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard three-phase
motor
4-pole at 400 V AC1
Motor starter
protector / circuit
breaker
Contactor2
P
Setting range
Overload
release
Motor
Motor starter
current
protector /
(guide value) circuit breaker
kW
A
A
Order No.
Order No.
0,06
0,2
0,14 ... 0,20
3RV10 11-0BA10
3RT10 15-1AP01
S00/S00
50
0,06
0,2
0,18 ... 0,25
3RV10 11-0CA10
3RT10 15-1AP01
S00/S00
50
0,09
0,3
0,22 ... 0,32
3RV10 11-0DA10
3RT10 15-1AP01
S00/S00
50
0,09
0,3
0,28 ... 0,40
3RV10 11-0EA10
3RT10 15-1AP01
S00/S00
50
0,12
0,4
0,35 ... 0,50
3RV10 11-0FA10
3RT10 15-1AP01
S00/S00
50
0,18
0,6
0,45 ... 0,63
3RV10 11-0GA10
3RT10 15-1AP01
S00/S00
50
0,25
0,85
0,55 ... 0,80
3RV10 11-0HA10
3RT10 15-1AP01
S00/S00
50
0,25
0,85
0,70 ... 1,00
3RV10 11-0JA10
3RT10 15-1AP01
S00/S00
50
0,37
1,1
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
50
0,55
1,5
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
50
0,75
1,9
1,40 ... 2,00
3RV10 11-1BA10
3RT10 15-1AP01
S00/S00
50
Standard
output
Size
Short-circuit
breaking capacity
Iq
I
kA
0,75
1,9
1,80 ... 2,50
3RV10 21-1CA10
3RT10 24-1AP00
S0/S0
50
1,1
2,7
2,20 ... 3,20
3RV10 21-1DA10
3RT10 24-1AP00
S0/S0
50
1,5
3,6
2,80 ... 4,00
3RV10 21-1EA10
3RT10 24-1AP00
S0/S0
50
1,5
3,6
3,50 ... 5,00
3RV10 21-1FA10
3RT10 24-1AP00
S0/S0
50
2,2
5,0
4,50 ... 6,30
3RV10 21-1GA10
3RT10 24-1AP00
S0/S0
50
3
6,5
5,50 ... 8,00
3RV10 21-1HA10
3RT10 24-1AP00
S0/S0
50
4
8,5
7,00 ... 10,0
3RV10 21-1JA10
3RT10 26-1AP00
S0/S0
50
5,5
11,5
9,00 ... 12,5
3RV10 21-1KA10
3RT10 26-1AP00
S0/S0
50
7,5
15,5
11,0 ... 16,0
3RV10 21-4AA10
3RT10 26-1AP00
S0/S0
50
7,5
15,5
14,0 ... 20,0
3RV10 21-4BA10
3RT10 26-1AP00
S0/S0
50
11
22
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00
S2/S2
50
15
29
22,0 ... 32,0
3RV10 31-4EA10
3RT10 34-1AP00
S2/S2
50
18,5
35
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
50
22
41
36,0 ... 45,0
3RV10 31-4GA10
3RT10 36-1AP00
S2/S2
50
22
41
40,0 ... 50,0
3RV10 31-4HA10
3RT10 36-1AP00
S2/S2
50
30
55
45,0 ... 63,0
3RV10 41-4JA10
3RT10 44-1AP00
S3/S3
50
37
66
57,0 ... 75,0
3RV10 41-4KA10
3RT10 45-1AP00
S3/S3
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
19
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
Standard three-phase
motor
4-pole at 400 V AC1
Motor starter
protector / circuit
breaker
Contactor2
P
Setting range
Overload
release
Motor
Motor starter
current
protector /
(guide value) circuit breaker
kW
A
A
Order No.
Order No.
45
80
70,0 ... 90,0
3RV10 41-4LA10
3RT10 46-1AP00
S3/S3
50
45
80
80,0 ... 100
3RV10 41-4MA10
3RT10 46-1AP00
S3/S3
50
55
97
40,0 ... 100
3VL27 10-2SP333
3RT10 54-1AP36
–/S6
50
75
132
64,0 ... 160
3VL27 16-2SP33
3RT10 55-6AP36
–/S6
50
Standard
output
Size
Short-circuit
breaking capacity
Iq
I
kA
90
160
80,0 ... 200
3VL37
110
195
80,0 ... 200
3VL37 20-2SP364
110
195
80,0 ... 200
3VL37 20-2SP364
3RT12 64-6AP56
–/S10V
50
132
230
100 ... 250
3VL37 25-2SP365
3RT10 65-6AP36
–/S10
50
100 ... 250
25-2SP365
3RT12 65-6AP36
–/S10V
50
132
230
3VL37
20-2SP363
3RT10 56-6AP36
–/S6
50
3RT10 64-6AP36
–/S10
50
160
280
125 ... 315
3VL47 31-2SP36
3RT10 66-6AP36
–/S10
50
160
280
125 ... 315
3VL47 31-2SP36
3RT12 66-6AP36
–/S10V
50
200
350
200 ... 500
3VL57 50-2SP36
3RT10 75-6AP36
–/S12
50
200
350
200 ... 500
3VL57 50-2SP36
3RT12 75-6AP36
–/S12V
50
250
430
200 ... 500
3VL57 50-2SP36
3RT10 76-6AP36
–/S12
50
250
430
200 ... 500
3VL57 50-2SP36
3RT12 76-6AP36
–/S12V
50
1
2
3
4
5
20
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL27 16-2SP33 also possible.
Alternatively 3VL37 25-2SP36 also possible.
Alternatively 3VL47 31-2SP36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard three-phase
motor
4-pole at 400 V AC1
Standard
output
Setting range
Overload
release
Motor starter
protector
Motor starter
protector
Contactor2
Size
Short-circuit
breaking
capacity
Iq
P
Motor
current
(guide value)
kW
A
A
Order No.
Order No.
0,04
0,16
0,11 ... 0,16
3RV10 11-0AA10
3RT10 15-1AP01
S00/S00
130
0,06
0,2
0,14 ... 0,20
3RV10 11-0BA10
3RT10 15-1AP01
S00/S00
130
0,06
0,2
0,18 ... 0,25
3RV10 11-0CA10
3RT10 15-1AP01
S00/S00
130
0,09
0,3
0,22 ... 0,32
3RV10 11-0DA10
3RT10 15-1AP01
S00/S00
130
0,09
0,3
0,28 ... 0,40
3RV10 11-0EA10
3RT10 15-1AP01
S00/S00
130
0,12
0,4
0,35 ... 0,50
3RV10 11-0FA10
3RT10 15-1AP01
S00/S00
130
0,18
0,6
0,45 ... 0,63
3RV10 11-0GA10
3RT10 15-1AP01
S00/S00
130
0,18
0,6
0,55 ... 0,80
3RV10 11-0HA10
3RT10 15-1AP01
S00/S00
130
0,25
0,85
0,70 ... 1,00
3RV10 11-0JA10
3RT10 15-1AP01
S00/S00
130
0,37
1,1
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
130
0,55
1,5
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
130
0,75
1,9
1,40 ... 2,00
3RV10 11-1BA10
3RT10 15-1AP01
S00/S00
130
0,04
0,16
0,11 ... 0,16
3RV10 21-0AA10
3RT10 24-1AP00
S0/S0
130
0,06
0,2
0,14 ... 0,20
3RV10 21-0BA10
3RT10 24-1AP00
S0/S0
130
0,06
0,2
0,18 ... 0,25
3RV10 21-0CA10
3RT10 24-1AP00
S0/S0
130
0,09
0,3
0,22 ... 0,32
3RV10 21-0DA10
3RT10 24-1AP00
S0/S0
130
0,09
0,3
0,28 ... 0,40
3RV10 21-0EA10
3RT10 24-1AP00
S0/S0
130
0,12
0,4
0,35 ... 0,50
3RV10 21-0FA10
3RT10 24-1AP00
S0/S0
130
0,18
0,6
0,45 ... 0,63
3RV10 21-0GA10
3RT10 24-1AP00
S0/S0
130
0,18
0,6
0,55 ... 0,80
3RV10 21-0HA10
3RT10 24-1AP00
S0/S0
130
0,25
0,85
0,70 ... 1,00
3RV10 21-0JA10
3RT10 24-1AP00
S0/S0
130
0,37
1,1
0,90 ... 1,25
3RV10 21-0KA10
3RT10 24-1AP00
S0/S0
130
0,55
1,5
1,10 ... 1,60
3RV10 21-1AA10
3RT10 24-1AP00
S0/S0
130
0,75
1,9
1,40 ... 2,00
3RV10 21-1BA10
3RT10 24-1AP00
S0/S0
130
I
kA
0,75
1,9
1,80 ... 2,50
3RV10 21-1CA10
3RT10 24-1AP00
S0/S0
130
1,1
2,7
2,20 ... 3,20
3RV10 21-1DA10
3RT10 24-1AP00
S0/S0
130
1,5
3,6
2,80 ... 4,00
3RV10 21-1EA10
3RT10 24-1AP00
S0/S0
130
1,5
3,6
3,50 ... 5,00
3RV10 21-1FA10
3RT10 24-1AP00
S0/S0
130
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
21
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
Standard three-phase
motor
4-pole at 400 V AC1
Standard
output
Setting range
Overload
release
Motor starter
protector
Motor starter
protector
Contactor2
Size
Short-circuit
breaking
capacity
Iq
P
Motor
current
(guide value)
kW
A
A
Order No.
Order No.
2,2
5
4,50 ... 6,30
3RV10 21-1GA10
3RT10 24-1AP00
3
6,5
5,50 ... 8,00
3RV10 21-1HA10
3RT10 24-1AP00
S0/S0
130
4
8,5
7,00 ... 10,0
3RV10 21-1JA10
3RT10 26-1AP00
S0/S0
130
5,5
11,5
9,00 ... 12,5
3RV10 21-1KA10
3RT10 26-1AP00
S0/S0
130
7,5
15,5
11,0 ... 16,0
3RV10 21-4AA10
3RT10 26-1AP00
S0/S0
100
7,5
15,5
14,0 ... 20,0
3RV10 21-4BA10
3RT10 26-1AP00
S0/S0
100
11
22
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00
S2/S2
100
15
29
22,0 ... 32,0
3RV10 31-4EA10
3RT10 34-1AP00
S2/S2
100
18,5
35
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
100
I
kA
S0/S0
130
22
41
36,0 ... 45,0
3RV10 31-4GA10
3RT10 36-1AP00
S2/S2
100
22
41
40,0 ... 50,0
3RV10 31-4HA10
3RT10 36-1AP00
S2/S2
100
30
55
45,0 ... 63,0
3RV10 42-4JA10
3RT10 54-1AP36
S3/S6
100
37
66
57,0 ... 75,0
3RV10 42-4KA10
3RT10 54-1AP36
S3/S6
100
45
80
70,0 ... 90,0
3RV10 42-4LA10
3RT10 54-1AP36
S3/S6
100
45
80
80,0 ... 100
3RV10 42-4MA10
3RT10 54-1AP36
S3/S6
100
1
2
22
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 100 kA
$&9
Standard three-phase
motor
4-pole at 400 V AC1
Standard
output
1
2
3
4
5
6
P
Motor
current
(guide value)
kW
A
Setting range
Overload
release
Circuit breaker
Circuit breaker
A
Order No.
Contactor2
Size
Short-circuit
breaking
capacity
Iq
I
16-3SP333
Order No.
55
97
40,0 ... 160
3VL27
75
132
64,0 ... 160
3VL27 16-3SP33
3RT10 55-6AP36
–/S6
100
90
160
80,0 ... 250
3VL37 25-3SP364
3RT10 56-6AP36
–/S6
100
110
195
80,0 ... 200
3VL37 20-3SP365
3RT10 64-6AP36
–/S10
100
110
195
80,0 ... 200
3VL37 20-3SP365
3RT12 64-6AP36
–/S10V
100
132
230
100 ... 250
3VL37 25-3SP36
3RT10 65-6AP36
–/S10
100
25-3SP366
3RT10 54-1AP36
kA
–/S6
100
132
230
100 ... 250
3VL37
3RT12 65-6AP36
–/S10V
100
160
280
125 ... 315
3VL47 31-3SP36
3RT10 75-6AP36
–/S12
100
160
280
125 ... 315
3VL47 31-3SP36
3RT12 66-6AP36
–/S10V
100
200
350
200 ... 500
3VL57 50-3SP36
3RT10 75-6AP36
–/S12
100
200
350
200 ... 500
3VL57 50-3SP36
3RT12 75-6AP36
–/S12V
100
250
430
200 ... 500
3VL57 50-3SP36
3RT10 76-6AP36
–/S12
100
250
430
200 ... 500
3VL57 50-3SP36
3RT12 76-6AP36
–/S12V
100
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL27 10-3SP33 also possible.
Alternatively 3VL27 20-3SP33 also possible.
Alternatively 3VL27 25-3SP36 also possible.
Alternatively 3VL47 31-3SP36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
23
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
CLASS 20, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA / 100 kA
$&9
Standard three-phase
motor
4-pole at 400 V AC1
Motor starter
protector / circuit
breaker
Contactor2
P
Setting range
Overload
release
Motor
Motor starter
current
protector /
(guide value) circuit breaker
kW
A
A
Order No.
Order No.
5,5
11,5
11,0 ... 16,0
3RV10 31-4AB10
3RT10 34-1AP00
S2/S2
50
7,5
15,5
14,0 ... 20,0
3RV10 31-4BB10
3RT10 34-1AP00
S2/S2
50
11
22
18,0 ... 25,0
3RV10 31-4DB10
3RT10 35-1AP00
S2/S2
50
11
22
22,0 ... 32,0
3RV10 31-4EB10
3RT10 35-1AP00
S2/S2
50
15
29
28,0 ... 40,0
3RV10 42-4FB10
3RT10 44-1AP00
S3/S3
50
18,5
35
28,0 ... 40,0
3RV10 42-4FB10
3RT10 44-1AP00
S3/S3
50
18,5
35
36,0 ... 50,0
3RV10 42-4HB10
3RT10 44-1AP00
S3/S3
50
22
41
36,0 ... 50,0
3RV10 42-4HB10
3RT10 44-1AP00
S3/S3
50
30
55
45,0 ... 63,0
3RV10 42-4JB10
3RT10 46-1AP00
S3/S3
50
30
55
57,0 ... 75,0
3RV10 42-4KB10
3RT10 46-1AP00
S3/S3
50
Standard
output
Size
Short-circuit
breaking
capacity
Iq
I
kA
Iq = 50 kA
37
66
57,0 ... 75,0
3RV10 42-4KB10
3RT10 46-1AP00
S3/S3
50
45
80
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36
S3/S6
50
45
80
80,0 ... 100
3RV10 42-4MB10
3RT10 54-1AP36
S3/S6
50
10-2SS333
55
97
40,0 ... 100
3VL27
3RT10 55-6AP36
–/S6
50
75
132
64,0 ... 160
3VL27 16-2SS33
3RT10 56-6AP36
–/S6
50
90
160
80,0 ... 200
3VL37 20-2SS363
3RT10 64-6AP36
–/S10
50
90
160
80,0 ... 200
3VL37 20-2SS363
3RT10 65-6AP36
–/S10
50
80,0 ... 200
3VL37
20-2SS364
3RT10 66-6AP36
–/S10
50
20-2SS364
110
195
110
195
80,0 ... 200
3VL37
3RT12 64-6AP36
–/S10V
50
132
230
100 ... 250
3VL37 25-2SS365
3RT12 65-6AP36
–/S10V
50
160
280
125 ... 315
3VL47 31-2SS36
3RT12 66-6AP36
–/S10V
50
160
280
125 ... 315
3VL47 31-2SS36
3RT10 75-6AP36
–/S12
50
200
350
200 ... 500
3VL57 50-2SS36
3RT10 76-6AP36
–/S12
50
200
350
200 ... 500
3VL57 50-2SS36
3RT12 75-6AP36
–/S12V
50
250
430
200 ... 500
3VL57 50-2SS36
3RT12 76-6AP36
–/S12V
50
80
40,0 ... 100
3VL27 10-3SS33
3RT10 54-1AP36
–/S6
100
Iq = 100 kA
45
24
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
Standard three-phase
motor
4-pole at 400 V AC1
Motor starter
protector / circuit
breaker
Contactor2
P
Setting range
Overload
release
Motor
Motor starter
current
protector /
(guide value) circuit breaker
kW
A
Order No.
Order No.
Standard
output
1
2
3
4
5
6
7
8
9
Size
Short-circuit
breaking
capacity
Iq
I
A
10-3SS336
3RT10 55-6AP36
kA
55
97
40,0 ... 100
3VL27
–/S6
100
75
132
64,0 ... 160
3VL27 16-3SS33
3RT10 56-6AP36
–/S6
100
90
160
80,0 ... 200
3VL37 20-3SS367
3RT10 64-6AP36
–/S10
100
90
160
80,0 ... 200
3VL37 20-3SS367
3RT10 65-6AP36
–/S10
100
20-3SS368
110
195
80,0 ... 200
3VL37
3RT10 66-6AP36
–/S10
100
110
195
80,0 ... 200
3VL37 20-3SS368
3RT12 64-6AP36
–/S10V
100
132
230
100 ... 250
3VL37 25-3SS369
3RT12 65-6AP36
–/S10V
100
160
280
125 ... 315
3VL47 31-3SS36
3RT12 66-6AP36
–/S10V
100
160
280
125 ... 315
3VL47 31-3SS36
3RT10 75-6AP36
–/S12
100
200
350
200 ... 500
3VL57 50-3SS36
3RT10 76-6AP36
–/S12
100
200
350
200 ... 500
3VL57 50-3SS36
3RT12 75-6AP36
–/S12V
100
250
430
200 ... 500
3VL57 50-3SS36
3RT12 76-6AP36
–/S12V
100
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL27 16-2SS33 also possible.
Alternatively 3VL37 25-2SS36 also possible.
Alternatively 3VL47 31-2SS36 also possible.
Alternatively 3VL27 16-3SS33 also possible.
Alternatively 3VL27 16-3SS33 also possible.
Alternatively 3VL37 25-3SS36 also possible.
Alternatively 3VL47 31-3SS36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
25
Selection tables 400 V AC
3.1 Motor starter protector / circuit breaker + contactor
CLASS 30, type of coordination 2,
short-circuit breaking capacity Iq = 100 kA
$&9
Standard three-phase
motor
4-pole at 400 V AC1
Standard
output
Setting range
Overload
release
Circuit breaker
Circuit breaker
Contactor2
Size
Short-circuit
breaking
capacity
Iq
P
Motor
current
(guide value)
kW
A
A
Order No.
Order No.
37
66
40,0 ... 100
3VL27 10-3SS33
3RT10 54-1AP36
–/S6
45
80
40,0 ... 100
3VL27 10-3SS33
3RT10 55-6AP36
–/S6
100
55
97
64,0 ... 160
3VL27 16-3SS333
3RT10 56-6AP36
–/S6
100
75
132
64,0 ... 160
3VL27 16-3SS33
3RT10 64-6AP36
–/S10
100
90
160
80,0 ... 200
3VL37 20-3SS334
3RT10 65-6AP36
–/S10
100
90
160
80,0 ... 200
3VL37 20-3SS334
3RT12 64-6AP36
–/S10V
100
110
195
100 ... 250
3VL37 25-3SS36
3RT12 65-6AP36
–/S10V
100
132
230
100 ... 250
3VL37 25-3SS365
3RT10 75-6AP36
–/S12
100
160
280
125 ... 315
3VL47 31-3SS36
3RT10 76-6AP36
–/S12
100
160
280
125 ... 315
3VL47 31-3SS36
3RT12 75-6AP36
–/S12V
100
200
350
200 ... 500
3VL57 50-3SS36
3RT12 76-6AP36
–/S12V
100
1
2
3
4
5
26
I
kA
100
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL27 10-3SS33 also possible.
Alternatively 3VL27 16-3SS33 also possible.
Alternatively 3VL47 31-3SS36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.2 Motor starter protector + contactor + 3RU11 thermal overload relay
3.2
Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq = 50 kA / 80 kA
$&9
Standard threephase motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector
Overload
Standard Motor release
output
current Motor
P
(guide starter
value) protector
Contactor2
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kA
Iq
I
kW
A
A
Order No.
Order No.
Order No.
A
0,06
0,2
None
3RV13 21-0BC10
3RT10 15-1AP01 S0/S00
3RU11 16-0BB0
0,14 ... 0,20 50
0,06
0,2
None
3RV13 21-0CC10
3RT10 15-1AP01 S0/S00
3RU11 16-0CB0
0,18 ... 0,25 50
0,09
0,3
None
3RV13 21-0DC10
3RT10 15-1AP01 S0/S00
3RU11 16-0DB0
0,22 ... 0,32 50
0,09
0,3
None
3RV13 21-0EC10
3RT10 15-1AP01 S0/S00
3RU11 16-0EB0
0,28 ... 0,40 50
0,12
0,4
None
3RV13 21-0FC10
3RT10 15-1AP01 S0/S00
3RU11 16-0FB0
0,35 ... 0,50 50
0,18
0,6
None
3RV13 21-0GC10
3RT10 15-1AP01 S0/S00
3RU11 16-0GB0
0,45 ... 0,63 50
0,25
0,85
None
3RV13 21-0HC10
3RT10 15-1AP01 S0/S00
3RU11 16-0HB0
0,55 ... 0,80 50
0,25
0,85
None
3RV13 21-0JC10
3RT10 15-1AP01 S0/S00
3RU11 16-0JB0
0,70 ... 1,00 50
0,37
1,1
None
3RV13 21-0KC10
3RT10 15-1AP01 S0/S00
3RU11 16-0KB0
0,90 ... 1,25 50
0,55
1,5
None
3RV13 21-1AC10
3RT10 15-1AP01 S0/S00
3RU11 16-1AB0
1,10 ... 1,60 50
0,75
1,9
None
3RV13 21-1BC10
3RT10 15-1AP01 S0/S00
3RU11 16-1BB0
1,40 ... 2,00 50
1,1
2,7
None
3RV13 21-1DC10
3RT10 15-1AP01 S0/S00
3RU11 16-1DB0
2,20 ... 3,20 50
1,5
3,6
None
3RV13 21-1EC10
3RT10 15-1AP01 S0/S00
3RU11 16-1EB0
2,80 ... 4,00 50
1,5
3,6
None
3RV13 21-1FC10
3RT10 15-1AP01 S0/S00
3RU11 16-1FB0
3,50 ... 5,00 50
2,2
5,0
None
3RV13 21-1GC10
3RT10 15-1AP01 S0/S00
3RU11 16-1GB0
4,50 ... 6,30 50
3
6,5
None
3RV13 21-1HC10
3RT10 15-1AP01 S0/S00
3RU11 16-1HB0
5,50 ... 8,00 50
4
8,5
None
3RV13 21-1JC10
3RT10 16-1AP01 S0/S00
3RU11 16-1JB0
7,00 ... 10,0 50
5,5
11,5
None
3RV13 21-1KC10
3RT10 17-1AP01 S0/S00
3RU11 16-1KB0
9,00 ... 12,0 50
7,5
15,5
None
3RV13 21-4AC10
3RT10 24-1AP00 S0/S0
3RU11 26-4AB0
11,0 ... 16,0 50
7,5
15,5
None
3RV13 21-4BC10
3RT10 25-1AP00 S0/S0
3RU11 26-4BB0
14,0 ... 20,0 50
11
22
None
3RV13 21-4CC10
3RT10 26-1AP00 S0/S0
3RU11 26-4CB0
17,0 ... 22,0 50
11
22
None
3RV13 21-4DC10
3RT10 26-1AP00 S0/S0
3RU11 26-4DB0
20,0 ... 25,0 50
15
29
None
3RV13 31-4EC10
3RT10 34-1AP00 S2/S2
3RU11 36-4EB0
22,0 ... 32,0 50
18,5
35
None
3RV13 31-4FC10
3RT10 35-1AP00 S2/S2
3RU11 36-4FB0
28,0 ... 40,0 50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
27
Selection tables 400 V AC
3.2 Motor starter protector + contactor + 3RU11 thermal overload relay
Standard threephase motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector
Overload
Standard Motor release
output
current Motor
P
(guide starter
value) protector
Contactor2
kW
A
A
Order No.
Order No.
22
41
None
3RV13 31-4GC10
22
41
None
30
55
None
30
55
37
37
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3RT10 36-1AP00 S2/S2
3RU11 36-4GB0
36,0 ... 45,0 50
3RV13 31-4HC10
3RT10 36-1AP00 S2/S2
3RU11 36-4HB0
40,0 ... 50,0 50
3RV13 41-4JC10
3RT10 44-1AP00 S3/S3
3RU11 46-4JB0
45,0 ... 63,0 50
None
3RV13 42-4JC10
3RT10 44-1AP00 S3/S3
3RU11 46-4JB0
45,0 ... 63,0 80
66
None
3RV13 41-4KC10
3RT10 45-1AP00 S3/S3
3RU11 46-4KB0
57,0 ... 75,0 50
66
None
3RV13 42-4KC10
3RT10 45-1AP00 S3/S3
3RU11 46-4KB0
57,0 ... 75,0 80
45
80
None
3RV13 41-4LC10
3RT10 46-1AP00 S3/S3
3RU11 46-4LB0
70,0 ... 90,0 50
45
80
None
3RV13 42-4LC10
3RT10 46-1AP00 S3/S3
3RU11 46-4LB0
70,0 ... 90,0 80
45
80
None
3RV13 41-4MC10
3RT10 46-1AP00 S3/S3
3RU11 46-4MB0
80,0 ... 100
50
45
80
None
3RV13 42-4MC10
3RT10 46-1AP00 S3/S3
3RU11 46-4MB0
80,0 ... 100
80
Iq
I
1
2
28
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.2 Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector
Overload
release
Motor
Standa Motor starter
rd
current protector
output (guide
P
value)
Contactor2
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kA
Iq
I
kW
A
A
Order No.
Order No.
Order No.
A
0,06
0,2
None
3RV13 21-0BC10
3RT10 15-1AP01
S0/S00
3RU11 16-0BB0
0,14 ... 0,20 50
0,06
0,2
None
3RV13 21-0CC10 3RT10 15-1AP01
S0/S00
3RU11 16-0CB0
0,18 ... 0,25 50
0,09
0,3
None
3RV13 21-0DC10 3RT10 15-1AP01
S0/S00
3RU11 16-0DB0
0,22 ... 0,32 50
0,09
0,3
None
3RV13 21-0EC10
3RT10 15-1AP01
S0/S00
3RU11 16-0EB0
0,28 ... 0,40 50
0,12
0,4
None
3RV13 21-0FC10
3RT10 15-1AP01
S0/S00
3RU11 16-0FB0
0,35 ... 0,50 50
0,18
0,6
None
3RV13 21-0GC10 3RT10 15-1AP01
S0/S00
3RU11 16-0GB0
0,45 ... 0,63 50
0,25
0,85
None
3RV13 21-0HC10 3RT10 15-1AP01
S0/S00
3RU11 16-0HB0
0,55 ... 0,80 50
0,25
0,85
None
3RV13 21-0JC10
3RT10 15-1AP01
S0/S00
3RU11 16-0JB0
0,70 ... 1,00 50
0,37
1,1
None
3RV13 21-0KC10
3RT10 15-1AP01
S0/S00
3RU11 16-0KB0
0,90 ... 1,25 50
0,55
1,5
None
3RV13 21-1AC10
3RT10 15-1AP01
S0/S00
3RU11 16-1AB0
1,10 ... 1,60 50
3RT10 15-1AP01
0,75
1,9
None
3RV13 21-1BC10
S0/S00
3RU11 16-1BB0
1,40 ... 2,00 50
0,75
1,9
None
3RV13 21-1CC10 3RT10 24-1AP00
S0/S0
3RU11 26-1CB0
1,80 ... 2,50 50
1,1
2,7
None
3RV13 21-1DC10 3RT10 24-1AP00
S0/S0
3RU11 26-1DB0
2,20 ... 3,20 50
1,5
3,6
None
3RV13 21-1EC10
3RT10 24-1AP00
S0/S0
3RU11 26-1EB0
2,80 ... 4,00 50
1,5
3,6
None
3RV13 21-1FC10
3RT10 24-1AP00
S0/S0
3RU11 26-1FB0
3,50 ... 5,00 50
2,2
5,0
None
3RV13 21-1GC10 3RT10 24-1AP00
S0/S0
3RU11 26-1GB0
4,50 ... 6,30 50
3
6,5
None
3RV13 21-1HC10 3RT10 24-1AP00
S0/S0
3RU11 26-1HB0
5,50 ... 8,00 50
4
8,5
None
3RV13 21-1JC10
3RT10 26-1AP00
S0/S0
3RU11 26-1JB0
7,00 ... 10,0 50
5,5
11,5
None
3RV13 21-1KC10
3RT10 26-1AP00
S0/S0
3RU11 26-1KB0
9,00 ... 12,5 50
7,5
15,5
None
3RV13 21-4AC10
3RT10 26-1AP00
S0/S0
3RU11 26-4AB0
11,0 ... 16,0 50
7,5
15,5
None
3RV13 21-4BC10
3RT10 26-1AP00
S0/S0
3RU11 26-4BB0
14,0 ... 20,0 50
11
22
None
3RV13 31-4DC10 3RT10 34-1AP00
S2/S2
3RU11 36-4DB0
18,0 ... 25,0 50
15
29
None
3RV13 31-4EC10
3RT10 34-1AP00
S2/S2
3RU11 36-4EB0
22,0 ... 32,0 50
18,5
35
None
3RV13 31-4FC10
3RT10 35-1AP00
S2/S2
3RU11 36-4FB0
28,0 ... 40,0 50
22
41
None
3RV13 31-4GC10 3RT10 36-1AP00
S2/S2
3RU11 36-4GB0
36,0 ... 45,0 50
22
41
None
3RV13 31-4HC10 3RT10 36-1AP00
S2/S2
3RU11 36-4HB0
40,0 ... 50,0 50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
29
Selection tables 400 V AC
3.2 Motor starter protector + contactor + 3RU11 thermal overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector
Overload
release
Motor
Standa Motor starter
rd
current protector
output (guide
P
value)
Contactor2
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
Order No.
A
kA
30
55
None
3RV13 41-4JC10
3RT10 44-1AP00
S3/S3
3RU11 46-4JB0
45,0 ... 63,0 50
37
66
None
3RV13 41-4KC10
3RT10 45-1AP00
S3/S3
3RU11 46-4KB0
57,0 ... 75,0 50
45
80
None
3RV13 41-4LC10
3RT10 46-1AP00
S3/S3
3RU11 46-4LB0
70,0 ... 90,0 50
45
80
None
3RV13 41-4MC10 3RT10 46-1AP00
S3/S3
3RU11 46-4MB0
80,0 ... 100
Iq
I
1
2
30
Order No.
50
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.2 Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Iq
I
kW
A
A
Order No.
Order No.
Order No.
A
kA
0,04
0,16
None
3RV13 21-0AC10
3RT10 15-1AP01
S0/S00
3RU11 16-0AB0
0,11 ... 0,16
130
0,06
0,2
None
3RV13 21-0BC10
3RT10 15-1AP01
S0/S00
3RU11 16-0BB0
0,14 ... 0,20
130
0,06
0,2
None
3RV13 21-0CC10
3RT10 15-1AP01
S0/S00
3RU11 16-0CB0
0,18 ... 0,25
130
0,09
0,3
None
3RV13 21-0DC10
3RT10 15-1AP01
S0/S00
3RU11 16-0DB0
0,22 ... 0,32
130
0,09
0,3
None
3RV13 21-0EC10
3RT10 15-1AP01
S0/S00
3RU11 16-0EB0
0,28 ... 0,40
130
0,12
0,4
None
3RV13 21-0FC10
3RT10 15-1AP01
S0/S00
3RU11 16-0FB0
0,35 ... 0,50
130
0,18
0,6
None
3RV13 21-0GC10
3RT10 15-1AP01
S0/S00
3RU11 16-0GB0
0,45 ... 0,63
130
0,18
0,6
None
3RV13 21-0HC10
3RT10 15-1AP01
S0/S00
3RU11 16-0HB0
0,55 ... 0,80
130
0,25
0,85
None
3RV13 21-0JC10
3RT10 15-1AP01
S0/S00
3RU11 16-0JB0
0,70 ... 1,00
130
0,37
1,1
None
3RV13 21-0KC10
3RT10 15-1AP01
S0/S00
3RU11 16-0KB0
0,90 ... 1,25
130
0,55
1,5
None
3RV13 21-1AC10
3RT10 15-1AP01
S0/S00
3RU11 16-1AB0
1,10 ... 1,60
130
0,75
1,9
None
3RV13 21-1BC10
3RT10 15-1AP01
S0/S00
3RU11 16-1BB0
1,40 ... 2,00
130
0,75
1,9
None
3RV13 21-1CC10
3RT10 24-1AP00
S0/S0
3RU11 26-1CB0
1,80 ... 2,50
130
1,1
2,7
None
3RV13 21-1DA10
3RT10 24-1AP00
S0/S0
3RU11 26-1DB0
2,20 ... 3,20
130
1,5
3,6
None
3RV13 21-1EA10
3RT10 24-1AP00
S0/S0
3RU11 26-1EB0
2,80 ... 4,00
130
1,5
3,6
None
3RV13 21-1FA10
3RT10 24-1AP00
S0/S0
3RU11 26-1FB0
3,50 ... 5,00
130
2,2
5
None
3RV13 21-1GC10
3RT10 24-1AP00
S0/S0
3RU11 26-1GB0
4,50 ... 6,30
130
3
6,5
None
3RV13 21-1HC10
3RT10 24-1AP00
S0/S0
3RU11 26-1HB0
5,50 ... 8,00
130
4
8,5
None
3RV13 21-1JC10
3RT10 26-1AP00
S0/S0
3RU11 26-1JB0
7,00 ... 10,0
130
5,5
11,5
None
3RV13 21-1KC10
3RT10 26-1AP00
S0/S0
3RU11 26-1KB0
9,00 ... 12,5
130
7,5
15,5
None
3RV13 21-4AC10
3RT10 26-1AP00
S0/S0
3RU11 26-4AB0
11,0 ... 16,0
100
7,5
15,5
None
3RV13 21-4BC10
3RT10 26-1AP00
S0/S0
3RU11 26-4BB0
14,0 ... 20,0
100
11
22
None
3RV13 31-4DC10
3RT10 34-1AP00
S2/S2
3RU11 36-4DB0
18,0 ... 25,0
100
15
29
None
3RV13 31-4EC10
3RT10 34-1AP00
S2/S2
3RU11 36-4EB0
22,0 ... 32,0
100
18,5
35
None
3RV13 31-4FC10
3RT10 35-1AP00
S2/S2
3RU11 36-4FB0
28,0 ... 40,0
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
31
Selection tables 400 V AC
3.2 Motor starter protector + contactor + 3RU11 thermal overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
kW
A
A
Order No.
Order No.
22
41
None
3RV13 31-4GC10
3RT10 36-1AP00
S2/S2
3RU11 36-4GB0
36,0 ... 45,0
100
22
41
None
3RV13 31-4HC10
3RT10 36-1AP00
S2/S2
3RU11 36-4HB0
40,0 ... 50,0
100
1
2
32
Order No.
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
3.3
Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21
solid-state overload relay
CLASS 5 and CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stan Motor starter
dard curre protector /
outp nt
circuit
ut
(guid breaker2
P
e
value
)
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,06
0,2
0,22 ... 0,32 3RV10 11-0DA10
3RT10 15-1AP01
S00/S00 3RB20 16-1RB0/
S00/S00 3RB21 13-4RB0
0,10 ... 0,40 50
0,32 ... 1,25 50
0,09
0,3
0,28 ... 0,40 3RV10 11-0EA10
3RT10 15-1AP01
0,12
0,4
0,70 ... 1,00 3RV10 11-0JA10
3RT10 15-1AP01
0,18
0,6
0,70 ... 1,00 3RV10 11-0JA10
3RT10 15-1AP01
S00/S00 3RB20 16-1NB0/
S00/S00 3RB21 13-4NB0
0,25
0,85
1,10 ... 1,60 3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
0,32 ... 1,25 50
0,37
1,1
1,10 ... 1,60 3RV10 11-1AA10
3RT10 15-1AP01
1,00 ... 4,00 50
1,00 ... 4,00 50
0,55
1,5
1,40 ... 2,00 3RV10 11-1BA10
3RT10 24-1AP00
S00/S00 3RB20 16-1PB0/
S00/S00 3RB21 13-4PB0
0,55
1,5
None
3RT10 24-1AP00
S0/S0
3RV13 21-1BC10
3RB21 23-4PB0
0,10 ... 0,40 50
0,32 ... 1,25 50
1,00 ... 4,00 50
0,75
1,9
None
3RV13 21-1CC10
3RT10 24-1AP00
S0/S0
1,00 ... 4,00 50
1,1
2,7
None
3RV13 21-1DC10
3RT10 24-1AP00
S0/S0
1,00 ... 4,00 50
1,5
3,5
None
3RV13 21-1EC10
3RT10 24-1AP00
S0/S0
2,2
5
None
3RV13 21-1GC10
3RT10 24-1AP00
S0/S0
3
6,5
None
3RV13 21-1HC10
3RT10 24-1AP00
S0/S0
4
8,5
None
3RV13 21-1JC10
3RT10 26-1AP00
S0/S0
5,5
11,5
None
3RV13 21-1KC10
3RT10 26-1AP00
S0/S0
7,5
15,5
14,0 ... 20,0 3RV10 21-4BA10
3RT10 26-1AP00
S0/S0
3RB20 26-1SB0/
3RB21 23-4SB0
3,00 ... 12,0 50
3,00 ... 12,0 50
3,00 ... 12,0 50
3RB20 26-1QB0/
3RB21 23-4QB0
6,00 ... 25,0 50
6,00 ... 25,0 50
6,00 ... 25,0 50
11
22
None
3RV13 31-4EC10
3RT10 34-1AP00
S2/S2
29
28,0 ... 40,0 3RV10 31-4FA10
3RT10 36-1AP00
S2/S2
3RB20 36-1UB0/
3RB21 33-4UB0
12,5 ... 50,0 50
15
15
29
None
3RT10 44-1AP00
S3/S3
3RB20 46-1EB0/
25,0 ... 100
3RV13 41-4FC10
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
12,5 ... 50,0 50
50
33
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stan Motor starter
dard curre protector /
outp nt
circuit
ut
(guid breaker2
P
e
value
)
Motor starter
protector / circuit
breaker
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Iq
I
kW
A
A
Order No.
Order No.
18,5
35
None
3RV13 41-4FC10
3RT10 44-1AP00
S3/S3
22
41
None
3RV13 41-4HC10
3RT10 44-1AP00
30
55
None
3RV13 41-4JC10
37
66
None
3RV13 41-4KC10
A
kA
25,0 ... 100
50
S3/S3
25,0 ... 100
50
3RT10 44-1AP00
S3/S3
25,0 ... 100
50
3RT10 45-1AP00
S3/S3
25,0 ... 100
50
45
80
70,0 ... 90,0 3RV10 41-4LA10
3RT10 46-1AP00
S3/S3
55
97
None
3VL27 10-2DK33
3RT10 54-1AP36
–/S6
55
97
None
3VL27 16-2DK33
3RT10 54-1AP36
–/S6
75
132
None
3VL27 16-2DK33
3RT10 55-6AP36
–/S6
90
160
None
3VL27 16-2DK33
3RT10 56-6AP36
–/S6
90
160
None
3VL37 25-2DK36
3RT10 56-6AP36
–/S6
110
195
None
3VL37 25-2DK36
3RT10 64-6AP36
–/S10
110
195
None
3VL37 25-2DK36
3RT12 64-6AP36
–/S10V
132
230
None
3VL47 25-2DK36
3RT10 65-6AP36
132
230
None
3VL47 25-2DK36
3RT12 65-6AP36
132
230
None
3VL47 31-2DK36
3RT10 65-6AP36
132
230
None
3VL47 31-2DK36
3RT12 65-6AP36
–/S10V
160
280
None
3VL47 31-2DK36
3RT10 66-6AP36
–/S10
160
280
None
3VL47 31-2DK36
3RT12 66-6AP36
–/S10V
200
350
None
3VL57 50-2DK36
3RT10 75-6AP36
200
350
None
3VL57 50-2DK36
3RT12 75-6AP36
Order No.
3RB21 43-4EB0
25,0 ... 100
50
3RB20 56-1FW2/
3RB21 53-4FW2
50,0 ... 200
50
50,0 ... 200
50
3RB20 56-1FC2/
3RB21 53-4FC2
50,0 ... 200
50
50,0 ... 200
50
50,0 ... 200
50
55,0 ... 250
50
55,0 ... 250
50
–/S10
55,0 ... 250
50
–/S10V
55,0 ... 250
50
–/S10
55,0 ... 250
50
3RB20 66-1GC2/
3RB21 63-4GC2
55,0 ... 250
50
160 ... 630
50
160 ... 630
50
–/S12
160 ... 630
50
–/S12V
160 ... 630
50
3RB20 66-1MC2/
3RB21 63-4MC2
250
430
None
3VL57 50-2DK36
3RT10 76-6AP36
–/S12
160 ... 630
50
250
430
None
3VL57 50-2DK36
3RT12 76-6AP36
–/S12V
160 ... 630
50
3RB20 6.-.M.2/
3RB21 63-4MC2
160 ... 630
50
160 ... 630
50
3UF1 868-3GA00
+ 3RB20 16-1NB0
205 ... 820
50
Type of coordination 1
315
540
None
3VL77 12-1DE36
3TF68 44-0CM7
–/14
355
610
None
3VL77 12-1DE36
3TF68 44-0CM7
–/14
400
690
None
3VL87 16-1DE30
3TF69 44-0CM7
–/14
1
2
3
34
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
CLASS 5 and CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
kW
Order No.
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,09
0,3
0,28 ... 0,40
3RV10 11-0DA10 3RT10 15-1AP01 S00/S00 3RB20 16-1RB0/
3RV10 11-0EA10 3RT10 15-1AP01 S00/S00 3RB21 13-4RB0
0,12
0,4
0,70 ... 1,00
3RV10 11-0JA10
0,18
0,6
0,70 ... 1,00
3RV10 11-0JA10
0,06
0,2
0,22 ... 0,32
3RT10 15-1AP01 S00/S00 3RB20 16-1NB0/
3RT10 15-1AP01 S00/S00 3RB21 13-4NB0
0,10 ... 0,40 130
0,32 ... 1,25 130
0,10 ... 0,40 130
0,32 ... 1,25 130
0,25
0,85
1,10 ... 1,60
3RV10 11-1AA10 3RT10 15-1AP01 S00/S00
0,32 ... 1,25 130
0,37
1,1
1,10 ... 1,60
3RV10 11-1AA10 3RT10 15-1AP01 S00/S00 3RB20 16-1PB0/
3RB21 13-4PB0
1,00 ... 4,00 130
0,37
1,1
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
3RB21 23-4PB0/
3RB20 26-1PB0
1,00 ... 4,00 130
0,55
1,5
1,40 ... 2,00
3RV10 11-1BA10 3RT10 15-1AP01 S00/S00 3RB20 16-1PB0/
3RB21 13-4PB0
1,00 ... 4,00 130
0,55
1,5
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
1,00 ... 4,00 130
0,75
1,9
None
3RV13 21-1CC10 3RT10 24-1AP00 S0/S0
3RB21 23-4PB0/
3RB20 26-1PB0
1,1
2,7
None
3RV13 21-1DC10 3RT10 24-1AP00 S0/S0
1,5
3,5
None
3RV13 21-1EC10 3RT10 24-1AP00 S0/S0
2,2
5
None
3RV13 21-1GC10 3RT10 24-1AP00 S0/S0
3
6,5
None
3RV13 21-1HC10 3RT10 24-1AP00 S0/S0
4
8,5
None
3RV13 21-1JC10 3RT10 26-1AP00 S0/S0
5,5
11,5
None
3RV13 21-1KC10 3RT10 26-1AP00 S0/S0
7,5
15,5
14,0 ... 20,0
3RV10 21-4BA10 3RT10 26-1AP00 S0/S0
11
22
None
3RV13 31-4EC10 3RT10 34-1AP00 S2/S2
15
29
28,0 ... 40,0
3RV10 31-4FA10 3RT10 36-1AP00 S2/S2
15
29
None
3RV13 42-4FC10 3RT10 54-1AP36 S3/S6
18,5
35
None
22
41
None
30
55
None
1,00 ... 4,00 130
1,00 ... 4,00 130
3RB20 26-1SB0/
3RB21 23-4SB0
3,00 ... 12,0 130
3,00 ... 12,0 130
3,00 ... 12,0 130
3RB20 26-1QB0/
3RB21 23-4QB0
6,00 ... 25,0 130
6,00 ... 25,0 130
6,00 ... 25,0 100
3RB20 36-1UB0/
3RB21 33-4UB0
12,5 ... 50,0 100
12,5 ... 50,0 100
100
3RV13 42-4FC10 3RT10 54-1AP36 S3/S6
3RB20 46-1EW1/ 25,0 ... 100
3RB21 43-4EW1 25,0 ... 100
3RV13 42-4HC10 3RT10 54-1AP36 S3/S6
25,0 ... 100
100
3RV13 42-4JC10 3RT10 54-1AP36 S3/S6
25,0 ... 100
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
100
35
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
Order No.
A
kA
30
55
None
3RV13 42-4JC10 3RT10 54-1AP36 S3/S6
3RB20 56-1FW2/ 50,0 ... 200
3RB21 53-4FW2
100
37
66
None
3RV13 42-4KC10 3RT10 54-1AP36 S3/S6
3RB20 46-1EW1/ 25,0 ... 100
3RB21 43-4EW1
100
37
66
None
3RV13 42-4KC10 3RT10 54-1AP36 S3/S6
3RB20 56-1FW2/ 50,0 ... 200
3RB21 53-4FW2
100
45
80
70,0 ... 90,0
3RV10 42-4LA10 3RT10 54-1AP36 S3/S6
3RB20 46-1EW1/ 25,0 ... 100
3RB21 43-4EW1
100
45
80
70,0 ... 90,0
3RV10 42-4LA10 3RT10 54-1AP36 S3/S6
100
55
97
None
3VL27 10-3DK33 3RT10 54-1AP36 –/S6
3RB20 56-1FW2/ 50,0 ... 200
3RB21 53-4FW2 50,0 ... 200
100
55
97
None
3VL27 16-3DK33 3RT10 54-1AP36 –/S6
50,0 ... 200
100
75
132
None
3VL27 16-3DK33 3RT10 55-6AP36 –/S6
50,0 ... 200
100
50,0 ... 200
100
50,0 ... 200
100
3RB20 66-1GC2/ 55,0 ... 250
3RB21 63-4GC2 55,0 ... 250
100
55,0 ... 250
100
Iq
I
Order No.
90
160
None
3VL27 16-3DK33 3RT10 56-6AP36 –/S6
90
160
None
3VL37 25-3DK36 3RT10 56-6AP36 –/S6
110
195
None
3VL37 25-3DK36 3RT10 64-6AP36 –/S10
3RB20 56-1FC2/
3RB21 53-4FC2
110
195
None
3VL37 25-3DK36 3RT12 64-6AP36 –/S10V
132
230
None
3VL47 25-3DK364 3RT10 75-6AP36 –/S12
100
132
230
None
3VL47 25-3DK364 3RT12 65-6AP36 –/S10V
160
280
None
3VL47 31-3DK36 3RT10 75-6AP36 –/S12
160
280
None
3VL47 31-3DK36 3RT12 66-6AP36 –/S10V
200
350
None
3VL57 50-3DK36 3RT10 75-6AP36 –/S12
160 ... 630
100
200
350
None
3VL57 50-3DK36 3RT12 75-6AP36 –/S12V
160 ... 630
100
55,0 ... 250
100
3RB20 66-1MC2/ 160 ... 630
3RB21 63-4MC2 160 ... 630
100
100
250
430
None
3VL57 50-3DK36 3RT10 76-6AP36 –/S12
160 ... 630
100
250
430
None
3VL57 50-3DK36 3RT12 76-6AP36 –/S12V
160 ... 630
100
36
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
kW
A
A
Type of coordination 1
Order No.
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3RB20 66-1M.2/
3RB21 6.-.M.2
160 ... 630
100
160 ... 630
100
3UF1 868-3GA00 205 ... 820
+ 3RB20 161NB05)
100
Iq
I
1
2
3
4
5
Order No.
315
540
None
3VL77 12-3DE36 3TF68 44-0CM7
–/14
355
610
None
3VL77 12-3DE36 3TF68 44-0CM7
–/14
400
690
None
3VL87 16-3DE30 3TF69 44-0CM7
–/14
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL47 31-3DK36 also possible.
Use terminal bracket for stand-alone installation of overload relays.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
37
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
CLASS 20, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
curren protector /
output t
circuit
P
(guide breaker2
value)
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
Overload relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,06
0,2
50
0,3
0,28 ... 0,40 3RV10 11-0EA10 3RT10 15-1AP01 S00/S00 3RB20 16-2RB0/
0,70 ... 1,00 3RV10 11-0JA10 3RT10 15-1AP01 S00/S00 3RB21 13-4RB0
0,10 ... 0,40
0,09
0,10 ... 0,40
50
0,12
0,4
0,70 ... 1,00 3RV10 11-0JA10
0,32 ... 1,25
50
0,18
0,6
3RT10 15-1AP01 S00/S00 3RB20 16-2NB0/
1,10 ... 1,60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00 3RB21 13-4NB0
0,32 ... 1,25
50
0,25
0,85
1,10 ... 1,60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00
0,32 ... 1,25
50
0,37
1,1
1,40 ... 2,00 3RV10 11-1BA10 3RT10 15-1AP01 S00/S00 3RB20 16-2PB0/
3RB21 13-4PB0
1,00 ... 4,00
50
0,37
1,1
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
1,00 ... 4,00
50
0,55
1,5
None
3RV13 21-1DC10 3RT10 24-1AP00 S0/S0
3RB21 23-4PB0/
3RB20 26-1PB0
1,00 ... 4,00
50
0,75
1,9
2,80 ... 4,00 3RV10 21-1EA10 3RT10 24-1AP00 S0/S0
1,00 ... 4,00
50
1,1
2,7
3,50 ... 5,00 3RV10 21-1FA10 3RT10 24-1AP00 S0/S0
1,00 ... 4,00
50
1,5
3,5
None
3RV13 21-1GC10 3RT10 24-1AP00 S0/S0
2,2
5
None
3RV13 21-1JC10
3
6,5
11,0 ... 16,0 3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
3RT10 26-1AP00 S0/S0
4
8,5
11,0 ... 16,0 3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
5,5
11,5
18,0 ... 25,0 3RV10 31-4DA10 3RT10 34-1AP00 S2/S2
7,5
15,5
22,0 ... 32,0 3RV10 31-4EA10 3RT10 35-1AP00 S2/S2
11
22
28,0 ... 40,0 3RV10 31-4FA10 3RT10 36-1AP00 S2/S2
15
29
36,0 ... 50,0 3RV10 42-4HA10 3RT10 54-1AP36 S3/S6
15
29
18,5
35
3,00 ... 12,0
50
3,00 ... 12,0
50
3RB20 36-2QB0/
3RB21 33-4QB0
6,00 ... 25,0
50
6,00 ... 25,0
50
6,00 ... 25,0
50
6,00 ... 25,0
50
3RB20 36-2UB0/
3RB21 33-4UB0
12,5 ... 50,0
50
12,5 ... 50,0
50
36,0 ... 50,0 3RV10 41-4HA10 3RT10 44-1AP00 S3/S3
3RB20 46-2UB0/
3RB21 43-4UB0
12,5 ... 50,0
50
None
3RB20 46-2EB0/
3RB21 43-4EB0
25,0 ... 100
50
3RV13 41-4JC10
3RT10 45-1AP00 S3/S3
22
41
57,0 ... 75,0 3RV10 41-4KA10 3RT10 46-1AP00 S3/S3
30
55
70,0 ... 90,0 3RV10 42-4LB10
3RT10 46-1AP00 S3/S3
37
66
None
3RT10 54-1AP36 –/S6
38
3RB20 26-2SB0/
3RB21 23-4SB0
3VL27 10-2DK33
25,0 ... 100
50
25,0 ... 100
50
3RB20 56-2FW2/ 50,0 ... 200
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
curren protector /
output t
circuit
P
(guide breaker2
value)
Motor starter
protector / circuit
breaker
Contactor3
Size
kW
A
A
Order No.
Order No.
45
80
None
3VL27 10-2DK33
3RT10 54-1AP36 –/S6
55
97
None
3VL27 10-2DK33
3RT10 55-6AP36 –/S6
Overload relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
50,0 ... 200
50
50
Iq
I
Order No.
3RB21 53-4FW2
55
97
None
3VL27 16-2DK33
3RT10 55-6AP36 –/S6
3RB20 56-2FW2/ 50,0 ... 200
3RB21 53-4FW2 50,0 ... 200
75
132
None
3VL37 25-2DK36
3RT10 56-6AP36 –/S6
50,0 ... 200
50
90
160
None
3VL27 16-2DK33
3RT10 64-6AP36 –/S10
160
None
3VL37 25-2DK36
3RT10 65-6AP36 –/S10
3RB20 66-2GC2/ 55,0 ... 250
3RB21 63-4GC2 55,0 ... 250
50
90
110
195
None
3VL37 25-2DK36
3RT10 66-6AP36 –/S10
55,0 ... 250
50
110
195
None
3VL37 25-2DK36
3RT12 64-6AP36 –/S10V
55,0 ... 250
50
132
230
None
3VL37 25-2DK36
3RT12 65-6AP36 –/S10V
55,0 ... 250
50
132
230
None
3VL47 31-2DK36
3RT12 65-6AP36 –/S10V
55,0 ... 250
50
160
280
None
3VL47 31-2DK36
3RT10 75-6AP36 –/S12
280
None
3VL47 31-2DK36
3RT12 66-6AP36 –/S10V
3RB20 66-2MC2/ 160 ... 630
3RB21 63-4MC2 160 ... 630
50
160
200
350
None
3VL57 50-2DK36
3RT10 76-6AP36 –/S12
160 ... 630
50
200
350
None
3VL57 50-2DK36
3RT12 75-6AP36 –/S12V
160 ... 630
50
250
430
None
3VL57 50-2DK36
3RT12 76-6AP36 –/S12V
160 ... 630
50
3VL77 12-1DE36
3TF69 44-0CM7
160 ... 630
50
50
50
50
Type of coordination 1
315
1
2
3
540
None
–/14
3RB20 6.-.M.2/
3RB21 6.-.M.2
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
39
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
CLASS 20, types of coordination 2 and 1,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Standar Motor starter
d
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,06
0,2
0,09
0,3
0,12
0,4
0,18
0,6
0,28 ... 0,40 3RV10 11-0EA10 3RT10 15-1AP01 S00/S00 3RB20 16-2RB0/ 0,10 ... 0,40 130
0,70 ... 1,00 3RV10 11-0JA10 3RT10 15-1AP01 S00/S00 3RB21 13-4RB0 0,10 ... 0,40 130
0,70 ... 1,00 3RV10 11-0JA10 3RT10 15-1AP01 S00/S00 3RB20 16-2NB0/ 0,32 ... 1,25 130
1,10 ... 1,60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00 3RB21 13-4NB0 0,32 ... 1,25 130
0,25
0,85
1,10 ... 1,60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00
0,37
1,1
1,40 ... 2,00 3RV10 11-1BA10 3RT10 15-1AP01 S00/S00 3RB20 16-2PB0/ 1,00 ... 4,00 130
3RB21 13-4PB0
0,32 ... 1,25 130
0,37
1,1
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,55
1,5
None
3RV13 21-1DC10 3RT10 24-1AP00 S0/S0
3RB21 23-4PB0/ 1,00 ... 4,00 130
3RB20 26-1PB0 1,00 ... 4,00 130
0,75
1,9
2,80 ... 4,00 3RV10 21-1EA10 3RT10 24-1AP00 S0/S0
1,00 ... 4,00 130
1,1
2,7
3,50 ... 5,00 3RV10 21-1FA10 3RT10 24-1AP00 S0/S0
1,5
3,5
None
3RV13 21-1GC10 3RT10 24-1AP00 S0/S0
1,00 ... 4,00 130
2,2
5
None
3RV13 21-1JC10 3RT10 26-1AP00 S0/S0
3
6,5
11,0 ... 16,0 3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
4
8,5
11,0 ... 16,0 3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
3RB20 36-2QB0/ 6,00 ... 25,0 100
3RB21 33-4QB0 6,00 ... 25,0 100
5,5
11,5
18,0 ... 25,0 3RV10 31-4DA10 3RT10 34-1AP00 S2/S2
6,00 ... 25,0 100
7,5
15,5
22,0 ... 32,0 3RV10 31-4EA10 3RT10 35-1AP00 S2/S2
6,00 ... 25,0 100
11
22
28,0 ... 40,0 3RV10 31-4FA10 3RT10 36-1AP00 S2/S2
3RB20 36-2UB0/ 12,5 ... 50,0 100
3RB21 33-4UB0
15
29
36,0 ... 50,0 3RV10 42-4HA10 3RT10 54-1AP36 S3/S6
3RB20 36-2UW1/ 12,5 ... 50,0 100
3RB21 33-4UB0
15
29
36,0 ... 50,0 3RV10 42-4HA10 3RT10 54-1AP36 S3/S6
3RB20 46-2EW1/ 25,0 ... 100 100
3RB21 43-4EW1
18,5
35
None
3RB20 26-2SB0/ 3,00 ... 12,0 130
3RB21 23-4SB0 3,00 ... 12,0 130
22
41
57,0 ... 75,0 3RV10 42-4KA10 3RT10 54-1AP36 S3/S6
3RB20 46-2EB0/ 25,0 ... 100 100
3RB21 43-4EB0 25,0 ... 100 100
30
55
70,0 ... 90,0 3RV10 42-4LB10 3RT10 54-1AP36 S3/S6
25,0 ... 100 100
40
3RV13 42-4JC10 3RT10 54-1AP36 S3/S6
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Standar Motor starter
d
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
A
kA
37
66
None
3VL27 10-3DK33 3RT10 54-1AP36 –/S6
37
66
None
3VL27 16-3DK33 3RT10 54-1AP36 –/S6
3RB20 56-2FW2/ 50,0 ... 200 100
3RB21 53-4FW2 50,0 ... 200 100
45
80
None
3VL27 10-3DK33 3RT10 54-1AP36 –/S6
50,0 ... 200 100
45
80
None
3VL27 16-3DK33 3RT10 54-1AP36 –/S6
50,0 ... 200 100
55
97
None
3VL27 10-3DK33 3RT10 55-6AP36 –/S6
Iq
I
Order No.
Order No.
75
132
None
3VL27 16-3DK33 3RT10 56-6AP36 –/S6
3RB20 56-2FC2/ 50,0 ... 200 100
3RB21 53-4FC2 50,0 ... 200 100
75
132
None
3VL37 25-3DK36 3RT10 56-6AP36 –/S6
50,0 ... 200 100
90
160
None
3VL27 16-3DK33 3RT10 64-6AP36 –/S10
90
160
None
3VL37 25-3DK36 3RT10 64-6AP36 –/S10
3RB20 66-2GC2/ 55,0 ... 250 100
3RB21 63-4GC2 55,0 ... 250 100
110
195
None
3VL37 25-3DK36 3RT10 64-6AP36 –/S10
55,0 ... 250 100
110
195
None
3VL37 25-3DK36 3RT12 64-6AP36 –/S10V
55,0 ... 250 100
25-3DK364
132
230
None
3VL37
132
230
None
3VL37 25-3DK364 3RT12 65-6AP36 –/S10V
3RT10 75-6AP36 –/S12
160
280
None
3VL47 31-3DK36 3RT10 75-6AP36 –/S12
160
280
None
3VL47 31-3DK36 3RT12 66-6AP36 –/S10V
200
350
None
55,0 ... 250 100
55,0 ... 250 100
3RB20 66-1MC2/ 160 ... 630
3RB21 63-4MC2 160 ... 630
100
3VL57 50-3DK36 3RT10 76-6AP36 –/S12
160 ... 630
100
100
200
350
None
3VL57 50-3DK36 3RT12 75-6AP36 –/S12V
160 ... 630
100
250
430
None
3VL57 50-3DK36 3RT12 76-6AP36 –/S12V
160 ... 630
100
160 ... 630
100
Type of coordination 1
315
540
None
3VL77 12-3DE36 3TF69 44-0CM7
–/14
3RB20 6.-.M.2/
3RB21 6.-.M.2
1 Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
2 The motor starter protector / circuit breaker is to be set to maximum current value.
3 Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
4 Alternatively 3VL47 31-3DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
41
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
CLASS 30, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
curren protector /
output t
circuit
P
(guide breaker2
value)
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,06
0,2
0,45 ... 0,63 3RV10 11-0GA10
3RT10 15-1AP01 S00/S00 3RB21 13-4RB0
0,10 ... 0,40
50
0,09
0,3
0,55 ... 0,80 3RV10 11-0HA10
3RT10 15-1AP01 S00/S00
0,10 ... 0,40
50
0,12
0,4
0,70 ... 1,00 3RV10 11-0JA10
3RT10 15-1AP01 S00/S00 3RB21 13-4NB0
0,32 ... 1,25
50
0,18
0,6
1,10 ... 1,60 3RV10 11-1AA10
3RT10 15-1AP01 S00/S00
0,32 ... 1,25
50
0,25
0,85
1,40 ... 2,00 3RV10 11-1BA10
3RT10 15-1AP01 S00/S00
0,32 ... 1,25
50
0,37
1,1
2,20 ... 3,20 3RV10 21-1DA10
3RT10 26-1AP00 S0/S0
1,00 ... 4,00
50
0,55
1,5
2,80 ... 4,00 3RV10 21-1EA10
3RT10 26-1AP00 S0/S0
1,00 ... 4,00
50
0,75
1,9
3,50 ... 5,00 3RV10 21-1FA10
3RT10 26-1AP00 S0/S0
1,00 ... 4,00
50
1,1
2,7
3,50 ... 5,00 3RV10 21-1GA10
3RT10 26-1AP00 S0/S0
1,5
3,5
5,50 ... 8,00 3RV10 21-1HA10
3RT10 26-1AP00 S0/S0
2,2
5
9,00 ... 12,5 3RV10 21-1KA10
3
6,5
4
8,5
3RB21 23-4PB0
1,00 ... 4,00
50
3,00 ... 12,0
50
3RT10 26-1AP00 S0/S0
3,00 ... 12,0
50
11,0 ... 16,0 3RV10 31-4AA10
3RT10 34-1AP00 S2/S2
3RB21 33-4QB0 6,00 ... 25,0
50
14,0 ... 20,0 3RV10 31-4BA10
3RT10 34-1AP00 S2/S2
6,00 ... 25,0
50
5,5
11,5
22,0 ... 32,0 3RV10 31-4EA10
3RT10 34-1AP00 S2/S2
7,5
15,5
28,0 ... 40,0 3RV10 31-4FA10
3RT10 35-1AP00 S2/S2
11
22
28,0 ... 40,0 3RV10 31-4FB10
3RT10 36-1AP00 S2/S2
3RB21 23-4SB0
3RB21 33-4UB0
6,00 ... 25,0
50
12,5 ... 50,0
50
12,5 ... 50,0
50
15
29
36,0 ... 50,0 3RV10 42-4HB10
3RT10 44-1AP00 S3/S3
18,5
35
45,0 ... 63,0 3RV10 42-4JB10
3RT10 45-1AP00 S3/S3
22
41
57,0 ... 75,0 3RV10 42-4KB10
3RT10 46-1AP00 S3/S3
37
66
None
3VL27 10-2DK33
3RT10 54-1AP36 –/S6
3RB21 53-4FW2 50,0 ... 200
50
45
80
None
3VL27 10-2DK33
3RT10 55-6AP36 –/S6
3RB21 53-4FC2
50
55
97
None
3VL27 10-2DK33
3RT10 56-6AP36 –/S6
50,0 ... 200
50
75
132
None
3VL37 25-2DK36
3RT10 64-6AP36 –/S10
3RB21 63-4GC2 55,0 ... 250
50
90
160
None
3VL27 16-2DK334)
3RT10 66-6AP36 –/S10
55,0 ... 250
50
42
3RB21 43-4EB0
12,5 ... 50,0
50
25,0 ... 100
50
25,0 ... 100
50
50,0 ... 200
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.3 Motor starter protector / circuit breaker + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
curren protector /
output t
circuit
P
(guide breaker2
value)
Motor starter
protector / circuit
breaker
Contactor3
kW
A
A
Order No.
Order No.
90
160
None
3VL27 16-2DK334)
110
195
None
3VL37 25-2DK36
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
3RT12 64-6AP36 –/S10V
55,0 ... 250
50
3RT12 65-6AP36 –/S10V
55,0 ... 250
50
Iq
I
25-2DK365)
Order No.
132
230
None
3VL37
3RT10 75-6AP36 –/S12
55,0 ... 250
50
132
230
None
3VL37 25-2DK365)
3RT12 66-6AP36 –/S10V
55,0 ... 250
50
160
280
None
3VL47 31-2DK36
3RT10 76-6AP36 –/S12
3RB21 63-4MC2 160 ... 630
50
160
280
None
3VL47 31-2DK36
3RT12 75-6AP36 –/S12V
160 ... 630
50
200
350
None
3VL57 50-2DK36
3RT12 76-6AP36 –/S12V
160 ... 630
50
3VL57 50-1DK36
3TF69 44-0CM7
160 ... 630
50
Type of coordination 1
250
1
2
3
4
5
430
None
–/14
3RB21 6.-.M.2
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL37 25-2DK36 also possible.
Alternatively 3VL47 31-2DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
43
Selection tables 400 V AC
3.4 Motor starter protector / circuit breaker + contactor + 3RB21 solid-state overload relay
3.4
Motor starter protector / circuit breaker + contactor + 3RB21 solid-state
overload relay
CLASS 30, types of coordination 2 and 1,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector / circuit
breaker
Overload
release
Motor starter
Standa Motor protector /
rd
current circuit
output (guide breaker2
P
value)
Contactor3
kW
Order No.
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,06
0,2
0,45 ... 0,63
3RV10 11-0GA10 3RT10 15-1AP01 S00/S00 3RB21 13-4RB0
0,10 ... 0,40 130
0,09
0,3
0,55 ... 0,80
3RV10 11-0HA10 3RT10 15-1AP01 S00/S00
0,10 ... 0,40 130
0,12
0,4
0,70 ... 1,00
3RV10 11-0JA10
0,32 ... 1,25 130
0,18
0,6
1,10 ... 1,60
3RV10 11-1AA10 3RT10 15-1AP01 S00/S00
3RT10 15-1AP01 S00/S00 3RB21 13-4NB0
0,32 ... 1,25 130
0,25
0,85
1,40 ... 2,00
3RV10 11-1BA10 3RT10 15-1AP01 S00/S00
0,37
1,1
2,20 ... 3,20
3RV10 21-1DA10 3RT10 26-1AP00 S0/S0
0,32 ... 1,25 130
0,55
1,5
2,80 ... 4,00
3RV10 21-1EA10 3RT10 26-1AP00 S0/S0
1,00 ... 4,00 130
0,75
1,9
3,50 ... 5,00
3RV10 21-1FA10 3RT10 26-1AP00 S0/S0
1,00 ... 4,00 130
1,1
2,7
4,50 ... 6,30
3RV10 21-1GA10 3RT10 26-1AP00 S0/S0
1,00 ... 4,00 130
1,5
3,5
5,50 ... 8,00
3RV10 21-1HA10 3RT10 26-1AP00 S0/S0
2,2
5
9,00 ... 12,5
3RV10 21-1KA10 3RT10 26-1AP00 S0/S0
3
6,5
11,0 ... 16,0
3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
4
8,5
14,0 ... 20,0
3RV10 31-4BA10 3RT10 34-1AP00 S2/S2
6,00 ... 25,0 100
5,5
11,5
22,0 ... 32,0
3RV10 31-4EA10 3RT10 34-1AP00 S2/S2
6,00 ... 25,0 100
7,5
15,5
28,0 ... 40,0
3RV10 31-4FA10 3RT10 35-1AP00 S2/S2
11
22
28,0 ... 40,0
3RV10 31-4FB10 3RT10 36-1AP00 S2/S2
15
29
36,0 ... 50,0
3RB21 23-4PB0
3RB21 23-4SB0
1,00 ... 4,00 130
3,00 ... 12,0 130
3,00 ... 12,0 130
3RB21 33-4QB0
6,00 ... 25,0 100
3RB21 33-4UB0
12,5 ... 50,0 100
3RV10 42-4HB10 3RT10 54-1AP36 S3/S6
3RB21 33-4UW1
12,5 ... 50,0 100
12,5 ... 50,0 100
15
29
36,0 ... 50,0
3RV10 42-4HB10 3RT10 54-1AP36 S3/S6
3RB21 43-4EW1
25,0 ... 100
100
18,5
35
45,0 ... 63,0
3RV10 42-4JB10
3RB21 43-4EB0
25,0 ... 100
100
22
41
57,0 ... 75,0
3RV10 42-4KB10 3RT10 54-1AP36 S3/S6
25,0 ... 100
100
30
55
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36 S3/S6
30
55
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36 S3/S6
44
3RT10 54-1AP36 S3/S6
3RB21 53-4FW2
25,0 ... 100
100
50,0 ... 200
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.4 Motor starter protector / circuit breaker + contactor + 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector / circuit
breaker
Overload
release
Motor starter
Standa Motor protector /
rd
current circuit
output (guide breaker2
P
value)
Contactor3
Size
kW
A
A
Order No.
Order No.
37
66
None
37
66
None
45
80
None
3VL27 10-3DK33 3RT10 55-6AP36 –/S6
45
80
None
55
97
None
55
97
75
132
75
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
3VL27 10-3DK33 3RT10 54-1AP36 –/S6
50,0 ... 200
100
3VL27 16-3DK33 3RT10 54-1AP36 –/S6
50,0 ... 200
100
50,0 ... 200
100
3VL27 16-3DK33 3RT10 55-6AP36 –/S6
50,0 ... 200
100
3VL27 10-3DK33 3RT10 56-6AP36 –/S6
50,0 ... 200
100
None
3VL27 16-3DK33 3RT10 56-6AP36 –/S6
50,0 ... 200
100
None
3VL27 16-3DK33 3RT10 64-6AP36 –/S10
50,0 ... 200
100
132
None
3VL37 25-3DK36 3RT10 64-6AP36 –/S10
55,0 ... 250
100
90
160
None
3VL27 163DK334
3RT10 66-6AP36 –/S10
55,0 ... 250
100
90
160
None
3VL27 163DK334
3RT12 64-6AP36 –/S10V
55,0 ... 250
100
110
195
None
3VL37 25-3DK36 3RT12 65-6AP36 –/S10V
55,0 ... 250
100
132
230
None
3VL37 253DK365
3RT10 75-6AP36 –/S12
55,0 ... 250
100
132
230
None
3VL37 253DK365
3RT12 66-6AP36 –/S10V
55,0 ... 250
100
Iq
I
Order No.
3RB21 53-4FC2
3RB21 63-4GC2
160
280
None
3VL47 31-3DK36 3RT10 76-6AP36 –/S12
160 ... 630
100
160
280
None
3VL47 31-3DK36 3RT12 75-6AP36 –/S12V
3RB21 63-4MC2
160 ... 630
100
200
350
None
3VL57 50-3DK36 3RT12 76-6AP36 –/S12V
160 ... 630
100
160 ... 630
100
Type of coordination 1
250
1
2
3
4
5
430
None
3VL57 50-3DK36 3TF69 44-0CM7
–/14
3RB21 6.-.M.2
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL37 25-3DK36 also possible.
Alternatively 3VL47 31-3DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
45
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
3.5
Motor starter protector / circuit breaker + contactor + SIMOCODE pro
3UF7 / 3RB22/3RB23 solid-state overload relay
CLASS 5 and CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3UF7 100-1AA00-0/
3RB29 06-2BG1
0,30 ... 3,00 50
Iq
I
A
A
Order No.
Type of coordination 2
0,09
0,3
None
3RV13 21-0HC10 3RT10 24-1AP00 S0/S0
0,12
0,4
None
3RV13 21-0HC10 3RT10 24-1AP00 S0/S0
0,18
0,6
None
3RV13 21-0JC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,25
0,85
None
3RV13 21-0KC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,37
1,1
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,55
1,5
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,30 ... 3,00 50
0,75
1,9
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
1,1
2,7
None
3RV13 21-1DC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
1,5
3,5
None
3RV13 21-1EC10 3RT10 24-1AP00 S0/S0
2,2
5
None
3RV13 21-1GC10 3RT10 24-1AP00 S0/S0
3
6,5
None
3RV13 21-1HC10 3RT10 24-1AP00 S0/S0
2,40 ... 25,0 50
4
8,5
None
3RV13 21-1JC10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 50
5,5
11,5
None
3RV13 21-1KC10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 50
7,5
15,5
14,0 ... 20,0 3RV10 21-4BA10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 50
7,5
15,5
None
3RV13 31-4BC10 3RT10 34-1AP00 S2/S2
11
22
None
3RV13 31-4EC10 3RT10 34-1AP00 S2/S2
15
29
40,0 ... 50,0 3RV10 31-4HA10 3RT10 36-1AP00 S2/S2
3UF7 101-1AA00-0/
3RB29 06-2DG1
2,40 ... 25,0 50
2,40 ... 25,0 50
2,40 ... 25,0 50
3UF7 102-1AA00-0/
3RB29 06-2JG1
10,0 ... 100 50
10,0 ... 100 50
15
29
None
3RV13 41-4FC10 3RT10 44-1AP00 S3/S3
10,0 ... 100 50
18,5
35
None
3RV13 41-4FC10 3RT10 44-1AP00 S3/S3
10,0 ... 100 50
22
41
None
3RV13 41-4HC10 3RT10 44-1AP00 S3/S3
10,0 ... 100 50
30
55
None
3RV13 41-4JC10 3RT10 44-1AP00 S3/S3
10,0 ... 100 50
46
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
Order No.
A
kA
37
66
None
3RV13 41-4KC10 3RT10 45-1AP00 S3/S3
10,0 ... 100 50
45
80
70,0 ... 90,0 3RV10 41-4LA10 3RT10 46-1AP00 S3/S3
10,0 ... 100 50
55
97
None
3VL27 10-2DK33 3RT10 54-1AP36 –/S6
55
97
None
3VL27 16-2DK33 3RT10 54-1AP36 –/S6
75
132
None
3VL27 16-2DK33 3RT10 55-1AP36 –/S6
90
160
None
3VL37 25-2DK36 3RT10 56-6AP36 –/S6
20,0 ... 200 50
110
195
None
3VL37 25-2DK36 3RT10 64-6AP36 –/S10
63,0 ... 630 50
110
195
None
3UF7 104-1BA00-0/
3VL37 25-2DK36 3RT12 64-6AP36 –/S10V 3RB29 66-2WH2
132
230
None
3VL47 25-2DK36 3RT10 65-6AP36 –/S10
63,0 ... 630 50
132
230
None
3VL47 25-2DK36 3RT12 65-6AP36 –/S10V
63,0 ... 630 50
132
230
None
3VL47 31-2DK36 3RT10 65-6AP36 –/S10
63,0 ... 630 50
132
230
None
3VL47 31-2DK36 3RT12 65-6AP36 –/S10V
63,0 ... 630 50
160
280
None
3VL47 31-2DK36 3RT10 66-6AP36 –/S10
63,0 ... 630 50
160
280
None
3VL47 31-2DK36 3RT12 66-6AP36 –/S10V
63,0 ... 630 50
200
350
None
3VL57 50-2DK36 3RT10 75-6AP36 –/S12
63,0 ... 630 50
200
350
None
3VL57 50-2DK36 3RT12 75-6AP36 –/S12V
63,0 ... 630 50
250
430
None
3VL57 50-2DK36 3RT10 76-6AP36 –/S12
63,0 ... 630 50
250
430
None
3VL57 50-2DK36 3RT12 76-6AP36 –/S12V
63,0 ... 630 50
315
540
None
3VL77 12-1DE36 3TF68 44-0CM7
–/14
63,0 ... 630 50
3VL77 12-1DE36 3TF68 44-0CM7
–/14
Iq
I
Order No.
3UF7 103-1AA00-0/
3RB29 56-2TG2
20,0 ... 200 50
20,0 ... 200 50
20,0 ... 200 50
63,0 ... 630 50
Type of coordination 1
355
1
2
3
4
610
None
3UF7 104-1BA00-0/
3RB29 66-2WH2
63,0 ... 630 50
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
47
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
CLASS 5 and CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3UF7 100-1AA00-0/
3RB29 06-2BG1
0,30 ... 3,00 130
Iq
I
A
A
Order No.
Type of coordination 2
0,09
0,3
None
3RV13 21-0HC10 3RT10 24-1AP00 S0/S0
0,12
0,4
None
3RV13 21-0HC10 3RT10 24-1AP00 S0/S0
0,18
0,6
None
3RV13 21-0JC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,25
0,85
None
3RV13 21-0KC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,37
1,1
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,55
1,5
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,30 ... 3,00 130
0,75
1,9
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
1,1
2,7
None
3RV13 21-1DC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
1,5
3,5
None
3RV13 21-1EC10 3RT10 24-1AP00 S0/S0
2,2
5
None
3RV13 21-1GC10 3RT10 24-1AP00 S0/S0
3
6,5
None
3RV13 21-1HC10 3RT10 24-1AP00 S0/S0
2,40 ... 25,0 130
4
8,5
None
3RV13 21-1JC10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 130
5,5
11,5
None
3RV13 21-1KC10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 130
7,5
15,5
14,0 ... 20,0 3RV10 21-4BA10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 100
11
22
None
15
29
28,0 ... 40,0 3RV10 31-4FA10 3RT10 36-1AP00 S2/S2
3RV13 31-4EC10 3RT10 34-1AP00 S2/S2
15
29
None
18,5
35
22
41
3UF7 101-1AA00-0/
3RB29 06-2DG1
2,40 ... 25,0 130
2,40 ... 25,0 130
10,0 ... 100
100
10,0 ... 100
100
3RV13 42-4FC10 3RT10 54-1AP36 S3/S6
10,0 ... 100
100
None
3RV13 42-4FC10 3RT10 54-1AP36 S3/S6
10,0 ... 100
100
None
3RV13 42-4HC10 3RT10 54-1AP36 S3/S6
10,0 ... 100
100
3UF7 102-1AA00-0/
3RB29 06-2JG1
30
55
None
3RV13 42-4JC10 3RT10 54-1AP36 S3/S6
10,0 ... 100
100
37
66
None
3RV13 42-4KC10 3RT10 54-1AP36 S3/S6
10,0 ... 100
100
45
80
None
3RV13 42-4LC10 3RT10 54-1AP36 S3/S6
20,0 ... 200
100
20,0 ... 200
100
20,0 ... 200
100
55
97
None
3VL27 10-3DK33 3RT10 54-1AP36 –/S6
55
97
None
3VL27 16-3DK33 3RT10 54-1AP36 –/S6
48
3UF7 103-1AA00-0/
3RB29 56-2TG2
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
A
A
Order No.
75
132
None
90
160
None
90
160
110
110
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3VL27 16-3DK33 3RT10 55-6AP36 –/S6
20,0 ... 200
100
3VL27 16-3DK36 3RT10 56-6AP36 –/S6
20,0 ... 200
100
None
3VL27 25-3DK36 3RT10 56-6AP36 –/S6
20,0 ... 200
100
195
None
3VL37 25-3DK36 3RT10 64-6AP36 –/S10
63,0 ... 630
100
195
None
63,0 ... 630
100
Iq
I
Order No.
3UF7 104-1BA00-0/
3VL37 25-3DK36 3RT12 64-6AP36 –/S10V 3RB29 66-2WH2
25-3DK365
132
230
None
3VL47
63,0 ... 630
100
132
230
None
3VL47 25-3DK365 3RT12 65-6AP36 –/S10V
3RT10 75-6AP36 –/S12
63,0 ... 630
100
160
280
None
3VL47 31-3DK36 3RT10 75-6AP36 –/S12
63,0 ... 630
100
160
280
None
3VL47 31-3DK36 3RT12 66-6AP36 –/S10V
63,0 ... 630
100
200
350
None
3VL57 50-3DK36 3RT10 75-6AP36 –/S12
63,0 ... 630
100
200
350
None
3VL57 50-3DK36 3RT12 75-6AP36 –/S12V
63,0 ... 630
100
250
430
None
3VL57 50-3DK36 3RT10 76-6AP36 –/S12
63,0 ... 630
100
250
430
None
3VL57 50-3DK36 3RT12 76-6AP36 –/S12V
63,0 ... 630
100
10,0 ... 100
80
10,0 ... 100
80
Type of coordination 1
1
2
3
4
5
15
29
None
3RV13 42-4FC10 3RT10 44-1AP00 S3/S3
18,5
35
None
3RV13 42-4FC10 3RT10 44-1AP00 S3/S3
22
41
None
3RV13 42-4HC10 3RT10 44-1AP00 S3/S3
10,0 ... 100
80
30
55
None
3RV13 42-4JC10 3RT10 44-1AP00 S3/S3
10,0 ... 100
80
37
66
None
3RV13 42-4KC10 3RT10 45-1AP00 S3/S3
10,0 ... 100
80
45
80
70,0 ... 90,0 3RV10 42-4LA10 3RT10 46-1AP00 S3/S3
10,0 ... 100
80
3UF7 102-1AA00-0/
3RB29 06-2JG1
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Alternatively 3VL47 31-3DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
49
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
CLASS 20, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Standa Motor starter
rd
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,09
0,3
None
3RV13 21-0HC10 3RT10 24-1AP00 S0/S0
0,12
0,4
None
3RV13 21-0JC10 3RT10 24-1AP00 S0/S0
3UF7 100-1AA00-0/ 0,30 ... 3,00 50
3RB29 06-2BG1
0,30 ... 3,00 50
0,18
0,6
None
3RV13 21-0KC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,25
0,85
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,37
1,1
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,55
1,5
None
3RV13 21-1DC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,75
1,9
None
3RV13 21-1EC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
1,1
2,7
None
3RV13 21-1EC10 3RT10 24-1AP00 S0/S0
1,5
3,5
None
3RV13 21-1GC10 3RT10 24-1AP00 S0/S0
3UF7 101-1AA00-0/ 2,40 ... 25,0 50
3RB29 06-2DG1
2,40 ... 25,0 50
2,2
5
None
3RV13 21-1HC10 3RT10 24-1AP00 S0/S0
2,40 ... 25,0 50
3
6,5
None
3RV13 21-1JC10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 50
4
8,5
11,0 ... 16,0
3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
5,5
11,5
18,0 ... 25,0
3RV10 31-4DA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
7,5
15,5
22,0 ... 32,0
3RV10 31-4EA10 3RT10 35-1AP00 S2/S2
2,40 ... 25,0 50
11
22
28,0 ... 40,0
3RV10 31-4FA10 3RT10 36-1AP00 S2/S2
29
36,0 ... 50,0
3RV10 41-4HA10 3RT10 44-1AP00 S3/S3
3UF7 102-1AA00-0/ 10,0 ... 100
3RB29 06-2JG1
10,0 ... 100
50
15
18,5
35
None
3RV13 41-4JC10 3RT10 45-1AP00 S3/S3
10,0 ... 100
50
50
22
41
57,0 ... 75,0
3RV10 41-4KA10 3RT10 46-1AP00 S3/S3
10,0 ... 100
50
30
55
70,0 ... 90,0
3RV10 42-4LB10 3RT10 46-1AP00 S3/S3
10,0 ... 100
50
37
66
None
3VL27 10-2DK33 3RT10 54-1AP36 –/S6
80
None
3VL27 10-2DK33 3RT10 55-1AP36 –/S6
3UF7 103-1AA00-0/ 20,0 ... 200
3RB29 56-2TG2
20,0 ... 200
50
45
55
97
None
3VL27 10-2DK33 3RT10 54-1AP36 –/S6
20,0 ... 200
50
55
97
None
3VL27 16-2DK33 3RT10 55-1AP36 –/S6
20,0 ... 200
50
75
132
None
3VL27 16-2DK33 3RT10 56-6AP36 –/S6
20,0 ... 200
50
50
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Standa Motor starter
rd
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
Size
kW
A
A
Order No.
90
160
None
3VL27 16-2DK33 3RT10 64-6AP36 –/S10
110
195
None
3VL37 25-2DK36 3RT10 66-6AP36 –/S10
110
195
None
3VL37 25-2DK36 3RT12 64-6AP36 –/S10V
132
230
None
160
280
None
160
280
None
200
350
None
200
350
250
430
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
A
kA
Iq
I
Order No.
Order No.
3UF7 104-1BA00-0/ 63,0 ... 630
3RB29 66-2WH2
63,0 ... 630
50
63,0 ... 630
50
3VL37 25-2DK36 3RT12 65-6AP36 –/S10V
63,0 ... 630
50
3VL47 31-2DK36 3RT10 75-6AP36 –/S12
63,0 ... 630
50
3VL47 31-2DK36 3RT12 66-6AP36 –/S10V
63,0 ... 630
50
3VL57 50-2DK36 3RT10 76-6AP36 –/S12
63,0 ... 630
50
None
3VL57 50-2DK36 3RT12 75-6AP36 –/S12V
63,0 ... 630
50
None
3VL57 50-2DK36 3RT12 76-6AP36 –/S12V
63,0 ... 630
50
63,0 ... 630
50
50
Type of coordination 1
315
1
2
3
4
540
None
3VL77 12-1DE36 3TF69 44-0CM7
–/14
3UF7 104-../
3RB29 66-..
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
51
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
CLASS 20, types of coordination 2 and 1,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
Size
kW
Order No.
Order No.
3RT10 24-1AP00 S0/S0
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3UF7 100-1AA00-0/
3RB29 06-2BG1
0,30 ... 3,00 130
Iq
I
A
A
Type of coordination 2
0,09
0,3
None
3RV13 21-0HC10
0,12
0,4
None
3RV13 21-0JC10
3RT10 24-1AP00 S0/S0
0,18
0,6
None
3RV13 21-0KC10
3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,25
0,85
None
3RV13 21-1AC10
3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,37
1,1
None
3RV13 21-1BC10
3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,55
1,5
None
3RV13 21-1DC10
3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,75
1,9
None
3RV13 21-1EC10
3RT10 24-1AP00 S0/S0
1,1
2,7
None
3RV13 21-1EC10
3RT10 24-1AP00 S0/S0
1,5
3,5
None
3RV13 21-1GC10
3RT10 24-1AP00 S0/S0
2,2
5
None
3RV13 21-1HC10
3RT10 24-1AP00 S0/S0
2,40 ... 25,0 130
3
6,5
None
3RV13 21-1JC10
3RT10 26-1AP00 S0/S0
2,40 ... 25,0 130
4
8,5
11,0 ... 16,0 3RV10 31-4AA10
3RT10 34-1AP00 S2/S2
2,40 ... 25,0 100
5,5
11,5
18,0 ... 25,0 3RV10 31-4DA10
3RT10 34-1AP00 S2/S2
2,40 ... 25,0 100
7,5
15,5
22,0 ... 32,0 3RV10 31-4EA10
3RT10 35-1AP00 S2/S2
2,40 ... 25,0 100
11
22
28,0 ... 40,0 3RV10 31-4FA10
3RT10 36-1AP00 S2/S2
15
29
36,0 ... 50,0 3RV10 42-4HA10
3RT10 54-1AP36 S3/S6
18,5
35
None
3RV13 42-4JC10
3RT10 54-1AP36 S3/S6
10,0 ... 100 100
0,30 ... 3,00 130
0,30 ... 3,00 130
3UF7 101-1AA00-0/
3RB29 06-2DG1
3UF7 102-1AA00-0/
3RB29 06-2JG1
2,40 ... 25,0 130
2,40 ... 25,0 130
10,0 ... 100 100
10,0 ... 100 100
22
41
57,0 ... 75,0 3RV10 42-4KA10
3RT10 54-1AP36 S3/S6
10,0 ... 100 100
30
55
70,0 ... 90,0 3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
10,0 ... 100 100
37
66
None
3VL27 10-3DK33
3RT10 54-1AP36 –/S6
37
66
None
3VL27 16-3DK33
3RT10 54-1AP36 –/S6
45
80
None
20,0 ... 200 100
20,0 ... 200 100
3VL27
10-3DK335
3RT10 54-1AP36 –/S6
20,0 ... 200 100
10-3DK335
3RT10 55-1AP36 –/S6
20,0 ... 200 100
3RT10 56-6AP36 –/S6
20,0 ... 200 100
55
97
None
3VL27
75
132
None
3VL27 16-3DK336
52
3UF7 103-1AA00-0/
3RB29 06-2TG2
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kA
Iq
I
A
A
16-3DK336
Order No.
Order No.
A
3RT10 64-6AP36 –/S10
3UF7 104-1BA00-0/
3RB29 66-2WH2
63,0 ... 630 100
90
160
None
3VL27
110
195
None
3VL37 25-3DK36
3RT10 66-6AP36 –/S10
110
195
None
3VL37 25-3DK36
3RT12 64-6AP36 –/S10V
63,0 ... 630 100
25-3DK367
63,0 ... 630 100
132
230
None
3VL37
3RT10 75-6AP36 –/S12
63,0 ... 630 100
132
230
None
3VL37 25-3DK367
3RT12 65-6AP36 –/S10V
63,0 ... 630 100
160
280
None
3VL47 31-3DK36
3RT10 75-6AP36 –/S12
63,0 ... 630 100
160
280
None
3VL47 31-3DK36
3RT12 66-6AP36 –/S10V
63,0 ... 630 100
200
350
None
3VL57 50-3DK36
3RT10 76-6AP36 –/S12
63,0 ... 630 100
200
350
None
3VL57 50-3DK36
3RT12 75-6AP36 –/S12V
63,0 ... 630 100
250
430
None
3VL57 50-3DK36
3RT12 76-6AP36 –/S12V
63,0 ... 630 100
3VL77 12-3DE36
3TF69 44-0CM7
Type of coordination 1
315
1
2
3
4
5
6
7
540
None
–/14
3UF7 104-../
3RB29 66-..
63,0 ... 630 100
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Alternatively 3VL37 16-3DK33 also possible.
Alternatively 3VL37 25-3DK36 also possible.
Alternatively 3VL47 31-3DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
53
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
CLASS 30, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector / circuit
breaker
Overload
release
Motor starter
Stand Motor protector /
ard
current circuit
output (guide breaker2
P
value)
Contactor3
kW
Order No.
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3UF7 100-1AA00-0/
3RB29 06-2BG1
0,30 ... 3,00 50
Iq
I
A
A
Order No.
Type of coordination 2
0,09
0,3
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,12
0,4
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,18
0,6
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,25
0,85
None
3RV13 21-1CC10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 50
0,37
1,1
None
3RV10 21-1DA10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 50
0,55
1,5
None
3RV13 21-1EC10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 50
0,30 ... 3,00 50
0,75
1,9
3,50 ... 5,00
3RV10 21-1FA10 3RT10 26-1AP00 S0/S0
1,1
2,7
None
3RV13 21-1GC10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 50
1,5
3,5
None
3RV13 21-1HC10 3RT10 26-1AP00 S0/S0
2,2
5
9,00 ... 12,5
3RV10 21-1KA10 3RT10 26-1AP00 S0/S0
2,40 ... 25,0 50
3
6,5
11,0 ... 16,0
3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
4
8,5
14,0 ... 20,0
3RV10 31-4BA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
5,5
11,5
22,0 ... 32,0
3RV10 31-4EA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
7,5
15,5
28,0 ... 40,0
3RV10 31-4FA10 3RT10 35-1AP00 S2/S2
2,40 ... 25,0 50
11
22
28,0 ... 40,0
3RV10 31-4FB10 3RT10 36-1AP00 S2/S2
15
29
36,0 ... 50,0
3RV10 42-4HB10 3RT10 54-1AP36 S3/S6
18,5
35
45,0 ... 63,0
3RV10 42-4JB10
3UF7 101-1AA00-0/
3RB29 06-2DG1
2,40 ... 25,0 50
2,40 ... 25,0 50
10,0 ... 100
50
10,0 ... 100
50
3RT10 54-1AP36 S3/S6
10,0 ... 100
50
3UF7 102-1AA00-0/
3RB29 06-2JG1
22
41
57,0 ... 75,0
3RV10 42-4KB10 3RT10 54-1AP36 S3/S6
10,0 ... 100
50
30
55
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36 S3/S6
10,0 ... 100
50
37
66
None
3VL27 10-2DK33 3RT10 54-1AP36 –/S6
20,0 ... 200
50
45
80
None
3VL27 10-2DK33 3RT10 55-1AP36 –/S6
20,0 ... 200
50
55
97
None
3VL27 16-2DK33 3RT10 56-6AP36 –/S6
20,0 ... 200
50
63,0 ... 630
50
63,0 ... 630
50
75
132
None
3VL27 16-2DK33 3RT10 64-6AP36 –/S10
90
160
None
3VL27 16-2DK335 3RT10 66-6AP36 –/S10
54
3UF7 103-1AA00-0/
3RB29 56-2TG2
3UF7 104-1BA00-0/
3RB29 66-2WH2
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector / circuit
breaker
Overload
release
Motor starter
Stand Motor protector /
ard
current circuit
output (guide breaker2
P
value)
Contactor3
kW
Order No.
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
Iq
I
A
A
Order No.
90
160
None
3VL27
3RT12 64-6AP36 –/S10V
63,0 ... 630
50
110
195
None
3VL37 25-2DK36 3RT12 65-6AP36 –/S10V
63,0 ... 630
50
132
230
None
16-2DK335
3VL37
25-2DK366
3RT10 75-6AP36 –/S12
63,0 ... 630
50
25-2DK366
3RT12 66-6AP36 –/S10V
132
230
None
3VL37
63,0 ... 630
50
160
280
None
3VL47 31-2DK36 3RT10 76-6AP36 –/S12
63,0 ... 630
50
160
280
None
3VL47 31-2DK36 3RT12 75-6AP36 –/S12V
63,0 ... 630
50
200
350
None
3VL57 50-2DK36 3RT12 76-6AP36 –/S12V
63,0 ... 630
50
63,0 ... 630
50
Type of coordination 1
250
1
2
3
4
5
6
430
None
3VL57 50-1DK36 3TF69 44-0CM7
–/14
3UF7 104-../
3RB29 66-..
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Alternatively 3VL37 25-2DK36 also possible.
Alternatively 3VL47 31-2DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
55
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
3.5.1
CLASS 30, types of coordination 2 and 1, short-circuit breaking capacity Iq ≥ 100
kA
CLASS 30, types of coordination 2 and 1,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3UF7 100-1AA00-0/
3RB29 06-2BG1
0,30 ... 3,00 130
Iq
I
A
A
Order No.
Type of coordination 2
0,09
0,3
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,12
0,4
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,18
0,6
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 130
0,30 ... 3,00 130
0,25
0,85
None
3RV13 21-1CC10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 130
0,37
1,1
2,20 ... 3,20 3RV10 21-1DA10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 130
0,55
1,5
2,80 ... 4,00 3RV10 21-1EA10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 130
0,75
1,9
3,50 ... 5,00 3RV10 21-1FA10
3RT10 26-1AP00 S0/S0
0,30 ... 3,00 130
1,1
2,7
4,50 ... 6,30 3RV10 21-1GA10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 130
1,5
3,5
5,50 ... 8,00 3RV10 21-1HA10 3RT10 26-1AP00 S0/S0
2,2
5
9,00 ... 12,5 3RV10 21-1KA10 3RT10 26-1AP00 S0/S0
3
6,5
11,0 ... 16,0 3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
3UF7 101-1AA00-0/
3RB29 06-2DG1
2,40 ... 25,0 130
2,40 ... 25,0 130
2,40 ... 25,0 100
4
8,5
14,0 ... 20,0 3RV10 31-4BA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 100
5,5
11,5
22,0 ... 32,0 3RV10 31-4EA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 100
7,5
15,5
28,0 ... 40,0 3RV10 31-4FA10
3RT10 35-1AP00 S2/S2
2,40 ... 25,0 100
11
22
28,0 ... 40,0 3RV10 31-4FB10
3RT10 36-1AP00 S2/S2
15
29
36,0 ... 50,0 3RV10 42-4HB10 3RT10 54-1AP36 S3/S6
18,5
35
45,0 ... 63,0 3RV10 42-4JB10
22
41
30
55
70,0 ... 90,0 3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
30
55
70,0 ... 90,0 3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
56
10,0 ... 100
100
10,0 ... 100
100
3RT10 54-1AP36 S3/S6
10,0 ... 100
100
57,0 ... 75,0 3RV10 42-4KB10 3RT10 54-1AP36 S3/S6
10,0 ... 100
100
10,0 ... 100
100
20,0 ... 200
100
3UF7 102-1AA00-0/
3RB29 06-2JG1
3UF7 103-1AA00-0/
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
Size
SIMOCODE pro
or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
Order No.
Order No.
3RB29 56-2TG2
A
kA
37
66
None
3VL27 10-3DK33
3RT10 54-1AP36 –/S6
37
66
None
3VL27 16-3DK33
3RT10 54-1AP36 –/S6
20,0 ... 200
100
20,0 ... 200
100
45
80
None
3VL27 10-3DK33
3RT10 55-1AP36 –/S6
20,0 ... 200
100
45
80
None
55
97
None
3VL27 16-3DK33
3RT10 55-1AP36 –/S6
20,0 ... 200
100
3VL27 10-3DK33
3RT10 56-6AP36 –/S6
20,0 ... 200
100
55
97
None
3VL27 16-3DK33
3RT10 56-6AP36 –/S6
75
132
None
3VL27 16-3DK33
3RT10 64-6AP36 –/S10
90
160
None
3VL27 16-3DK335 3RT10 65-6AP36 –/S10
Iq
I
90
160
None
3VL27
110
195
None
3VL37 25-3DK36
132
230
None
16-3DK335
3VL37
25-3DK366
25-3DK366
3UF7 104-1BA00-0/
3RB29 66-2WH2
20,0 ... 200
100
63,0 ... 630
100
63,0 ... 630
100
3RT12 64-6AP36 –/S10V
63,0 ... 630
100
3RT12 65-6AP36 –/S10V
63,0 ... 630
100
3RT10 75-6AP36 –/S12
63,0 ... 630
100
132
230
None
3VL37
3RT12 66-6AP36 –/S10V
63,0 ... 630
100
160
280
None
3VL47 31-3DK36
3RT10 76-6AP36 –/S12
63,0 ... 630
100
160
280
None
3VL47 31-3DK36
3RT12 75-6AP36 –/S12V
63,0 ... 630
100
200
350
None
3VL57 50-3DK36
3RT12 76-6AP36 –/S12V
63,0 ... 630
100
3VL57 50-3DK36
3TF69 44-0CM7
63,0 ... 630
100
Type of coordination 1
250
1
2
3
4
5
6
430
None
–/14
3UF7 104-../
3RB29 66-..
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Alternatively 3VL37 25-3DK36 also possible.
Alternatively 3VL47 31-3DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
57
Selection tables 400 V AC
3.6 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7
3.6
Motor starter protector / circuit breaker + contactor + SIMOCODE pro
3UF7
CLASS 40, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
Order No.
Contactor3
Size
SIMOCODE pro
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
A
A
Order No.
Order No.
Type of coordination 2
0,09
0,3
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
3UF7 100-1AA00-0 0,30 ... 3,00 50
0,12
0,4
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,18
0,6
1,40 ... 2,00 3RV10 21-1BA10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 50
0,25
0,85
1,80 ... 2,50 3RV10 21-1CA10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00 50
0,37
1,1
2,20 ... 3,20 3RV10 21-1DA10 3RT10 34-1AP00 S0/S2
0,30 ... 3,00 50
0,55
1,5
3,50 ... 5,00 3RV10 21-1FA10 3RT10 34-1AP00 S0/S2
0,30 ... 3,00 50
0,75
1,9
4,50 ... 6,30 3RV10 21-1GA10 3RT10 34-1AP00 S0/S2
0,30 ... 3,00 50
1,1
2,7
5,50 ... 8,00 3RV10 21-1HA10 3RT10 34-1AP00 S0/S2
3UF7 101-1AA00-0 2,40 ... 25,0 50
1,5
3,5
9,00 ... 12,5 3RV10 21-1KA10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0 50
2,2
5
11,0 ... 16,0 3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
3
6,5
14,0 ... 20,0 3RV10 31-4BA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
4
8,5
18,0 ... 25,0 3RV10 31-4DA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 50
5,5
11,5
22,0 ... 32,0 3RV10 31-4EA10 3RT10 34-1AP00 S2/S2
7,5
15,5
22,0 ... 32,0 3RV10 31-4EB10 3RT10 44-1AP00 S2/S3
3UF7 102-1AA00-0 10,0 ... 100
2,40 ... 25,0 50
50
11
22
36,0 ... 50,0 3RV10 42-4HB10 3RT10 44-1AP00 S3/S3
10,0 ... 100
50
15
29
45,0 ... 63,0 3RV10 42-4JB10
3RT10 45-1AP00 S3/S3
10,0 ... 100
50
18,5
35
57,0 ... 75,0 3RV10 42-4KB10 3RT10 45-1AP00 S3/S3
10,0 ... 100
50
22
41
70,0 ... 90,0 3RV10 42-4LB10 3RT10 54-1AP36 S3/S6
10,0 ... 100
50
30
55
70,0 ... 90,0 3RV10 42-4LB10 3RT10 54-1AP36 S3/S6
10,0 ... 100
50
37
66
None
3VL27 10-2DK33 3RT10 55-1AP36 –/S6
3UF7 103-1AA00-0 20,0 ... 200
50
45
80
None
3VL27 16-2DK33 3RT10 56-6AP36 –/S6
55
97
None
3VL27 16-2DK33 3RT10 64-6AP36 –/S10
58
20,0 ... 200
50
3UF7 104-1BA00-0 63,0 ... 630
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.6 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
kW
A
A
Order No.
75
132
None
90
160
None
110
195
132
160
Contactor3
Size
SIMOCODE pro
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
3VL37 25-2DK36 3RT12 65-6AP36 –/S10V
63,0 ... 630
50
3VL37 25-2DK36 3RT12 66-6AP36 –/S10V
63,0 ... 630
50
None
3VL47 31-2DK36 3RT10 76-6AP36 –/S12
63,0 ... 630
50
230
None
3VL47 31-2DK36 3RT10 76-6AP36 –/S12
63,0 ... 630
50
280
None
3VL57 50-2DK36 3RT12 76-6AP36 –/S12V
63,0 ... 630
50
Iq
I
Order No.
Order No.
Type of coordination 1
1
2
3
4
200
350
None
3VL67 80-1DE36 3RTF69 44-0CM7 –/14
3UF7 104-1BA00-0 63,0 ... 630
50
250
430
None
3VL67 80-1DE36 3RTF69 44-0CM7 –/14
63,0 ... 630
50
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 are specified. See page 9 for details of the 3UF7 basic units which
are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
59
Selection tables 400 V AC
3.6 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7
CLASS 40, type of coordination 2,
short-circuit breaking capacity Iq ≥ 100 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector / circuit
breaker
Overload
release
Motor starter
Stand Motor protector /
ard
curren circuit
output t
breaker2
P
(guide
value)
Contactor3
Size
SIMOCODE pro
Setting
(current measuring range
module)4
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
kW
A
A
Order No.
Order No.
Order No.
kA
0,09
0,3
None
3RV13 21-1AC10
3RT10 24-1AP00
0,12
0,4
None
3RV13 21-1BC10
3RT10 24-1AP00
S0/S0
0,30 ... 3,00 130
0,18
0,6
1,40 ... 2,00
3RV10 21-1BA10
3RT10 24-1AP00
S0/S0
0,30 ... 3,00 130
0,25
0,85
1,80 ... 2,50
3RV10 21-1CA10
3RT10 26-1AP00
S0/S0
0,30 ... 3,00 130
0,37
1,1
2,20 ... 3,20
3RV10 21-1DA10
3RT10 34-1AP00
S0/S2
0,30 ... 3,00 130
0,55
1,5
3,50 ... 5,00
3RV10 21-1FA10
3RT10 34-1AP00
S0/S2
0,30 ... 3,00 130
0,75
1,9
4,50 ... 6,30
3RV10 21-1GA10
3RT10 34-1AP00
S0/S2
0,30 ... 3,00 130
1,1
2,7
5,50 ... 8,00
3RV10 21-1HA10
3RT10 34-1AP00
S0/S2
3UF7 101-1AA00-0 2,40 ... 25,0 130
1,5
3,5
9,00 ... 12,5
3RV10 21-1KA10
3RT10 34-1AP00
S0/S2
2,40 ... 25,0 130
2,2
5
11,0 ... 16,0
3RV10 31-4AA10
3RT10 34-1AP00
S2/S2
2,40 ... 25,0 100
3
6,5
14,0 ... 20,0
3RV10 31-4BA10
3RT10 34-1AP00
S2/S2
2,40 ... 25,0 100
4
8,5
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00
S2/S2
2,40 ... 25,0 100
Iq
I
S0/S0
A
3UF7 100-1AA00-0 0,30 ... 3,00 130
5,5
11,5
22,0 ... 32,0
3RV10 31-4EA10
3RT10 34-1AP00
S2/S2
7,5
15,5
22,0 ... 32,0
3RV10 31-4EB10
3RT10 54-1AP36
S2/S6
3UF7 102-1AA00-0 10,0 ... 100
2,40 ... 25,0 100
100
11
22
36,0 ... 50,0
3RV10 42-4HB10
3RT10 54-1AP36
S3/S6
10,0 ... 100
100
15
29
45,0 ... 63,0
3RV10 42-4JB10
3RT10 54-1AP36
S3/S6
10,0 ... 100
100
18,5
35
57,0 ... 75,0
3RV10 42-4KB10
3RT10 54-1AP36
S3/S6
3UF7 103-1AA00-0 20,0 ... 200
100
22
41
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36
S3/S6
3UF7 103-1AA00-0 20,0 ... 200
100
30
55
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36
S3/S6
3UF7 102-1AA00-0 10,0 ... 100
100
60
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.6 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
Motor starter
range
protector / circuit
breaker
Overload
release
Motor starter
Stand Motor protector /
ard
curren circuit
output t
breaker2
P
(guide
value)
Contactor3
Size
SIMOCODE pro
Setting
(current measuring range
module)4
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
kW
A
A
Order No.
Order No.
Order No.
kA
30
55
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36
S3/S6
37
66
None
3VL27 16-3DK33
3RT10 55-1AP36
–/S6
45
80
None
3VL27 16-3DK33
3RT10 56-6AP36
–/S6
55
97
None
3VL37 25-3DK36
3RT10 64-6AP36
–/S10
55
97
None
3VL37 25-3DK36
3RT12 64-6AP36
–/S10V
63,0 ... 630
100
75
132
None
3VL47 31-3DK36
3RT10 75-6AP36
–/S12
63,0 ... 630
100
90
160
None
3VL47 31-3DK36
3RT10 75-6AP36
–/S12
63,0 ... 630
100
110
195
None
3VL47 31-3DK36
3RT10 75-6AP36
–/S12
63,0 ... 630
100
132
230
None
3VL57 50-3DK36
3RT10 76-6AP36
–/S12
63,0 ... 630
100
160
280
None
3VL57 50-3DK36
3RT12 76-6AP36
–/S12V
63,0 ... 630
100
Iq
I
1
2
3
4
A
3UF7 103-1AA00-0 20,0 ... 200
100
20,0 ... 200
100
20,0 ... 200
100
3UF7 104-1BA00-0 63,0 ... 630
100
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 are specified. See page 9 for details of the 3UF7 basic units which
are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
61
Selection tables 400 V AC
3.7 Motor starter protector + solid-state contactor
3.7
Motor starter protector + solid-state contactor
NSB0_01948
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq ≥ 5 kA / 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC2
Stand
ard
outpu
t
P
Motor
curren
t
(guide
value)
Setting
Motor starter
range
protector
Overload
release
Motor starter
protector
Size
Solid-state contactor1 3
Shortcircuit
breaking
capacity
Iq
Mounting with lateral
clearance of 20 mm
Butt-mounting
I
kW
A
A
Order No.
0,06
0,2
0,14 ... 0,20
3RV10 21-0BA10
S0
Order No.
Order No.
kA
3RF24 05-1BB24
3RF24 05-1BB24
50
0,06
0,2
0,18 ... 0,25
3RV10 21-0CA10
S0
50
0,09
0,3
0,22 ... 0,32
3RV10 21-0DA10
S0
50
0,09
0,3
0,28 ... 0,40
3RV10 21-0EA10
S0
50
0,12
0,4
0,35 ... 0,50
3RV10 21-0FA10
S0
50
0,18
0,6
0,45 ... 0,63
3RV10 21-0GA10
S0
50
0,25
0,85
0,55 ... 0,80
3RV10 21-0HA10
S0
50
0,25
0,85
0,70 ... 1,00
3RV10 21-0JA10
S0
50
0,37
1,1
0,90 ... 1,25
3RV10 21-0KA10
S0
50
0,55
1,5
1,10 ... 1,60
3RV10 21-1AA10
S0
50
0,75
1,9
1,40 ... 2,00
3RV10 21-1BA10
S0
50
0,75
1,9
1,80 ... 2,50
3RV10 21-1CA10
S0
50
1,1
2,7
2,20 ... 3,20
3RV10 21-1DA10
S0
50
1,5
3,6
2,80 ... 4,00
3RV10 21-1EA10
S0
50
1,5
3,6
3,50 ... 5,00
3RV10 21-1FA10
S0
50
2,2
5
4,50 ... 6,30
3RV10 21-1GA10
S0
3
6,5
5,50 ... 8,00
3RV10 21-1HA10
S0
4
8,5
7,00 ... 10,0
3RV10 21-1JA10
S0
62
3RF24 10-1BB24
3RF24 10-1BB24
50/5
3RF24 10-1BB24
5
20
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.7 Motor starter protector + solid-state contactor
Standard
three-phase
motor
4-pole at
400 V AC2
Stand
ard
outpu
t
1
2
3
Setting
Motor starter
range
protector
Overload
release
Motor starter
protector
Size
Solid-state contactor1 3
Shortcircuit
breaking
capacity
Iq
P
Motor
curren
t
(guide
value)
Mounting with lateral
clearance of 20 mm
Butt-mounting
kW
A
A
Order No.
Order No.
Order No.
kA
5,5
11,5
9,00 ... 12,0
3RV10 21-1KA10
S0
3RF24 12-1BB24
3RF24 12-1BB24
5
7,5
15,5
11,0 ... 16,0
3RV10 21-4AA10
S0
3RF24 16-1BB24
3RF24 16-1BB24
3
7,5
15,5
14,0 ... 20,0
3RV10 21-4BA10
S0
I
5
If the solid-state contactor is mounted directly on the motor starter protector, the switching frequencies are sometimes
reduced for thermal reasons. Detailed characteristic curves can be found in LV1T Chapter 4 or at
http://www.siemens.de/halbleiterschaltgeraete.
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated currents taken into account at 40 °C ambient temperature. Rated control supply voltage 110 ... 230 V AC,
50 / 60 Hz. Other control voltages are also possible. Screw terminals or spring-loaded terminals can be selected. 3RA19
21-1AA00 link module can only be used with screw terminals.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
63
Selection tables 400 V AC
3.8 Motor starter protector + solid-state reversing contactor
3.8
Motor starter protector + solid-state reversing contactor
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq = 10 kA / 50 kA
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Stand Motor
ard
curre
output nt
P
(guide
value)
Setting
Motor starter
range
protector
Overload
release
Motor starter
protector
Size
Solid-state reversing contactor2
Shortcircuit
breaking
capacity
Iq
Mounting with lateral
clearance of 20 mm
Butt-mounting
Order No.
Order No.
3RF24 03-1BD24
3RF24 03-1BD24
I
kW
A
A
Order No.
kA
0,06
0,2
0,14 ... 0,20
3RV10 21-0BA10
S0
0,06
0,2
0,18 ... 0,25
3RV10 21-0CA10
S0
50
0,09
0,3
0,22 ... 0,32
3RV10 21-0DA10
S0
50
0,09
0,3
0,28 ... 0,40
3RV10 21-0EA10
S0
50
0,12
0,4
0,35 ... 0,50
3RV10 21-0FA10
S0
50
0,18
0,6
0,45 ... 0,63
3RV10 21-0GA10
S0
50
0,25
0,85
0,55 ... 0,80
3RV10 21-0HA10
S0
50
0,25
0,85
0,70 ... 1,00
3RV10 21-0JA10
S0
50
0,37
1,1
0,90 ... 1,25
3RV10 21-0KA10
S0
50
0,55
1,5
1,10 ... 1,60
3RV10 21-1AA10
S0
50
0,75
1,9
1,40 ... 2,00
3RV10 21-1BA10
S0
50
50
0,75
1,9
1,80 ... 2,50
3RV10 21-1CA10
S0
50
1,1
2,7
2,20 ... 3,20
3RV10 21-1DA10
S0
50
1,5
3,6
2,80 ... 4,00
3RV10 21-1EA10
S0
1,5
3,6
3,50 ... 5,00
3RV10 21-1FA10
S0
2,2
5
4,50 ... 6,30
3RV10 21-1GA10
S0
3
6,5
5,50 ... 8,00
3RV10 21-1HA10
S0
1
2
64
3RF24 05-1BD24
50
3RF24 05-1BD24
3RF24 10-1BD24
50/10
3RF24 10-1BD24
3RF24 10-1BD24
10
50
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated currents taken into account at 40 °C ambient temperature. Rated control supply voltage 110 ... 230 V AC,
50 / 60 Hz. Other control voltages are also possible. 3RA19 21-1AA00 link module can be used. Detailed information
can be found in LV1T Chapter 4 or at http://www.siemens.de/halbleiterschaltgeraete.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.9 Motor starter protector + star(wye)-delta starting + 3RU11 thermal overload relay
3.9
Motor starter protector + star(wye)-delta starting + 3RU11 thermal
overload relay
CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
M
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Motor starter Contactors3
protector
kW
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
I
A
A
Size
Overload
relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
Iq
Type of coordination 2
5,5
11,5
None
3RV13 214AC10
3RT10 261AP00
3RT10 241AP00
S0/S0/S0
3RU11 261HB0
5,50 ... 8,00 50
7,5
15,5
None
3RV13 214BC10
3RT10 261AP00
3RT10 241AP00
S0/S0/S0
3RU11 261JB0
7,00 ... 10,0 50
11
22
None
3RV13 314DC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
3RU11 364AB0
11,0 ... 16,0 50
15
29
None
3RV13 314FC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
3RU11 364BB0
14,0 ... 20,0 50
18,5
35
None
3RV13 314FC10
3RT10 351AP00
3RT10 241AP00
S2/S2/S0
3RU11 364DB0
18,0 ... 25,0 50
22
41
None
3RV13 314GC10
3RT10 361AP00
3RT10 261AP00
S2/S2/S0
3RU11 364EB0
22,0 ... 32,0 50
30
55
None
3RV13 414JC10
3RT10 441AP00
3RT10 261AP00
S3/S3/S0
3RU11 464FB0
28,0 ... 40,0 50
37
66
None
3RV13 414KC10
3RT10 441AP00
3RT10 341AP00
S3/S3/S2
3RU11 464HB0
36,0 ... 50,0 50
45
80
None
3RV13 414LC10
3RT10 451AP00
3RT10 341AP00
S3/S3/S2
3RU11 464JB0
45,0 ... 63,0 50
Type of coordination 1
5,5
11,5
9,00 ... 12 3RV10 11,0
1KA10
3RT10 151AP01
3RT10 151AP00
S00/S00/S00 3RU11 161HB0
5,50 ... 8,00 50
7,5
15,5
None
3RV13 214BC10
3RT10 161AP01
3RT10 151AP00
S0/S00/S00
3RU11 161JB0
7,00 ... 10,0 50
11
22
None
3RV13 214DC10
3RT10 241AP00
3RT10 241AP00
S0/S0/S0
3RU11 264AB0
11,0 ... 16,0 50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
65
Selection tables 400 V AC
3.9 Motor starter protector + star(wye)-delta starting + 3RU11 thermal overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Motor starter Contactors3
protector
kW
A
A
15
29
18,5
Size
Overload
relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
Iq
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
None
3RV13 314FC10
3RT10 261AP00
3RT10 241AP00
S2/S0/S0
3RU11 264BB0
14,0 ... 20,0 50
35
None
3RV13 314FC10
3RT10 261AP00
3RT10 241AP00
S2/S0/S0
3RU11 264DB0
20,0 ... 25,0 50
22
41
None
3RV13 314GC10
3RT10 341AP00
3RT10 261AP00
S2/S0/S0
3RU11 364EB0
22,0 ... 32,0 50
30
55
None
3RV13 414JC10
3RT10 341AP00
3RT10 261AP00
S3/S2/S0
3RU11 364FB0
28,0 ... 40,0 50
37
66
None
3RV13 414KC10
3RT10 351AP00
3RT10 341AP00
S3/S2/S2
3RU11 364GB0
36,0 ... 45,0 50
45
80
None
3RV13 414LC10
3RT10 361AP00
3RT10 341AP00
S3/S2/S2
3RU11 364HB0
40,0 ... 50,0 50
I
1
2
3
66
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.10 Motor starter protector / circuit breaker + star(wye)-delta starting + 3RB20/3RB21 solid-state overload relay
3.10
Motor starter protector / circuit breaker + star(wye)-delta starting +
3RB20/3RB21 solid-state overload relay
CLASS 5 and CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
M
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor starter
Stand Motor protector /
ard
curren circuit
output t
breaker2
P
(guide
value)
Motor
starter
protector /
circuit
breaker
kW
A
A
5,5
11,5
7,5
Contactors3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
None
3RV13 211KC10
3RT10 261AP00
3RT10 241AP00
S0/S0/S0
3RB20 26-1QB0/ 6,00 ... 25,0 50
3RB21 23-4QB0
15,5
14,0 ... 20,0
3RV10 214BA10
3RT10 261AP00
3RT10 241AP00
S0/S0/S0
6,00 ... 25,0 50
11
22
None
3RV13 314EC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
15
29
28,0 ... 40,0
3RV10 314FA10
3RT10 351AP00
3RT10 241AP00
S2/S2/S0
18,5
35
None
3RV13 414FC10
3RT10 441AP00
3RT10 341AP00
S3/S3/S2
22
41
None
3RV13 414HC10
3RT10 441AP00
3RT10 341AP00
S3/S3/S2
30
55
None
3RV13 414JC10
3RT10 441AP00
3RT10 341AP00
S3/S3/S2
37
66
None
3RV13 414KC10
3RT10 451AP00
3RT10 341AP00
S3/S3/S2
25,0 ... 100 50
45
80
70,0 ... 90,0
3RV10 414LA10
3RT10 461AP00
3RT10 341AP00
S3/S3/S2
25,0 ... 100 50
55
97
None
3VL27 102DK33
3RT10 541AP36
3RT10 441AP00
-/S6/S3
3RB20 56-1FW2/ 50,0 ... 200 50
3RB21 53-4FW2
75
132
None
3VL27 162DK33
3RT10 556AP36
3RT10 441AP00
-/S6/S3
3RB20 56-1FC2/
3RB21 53-4FC2
90
160
None
3VL27 162DK33
3RT10 556AP36
3RT10 441AP00
-/S6/S3
Iq
I
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Order No.
3RB20 36-1UB0/
3RB21 33-4UB0
12,5 ... 50,0 50
12,5 ... 50,0 50
3RB20 46-1UB0/
3RB21 43-4UB0
12,5 ... 50,0 50
12,5 ... 50,0 50
3RB20 46-1EB0/
3RB21 43-4EB0
25,0 ... 100 50
50,0 ... 200 50
50,0 ... 200 50
67
Selection tables 400 V AC
3.10 Motor starter protector / circuit breaker + star(wye)-delta starting + 3RB20/3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor starter
Stand Motor protector /
ard
curren circuit
output t
breaker2
P
(guide
value)
Motor
starter
protector /
circuit
breaker
kW
A
A
110
195
132
Contactors3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
None
3VL37 252DK36
3RT10 646AP36
3RT10 541AP36
-/S10/S6
3RB20 66-1GC2/ 55,0 ... 250 50
3RB21 63-4GC2
230
None
3VL47 252DK36
3RT10 656AP36
3RT10 541AP36
-/S10/S6
55,0 ... 250 50
160
280
None
3VL47 312DK36
3RT10 666AP36
3RT10 541AP36
-/S10/S6
200
350
None
3VL57 502DK36
3RT10 756AP36
3RT10 646AP36
250
430
None
3VL57 502DK36
3RT10 756AP36
3RT10 646AP36
Iq
I
1
2
3
68
Order No.
3RB20 66-1MC2/ 160 ... 630
3RB21 63-4MC2
50
-/S12/S10
160 ... 630
50
-/S12/S10
160 ... 630
50
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.11 Motor starter protector / circuit breaker + star(wye)-delta starting + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
3.11
Motor starter protector / circuit breaker + star(wye)-delta starting +
SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
CLASS 5 and CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
M
$&9
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter Contactors3
protector /
circuit
breaker
kW
A
A
5,5
11,5
None
7,5
Size
SIMOCODE pro or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty Iq
kA
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
Order No.
A
3RV13 211KC10
3RT10 261AP00
3RT10 24- S0/S0/S0
1AP00
3UF7 101-1AA00-0/
3RB29 06-2DG1
2,40 ... 25,0 50
15,5
14,0 ... 20,0 3RV10 214BA10
3RT10 261AP00
3RT10 24- S0/S0/S0
1AP00
11
22
None
3RV13 314EC10
3RT10 341AP00
3RT10 24- S2/S2/S0
1AP00
15
29
28,0 ... 40,0 3RV10 314FA10
3RT10 351AP00
3RT10 24- S2/S2/S0
1AP00
10,0 ... 100 50
18,5
35
None
3RV13 414FC10
3RT10 441AP00
3RT10 34- S3/S3/S2
1AP00
10,0 ... 100 50
22
41
None
3RV13 414HC10
3RT10 441AP00
3RT10 34- S3/S3/S2
1AP00
10,0 ... 100 50
30
55
None
3RV13 414JC10
3RT10 441AP00
3RT10 34- S3/S3/S2
1AP00
10,0 ... 100 50
37
66
None
3RV13 414KC10
3RT10 451AP00
3RT10 34- S3/S3/S2
1AP00
10,0 ... 100 50
45
80
70,0 ... 90,0 3RV10 414LA10
3RT10 461AP00
3RT10 34- S3/S3/S2
1AP00
10,0 ... 100 50
I
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
2,40 ... 25,0 50
3UF7 102-1AA00-0/
3RB29 06-2JG1
10,0 ... 100 50
69
Selection tables 400 V AC
3.11 Motor starter protector / circuit breaker + star(wye)-delta starting + SIMOCODE pro 3UF7 / 3RB22/3RB23
solid-state overload relay
Standard
three-phase
motor
4-pole at
400 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter Contactors3
protector /
circuit
breaker
kW
Order No.
I
A
A
Size
SIMOCODE pro or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty Iq
kA
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
A
3UF7 103-1AA00-0/
3RB29 56-2TG2
20,0 ... 200 50
55
97
None
3VL27 102DK33
3RT10 541AP36
3RT10 44- -/S6/S3
1AP00
75
132
None
3VL27 162DK33
3RT10 556AP36
3RT10 44- -/S6/S3
1AP00
20,0 ... 200 50
90
160
None
3VL27 162DK33
3RT10 556AP36
3RT10 44- -/S6/S3
1AP00
20,0 ... 200 50
110
195
None
3VL37 252DK36
3RT10 646AP36
3RT10 54- -/S10/S6
1AP36
132
230
None
3VL47 252DK36
3RT10 656AP36
3RT10 54- -/S10/S6
1AP36
63,0 ... 630 50
160
280
None
3VL47 312DK36
3RT10 666AP36
3RT10 54- -/S10/S6
1AP36
63,0 ... 630 50
200
350
None
3VL57 502DK36
3RT10 756AP36
3RT10 64- -/S12/S10
6AP36
63,0 ... 630 50
250
430
None
3VL57 502DK36
3RT10 756AP36
3RT10 64- -/S12/S10
6AP36
63,0 ... 630 50
1
2
3
4
70
3UF7 104-1BA00-0/
3RB29 66-2WH2
63,0 ... 630 50
Guide value for 4-pole standard motors at 400 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.12 Motor starter protector / circuit breaker + 3RW30/3RW40 soft starter
3.12
Motor starter protector / circuit breaker + 3RW30/3RW40 soft starter
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq = 10 ... 50 kA
Q1
M
3~
NSB0_01935
Q11
$&9
Rated
operational
current
soft starter1
Setting range
Overload release
Motor starter
protector / circuit
breaker
Motor starter protector / Size
circuit breaker
Soft starter type
Short-circuit
breaking capacity Iq
A
A
Order No.
Order No.
kA
I
Soft starter type 3RW30
3
2,80 ... 4,00
3RV10 11-1EA10
S00
3RW30 03
50
3,6
3,50 ... 5,00
3RV10 21-1FA10
S0
3RW30 13
10
6,5
5,50 ... 8,00
3RV10 21-1HA10
S0
3RW30 14
10
9
7,00 ... 10,0
3RV10 21-1JA10
S0
3RW30 16
10
12,5
9,00 ... 12,5
3RV10 21-1KA10
S0
3RW30 17
10
17,6
14,0 ... 20,0
3RV10 21-4BA10
S0
3RW30 18
10
25
20,0 ... 25,0
3RV10 21-4DA10
S0
3RW30 26
55
32
22,0 ... 32,0
3RV10 31-4EA10
S2
3RW30 27
55
38
28,0 ... 40,0
3RV10 31-4FA10
S2
3RW30 28
55
45
36,0 ... 45,0
3RV10 31-4GA10
S2
3RW30 36
20
63
45,0 ... 63,0
3RV10 41-4JA10
S3
3RW30 37
20
72
57,0 ... 75,0
3RV10 41-4KA10
S3
3RW30 38
20
80
70,0 ... 90,0
3RV10 41-4LA10
S3
3RW30 46
11
106
80,0 ... 100
3RV10 41-4MA10
S3
3RW30 47
11
S0
3RW40 24
55
Soft starter type 3RW40
12,5
9,00 ... 12,5
3RV10 21-1KA10
25
20,0 ... 25,0
3RV10 21-4DA10
S0
3RW40 26
55
32
22,0 ... 32,0
3RV10 31-4EA10
S2
3RW40 27
55
38
28,0 ... 40,0
3RV10 31-4FA10
S2
3RW40 28
55
45
36,0 ... 45,0
3RV10 31-4GA10
S2
3RW40 36
20
63
45,0 ... 63,0
3RV10 41-4JA10
S3
3RW40 37
20
72
57,0 ... 75,0
3RV10 41-4KA10
S3
3RW40 38
20
80
70,0 ... 90,0
3RV10 41-4LA10
S3
3RW40 46
11
106
80,0 ... 100
3RV10 41-4MA10
S3
3RW40 47
11
12,5
None
3RV13 21-1KC10
S0
3RW40 24
55
25
None
3RV13 21-4DC10
S0
3RW40 26
55
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
71
Selection tables 400 V AC
3.12 Motor starter protector / circuit breaker + 3RW30/3RW40 soft starter
Rated
operational
current
soft starter1
Setting range
Overload release
Motor starter
protector / circuit
breaker
Motor starter protector / Size
circuit breaker
Soft starter type
Short-circuit
breaking capacity Iq
A
A
Order No.
Order No.
kA
32
None
3RV13 31-4EC10
S2
3RW40 27
55
38
None
3RV13 31-4FC10
S2
3RW40 28
55
I
45
None
3RV13 31-4GC10
S2
3RW40 36
20
63
None
3RV13 41-4JC10
S3
3RW40 37
20
72
None
3RV13 41-4KC10
S3
3RW40 38
20
80
None
3RV13 41-4LC10
S3
3RW40 46
11
106
None
3RV13 41-4MC10
S3
3RW40 47
11
134
None
3VL37 20-2DC36
-
3RW40 55
35
162
None
-
3RW40 56
35
230
None
3VL47 31-2DC36
-
3RW40 73
65
280
None
-
3RW40 74
65
356
None
3VL47 40-2DC36
-
3RW40 75
65
432
None
3VL57 50-2DC36
-
3RW40 76
65
1
72
At 40 °C ambient temperature (for higher ambient temperatures see Catalog LV 1 T)
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 400 V AC
3.13 Motor starter protector / circuit breaker + 3RW44 soft starter
3.13
Motor starter protector / circuit breaker + 3RW44 soft starter
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq = 16 ... 65 kA
Q1
M
3~
NSB0_01016b
Q11
$&9
Rated
operational
current
soft starter1
Setting range
Overload release
Motor starter
protector / circuit
breaker
Motor starter
protector / circuit
breaker
A
A
Order No.
29
36,0 ... 50,0
3RV10 42-4HA10
36
45,0 ... 63,0
3RV10 42-4JA10
S3
3RW44 23
32
47
57,0 ... 75,0
3RV10 42-4KA10
S3
3RW44 24
32
57
70,0 ... 90,0
3RV10 42-4LA10
S3
3RW44 25
32
77
80,0 ... 100
3RV10 42-4MA10
S3
3RW44 26
32
93
80,0 ... 100
S3
3RW44 27
32
-
3RW44 34
16
-
3RW44 35
16
I
1
3VL17 16-2DD36
Size
Soft starter type
Short-circuit breaking
capacity
Iq
S3
Order No.
kA
3RW44 22
32
113
None
134
None
162
None
3VL37 25-2DC36
-
3RW44 36
65
203
None
3VL47 31-3DC36
-
3RW44 43
65
250
None
-
3RW44 44
65
313
None
3VL47 40-3DC36
-
3RW44 45
65
356
None
-
3RW44 46
65
432
None
3VL57 50-3DC36
-
3RW44 47
65
551
None
3VL67 80-3AB36
-
3RW44 53
65
615
None
-
3RW44 54
65
693
None
-
3RW44 55
65
-
3RW44 56
65
-
3RW44 57
65
-
3RW44 58
65
780
None
880
None
970
None
3VL77 10-3AB36
3VL77 12-3AB36
1076
None
-
3RW44 65
65
1214
None
-
3RW44 66
65
At 40 °C ambient temperature (for higher ambient temperatures see Catalog LV 1 T)
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
73
Selection tables 400 V AC
3.13 Motor starter protector / circuit breaker + 3RW44 soft starter
74
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
4
Selection tables 440 V AC
4.1
Motor starter protector + contactor
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 75 kA / 100 kA
$&9
Standard threephase motor
4-pole at
440 V AC1
Standa Motor
rd
current
output (guide
P
value)
Setting
Motor starter protector
range
Overload
release
Motor starter
protector
Contactor2
Size
Short-circuit
breaking capacity
Iq
I
kW
A
A
Order No.
Order No.
kA
0,37
1,0
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
100
0,55
1,4
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
100
0,75
1,7
1,40 ... 2,00
3RV10 11-1BA10
3RT10 15-1AP01
S00/S00
100
1,1
2,5
2,20 ... 3,20
3RV10 21-1DA10
3RT10 26-1AP00
S0/S0
100
1,5
3,3
2,80 ... 4,00
3RV10 21-1EA10
3RT10 26-1AP00
S0/S0
100
2,2
4,6
3,50 ... 5,00
3RV10 21-1FA10
3RT10 26-1AP00
S0/S0
100
3
5,9
5,5 0... 8,00
3RV10 21-1HA10
3RT10 26-1AP00
S0/S0
100
4
7,7
7,00 ... 10,0
3RV10 21-1JA10
3RT10 26-1AP00
S0/S0
100
5,5
10,5
9,0 ... 12,5
3RV10 21-1KA10
3RT10 26-1AP00
S0/S0
100
7,5
14,0
11,0 ... 16,0
3RV10 21-4AA10
3RT10 26-1AP00
S0/S0
100
9
16,9
14,0 ... 20,0
3RV10 31-4BA10
3RT10 34-1AP00
S2/S2
100
11
20
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00
S2/S2
100
15
26
22,0 ... 32,0
3RV10 31-4EA10
3RT10 35-1AP00
S2/S2
100
18,5
32
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
100
22
37
36,0 ... 45,0
3RV10 31-4GA10
3RT10 36-1AP00
S2/S2
100
30
50
45,0 ... 63,0
3RV10 41-4JA10
3RT10 44-1AP00
S3/S3
100
37
60
57,0 ... 75,0
3RV10 41-4KA10
3RT10 54-1AP36
S3/S6
100
45
73
70,0 ... 90,0
3RV10 41-4LA10
3RT10 54-1AP36
S3/S6
100
55
88
80,0 ... 100
3RV10 41-4MA10
3RT10 54-1AP36
S3/S6
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
75
Selection tables 440 V AC
4.1 Motor starter protector + contactor
Standard threephase motor
4-pole at
440 V AC1
Standa Motor
rd
current
output (guide
P
value)
Setting
Motor starter protector
range
Overload
release
Motor starter
protector
Contactor2
Size
Short-circuit
breaking capacity
Iq
I
kW
A
A
Order No.
Order No.
75
120
64,0 ... 160
3RV10 63-7CL10
3RT10 55-6AP36
90
145
64,0 ... 160
3RV10 63-7CL10
3RT10 56-6AP36
-/S6
100
110
177
80,0 ... 200
3RV10 63-7DL10
3RT10 64-6AP36
-/S10
100
132
209
160 ... 400
3RV10 73-7GL10
3RT10 65-6AP36
-/S10
100
160
255
160 ... 400
3RV10 73-7GL10
3RT10 66-6AP36
-/S10
100
185
318
252 ... 630
3RV10 83-7JL10
3RT12 75-6AP36
-/S12V
75
200
391
252 ... 630
3RV10 83-7JL10
3RT12 75-6AP36
-/S12V
75
250
491
252 ... 630
3RV10 83-7JL10
3RT12 76-6AP36
-/S12V
75
1
2
76
kA
-/S6
100
Guide value for 4-pole standard motors at 440 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 440 V AC
4.2 Motor starter protector + contactor + 3RU11 thermal overload relay
4.2
Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 100 kA
$&9
Standard threephase motor
4-pole at
440 V AC1
Stand
ard
outpu
t
Motor
current
(guide
value)
I
Setting
range
Overloa
d
release
Motor
starter
protecto
r
kW
A
A
Order No.
Order No.
0,37
1,0
None
3RV13 21-0KC10
3RT10 15-1AP01
0,55
1,4
None
3RV13 21-1AC10
0,75
1,7
None
3RV13 21-1BC10
1,1
2,5
None
3RV13 21-1DC10
P
1
2
Motor starter
protector
Contactor2
Size
Overload relay
Setting
range
Overload
relay
Shortcircuit
breaking
capacity
Iq
Order No.
A
kA
S0/S00
3RU11 16-0KB0
0,90 ... 1,25
100
3RT10 15-1AP01
S0/S00
3RU11 16-1AB0
1,10 ... 1,60
100
3RT10 15-1AP01
S0/S00
3RU11 16-1BB0
1,40 ... 2,00
100
3RT10 24-1AP00
S0/S0
3RU11 26-1DB0
2,20 ... 3,20
100
1,5
3,3
None
3RV13 21-1EC10
3RT10 24-1AP00
S0/S0
3RU11 26-1EB0
2,80 ... 4,00
100
2,2
4,6
None
3RV13 21-1FC10
3RT10 24-1AP00
S0/S0
3RU11 26-1FB0
3,50 ... 5,00
100
3
5,9
None
3RV13 21-1HC10
3RT10 26-1AP00
S0/S0
3RU11 26-1GB0
5,50 ... 8,00
100
4
7,7
None
3RV13 21-1JC10
3RT10 26-1AP00
S0/S0
3RU11 26-1JB0
7,00 ... 10,0
100
5,5
10,5
None
3RV13 21-1KC10
3RT10 26-1AP00
S0/S0
3RU11 26-1KB0
9,00 ... 12,5
100
7,5
14,0
None
3RV13 21-4AC10
3RT10 26-1AP00
S0/S0
3RU11 26-4AB0
11,0 ... 16,0
100
9
16,9
None
3RV13 31-4BC10
3RT10 34-1AP00
S2/S2
3RU11 36-4BB0
14,0 ... 20,0
100
11
20
None
3RV13 31-4DC10
3RT10 34-1AP00
S2/S2
3RU11 36-4DB0
18,0 ... 25,0
100
15
26
None
3RV13 31-4EC10
3RT10 34-1AP00
S2/S2
3RU11 36-4EB0
22,0 ... 32,0
100
18,5
39
None
3RV13 31-4FC10
3RT10 35-1AP00
S2/S2
3RU11 36-4FB0
28,0 ... 40,0
100
22
37
None
3RV13 31-4GC10
3RT10 36-1AP00
S2/S2
3RU11 36-4GB0
36,0 ... 45,0
100
30
50
None
3RV13 41-4JC10
3RT10 44-1AP00
S3/S6
3RU11 46-4JB0
45,0 ... 63,0
100
37
60
None
3RV13 41-4KC10
3RT10 54-6AP36
S3/S6
3RU11 46-4KB0
57,0 ... 75,0
100
45
73
None
3RV13 41-4LC10
3RT10 54-6AP36
S3/S6
3RU11 46-4LB0
70,0 ... 90,0
100
55
88
None
3RV13 41-4MC10
3RT10 54-6AP36
S3/S6
3RU11 46-4LB0
80,0 ... 100
100
Guide value for 4-pole standard motors at 440 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
77
Selection tables 440 V AC
4.3 Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay
4.3
Motor starter protector + contactor + 3RB20 / 3RB21 solid-state
overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 75 kA / 100 kA
$&9
Standard
three-phase
motor
4-pole at
440 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
curren protector2
output t
P
(guide
value)
Motor starter
protector
Contactor3
Size
Overload relay
Setting
range
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
Order No.
A
kA
0,37
1,0
None
3RV13 21-0KC10
3RT10 15-1AP01 S0/S00 3RB20 16-1NB0/
3RB21 13-4NB0
0,32 ... 1,25 100
Iq
I
Order No.
0,55
1,4
None
3RV13 21-1AC10
1,7
None
3RV13 21-1BC10
3RT10 15-1AP01 S0/S00 3RB20 16-1PB0/
3RT10 15-1AP01 S0/S00 3RB21 13-4PB0
1,00 ... 4,00 100
0,75
1,1
2,5
None
3RV13 21-1DC10
3RT10 26-1AP00 S0/S0
3RB21 23-4PB0/
3RB20 26-1PB0
1,00 ... 4,00 100
1,5
3,3
None
3RV13 21-1EC10
3RT10 26-1AP00 S0/S0
3RB21 23-4SB0/
3RB20 26-1SB0
3,00 ... 12,0 100
2,2
4,6
None
3RV13 21-1FC10
3RT10 26-1AP00 S0/S0
3
5,9
None
3RV13 21-1HC10
3RT10 26-1AP00 S0/S0
3RB20 26-1SB0/
3RB21 23-4SB0
4
7,7
None
3RV13 21-1JC10
3RT10 26-1AP00 S0/S0
5,5
10,5
None
3RV13 21-1KC10
3RT10 26-1AP00 S0/S0
7,5
14,0
None
3RV13 21-4AC10
3RT10 26-1AP00 S0/S0
9
16,9
None
3RV13 31-4BC10
3RT10 34-1AP00 S2/S2
11
20
None
3RV13 31-4EC10
3RT10 35-1AP00 S2/S2
1,00 ... 4,00 100
3,00 ... 12,0 100
3,00 ... 12,0 100
3,00 ... 12,0 100
3RB20 26-1QB0/
3RB21 23-4QB0
3RB20 36-1UB0/
3RB21 33-4UB0
3,00 ... 12,0 100
6,00 ... 25,0 100
12,5 ... 50,0 100
12,5 ... 50,0 100
15
26
28,0 ... 40,0 3RV10 31-4FA10
3RT10 35-1AP00 S2/S2
12,5 ... 50,0 100
18,5
32
None
3RV13 31-4GC10
3RT10 35-1AP00 S2/S2
12,5 ... 50,0 100
22
37
None
3RV13 41-4HC10
3RT10 44-1AP00 S3/S3
30
50
None
3RV13 41-4JC10
3RT10 44-1AP00 S3/S3
37
60
None
3RV13 41-4KC10
3RT10 54-1AP36 S3/S6
45
78
None
3RV13 41-4LC10
3RT10 54-1AP36 S3/S6
55
88
None
3RV13 41-4MC10
3RT10 54-1AP36 S3/S6
75
120
None
3RV13 63-7CN10
3RT10 55-6AP36 -/S6
78
3RB20 46-1EB0/
3RB21 43-4EB0
25,0 ... 100
100
25,0 ... 100
100
25,0 ... 100
100
25,0 ... 100
100
25,0 ... 100
100
3RB20 56-1FW2/ 50,0 ... 200
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 440 V AC
4.3 Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
440 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
curren protector2
output t
P
(guide
value)
Motor starter
protector
Contactor3
Size
kW
A
A
Order No.
Order No.
90
145
None
3RV13 63-7EN10
3RT10 56-6AP36 -/S6
110
177
None
3RV13 63-7EN10
3RT10 64-6AP36 -/S10
132
209
None
3RV13 73-7GN10
3RT10 65-6AP36 -/S10
160
255
None
3RV13 73-7GN10
3RT10 66-6AP36 -/S10
185
294
None
3RV13 73-7JN10
200
318
None
3RV13 73-7JN10
250
391
None
315
491
None
Overload relay
Setting
range
Overload
relay
Shortcircuit
breaking
capacity
A
kA
50,0 ... 200
100
3RB20 66-1GC2/ 55,0 ... 250
3RB21 63-4GC2 55,0 ... 250
100
100
3RT10 75-6AP36 -/S12
3RB20 66-1MC2/ 160 ... 630
3RB21 63-4MC2 160 ... 630
3RT10 75-6AP36 -/S12
160 ... 630
100
3RV13 73-7JN10
3RT12 75-6AP36 -/S12V
160 ... 630
100
3RV13 83-7KN10
3RT12 76-6AP36 -/S12V
160 ... 630
75
Iq
I
1
2
3
Order No.
3RB21 53-4FW2
100
100
Guide value for 4-pole standard motors at 440 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
79
Selection tables 440 V AC
4.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
4.4
Motor starter protector + contactor + SIMOCODE pro 3UF7 /
3RB22/3RB23 solid-state overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 75 kA / 100 kA
$&9
Standard
three-phase
motor
4-pole at
440 V AC1
Setting
range
Motor
starter
protector2
Motor starter
protector
Contactor3
Size
SIMOCODE pro or
overload relay
(current measuring
module)4
Setting
range
Overload
relay
Stand
ard
outpu
t
Motor
current
(guide
value)
kW
A
A
Order No.
Order No.
Order No.
A
kA
0,37
1,0
None
3RV13 21-0KC10
3RT10 15-1AP01 S0/S00
0,3 ... 3
100
0,55
1,4
None
3RV13 21-1AC10
3RT10 15-1AP01 S0/S00
3UF71 00-1AA00-0/
3RB29 06-2BG1
0,3 ... 3
100
0,75
1,7
None
3RV13 21-1BC10
3RT10 15-1AP01 S0/S00
0,3 ... 3
100
1,1
2,5
None
3RV13 21-1DC10
3RT10 26-1AP00 S0/S0
0,3 ... 3
100
1,5
3,3
None
3RV13 21-1EC10
3RT10 26-1AP00 S0/S0
2,2
4,6
None
3RV13 21-1FC10
3RT10 26-1AP00 S0/S0
3
5,9
None
3RV13 21-1HC10
3RT10 26-1AP00 S0/S0
2,4 ... 25 100
4
7,7
None
3RV13 21-1JC10
3RT10 26-1AP00 S0/S0
2,4 ... 25 100
5,5
10,5
None
3RV13 21-1KC10
3RT10 26-1AP00 S0/S0
2,4 ... 25 100
7,5
14,0
None
3RV13 21-4AC10
3RT10 26-1AP00 S0/S0
2,4 ... 25 100
9
16,9
None
3RV13 31-4BC10
3RT10 34-1AP00 S2/S2
2,4 ... 25 100
11
20
None
3RV13 31-4EC10
3RT10 34-1AP00 S2/S2
15
26
None
3RV13 31-4EC10
3RT10 35-1AP00 S2/S2
18,5
32
28,0 ... 40,0 3RV10 31-4FA10
3RT10 35-1AP00 S2/S2
22
37
None
3RV13 41-4FC10
3RT10 36-1AP00 S2/S2
10 ... 100 100
30
50
None
3RV13 41-4JC10
3RT10 44-1AP00 S3/S3
10 ... 100 100
37
60
None
3RV13 41-4KC10
3RT10 54-1AP36 S3/S6
45
73
None
3RV13 41-4LC10
3RT10 54-1AP36 S3/S6
3UF71 03-1AA00-0/
3RB29 56-2TG2
20 ... 200 100
55
88
None
3RV13 41-4MC10
3RT10 54-1AP36 S3/S6
3UF71 03-1AA00-0/
3RB29 56-2TG2
20 ... 200 100
P
80
AC and DC drive
Shortcircuit
breaking
capacity
Iq
I
3UF71 01-1AA00-0/
3RB29 06-2DG1
2,4 ... 25 100
2,4 ... 25 100
10 ... 100 100
3UF71 02-1AA00-0/
3RB29 06-2JG1
10 ... 100 100
10 ... 100 100
10 ... 100 100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 440 V AC
4.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
440 V AC1
2
3
4
Motor starter
protector
Stand
ard
outpu
t
Motor
current
(guide
value)
kW
A
A
Order No.
75
120
None
90
145
None
110
177
132
160
P
1
Setting
range
Motor
starter
protector2
Contactor3
Size
SIMOCODE pro or
overload relay
(current measuring
module)4
Setting
range
Overload
relay
AC and DC drive
Shortcircuit
breaking
capacity
Iq
I
Order No.
Order No.
A
kA
3RV13 63-7CN10
3RT10 55-6AP36 -/S6
3RT10 56-6AP36 -/S6
3UF71 03-1AA00-0/
3RB29 56-2TG2
20 ... 200 100
3RV13 63-7EN10
None
3RV13 63-7EN10
3RT10 64-6AP36 -/S10
209
None
3RV13 73-7GN10
3RT10 65-6AP36 -/S10
255
None
3RV13 73-7GN10
3RT10 66-6AP36 -/S10
185
294
None
3RV13 73-7JN10
3RT10 75-6AP36 -/S12
63 ... 630 100
200
318
None
3RV13 73-7JN10
3RT10 75-6AP36 -/S12
63 ... 630 100
250
391
None
3RV13 73-7JN10
3RT12 75-6AP36 -/S12V
63 ... 630 100
315
491
None
3RV13 83-7KN10
3RT12 76-6AP36 -/S12V
63 ... 630 75
20 ... 200 100
20 ... 200 100
3UF71 04-1BA00-0/
3RB29 66-2WH2
63 ... 630 100
63 ... 630 100
Guide value for 4-pole standard motors at 440 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
81
Selection tables 440 V AC
4.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
82
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
5
Selection tables 480 V AC
5.1
Motor starter protector + contactor
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 75 kA / 100 kA
$&9
Standard
three-phase
motor
4-pole at
480 V AC1
Stan
dard
outpu
t
P
Motor
curren
t
(guide
value)
Setting range Motor starter protector
Overload
release
Motor starter
protector
Contactor2
Size
Short-circuit
breaking capacity
Iq
I
kW
A
A
Order No.
Order No.
0,37
0,9
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
100
kA
0,55
1,3
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
100
0,75
1,6
1,40 ... 2,00
3RV10 21-1BA10
3RT10 24-1AP00
S0/S0
100
1,1
2,3
1,80 ... 2,50
3RV10 21-1CA10
3RT10 26-1AP00
S0/S0
100
1,5
3,0
2,80 ... 4,00
3RV10 21-1EA10
3RT10 34-1AP00
S0/S2
100
2,2
4,2
3,50 ... 5,00
3RV10 21-1FA10
3RT10 34-1AP00
S0/S2
100
3
5,4
4,50 ... 6,30
3RV10 21-1GA10
3RT10 34-1AP00
S0/S2
100
4
7,0
5,50 ... 8,00
3RV10 21-1HA10
3RT10 34-1AP00
S0/S2
100
5,5
9,6
9,00 ... 12,5
3RV10 21-1KA10
3RT10 34-1AP00
S0/S2
100
7,5
12,92
11,0 ... 16,0
3RV10 21-4AA10
3RT10 34-1AP00
S0/S2
100
9
15,5
14,0 ... 20,0
3RV10 31-4BA10
3RT10 34-1AP00
S2/S2
100
11
18,3
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00
S2/S2
100
15
24
22,0 ... 32,0
3RV10 31-4EA10
3RT10 35-1AP00
S2/S2
100
18,5
29
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
100
22
34
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
100
30
46
40,0 ... 50,0
3RV10 31-4HA10
3RT10 36-1AP00
S2/S2
100
37
55
45,0 ... 63,0
3RV10 41-4JA10
3RT10 54-1AP36
S3/S6
100
45
67
57,0 ... 75,0
3RV10 41-4KA10
3RT10 54-1AP36
S3/S6
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
83
Selection tables 480 V AC
5.1 Motor starter protector + contactor
Standard
three-phase
motor
4-pole at
480 V AC1
Stan
dard
outpu
t
Setting range Motor starter protector
Overload
release
Motor starter
protector
Contactor2
Size
Short-circuit
breaking capacity
Iq
P
Motor
curren
t
(guide
value)
kW
A
A
Order No.
Order No.
55
81
80,0 ... 100
3RV10 41-4MA10
3RT10 54-1AP36
S3/S6
100
75
110
64,0 ... 160
3RV10 63-7CL10
3RT10 54-1AP36
-/S6
100
90
133
64,0 ... 160
3RV10 63-7CL10
3RT10 55-6AP36
-/S6
100
110
163
80,0 ... 200
3RV10 63-7DL10
3RT10 56-6AP36
-/S6
100
132
192
160 ... 400
3RV10 73-7GL10
3RT10 65-6AP36
-/S10
100
160
233
160 ... 400
3RV10 73-7GL10
3RT10 65-6AP36
-/S10
100
185
292
252 ... 630
3RV10 83-7GL10
3RT12 75-6AP36
-/S12V
75
200
358
252 ... 630
3RV10 83-7GL10
3RT12 75-6AP36
-/S12V
75
250
358
252 ... 630
3RV10 83-7JL10
3RT12 76-6AP36
-/S12V
75
1
2
84
I
kA
Guide value for 4-pole standard motors at 480 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 480 V AC
5.2 Motor starter protector + contactor + 3RU11 thermal overload relay
5.2
Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 100 kA
$&9
Standard
three-phase
motor
4-pole at
480 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector
output (guide
P
value)
Motor starter
protector
Contactor2
Size
kW
A
A
Order No.
0,37
0,9
None
3RV13 21-0KC10 3RT10 15-1AP01 S0/S00
0,55
1,3
None
3RV13 21-1AC10 3RT10 15-1AP01 S0/S00
0,75
1,6
None
1,1
2,3
1,5
3,0
2,2
Overload relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
3RU11 16-0KB0
0,90 ... 1,25
100
3RU11 16-1AB0
1,10 ... 1,6,0
100
3RV13 21-1BC10 3RT10 15-1AP01 S0/S00
3RU11 16-1BB0
1,40 ... 2,00
100
None
3RV13 21-1DC10 3RT10 26-1AP00 S0/S0
3RU11 26-1DB0
2,20 ... 3,20
100
None
3RV13 21-1EC10 3RT10 34-1AP00 S0/S2
3RU11 26-1EB0
2,80 ... 4,00
100
4,2
None
3RV13 21-1FC10
3RU11 26-1FB0
3,50 ... 5,00
100
3
5,4
None
3RV13 21-1GC10 3RT10 34-1AP00 S0/S2
3RU11 26-1GB0
4,50 ... 6,30
100
4
7,0
None
3RV13 21-1HC10 3RT10 34-1AP00 S0/S2
3RU11 36-1HB0
5,50 ... 8,00
100
5,5
9,9
None
3RV13 21-1KC10 3RT10 34-1AP00 S0/S2
3RU11 36-1KB0
9,00 ... 12,5
100
7,5
12,9
None
3RV13 21-4AC10 3RT10 34-1AP00 S0/S2
3RU11 36-4AB0
11,0 ... 16,0
100
9
15,5
None
3RV13 31-4BC10 3RT10 34-1AP00 S2/S2
3RU11 36-4BB0
14,0 ... 20,0
100
11
18,3
None
3RV13 31-4DC10 3RT10 34-1AP00 S2/S2
3RU11 36-4DB0
18,0 ... 25,0
100
15
24
None
3RV13 31-4EC10 3RT10 34-1AP00 S2/S2
3RU11 36-4EB0
22,0 ... 32,0
100
18,5
29
None
3RV13 31-4FC10
3RT10 34-1AP00 S2/S2
3RU11 36-4FB0
28,0 ... 40,0
100
22
34
None
3RV13 31-4FC10
3RT10 35-1AP00 S2/S2
3RU11 36-4FB0
28,0 ... 40,0
100
30
46
None
3RV13 31-4HC10 3RT10 36-1AP00 S2/S2
3RU11 36-4HB0
40,0 ... 50,0
100
37
55
None
3RV13 41-4JC10
3RT10 54-1AP36 S3/S6
3RU11 46-4JB0
45,0 ... 63,0
100
45
67
None
3RV13 41-4KC10 3RT10 54-1AP36 S3/S6
3RU11 46-4KB0
57,0 ... 75,0
100
55
81
None
3RV13 41-4MC10 3RT10 54-1AP36 S3/S6
3RU11 46-4MB0
80,0 ... 100
100
Iq
I
1
2
Order No.
3RT10 34-1AP00 S0/S2
Order No.
Guide value for 4-pole standard motors at 480 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
85
Selection tables 480 V AC
5.3 Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay
5.3
Motor starter protector + contactor + 3RB20 / 3RB21 solid-state
overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 75 kA / 100 kA
$&9
Standard
three-phase
motor
4-pole at
480 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting range Motor starter
protector
Overload
release
Motor starter
protector2
Contactor3
Order No.
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
kW
A
A
Order No.
Order No.
0,37
0,9
None
3RV13 21-0KC10 3RT10 15-1AP01 S0/S00 3RB20 16-1NB0/
3RB21 13-4NB0
0,32 ... 1,25
100
0,55
1,3
None
3RV13 21-1AC10 3RT10 15-1AP01 S0/S00 3RB20 16-1PB0/
3RB21 13-4PB0
1,00 ... 4,00
100
0,75
1,6
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
1,00 ... 4,00
100
1,1
2,3
None
3RV13 21-1CC10 3RT10 26-1AP00 S0/S0
3RB21 23-4PB0/
3RB20 26-1PB0
1,00 ... 4,00
100
1,5
3,0
None
3RV13 21-1EC10 3RT10 34-1AP00 S0/S2
1,00 ... 4,00
100
2,2
4,2
None
3RV13 21-1FC10 3RT10 34-1AP00 S0/S2
3RB20 26-1SB0/
3RB21 23-4SB0
3,00 ... 12,0
100
3,00 ... 12,0
100
3,00 ... 12,0
100
3RB20 26-1QB0/
3RB21 23-4QB0
6,00 ... 25,0
100
6,00 ... 25,0
100
3RB20 36-1UB0/
3RB21 33-4UB0
12,5 ... 50,0
100
12,5 ... 50,0
100
3
5,4
None
3RV13 21-1GC10 3RT10 34-1AP00 S0/S2
4
7,1
None
3RV13 21-1HC10 3RT10 34-1AP00 S0/S2
5,5
9,6
None
3RV13 21-1KC10 3RT10 34-1AP00 S0/S2
7,5
12,9
None
3RV13 21-4AC10 3RT10 34-1AP00 S0/S2
9
15,5
None
3RV13 31-4BC10 3RT10 34-1AP00 S2/S2
11
18,3
None
3RV13 31-4EC10 3RT10 34-1AP00 S2/S2
15
24
None
3RV13 31-4EC10 3RT10 35-1AP00 S2/S2
12,5 ... 50,0
100
18,5
29
28,0 ... 40,0
3RV10 31-4FA10 3RT10 35-1AP00 S2/S2
12,5 ... 50,0
100
22
34
None
3RV13 41-4HC10 3RT10 44-1AP00 S3/S3
25,0 ... 100
100
30
46
None
3RV13 41-4HC10 3RT10 44-1AP00 S3/S3
25,0 ... 100
100
37
55
None
3RV13 41-4JC10 3RT10 54-1AP36 -/S6
25,0 ... 100
100
3RB20 46-1EB0/
3RB21 43-4EB0
45
67
None
3RV13 41-4KC10 3RT10 54-1AP36 -/S6
25,0 ... 100
100
55
81
None
3RV13 41-4MC10 3RT10 54-1AP36 -/S6
25,0 ... 100
100
3RB20 56-1FW2/ 50,0 ... 200
3RB21 53-4FW2 50,0 ... 200
100
75
110
None
3RV13 63-7CN10 3RT10 54-1AP36 -/S6
90
133
None
3RV13 63-7CN10 3RT10 55-6AP36 -/S6
86
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 480 V AC
5.3 Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
480 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting range Motor starter
protector
Overload
release
Motor starter
protector2
Contactor3
A
Order No.
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
kW
1
2
3
A
Order No.
Order No.
110
163
None
3RV13 63-7EN10 3RT10 56-6AP36 -/S6
132
192
None
3RV13 73-7GN10 3RT10 65-6AP36 -/S10
3RB20 66-1GC2/ 55,0 ... 250
3RB21 63-4GC2
55,0 ... 250
100
160
233
None
3RV13 73-7GN10 3RT10 65-6AP36 -/S10
55,0 ... 250
100
185
292
None
3RV13 73-7JN10 3RT10 75-6AP36 -/S12
315
None
3RV13 73-7JN10 3RT10 75-6AP36 -/S12
3RB20 66-1MC2/ 160 ... 630
3RB21 63-4MC2 160 ... 630
100
200
100
100
250
358
None
3RV13 83-7JN10 3RT12 75-6AP36 -/S12V
160 ... 630
75
315
450
None
3RV13 83-7KN10 3RT12 76-6AP36 -/S12V
160 ... 630
75
Guide value for 4-pole standard motors at 480 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
87
Selection tables 480 V AC
5.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
5.4
Motor starter protector + contactor + SIMOCODE pro 3UF7 /
3RB22/3RB23 solid-state overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 75 kA / 100 kA
$&9
Standard
three-phase
motor
4-pole at
480 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector
output (guide
P
value)
Motor starter
protector
Contactor2
Size
SIMOCODE pro or
overload relay
(current measuring
module)3
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
Order No.
Order No.
A
kA
3RV13 21-0KC10 3RT10 15-1AP01 S0/S00 3UF7 100-1AA00-0/
3RV13 21-1AC10 3RT10 15-1AP01/ S0/S00 3RB29 06-2BG1
3RT10 15-1BB41
Iq
I
A
0,37
0,9
None
0,55
1,3
None
Order No.
0,30 ... 3,00 100
0,30 ... 3,00 100
0,75
1,6
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00 100
1,1
2,3
None
3RV13 21-1CC10 3RT10 26-1AP00/ S0/S0
3RT10 26-1BB40
0,30 ... 3,00 100
1,5
3,0
None
3RV13 21-1EC10 3RT10 34-1AP00 S0/S2
2,2
4,2
None
3RV13 21-1FC10 3RT10 34-1AP00 S0/S2
3UF7 101-1AA00-0/
3RB29 06-2DG1
2,40 ... 25,0 100
2,40 ... 25,0 100
3
5,4
None
3RV13 21-1GC10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0 100
4
7,1
None
3RV13 21-1HC10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0 100
5,5
9,6
None
3RV13 21-1KC10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0 100
7,5
12,9
None
3RV13 21-4AC10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0 100
9
15,5
None
3RV13 31-4BC10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0 100
11
18,3
None
3RV13 31-4DC10 3RT10 34-1AP00 S2/S2
3UF7 102-1AA00-0/
3RB29 06-2JG1
2,40 ... 25,0 100
15
24
None
3RV13 31-4EC10 3RT10 35-1AP00 S2/S2
3UF7 112-1AA00-0/
3RB29 06-2JG1
2,40 ... 25,0 100
18,5
29
None
3RV13 31-4FC10 3RT10 35-1AP00 S2/S2
34
None
3RV13 31-4HC10 3RT10 35-1AP00/ S2/S2
3RT10 35-1BB40
3UF7 102-1AA00-0/
3RB29 06-2JG1
10,0 ... 100 100
22
30
46
None
3RV13 41-4HC10 3RT10 36-1AP00/ S3/S2
3RT10 36-1BB40
37
55
None
3RV13 41-4JC10 3RT10 54-1AP36 S3/S6
45
67
None
3RV13 41-4KC10 3RT10 54-1AP36 S3/S6
88
10,0 ... 100 100
10,0 ... 100 100
3UF7 103-1AA00-0/
3RB29 56-2TG1
20,0 ... 200 100
20,0 ... 200 100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 480 V AC
5.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
480 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector
output (guide
P
value)
Motor starter
protector
Contactor2
Size
SIMOCODE pro or
overload relay
(current measuring
module)3
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
Order No.
A
kA
55
81
None
3RV13 41-4MC10 3RT10 54-1AP36 S3/S6
75
110
None
3RV13 63-7CN10 3RT10 54-1AP36 -/S6
3UF7 103-1AA00-0/
3RB29 56-2TG2
20,0 ... 200 100
90
133
None
3RV13 63-7CN10 3RT10 55-6AP36 -/S6
20,0 ... 200 100
Iq
I
1
2
3
Order No.
20,0 ... 200 100
110
163
None
3RV13 63-7EN10 3RT10 56-6AP36 -/S6
20,0 ... 200 100
132
192
None
3RV13 73-7GN10 3RT10 65-6AP36 -/S10
20,0 ... 200 100
160
233
None
3RV13 73-7GN10 3RT10 65-6AP36 -/S10
185
292
None
3RV13 73-7JN10 3RT10 75-6AP36 -/S12
200
315
None
3RV13 73-7JN10 3RT10 75-6AP36 -/S12
63,0 ... 630 100
3UF7 104-1BA00-0/
3RB29 66-2WH2
63,0 ... 630 100
63,0 ... 630 100
250
358
None
3RV13 83-7JN10 3RT12 75-6AP36 -S12V
63,0 ... 630 75
315
450
None
3RV13 83-7KN10 3RT12 76-6AP36 -S12V
63,0 ... 630 75
Guide value for 4-pole standard motors at 480 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
89
Selection tables 480 V AC
5.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
90
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
6
Selection tables 500 V AC
6.1
Motor starter protector / circuit breaker + contactor
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard threephase motor
4-pole at
500 V AC1
Setting range
Overload
release
Motor starter
protector /
circuit breaker
Motor starter protector /
circuit breaker
Contactor2
Size
Short-circuit breaking
capacity
Iq
Stand
ard
outpu
t
Motor
current
(guide
value)
kW
A
A
Order No.
Order No.
0,06
0,2
0,14 ... 0,20
3RV10 11-0BA10
3RT10 15-1AP01
S00/S00
50
0,09
0,2
0,18 ... 0,25
3RV10 11-0CA10
3RT10 15-1AP01
S00/S00
50
0,12
0,3
0,22 ... 0,32
3RV10 11-0DA10
3RT10 15-1AP01
S00/S00
50
0,12
0,3
0,28 ... 0,40
3RV10 11-0EA10
3RT10 15-1AP01
S00/S00
50
0,18
0,5
0,35 ... 0,50
3RV10 11-0FA10
3RT10 15-1AP01
S00/S00
50
0,18
0,5
0,45 ... 0,63
3RV10 11-0GA10
3RT10 15-1AP01
S00/S00
50
0,25
0,7
0,55 ... 0,80
3RV10 11-0HA10
3RT10 15-1AP01
S00/S00
50
0,37
0,9
0,70 ... 1,00
3RV10 11-0JA10
3RT10 15-1AP01
S00/S00
50
0,55
1,2
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
50
0,75
1,5
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
50
P
I
kA
0,75
1,5
1,40 ... 2,00
3RV10 11-1BA10
3RT10 15-1AP01
S00/S00
50
1,1
2,2
1,80 ... 2,50
3RV10 11-1CA10
3RT10 15-1AP01
S00/S00
50
1,5
2,9
2,20 ... 3,20
3RV10 11-1DA10
3RT10 15-1AP01
S00/S00
50
2,2
4,0
3,50 ... 5,00
3RV10 11-1FA10
3RT10 15-1AP01
S00/S00
50
3
5,2
4,50 ... 6,30
3RV10 11-1GA10
3RT10 15-1AP01
S00/S00
50
4
6,8
5,50 ... 8,00
3RV10 11-1HA10
3RT10 16-1AP01
S00/S00
50
5,5
9,2
7,00 ... 10,0
3RV10 11-1JA10
3RT10 17-1AP01
S00/S00
50
7,5
12,4
9,00 ... 12,5
3RV10 21-1KA10
3RT10 25-1AP00
S0/S0
50
7,5
12,4
11,0 ... 16,0
3RV10 21-4AA10
3RT10 25-1AP00
S0/S0
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
91
Selection tables 500 V AC
6.1 Motor starter protector / circuit breaker + contactor
Standard threephase motor
4-pole at
500 V AC1
Setting range
Overload
release
Motor starter
protector /
circuit breaker
Motor starter protector /
circuit breaker
Contactor2
Size
Short-circuit breaking
capacity
Iq
Stand
ard
outpu
t
Motor
current
(guide
value)
kW
A
A
Order No.
Order No.
11
17,6
14,0 ... 20,0
3RV10 21-4BA10
3RT10 26-1AP00
S0/S0
50
P
I
kA
15
23
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00
S2/S2
50
18,5
28
22,0 ... 32,0
3RV10 31-4EA10
3RT10 34-1AP00
S2/S2
50
22
33
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
50
30
44
36,0 ... 45,0
3RV10 31-4GA10
3RT10 36-1AP00
S2/S2
50
30
44
40,0 ... 50,0
3RV10 31-4HA10
3RT10 36-1AP00
S2/S2
50
37
53
45,0 ... 63,0
3RV10 41-4JA10
3RT10 44-1AP00
S3/S3
50
45
64
57,0 ... 75,0
3RV10 41-4KA10
3RT10 44-1AP00
S3/S3
50
55
78
70,0 ... 90,0
3RV10 41-4LA10
3RT10 45-1AP00
S3/S3
50
75
106
64,0 ... 160
3VL27 16-2SP33
3RT10 54-6AP36
-/S6
50
90
128
64,0 ... 160
3VL27 16-2SP33
3RT10 55-6AP36
-/S6
50
3VL27
16-2SP333
3RT10 56-6AP36
-/S6
50
20-2SP364
110
156
64,0 ... 160
132
184
80,0 ... 200
3VL37
3RT10 64-6AP36
-/S10
50
132
184
80,0 ... 200
3VL37 20-2SP364
3RT12 64-6AP36
-/S10V
50
160
224
100 ... 250
3VL37 25-2SP365
3RT10 65-6AP36
-/S10
50
160
224
100 ... 250
3VL37 25-2SP365
3RT12 65-6AP36
-/S10V
50
200
280
125 ... 315
3VL47 31-2SP36
3RT10 66-6AP36
-/S10
50
200
280
125 ... 315
3VL47 31-2SP36
3RT12 66-6AP36
-/S10V
50
250
344
200 ... 500
3VL57 50-2SP36
3RT10 75-6AP36
-/S12
50
250
344
200 ... 500
3VL57 50-2SP36
3RT12 75-6AP36
-/S12V
50
315
432
200 ... 500
3VL57 50-2SP36
3RT10 76-6AP36
-/S12
50
315
432
200 ... 500
3VL57 50-2SP36
3RT12 76-6AP36
-/S12V
50
355
488
200 ... 500
3VL57 50-2SP36
3RT10 76-6AP36
-/S12
50
355
488
200 ... 500
3VL57 50-2SP36
3RT12 76-6AP36
-/S12V
50
1
2
3
4
5
92
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL37 20-2SP36 also possible.
Alternatively 3VL37 25-2SP36 also possible.
Alternatively 3VL47 31-2SP36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.1 Motor starter protector / circuit breaker + contactor
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting range
Overload
release
Motor starter
protector /
circuit breaker
Motor starter protector /
circuit breaker
Contactor2
Size
Short-circuit breaking
capacity
Iq
Stand
ard
outpu
t
Motor
current
(guide
value)
kW
A
A
Order No.
Order No.
0,06
0,2
0,14 ... 0,20
3RV10 11-0BA10
3RT10 15-1AP01
S00/S00
50
0,09
0,2
0,18 ... 0,25
3RV10 11-0CA10
3RT10 15-1AP01
S00/S00
50
0,12
0,3
0,22 ... 0,32
3RV10 11-0DA10
3RT10 15-1AP01
S00/S00
50
0,12
0,3
0,28 ... 0,40
3RV10 11-0EA10
3RT10 15-1AP01
S00/S00
50
0,18
0,5
0,35 ... 0,50
3RV10 11-0FA10
3RT10 15-1AP01
S00/S00
50
0,18
0,5
0,45 ... 0,63
3RV10 11-0GA10
3RT10 15-1AP01
S00/S00
50
0,25
0,7
0,55 ... 0,80
3RV10 11-0HA10
3RT10 15-1AP01
S00/S00
50
0,37
0,9
0,70 ... 1,00
3RV10 11-0JA10
3RT10 15-1AP01
S00/S00
50
0,55
1,2
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
50
0,75
1,5
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
50
P
I
kA
0,75
1,5
1,40 ... 2,00
3RV10 21-1BA10
3RT10 24-1AP00
S0/S0
50
1,1
2,2
1,80 ... 2,50
3RV10 21-1CA10
3RT10 26-1AP00
S0/S0
50
1,5
2,9
2,20 ... 3,20
3RV10 21-1DA10
3RT10 34-1AP00
S0/S2
50
2,2
4,0
3,50 ... 5,00
3RV10 21-1FA10
3RT10 34-1AP00
S0/S2
50
3
5,2
4,50 ... 6,30
3RV10 21-1GA10
3RT10 34-1AP00
S0/S2
50
4
6,8
5,50 ... 8,00
3RV10 21-1HA10
3RT10 34-1AP00
S0/S2
50
5,5
9,2
7,00 ... 10,0
3RV10 21-1JA10
3RT10 34-1AP00
S0/S2
50
7,5
12,4
9,00 ... 12,5
3RV10 21-1KA10
3RT10 34-1AP00
S0/S2
50
7,5
12,4
11,0 ... 16,0
3RV10 31-4AA10
3RT10 34-1AP00
S2/S2
50
11
17,6
14,0 ... 20,0
3RV10 31-4BA10
3RT10 34-1AP00
S2/S2
50
15
23
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00
S2/S2
50
18,5
28
22,0 ... 32,0
3RV10 31-4EA10
3RT10 34-1AP00
S2/S2
50
22
33
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
50
30
44
36,0 ... 45,0
3RV10 31-4GA10
3RT10 36-1AP00
S2/S2
50
30
44
40,0 ... 50,0
3RV10 31-4HA10
3RT10 36-1AP00
S2/S2
50
37
53
45,0 ... 63,0
3RV10 41-4JA10
3RT10 44-1AP00
S3/S3
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
93
Selection tables 500 V AC
6.1 Motor starter protector / circuit breaker + contactor
Standard
three-phase
motor
4-pole at
500 V AC1
Stand
ard
outpu
t
Motor
current
(guide
value)
kW
A
P
Setting range
Overload
release
Motor starter
protector /
circuit breaker
Motor starter protector /
circuit breaker
Contactor2
A
Order No.
Order No.
Size
Short-circuit breaking
capacity
Iq
I
kA
45
64
57,0 ... 75,0
3RV10 41-4KA10
3RT10 44-1AP00
S3/S3
50
55
78
70,0 ... 90,0
3RV10 41-4LA10
3RT10 45-1AP00
S3/S3
50
75
106
64,0 ... 160
3VL27 16-2SP33
3RT10 54-1AP36
-/S6
50
16-2SP333
90
128
64,0 ... 160
3VL27
3RT10 55-6AP36
-/S6
50
110
156
64,0 ... 160
3VL27 16-2SP334
3RT10 56-6AP36
-/S6
50
20-2SP364
132
184
80,0 ... 200
3VL37
3RT10 64-6AP36
-/S10
50
132
184
80,0 ... 200
3VL37 20-2SP365
3RT12 64-6AP36
-/S10V
50
160
224
100 ... 250
3VL37 25-2SP365
3RT10 65-6AP36
-/S10
50
160
224
100 ... 250
3VL37 25-2SP36
3RT12 65-6AP36
-/S10V
50
200
280
125 ... 315
3VL47 31-2SP36
3RT10 66-6AP36
-/S10
50
200
280
125 ... 315
3VL47 31-2SP36
3RT12 66-6AP36
-/S10V
50
250
344
200 ... 500
3VL57 50-2SP36
3RT10 75-6AP36
-/S12
50
250
344
200 ... 500
3VL57 50-2SP36
3RT12 76-6AP36
-/S12V
50
315
432
200 ... 500
3VL57 50-2SP36
3RT10 76-6AP36
-/S12
50
315
432
200 ... 500
3VL57 50-2SP36
3RT12 76-6AP36
-/S12V
50
355
488
200 ... 500
3VL57 50-2SP36
3RT10 76-6AP36
-/S12
50
355
488
200 ... 500
3VL57 50-2SP36
3RT12 76-6AP36
-/S12V
50
1
2
3
4
5
94
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL37 20-2SP36 also possible.
Alternatively 3VL37 25-2SP36 also possible.
Alternatively 3VL47 31-2SP36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.1 Motor starter protector / circuit breaker + contactor
CLASS 20, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard threephase motor
4-pole at
500 V AC1
Standa Motor
rd
current
output (guide
P
value)
Setting range
Overload
release
Motor starter
protector /
circuit breaker
Motor starter protector / Contactor2
circuit breaker
Size
Short-circuit breaking
capacity
Iq
I
kW
A
A
Order No.
Order No.
kA
7,5
12,4
11,0 ... 16,0
3RV10 31-4AB10
3RT10 34-1AP00
11
17,6
14,0 ... 20,0
3RV10 31-4BB10
3RT10 34-1AP00
S2/S2
50
11
17,6
18,0 ... 25,0
3RV10 31-4DB10
3RT10 34-1AP00
S2/S2
50
S2/S2
50
15
23
22,0 ... 32,0
3RV10 31-4EB10
3RT10 35-1AP00
S2/S2
50
18,5
28
22,0 ... 32,0
3RV10 31-4EB10
3RT10 44-1AP00
S2/S3
50
18,5
28
28,0 ... 40,0
3RV10 42-4FB10
3RT10 44-1AP00
S3/S3
50
22
33
28,0 ... 40,0
3RV10 42-4FB10
3RT10 44-1AP00
S3/S3
50
30
44
36,0 ... 50,0
3RV10 42-4HB10
3RT10 44-1AP00
S3/S3
50
30
44
45,0 ... 63,0
3RV10 42-4JB10
3RT10 44-1AP00
S3/S3
50
37
53
45,0 ... 63,0
3RV10 42-4JB10
3RT10 45-1AP00
S3/S3
50
37
53
57,0 ... 75,0
3RV10 42-4KB10
3RT10 45-1AP00
S3/S3
50
45
64
57,0 ... 75,0
3RV10 42-4KB10
3RT10 54-1AP36
S3/S6
50
55
79
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36
S3/S6
50
75
106
64,0 ... 160
3VL27 16-2SS33
3RT10 55-6AP36
-/S6
50
90
128
64,0 ... 160
3VL27 16-2SS33
3RT10 56-6AP36
-/S6
50
110
156
64,0 ... 160
3VL27 16-2SS333
3RT10 64-6AP36
-/S10
50
132
184
80,0 ... 200
3VL37 20-2SS364
3RT10 65-6AP36
-/S10
50
20-2SS364
132
184
80,0 .. 200
3VL37
3RT10 66-6AP36
-/S10
50
132
184
80,0 ... 200
3VL37 20-2SS364
3RT12 64-6AP36
-/S10V
50
25-2SS365
160
224
100 ... 250
3VL37
3RT12 65-6AP36
-/S10V
50
200
280
125 ... 315
3VL47 31-2SS36
3RT12 66-6AP36
-/S10V
50
200
280
125 ... 315
3VL47 31-2SS36
3RT10 75-6AP36
-/S12
50
250
344
200 ... 500
3VL57 50-2SS36
3RT10 76-6AP36
-/S12
50
250
344
200 ... 500
3VL57 50-2SS36
3RT12 75-6AP36
-/S12V
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
95
Selection tables 500 V AC
6.1 Motor starter protector / circuit breaker + contactor
Standard threephase motor
4-pole at
500 V AC1
Standa Motor
rd
current
output (guide
P
value)
Setting range
Overload
release
Motor starter
protector /
circuit breaker
Motor starter protector / Contactor2
circuit breaker
Size
Short-circuit breaking
capacity
Iq
I
kW
A
A
Order No.
Order No.
315
432
200 ... 500
3VL57 50-2SS36
3RT12 76-6AP36
-/S12V
50
255
488
200 ... 500
3VL57 50-2SS36
3RT12 76-6AP36
-/S12V
50
1
2
3
4
5
96
kA
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL37 20-2SS36 also possible.
Alternatively 3VL37 25-2SS36 also possible.
Alternatively 3VL47 31-2SS36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.2 Motor starter protector + contactor + 3RU11 thermal overload relay
6.2
Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard threephase motor
4-pole at
500 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
Overload relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Iq
I
kW
A
A
Order No.
Order No.
Order No.
A
kA
0,06
0,2
None
3RV13 21-0BC10
3RT10 15-1AP01 S0/S00
3RU11 16-0BB0
0,14 ... 0,20
50
0,09
0,2
None
3RV13 21-0CC10
3RT10 15-1AP01 S0/S00
3RU11 16-0CB0 0,18 ... 0,25
50
0,12
0,3
None
3RV13 21-0DC10
3RT10 15-1AP01 S0/S00
3RU11 16-0DB0 0,22 ... 0,32
50
0,12
0,3
None
3RV13 21-0EC10
3RT10 15-1AP01 S0/S00
3RU11 16-0EB0
0,28 ... 0,40
50
0,18
0,5
None
3RV13 21-0FC10
3RT10 15-1AP01 S0/S00
3RU11 16-0FB0
0,35 ... 0,50
50
0,18
0,5
None
3RV13 21-0GC10
3RT10 15-1AP01 S0/S00
3RU11 16-0GB0 0,45 ... 0,63
50
0,25
0,7
None
3RV13 21-0HC10
3RT10 15-1AP01 S0/S00
3RU11 16-0HB0 0,55 ... 0,80
50
0,37
0,9
None
3RV13 21-0JC10
3RT10 15-1AP01 S0/S00
3RU11 16-0JB0
0,70 ... 1,00
50
0,55
1,2
None
3RV13 21-0KC10
3RT10 15-1AP01 S0/S00
3RU11 16-0KB0
0,90 ... 1,25
50
0,75
1,5
None
3RV13 21-1AC10
3RT10 15-1AP01 S0/S00
3RU11 16-1AB0
1,10 ... 1,60
50
0,75
1,5
None
3RV13 21-1BC10
3RT10 15-1AP01 S0/S00
3RU11 16-1BB0
1,40 ... 2,00
50
1,1
2,2
None
3RV13 21-1CC10
3RT10 15-1AP01 S0/S00
3RU11 16-1CB0 1,80 ... 2,50
50
1,5
2,9
None
3RV13 21-1DC10
3RT10 15-1AP01 S0/S00
3RU11 16-1DB0 2,20 ... 3,20
50
2,2
4,0
None
3RV13 21-1FC10
3RT10 15-1AP01 S0/S00
3RU11 16-1FB0
3,50 ... 5,00
50
3
5,2
None
3RV13 21-1GC10
3RT10 15-1AP01 S0/S00
3RU11 16-1GB0 4,50 ... 6,30
50
4
6,8
None
3RV13 21-1HC10
3RT10 16-1AP01 S0/S00
3RU11 16-1HB0 5,50 ... 8,00
50
5,5
9,2
None
3RV13 21-1JC10
3RT10 17-1AP01 S0/S00
3RU11 16-1JB0
7,00 ... 10,0
50
7,5
12,4
None
3RV13 21-1KC10
3RT10 25-1AP00 S0/S0
3RU11 26-1KB0
9,00 ... 12,5
50
7,5
12,4
None
3RV13 21-4AC10
3RT10 25-1AP00 S0/S0
3RU11 26-4AB0
11,0 ... 16,0
50
11
17,6
None
3RV13 21-4BC10
3RT10 26-1AP00 S0/S0
3RU11 26-4BB0
14,0 ... 20,0
50
15
23
None
3RV13 31-4DC10
3RT10 34-1AP00 S2/S2
3RU11 36-4DB0 18,0 ... 25,0
50
18,5
28
None
3RV13 31-4EC10
3RT10 34-1AP00 S2/S2
3RU11 36-4EB0
22,0 ... 32,0
50
22
33
None
3RV13 31-4FC10
3RT10 35-1AP00 S2/S2
3RU11 36-4FB0
28,0 ... 40,0
50
30
44
None
3RV13 31-4GC10
3RT10 36-1AP00 S2/S2
3RU11 36-4GB0 36,0 ... 45,0
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
97
Selection tables 500 V AC
6.2 Motor starter protector + contactor + 3RU11 thermal overload relay
Standard threephase motor
4-pole at
500 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
Overload relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
I
kW
A
A
Order No.
Order No.
Order No.
30
44
None
3RV13 31-4HC10
3RT10 36-1AP00 S2/S2
3RU11 36-4HB0 40,0 ... 50,0
50
37
53
None
3RV13 41-4JC10
3RT10 44-1AP00 S3/S3
3RU11 46-4JB0
45,0 ... 63,0
50
45
64
None
3RV13 41-4KC10
3RT10 44-1AP00 S3/S3
3RU11 46-4KB0
57,0 ... 75,0
50
55
78
None
3RV13 41-4LC10
3RT10 45-1AP00 S3/S3
3RU11 46-4LB0
70,0 ... 90,0
50
1
2
98
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.2 Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard threephase motor
4-pole at
500 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
Motor starter
range
protector
Overload
release
Motor
starter
protector
Contactor2
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breakin
g
capacit
y
Order No.
A
kA
Iq
I
kW
A
A
Order No.
Order No.
0,06
0,2
None
3RV13 21-0BC10
3RT10 15-1AP01
S0/S00
3RU11 16-0BB0
0,14 ... 0,20
50
0,09
0,2
None
3RV13 21-0CC10
3RT10 15-1AP01
S0/S00
3RU11 16-0CB0
0,18 ... 0,25
50
0,12
0,3
None
3RV13 21-0DC10
3RT10 15-1AP01
S0/S00
3RU11 16-0DB0
0,22 ... 0,32
50
0,12
0,3
None
3RV13 21-0EC10
3RT10 15-1AP01
S0/S00
3RU11 16-0EB0
0,28 ... 0,40
50
0,18
0,5
None
3RV13 21-0FC10
3RT10 15-1AP01
S0/S00
3RU11 16-0FB0
0,35 ... 0,50
50
0,18
0,5
None
3RV13 21-0GC10
3RT10 15-1AP01
S0/S00
3RU11 16-0GB0
0,45 ... 0,63
50
0,25
0,7
None
3RV13 21-0HC10
3RT10 15-1AP01
S0/S00
3RU11 16-0HB0
0,55 ... 0,80
50
0,37
0,9
None
3RV13 21-0JC10
3RT10 15-1AP01
S0/S00
3RU11 16-0JB0
0,70 ... 1,00
50
0,55
1,2
None
3RV13 21-0KC10
3RT10 15-1AP01
S0/S00
3RU11 16-0KB0
0,90 ... 1,25
50
0,75
1,5
None
3RV13 21-1AC10
3RT10 15-1AP01
S0/S00
3RU11 16-1AB0
1,10 ... 1,60
50
0,75
1,5
None
3RV13 21-1BC10
3RT10 24-1AP00
S0/S0
3RU11 16-1BB0
1,40 ... 2,00
50
1,1
2,2
None
3RV13 21-1CC10
3RT10 26-1AP00
S0/S0
3RU11 26-1CB0
1,80 ... 2,50
50
26-1DB03
1,5
2,9
None
3RV13 21-1DC10
3RT10 34-1AP00
S0/S2
3RU11
2,2
4,0
None
3RV13 21-1FC10
3RT10 34-1AP00
S0/S2
3RU11 26-1FB03
2,20 ... 3,20
50
3,50 ... 5,00
50
3
5,2
None
3RV13 21-1GC10
3RT10 34-1AP00
S0/S2
3RU11 26-1GB03
4,50 ... 6,30
50
4
6,8
None
3RV13 21-1HC10
3RT10 34-1AP00
S0/S2
3RU11 36-1HB0
5,50 ... 8,00
50
5,5
9,2
None
3RV13 21-1JC10
3RT10 34-1AP00
S0/S2
3RU11 36-1JB0
7,00 ... 10,0
50
7,5
12,4
None
3RV13 21-1KC10
3RT10 34-1AP00
S0/S2
3RU11 36-1KB0
9,00 ... 12,5
50
11
17,6
None
3RV13 31-4BC10
3RT10 34-1AP00
S2/S2
3RU11 36-4BB0
14,0 ... 20,0
50
15
23
None
3RV13 31-4DC10
3RT10 34-1AP00
S2/S2
3RU11 36-4DB0
18,0 ... 25,0
50
18,5
28
None
3RV13 31-4EC10
3RT10 34-1AP00
S2/S2
3RU11 36-4EB0
22,0 ... 32,0
50
22
33
None
3RV13 31-4FC10
3RT10 35-1AP00
S2/S2
3RU11 36-4FB0
28,0 ... 40,0
50
30
44
None
3RV13 31-4GC10
3RT10 36-1AP00
S2/S2
3RU11 36-4GB0
36,0 ... 45,0
50
30
44
None
3RV13 31-4HC10
3RT10 36-1AP00
S2/S2
3RU11 36-4HB0
40,0 ... 50,0
50
37
53
None
3RV13 41-4JC10
3RT10 44-1AP00
S3/S3
3RU11 46-4JB0
45,0 ... 63,0
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
99
Selection tables 500 V AC
6.2 Motor starter protector + contactor + 3RU11 thermal overload relay
Standard threephase motor
4-pole at
500 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
Motor starter
range
protector
Overload
release
Motor
starter
protector
Contactor2
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breakin
g
capacit
y
Order No.
A
kA
Iq
I
1
2
3
kW
A
A
Order No.
Order No.
45
64
None
3RV13 41-4KC10
3RT10 44-1AP00
S3/S3
3RU11 46-4KB0
57,0 ... 75,0
50
55
78
None
3RV13 41-4LC10
3RT10 45-1AP00
S3/S3
3RU11 46-4LB0
70,0 ... 90,0
50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Stand-alone installation.
100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.3 Motor starter protector / circuit breaker + contactor + 3RB20/3RB21 solid-state overload relay
6.3
Motor starter protector / circuit breaker + contactor + 3RB20/3RB21
solid-state overload relay
CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
outpu (guide circuit
t
value) breaker2
Motor starter
protector / circuit
breaker
P
I
kW
A
Order No.
A
Contactor3
Size
Order No.
Overload relay
Order No.
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
Type of coordination 2
0,06
0,2
0,10 ... 0,40 50
0,2
0,22 ... 0,32 3RV10 11-0DA10 3RT10 15-1AP01 S00/S00 3RB20 16-1RB0/
0,28 ... 0,40 3RV10 11-0EA10 3RT10 15-1AP01 S00/S00 3RB21 13-4RB0
0,09
0,12
0,3
0,45 ... 0,63 3RV10 11-0GA10 3RT10 15-1AP01 S00/S00
0,10 ... 0,40 50
0,18
0,5
0,32 ... 1,25 50
0,25
0,7
0,60 ... 0,80 3RV10 11-0HA10 3RT10 15-1AP01 S00/S00 3RB20 16-1NB0/
0,70 ... 1,00 3RV10 11-0JA10 3RT10 15-1AP01 S00/S00 3RB21 13-4NB0
0,37
0,9
1,10 ... 1,60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00
0,32 ... 1,25 50
0,55
1,2
1,10 ... 1,60 3RV10 11-1AA10 3RT10 15-1AP01 S00/S00 3RB20 16-1PB0/
3RB21 23-4PB0
1,00 ... 4,00 50
0,55
1,2
None
3RV13 21-0KC10 3RT10 24-1AP01 S0/S0
1,00 ... 4,00 50
0,75
1,5
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
3RB21 23-4PB0/
3RB21 13-4PB0
0,10 ... 0,40 50
0,32 ... 1,25 50
1,00 ... 4,00 50
1,1
2,2
None
3RV13 21-1CC10 3RT10 26-1AP00 S0/S0
1,00 ... 4,00 50
1,5
2,9
None
3RV13 21-1DC10 3RT10 34-1AP00 S0/S2
1,00 ... 4,00 50
2,2
4
None
3RV13 21-1FC10 3RT10 34-1AP00 S0/S2
3
5,2
None
3RV13 21-1GC10 3RT10 34-1AP00 S0/S2
4
6,8
None
3RV13 21-1HC10 3RT10 34-1AP00 S0/S2
5,5
9,2
None
3RV13 21-1JC10 3RT10 34-1AP00 S0/S2
7,5
12,4
None
3RV13 31-4AC10 3RT10 34-1AP00 S2/S2
11
17,6
None
3RV13 31-4BC10 3RT10 34-1AP00 S2/S2
3RV13 31-4EC10 3RT10 34-1AP00 S2/S2
3RB20 26-1SB0/
3RB21 23-4SB0
3,00 ... 12,0 50
3RB20 36-1QB0/
3RB21 23-4QB0
6,00 ... 25,0 50
3,00 ... 12,0 50
6,00 ... 25,0 50
6,00 ... 25,0 50
3RB20 36-1UB0/
3RB21 33-4UW1
12,5 ... 50,0 50
15
23
None
18,5
28
28,0 ... 40,0 3RV10 31-4FA10 3RT10 35-1AP00 S2/S2
12,5 ... 50,0 50
22
33
40,0 ... 50,0 3RV10 31-4HA10 3RT10 36-1AP00 S2/S2
12,5 ... 50,0 50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
12,5 ... 50,0 50
101
Selection tables 500 V AC
6.3 Motor starter protector / circuit breaker + contactor + 3RB20/3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
outpu (guide circuit
t
value) breaker2
Motor starter
protector / circuit
breaker
P
I
kW
A
A
Order No.
22
33
None
30
44
37
45
55
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3RV13 41-4FC10 3RT10 44-1AP00 S3/S3
3RB20 46-1UB0/
3RB21 43-4UB0
12,5 ... 50,0 50
None
3RV13 41-4HC10 3RT10 44-1AP00 S3/S3
25,0 ... 100
50
53
None
3RV13 41-4JC10 3RT10 44-1AP00 S3/S3
3RB20 46-1EB0/
3RB21 43-4EB0
25,0 ... 100
50
64
57,0 ... 75,0 3RV10 41-4KA10 3RT10 44-1AP00 S3/S3
25,0 ... 100
50
78
70,0 ... 90,0 3RV10 41-4LA10 3RT10 45-1AP00 S3/S3
25,0 ... 100
50
3RB20 56-1FW2/
3RB21 53-4FW2
50,0 ... 200
50
50,0 ... 200
50
3RB20 56-1FC2/
3RB21 53-4FC2
50,0 ... 200
50
50,0 ... 200
50
3RB20 66-1GC2/
3RB21 63-4GC2
55,0 ... 250
50
Order No.
Iq
55
78
None
3VL27 10-3DK33 3RT10 54-1AP36 –/S6
75
106
None
3VL27 16-3DK33 3RT10 54-1AP36 –/S6
90
128
None
3VL27 16-3DK33 3RT10 55-6AP36 –/S6
110
156
None
3VL27 16-3DK33 3RT10 56-6AP36 –/S6
110
156
None
3VL37 25-3DK36 3RT10 56-6AP36 –/S6
132
184
None
3VL37 25-3DK36 3RT10 64-6AP36 –/S10
55,0 ... 250
50
132
184
None
3VL37 25-3DK36 3RT12 64-6AP36 –/S10V
55,0 ... 250
50
160
224
None
3VL37 25-3DK36 3RT10 65-6AP36 –/S10
55,0 ... 250
50
160
224
None
3VL47 31-3DK36 3RT10 65-6AP36 –/S10
55,0 ... 250
50
160
224
None
3VL37 25-3DK36 3RT12 65-6AP36 –/S10V
55,0 ... 250
50
200
280
None
3VL47 31-3DK36 3RT10 66-6AP36 –/S10
200
280
None
3VL47 31-3DK36 3RT12 66-6AP36 –/S10V
250
344
None
250
344
315
432
315
432
3RB20 66-1MC2/
3RB21 63-4MC2
160 ... 630
50
160 ... 630
50
3VL57 50-3DK36 3RT10 75-6AP36 –/S12
160 ... 630
50
None
3VL57 50-3DK36 3RT12 75-6AP36 –/S12V
160 ... 630
50
None
3VL57 50-3DK36 3RT10 76-6AP36 –/S12
160 ... 630
50
None
3VL57 50-3DK36 3RT12 76-6AP36 –/S12V
160 ... 630
50
355
488
None
3VL57 50-3DK36 3RT10 76-6AP36 –/S12
160 ... 630
50
355
488
None
3VL57 50-3DK36 3RT12 76-6AP36 –/S12V
160 ... 630
50
102
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.3 Motor starter protector / circuit breaker + contactor + 3RB20/3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
outpu (guide circuit
t
value) breaker2
Motor starter
protector / circuit
breaker
kW
A
A
Type of coordination 1
Order No.
400
552
None
3VL77 12-2DE36 3TF68 44-0CM7
500
680
None
560
760
None
P
1
2
3
4
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
–/14
3RB20 66-2MC2/
3RB21 63-4MC2
160 ... 630
50
3VL87 16-2DE30 3TF69 44-0CM7
–/14
50
3VL87 16-2DE30 3TF69 44-0CM7
–/14
3UF1 868-3GA00 + 205 ... 820
3RB20 16-1NB0/
160 ... 630
3UF1 868-3GA00 +
3RB21 13-4RB04)
Iq
I
Order No.
50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Use terminal bracket for stand-alone installation of overload relays.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
103
Selection tables 500 V AC
6.3 Motor starter protector / circuit breaker + contactor + 3RB20/3RB21 solid-state overload relay
CLASS 20, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stan Motor starter
dard curre protector /
outpu nt
circuit
t
(guide breaker2
P
value)
Motor starter
protector / circuit
breaker
Contactor3
kW
Order No.
Order No.
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
A
kA
3RT10 15-1AP01 S00/S00 3RB20 16-2RB0/
3RT10 15-1AP01 S00/S00 3RB21 13-4RB0
0,10 ... 0,40
50
0,10 ... 0,40
50
0,32 ... 1,25
50
Iq
I
A
A
Order No.
Type of coordination 2
0,06
0,2
0,28 ... 0,40
3RV10 11-0EA10
0,09
0,2
0,45 ... 0,63
3RV10 11-0GA10
0,12
0,3
0,55 ... 0,80
3RV10 11-0HA10
0,18
0,5
0,70 ... 1,00
3RV10 11-0JA10
3RT10 15-1AP01 S00/S00 3RB20 16-2NB0/
3RT10 15-1AP01 S00/S00 3RB21 13-4NB0
0,32 ... 1,25
50
0,25
0,7
0,90 ... 1,25
3RV10 11-0KA10
3RT10 15-1AP01 S00/S00
0,32 ... 1,25
50
0,37
0,9
1,10 ... 1,60
3RV10 11-1AA10
3RT10 15-1AP01 S00/S00
0,32 ... 1,25
50
0,55
1,2
None
3RV13 21-1BC10
3RT10 24-1AP00 S0/S0
1,00 ... 4,00
50
0,75
1,5
None
3RV13 21-1DC10
3RT10 26-1AP00 S0/S0
1,00 ... 4,00
50
3RB21 23-4PB0/
3RB21 13-4PB0
1,1
2,2
2,80 ... 4,00
3RV10 21-1EA10
3RT10 34-1AP00 S0/S2
1,00 ... 4,00
50
1,5
2,9
4,50 ... 6,30
3RV10 21-1GA10
3RT10 34-1AP00 S0/S2
3RB21 23-4PB0/
3RB20 26-2PB0
1,00 ... 4,00
50
2,2
4
None
3RV13 21-1HC10
3RT10 34-1AP00 S0/S2
50
5,2
None
3RV13 21-1JC10
3RT10 34-1AP00 S0/S2
3RB20 26-2SB0/
3RB21 23-4SB0
3,00 ... 12,0
3
3,00 ... 12,0
50
4
6,8
None
3RV13 21-4AC10
3RT10 34-1AP00 S0/S2
6,00 ... 25,0
50
5,5
9,2
11,0 ... 16,0
3RV10 31-4AA10
3RT10 34-1AP00 S2/S2
3RB20 36-2QB0/
3RB21 23-4QB0
7,5
12,4
18,0 ... 25,0
3RV10 31-4DA10
3RT10 34-1AP00 S2/S2
11
17,6
22,0 ... 32,0
3RV10 31-4EA10
3RT10 35-1AP00 S2/S2
15
23
28,0 ... 40,0
3RV10 31-4FA10
3RT10 36-1AP00 S2/S2
18,5
28
36,0 ... 50,0
3RV10 41-4HA10
3RT10 44-1AP00 S3/S3
22
33
45,0 ... 63,0
3RV10 41-4JA10
22
33
45,0 ... 63,0
30
44
37
53
104
6,00 ... 25,0
50
6,00 ... 25,0
50
6,00 ... 25,0
50
12,5 ... 50,0
50
12,5 ... 50,0
50
3RT10 44-1AP00 S3/S3
3RB20 36-2UW1/ 12,5 ... 50,0
3RB21 33-4UW1
50
3RV10 41-4JA10
3RT10 44-1AP00 S3/S3
3RB20 46-2UB0/
3RB21 43-4UB0
12,5 ... 50,0
50
57,0 ... 75,0
3RV10 41-4KA10
3RT10 44-1AP00 S3/S3
25,0 ... 100
50
70,0 ... 90,0
3RV10 41-4LA10
3RT10 45-1AP00 S3/S3
3RB20 46-2EB0/
3RB21 43-4EB0
25,0 ... 100
50
3RB20 36-2UB0/
3RB21 33-4UW1
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.3 Motor starter protector / circuit breaker + contactor + 3RB20/3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stan Motor starter
dard curre protector /
outpu nt
circuit
t
(guide breaker2
P
value)
Motor starter
protector / circuit
breaker
Contactor3
kW
A
A
Order No.
Order No.
45
64
70,0 ... 90,0
3RV10 42-4LB10
45
64
70,0 ... 90,0
55
78
75
106
90
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
A
kA
3RT10 54-1AP36 S3/S6
25,0 ... 100
50
3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
50
None
3VL27 10-3DK33
3RT10 54-1AP36 –/S6
3RB20 56-2FW2/ 50,0 ... 200
3RB21 53-4FW2 50,0 ... 200
50
None
3VL27 16-3DK33
3RT10 55-1AP36 –/S6
50,0 ... 200
50
128
None
3VL27 16-3DK33
3RT10 56-6AP36 –/S6
3RB20 56-2FC2/
3RB21 53-4FC2
50,0 ... 200
50
110
156
None
3VL27 16-3DK33
3RT10 64-6AP36 –/S10
50
132
184
None
3VL37 25-3DK36
3RT10 65-6AP36 –/S10
3RB20 66-2GC2/ 55,0 ... 250
3RB21 63-4GC2 55,0 ... 250
132
184
None
3VL37 25-3DK36
3RT12 64-6AP36 –/S10V
55,0 ... 250
50
3RT12 65-6AP36 –/S10V
55,0 ... 250
50
3RB20 66-2MC2/ 160 ... 630
3RB21 63-4MC2 160 ... 630
50
Iq
I
160
224
None
3VL37
25-3DK364
Order No.
200
280
None
3VL47 31-3DK36
3RT10 75-6AP36 –/S12
200
280
None
3VL47 31-3DK36
3RT12 66-6AP36 –/S10V
50
50
250
344
None
3VL57 50-3DK36
3RT10 76-6AP36 –/S12
160 ... 630
50
250
344
None
3VL57 50-3DK36
3RT12 75-6AP36 –/S12V
160 ... 630
50
315
432
None
3VL57 50-3DK36
3RT12 76-6AP36 –/S12V
160 ... 630
50
355
488
None
3VL57 50-3DK36
3RT12 76-6AP36 –/S12V
160 ... 630
50
3VL77 12-2DE36
3TF69 44-0CM7
3RB20 66-2MC2/ 160 ... 630
3RB21 63-4MC2
50
Type of coordination 1
400
1
2
3
4
552
None
–/14
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL47 31-3DK36 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
105
Selection tables 500 V AC
6.4 Motor starter protector / circuit breaker + contactor + 3RB21 solid-state overload relay
6.4
Motor starter protector / circuit breaker + contactor + 3RB21 solid-state
overload relay
CLASS 30, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
outpu (guide circuit
t
value) breaker2
Motor starter
protector / circuit
breaker
P
I
kW
A
Order No.
A
Contactor3
Size
Overload relay
Order No.
Order No.
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
Iq
Type of coordination 2
0,06
0,2
0,45 ... 0,63 3RV10 11-0GA10
3RT10 15-1AP01
S00/S00 3RB21 13-4RB0
0,10 ... 0,40 50
0,09
0,2
0,55 ... 0,80 3RV10 11-0HA10
3RT10 15-1AP01
S00/S00
0,10 ... 0,40 50
0,12
0,3
0,70 ... 1,00 3RV10 11-0JA10
3RT10 15-1AP01
S00/S00 3RB21 13-4NB0
0,32 ... 1,25 50
0,18
0,5
0,90 ... 1,25 3RV10 11-0KA10
3RT10 15-1AP01
S00/S00
0,32 ... 1,25 50
0,25
0,7
1,10 ... 1,60 3RV10 11-1AA10
3RT10 15-1AP01
S00/S00
0,32 ... 1,25 50
0,37
0,9
1,40 ... 2,00 3RV10 11-1BA10
3RT10 15-1AP01
S00/S00
0,32 ... 1,25 50
0,55
1,2
2,20 ... 3,20 3RV10 21-1DA10
3RT10 34-1AP00
S0/S2
3RB21 23-4PB0/
3RB21 13-4PB0
1,00 ... 4,00 50
0,75
1,5
2,80 ... 4,00 3RV10 21-1EA10
3RT10 34-1AP00
S0/S2
1,1
2,2
3,50 ... 5,00 3RV10 21-1FA10
3RT10 34-1AP00
S0/S2
1,5
2,9
4,50 ... 6,30 3RV10 21-1GA10
3RT10 34-1AP00
S0/S2
3RB21 23-4PB0
1,00 ... 4,00 50
2,2
4
7,00 ... 10,0 3RV10 21-1JA10
3RT10 34-1AP00
S0/S2
3RB21 23-4SB0
3,00 ... 12,0 50
3
5,2
9,00, ... 12,
5
3RV10 21-1KA10
3RT10 34-1AP00
S0/S2
4
6,8
11,0 ... 16,0 3RV10 31-4AA10
3RT10 34-1AP00
S2/S2
5,5
9,2
14,0 ... 20,0 3RV10 31-4BA10
3RT10 34-1AP00
S2/S2
7,5
12,4
22,0 ... 32,0 3RV10 31-4EA10
3RT10 34-1AP00
S2/S2
11
17,6
28,0 ... 40,0 3RV10 31-4FA10
3RT10 35-1AP00
S2/S2
3RB21 36-2UB0/
3RB21 33-4UW1
12,5 ... 50,0 50
15
23
28,0 ... 40,0 3RV10 42-4FB10
3RT10 44-1AP00
S3/S3
3RB21 33-4UW1
12,5 ... 50,0 50
15
23
28,0 ... 40,0 3RV10 42-4FB10
3RT10 44-1AP00
S3/S3
3RB21 43-4UB0
12,5 ... 50,0 50
18,5
28
36,0 ... 50,0 3RV10 42-4HB10
3RT10 44-1AP00
S3/S3
3RB21 33-4UW1
12,5 ... 50,0 50
18,5
28
36,0 ... 50,0 3RV10 42-4HB10
3RT10 44-1AP00
S3/S3
3RB21 43-4UB0
12,5 ... 50,0 50
106
1,00 ... 4,00 50
1,00 ... 4,00 50
3,00 ... 12,0 50
3RB21 33-4QB0/
3RB21 23-4QB0
6,00 ... 25,0 50
6,00 ... 25,0 50
6,00 ... 25,0 50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.4 Motor starter protector / circuit breaker + contactor + 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
outpu (guide circuit
t
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
P
I
kW
A
A
Order No.
22
33
36,0 ... 50,0 3RV10 42-4HB10
3RT10 44-1AP00
22
33
36,0 ... 50,0 3RV10 42-4HB10
3RT10 44-1AP00
30
44
57,0 ... 75,0 3RV10 42-4KB10
Size
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
S3/S3
3RB21 33-4UW1
12,5 ... 50,0 50
S3/S3
3RB21 43-4UB0
12,5 ... 50,0 50
3RT10 45-1AP00
S3/S3
3RB21 43-4EB0
25,0 ... 100 50
3RB21 53-4FW2
50,0 ... 200 50
Order No.
Overload relay
Iq
37
53
70,0 ... 90,0 3RV10 42-4LB10
3RT10 54-1AP36
S3/S6
45
64
None
3VL27 10-3DK33
3RT10 54-1AP36
–/S6
55
78
None
3VL27 10-3DK33
3RT10 55-1AP36
–/S6
75
106
None
3VL27 16-3DK33
3RT10 56-6AP36
–/S6
3RB21 53-4FC2
50,0 ... 200 50
90
128
None
3VL27 16-3DK33
3RT10 64-6AP36
–/S10
3RB21 63-4GC2
55,0 ... 250 50
16-3DK334
50,0 ... 200 50
50,0 ... 200 50
110
156
None
3VL27
3RT10 65-6AP36
–/S10
55,0 ... 250 50
110
156
None
3VL27 16-3DK33
3RT12 64-6AP36
–/S10V
55,0 ... 250
50
132
184
None
3VL37 25-3DK36
3RT12 65-6AP36
–/S10V
55,0 ... 250
50
160
224
None
3VL37 25-3DK36
3RT10 75-6AP36
–/S12
55,0 ... 250 50
160
224
None
3VL37 25-3DK36
3RT12 66-6AP36
–/S10V
55,0 ... 250 50
200
280
None
3VL47 31-3DK36
3RT10 76-6AP36
–/S12
160 ... 630
50
200
280
None
3VL47 31-3DK36
3RT12 75-6AP36
–/S12V
160 ... 630
50
250
344
None
3VL57 50-3DK36
3RT12 76-6AP36
–/S12V
160 ... 630
50
3RB21 63-2MC2/ 160 ... 630
3RB21 63-4MC2 160 ... 630
50
3RB21 63-4MC2
Type of coordination 1
1
2
3
4
315
432
None
3VL57 50-2DK36
3TF69 44-0CM7
–/14
355
488
None
3VL57 50-2DK36
3TF69 44-0CM7
–/14
50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
Alternatively 3VL27 25-3DK33 also possible.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
107
Selection tables 500 V AC
6.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
6.5
Motor starter protector / circuit breaker + contactor + SIMOCODE pro
3UF7 / 3RB22/3RB23 solid-state overload relay
CLASS 5 and CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
Size
kW
Order No.
Order No.
3RT10 24-1AP00
S0/S0
SIMOCODE pro or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
Order No.
A
kA
3UF7 100-1AA00/
3RB29 06-2BG1
0,30 ... 3,00 50
Iq
I
A
A
Type of coordination 2
0,12
0,3
None
3RV13 21-0HC10
0,18
0,5
None
3RV13 21-0HC10
3RT10 24-1AP00
S0/S0
0,25
0,7
None
3RV13 21-0JC10
3RT10 24-1AP00
S0/S0
0,30 ... 3,00 50
0,37
0,9
None
3RV13 21-0KC10
3RT10 24-1AP00
S0/S0
0,30 ... 3,00 50
0,55
1,2
None
3RV13 21-0KC10
3RT10 24-1AP00
S0/S0
0,30 ... 3,00 50
0,75
1,5
None
3RV13 21-1BC10
3RT10 24-1AP00
S0/S0
0,30 ... 3,00 50
0,30 ... 3,00 50
1,1
2,2
None
3RV13 21-1CC10
3RT10 26-1AP00
S0/S0
0,30 ... 3,00 50
1,5
2,9
None
3RV13 21-1DC10
3RT10 34-1AP00
S0/S2
0,30 ... 3,00 50
2,2
4
None
3RV13 21-1EC10
3RT10 34-1AP00
S0/S2
3UF7 101-1AA00/
3RB29 06-2DG1
2,40 ... 25,0 50
3
5,2
None
3RV13 21-1GC10
3RT10 34-1AP00
S0/S2
4
6,8
None
3RV13 21-1HC10
3RT10 34-1AP00
S0/S2
2,40 ... 25,0 50
2,40 ... 25,0 50
5,5
9,2
None
3RV13 21-1JC10
3RT10 34-1AP00
S0/S2
2,40 ... 25,0 50
7,5
12,4
None
3RV13 21-1KC10
3RT10 34-1AP00
S0/S2
2,40 ... 25,0 50
7,5
12,4
None
3RV13 31-4AC10
3RT10 34-1AP00
S2/S2
2,40 ... 25,0 50
11
17,6
None
3RV13 31-4BC10
3RT10 34-1AP00
S2/S2
15
23
None
3RV13 31-4EC10
3RT10 34-1AP00
S2/S2
18,5
28
None
3RV13 31-4FC10
3RT10 35-1AP00
S2/S2
2,40 ... 25,0 50
3UF7 102-1AA00/
3RB29 06-2JG1
10,0 ... 100 50
10,0 ... 100 50
22
33
40,0 ... 50,0 3RV10 31-4HA10
3RT10 36-1AP00
S2/S2
10,0 ... 100 50
22
33
None
3RV13 41-4FC10
3RT10 44-1AP00
S3/S3
10,0 ... 100 50
30
44
None
3RV13 41-4HC10
3RT10 44-1AP00
S3/S3
10,0 ... 100 50
37
53
None
3RV13 41-4JC10
3RT10 44-1AP00
S3/S3
10,0 ... 100 50
108
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor starter
protector / circuit
breaker
Contactor3
kW
Order No.
Order No.
Size
SIMOCODE pro or
overload relay
(current measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
A
kA
Iq
I
A
A
Order No.
45
64
None
3RV13 41-4KC10
3RT10 44-1AP00
S3/S3
10,0 ... 100 50
55
78
None
3RV13 41-4LC10
3RT10 45-1AP00
S3/S3
10,0 ... 100 50
55
78
None
3VL27 10-3DK33
3RT10 54-1AP36
–/S6
75
106
None
3VL27 16-3DK33
3RT10 54-1AP36
–/S6
90
128
None
3VL27 16-3DK33
3RT10 55-6AP36
–/S6
20,0 ... 200 50
3UF7 103-1AA00/
3RB29 56-2TG2
20,0 ... 200 50
20,0 ... 200 50
110
156
None
3VL27 16-3DK33
3RT10 56-6AP36
–/S6
20,0 ... 200 50
110
156
None
3VL27 25-3DK33
3RT10 56-6AP36
–/S6
20,0 ... 200 50
132
184
None
3VL37 25-3DK36
3RT10 64-6AP36
–/S10
132
184
None
3VL37 25-3DK36
3RT12 64-6AP36
–/S10V
160
224
None
3VL37 25-3DK36
3RT10 65-6AP36
–/S10
63,0 ... 630 50
160
224
None
3VL37 25-3DK36
3RT12 65-6AP36
–/S10V
63,0 ... 630
200
280
None
3VL47 31-3DK36
3RT10 66-6AP36
–/S10
63,0 ... 630 50
200
280
None
3VL47 31-3DK36
3RT12 66-6AP36
–/S10V
63,0 ... 630
250
344
None
3VL57 50-3DK36
3RT10 75-6AP36
–/S12
63,0 ... 630 50
250
344
None
3VL57 50-3DK36
3RT12 75-6AP36
–/S12V
63,0 ... 630
315
432
None
3VL57 50-3DK36
3RT10 76-6AP36
–/S12
63,0 ... 630 50
315
432
None
3VL57 50-3DK36
3RT12 76-6AP36
–/S12V
63,0 ... 630
355
488
None
3VL57 50-3DK36
3RT10 76-6AP36
–/S12
63,0 ... 630 50
355
488
None
3VL57 50-3DK36
3RT12 76-6AP36
–/S12V
63,0 ... 630 50
3VL77 12-2DE36
3TF68 44-0CM7
–/14
3UF7 104-1AA00/
3RB29 66-2WH2
3UF1 868-3GA00 + 205 ... 820
3UF7 100-1AA0/
205 ... 820
3UF1 868-3GA00 +
3RB29 06-2BG1
3UF7 104-1AA00/
3RB29 66-2WH2
63,0 ... 630 50
63,0 ... 630
50
50
50
50
50
Type of coordination 1
400
1
2
3
4
552
None
500
680
None
3VL87 16-2DE30
3TF69 44-0CM7
–/14
560
760
None
3VL87 16-2DE30
3TF69 44-0CM7
–/14
63,0 ... 630 50
50
50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
109
Selection tables 500 V AC
6.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
CLASS 20, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
kW
Order No.
Size
SIMOCODE pro
or overload relay
(current
measuring
module)4
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
Iq
I
A
A
Order No.
Order No.
A
kA
3UF7 100-1AA0/
3RB29 06-2BG1
0,30 ... 3,00
50
Type of coordination 2
0,12
0,3
None
3RV13 21-0HC10 3RT10 24-1AP00
S0/S0
0,18
0,5
None
3RV13 21-0JC10 3RT10 24-1AP00
S0/S0
0,30 ... 3,00
50
0,25
0,7
None
3RV13 21-0KC10 3RT10 24-1AP00
S0/S0
0,30 ... 3,00
50
0,37
0,9
None
3RV13 21-1AC10 3RT10 24-1AP00
S0/S0
0,30 ... 3,00
50
0,55
1,2
None
3RV13 21-1BC10 3RT10 24-1AP00
S0/S0
0,30 ... 3,00
50
0,75
1,5
None
3RV13 21-1DC10 3RT10 26-1AP00
S0/S0
0,30 ... 3,00
50
1,1
2,2
2,80 ... 4,00
3RV10 21-1EA10 3RT10 34-1AP00
S0/S2
1,5
2,9
None
3RV13 21-1EC10 3RT10 34-1AP00
S0/S2
0,30 ... 3,00
50
2,40 ... 25,0
50
1,5
2,9
4,50 ... 6,30
3RV10 21-1GA10 3RT10 34-1AP00
S0/S2
2,40 ... 25,0
50
2,2
4
None
3RV13 21-1GC10 3RT10 34-1AP00
3
5,2
None
3RV13 21-1HC10 3RT10 34-1AP00
S0/S2
2,40 ... 25,0
50
S0/S2
2,40 ... 25,0
50
4
6,8
None
3RV13 21-1JC10 3RT10 34-1AP00
S0/S2
2,40 ... 25,0
50
5,5
9,2
7,5
12,4
11,0 ... 16,0
3RV10 31-4AA10 3RT10 34-1AP00
S2/S2
2,40 ... 25,0
50
18,0 ... 25,0
3RV10 31-4DA10 3RT10 34-1AP00
S2/S2
2,40 ... 25,0
50
11
15
17,6
22,0 ... 32,0
3RV10 31-4EA10 3RT10 35-1AP00
S2/S2
23
28,0 ... 40,0
3RV10 31-4FA10 3RT10 36-1AP00
S2/S2
18,5
28
36,0 ... 50,0
3RV10 41-4HA10 3RT10 44-1AP00
S3/S3
3UF7 101-1AA0/
3RB29 06-2DG1
3UF7 102-1AA0/
3RB29 06-2JG1
2,40 ... 25,0
50
10,0 ... 100
50
10,0 ... 100
50
22
33
45,0 ... 63,0
3RV10 41-4JA10
3RT10 44-1AP00
S3/S3
10,0 ... 100
50
30
44
57,0 ... 75,0
3RV10 41-4KA10 3RT10 44-1AP00
S3/S3
10,0 ... 100
50
37
53
70,0 ... 90,0
3RV10 41-4LA10 3RT10 45-1AP00
S3/S3
10,0 ... 100
50
45
64
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36
S3/S6
10,0 ... 100
50
45
64
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36
S3/S6
20,0 ... 200
50
55
78
None
3VL27 10-3DK33 3RT10 54-1AP36
–/S6
20,0 ... 200
50
75
106
None
3VL27 16-3DK33 3RT10 55-1AP36
–/S6
20,0 ... 200
50
110
3UF7 103-1AA0/
3RB29 56-2TG2
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
Size
SIMOCODE pro
or overload relay
(current
measuring
module)4
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
kW
A
A
Order No.
Order No.
90
128
None
3VL27 16-3DK33 3RT10 56-6AP36
–/S6
110
156
None
3VL27 16-3DK33 3RT10 64-6AP36
–/S10
132
184
None
3VL37 25-3DK36 3RT10 65-6AP36
–/S10
132
184
None
3VL37 25-3DK36 3RT12 64-6AP36
160
224
None
3VL37 25-3DK36 3RT12 65-6AP36
160
224
None
3VL47 31-3DK36 3RT12 65-6AP36
–/S10V
63,0 ... 630
50
200
280
None
3VL47 31-3DK36 3RT10 75-6AP36
–/S12
63,0 ... 630
50
200
280
None
3VL47 31-3DK36 3RT12 66-6AP36
–/S10V
63,0 ... 630
50
250
344
None
3VL57 50-3DK36 3RT10 76-6AP36
–/S12
63,0 ... 630
50
250
344
None
3VL57 50-3DK36 3RT12 75-6AP36
–/S12V
63,0 ... 630
50
315
432
None
3VL57 50-3DK36 3RT12 76-6AP36
–/S12V
63,0 ... 630
50
355
488
None
3VL57 50-3DK36 3RT12 76-6AP36
–/S12V
63,0 ... 630
50
3VL77 12-2DE36 3TF69 44-0CM7
–/S14
63,0 ... 630
50
Iq
I
Order No.
A
kA
20,0 ... 200
50
63,0 ... 630
50
63,0 ... 630
50
–/S10V
63,0 ... 630
50
–/S10V
63,0 ... 630
50
3UF7 104-1AA0/
3RB29 66-2WH2
Type of coordination 1
400
1
2
3
4
552
None
3UF7 104-1AA0/
3RB29 66-2WH2
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
111
Selection tables 500 V AC
6.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
CLASS 30, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
Size
SIMOCODE pro
or overload relay
(current
measuring
module)4
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Order No.
Order No.
0,12
0,3
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,18
0,5
None
3RV13 21-1AC10 3RT10 24-1AP00 S0/S0
0,18
0,5
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00
50
0,25
0,7
1,40 ... 2,00
3RV10 21-1BA10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00
50
0,25
0,7
None
3RV13 21-1BC10 3RT10 24-1AP00 S0/S0
0,30 ... 3,00
50
0,37
0,9
1,80 ... 2,50
3RV10 21-1CA10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00
50
0,37
0,9
None
3RV13 21-1CC10 3RT10 26-1AP00 S0/S0
0,30 ... 3,00
50
0,55
1,2
2,20 ... 3,20
3RV10 21-1DA10 3RT10 34-1AP00 S0/S2
0,30 ... 3,00
50
0,75
1,5
2,80 ... 4,00
3RV10 21-1EA10 3RT10 34-1AP00 S0/S2
0,30 ... 3,00
50
0,75
1,5
4,00 ... 5,00
3RV10 21-1FA10
3RT10 34-1AP00 S0/S2
0,30 ... 3,00
50
1,1
2,2
4,00 ... 5,00
3RV10 21-1FA10
3RT10 34-1AP00 S0/S2
0,30 ... 3,00
50
1,1
2,2
5,00 ... 6,30
3RV10 21-1GA10 3RT10 34-1AP00 S0/S2
0,30 ... 3,00
50
1,5
2,9
5,00 ... 6,30
3RV10 21-1GA10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0
50
1,5
2,9
6,00 ... 8,00
3RV10 21-1HA10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0
50
2,2
4
7,00 ... 10,0
3RV10 21-1JA10
3RT10 34-1AP00 S0/S2
2,40 ... 25,0
50
2,2
4
9,00 ... 13,0
3RV10 21-1KA10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0
50
3
5,2
9,00 ... 13,0
3RV10 21-1KA10 3RT10 34-1AP00 S0/S2
2,40 ... 25,0
50
3
5,2
11,0 ... 16,0
3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0
50
4
6,8
11,0 ... 16,0
3RV10 31-4AA10 3RT10 34-1AP00 S2/S2
2,40 ... 25,0
50
4
6,8
14,0 ... 20,0
3RV10 31-4BA10 3RT10 34-1AP00 S2/S2
2,00 ... 25,0
50
5,5
9,2
14,0 ... 20,0
3RV10 31-4BA10 3RT10 34-1AP00 S2/S2
2,00 ... 25,0
50
5,5
9,2
18,0 ... 25,0
3RV10 31-4DA10 3RT10 34-1AP00 S2/S2
2,00 ... 25,0
50
7,5
12,4
22,0 ... 32,0
3RV10 31-4EA10 3RT10 34-1AP00 S2/S2
2,00 ... 25,0
50
11
17,6
28,0 ... 40,0
3RV10 31-4FA10
3RT10 35-1AP00 S2/S2
2,00 ... 25,0
50
15
23
28,0 ... 40,0
3RV10 42-4FB10
3RT10 44-1AP00 S3/S3
10,0 ... 100
50
Iq
I
112
Order No.
A
kA
3UF7 100-1AA0/
3RB29 06-2BG1
0,30 ... 3,00
50
0,30 ... 3,00
50
3UF7 101-1AA0/
3RB29 06-2DG1
3UF7 102-1AA0/
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
kW
Order No.
Size
SIMOCODE pro
or overload relay
(current
measuring
module)4
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Iq
I
1
2
3
4
A
A
Order No.
Order No.
3RB29 06-2JG1
A
kA
15
22
36,0 ... 50,0
3RV10 42-4HB10 3RT10 44-1AP00 S3/S3
10,0 ... 100
50
18,5
28
36,0 ... 50,0
3RV10 42-4HB10 3RT10 44-1AP00 S3/S3
10,0 ... 100
50
18,5
28
45,0 ... 63,0
3RV10 42-4JB10
3RT10 45-1AP00 S3/S3
10,0 ... 100
50
22
33
36,0 ... 50,0
3RV10 42-4HB10 3RT10 44-1AP00 S3/S3
10,0 ... 100
50
22
33
57,0 ... 75,0
3RV10 42-4KB10 3RT10 45-1AP00 S3/S3
10,0 ... 100
50
30
44
57,0 ... 75,0
3RV10 42-4KB10 3RT10 45-1AP00 S3/S3
10,0 ... 100
50
30
44
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
10,0 ... 100
50
30
44
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
3UF7 103-1AA0/
3RB29 56-2TG2
20,0 ... 200
50
37
53
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
3UF7 102-1AA0/
3RB29 06-2JG1
10,0 ... 100
50
3UF7 103-1AA0/
3RB29 56-2TG2
37
53
70,0 ... 90,0
3RV10 42-4LB10
3RT10 54-1AP36 S3/S6
45
64
None
3VL27 10-3DK33
3RT10 54-1AP36 –/S6
20,0 ... 200
50
20,0 ... 200
50
55
78
None
3VL27 10-3DK33
3RT10 55-1AP36 –/S6
20,0 ... 200
50
75
106
None
3VL27 16-3DK33
3RT10 56-6AP36 –/S6
20,0 ... 200
50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
113
Selection tables 500 V AC
6.5 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state
overload relay
CLASS 30, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Stand
ard
outpu
t
Motor
current
(guide
value)
kW
A
P
Setting
range
Overload
release
Circuit
breaker
Circuit breaker
Contactor2
A
Order No.
Order No.
Size
SIMOCODE pro
or overload relay
(current
measuring
module)3
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3UF7 104-1BA0/
3RB29 66-2WH2
63,0 ... 630
50
Iq
I
Type of coordination 2
75
106
None
3VL27 16-3DK33
3RT10 64-6AP36
–/S10
90
128
None
3VL27 16-3DK33
3RT10 64-6AP36
–/S10
63,0 ... 630
50
90
128
None
3VL37 25-3DK36
3RT12 65-6AP36
–/S10V
63,0 ... 630
50
3RT10 65-6AP36
–/S10
63,0 ... 630
50
110
156
None
3VL27
16-3DK334)
16-3DK334)
110
156
None
3VL27
3RT12 64-6AP36
–/S10V
63,0 ... 630
50
132
184
None
3VL47 31-3DK36
3RT10 76-6AP36
–/S12
63,0 ... 630
50
132
184
None
3VL37 25-3DK36
3RT12 65-6AP36
–/S10V
63,0 ... 630
50
160
224
None
3VL37 25-3DK36
3RT10 75-6AP36
–/S12
63,0 ... 630
50
160
224
None
3VL37 25-3DK36
3RT12 66-6AP36
–/S10V
63,0 ... 630
50
200
280
None
3VL47 31-3DK36
3RT10 76-6AP36
–/S12
63,0 ... 630
50
200
280
None
3VL47 31-3DK36
3RT12 75-6AP36
–/S12V
63,0 ... 630
50
250
344
None
3VL57 50-3DK36
3RT12 76-6AP36
–/S12V
63,0 ... 630
50
63,0 ... 630
50
63,0 ... 630
50
Type of coordination 1
1
2
3
4
315
432
None
3VL57 50-2DK36
3TF69 44-0CM7
–/14
355
488
None
3VL57 50-2DK36
3TF69 44-0CM7
–/14
3UF7 104-1BA0/
3RB29 66-2WH2
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
Alternatively 3VL37 25-3DK36 also possible.
114
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.6 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7
6.6
Motor starter protector / circuit breaker + contactor + SIMOCODE pro
3UF7
CLASS 40, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
kW
Order No.
Size
SIMOCODE pro Setting range
(current
Overload
measuring
release
module)4
Overload
relay
Shortcircuit
breaking
capacity
Order No.
kA
Iq
I
A
A
Order No.
A
Type of coordination 2
0,12
0,3
None
3RV13 21-1AC10 3RT10 24-1AP00
S0/S0
3UF7 100-1AA0 0,30 ... 3,00
50
0,18
0,5
None
3RV13 21-1BC10 3RT10 24-1AP00
S0/S0
0,30 ... 3,00
50
0,25
0,7
1,40 ... 2,00
3RV10 21-1BA10 3RT10 24-1AP00
S0/S0
0,30 ... 3,00
50
0,37
0,9
1,80 ... 2,50
3RV10 21-1CA10 3RT10 26-1AP00
S0/S0
0,30 ... 3,00
50
0,55
1,2
2,20 ... 3,20
3RV10 21-1DA10 3RT10 34-1AP00
S0/S2
0,30 ... 3,00
50
0,75
1,5
3,50 ... 5,00
3RV10 21-1FA10 3RT10 34-1AP00
S0/S2
0,30 ... 3,00
50
1,1
2,2
4,50 ... 6,30
3RV10 21-1GA10 3RT10 34-1AP00
S0/S2
0,30 ... 3,00
50
1,5
2,9
5,50 ... 8,00
3RV10 21-1HA10 3RT10 34-1AP00
S0/S2
3UF7 101-1AA0 2,40 ... 25,0
50
2,2
4
9,00 ... 12,5
3RV10 21-1KA10 3RT10 34-1AP00
S0/S2
2,40 ... 25,0
50
3
5,2
11,0 ... 16,0
3RV10 31-4AA10 3RT10 34-1AP00
S2/S2
2,40 ... 25,0
50
4
6,8
14,0 ... 20,0
3RV10 31-4BA10 3RT10 34-1AP00
S2/S2
2,40 ... 25,0
50
5,5
9,2
18,0 ... 25,0
3RV10 31-4DA10 3RT10 34-1AP00
S2/S2
2,40 ... 25,0
50
7,5
12,4
22,0 ... 32,0
3RV10 31-4EA10 3RT10 34-1AP00
S2/S2
2,40 ... 25,0
50
11
17,6
22,0 ... 32,0
3RV10 31-4EB10 3RT10 44-1AP00
S2/S3
3UF7 102-1AA0 10,0 ... 100
50
15
22
36,0 ... 50,0
3RV10 42-4HB10 3RT10 44-1AP00
S3/S3
10,0 ... 100
50
18,5
28
45,0 ... 63,0
3RV10 42-4JB10
3RT10 45-1AP00
S3/S3
10,0 ... 100
50
22
33
57,0 ... 75,0
3RV10 42-4KB10 3RT10 45-1AP00
S3/S3
10,0 ... 100
50
30
44
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36
S3/S6
10,0 ... 100
50
30
44
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36
S3/S6
3UF7 103-1AA0 20,0 ... 200
50
37
53
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36
S3/S6
3UF7 102-1AA0 10,0 ... 100
50
3UF7 103-1AA0 20,0 ... 200
50
20,0 ... 200
50
37
53
70,0 ... 90,0
3RV10 42-4LB10 3RT10 54-1AP36
S3/S6
45
64
None
3VL27 10-3DK33 3RT10 55-1AP36
–/S6
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
115
Selection tables 500 V AC
6.6 Motor starter protector / circuit breaker + contactor + SIMOCODE pro 3UF7
Standard
three-phase
motor
4-pole at
500 V AC1
Setting range Motor starter
protector / circuit
Overload
breaker
release
Motor starter
protector /
Stand Motor circuit
ard
current breaker2
output (guide
P
value)
Contactor3
Size
kW
A
A
Order No.
Order No.
55
78
None
3VL27 16-3DK33 3RT10 56-6AP36
–/S6
75
106
None
3VL27 16-3DK33 3RT10 64-6AP36
–/S10
90
128
None
3VL37 25-3DK33 3RT12 65-6AP36
110
156
None
132
184
None
SIMOCODE pro Setting range
(current
Overload
measuring
release
module)4
Overload
relay
Shortcircuit
breaking
capacity
Order No.
kA
Iq
I
A
20,0 ... 200
50
3UF7 104-1AA0 63,0 ... 630
50
–/S10V
63,0 ... 630
50
3VL37 25-3DK33 3RT12 65-6AP36
–/S10V
63,0 ... 630
50
3VL47 31-3DK36 3RT10 76-6AP36
–/S12
63,0 ... 630
50
160
224
None
3VL47 31-3DK36 3RT10 76-6AP36
–/S12
63,0 ... 630
50
200
280
None
3VL57 50-3DK36 3RT12 76-6AP36
–/S12V
63,0 ... 630
50
3VL67 80-2DE36 3TF69 44-0CM7
–/14
3UF7 104-1AA0 63,0 ... 630
50
Type of coordination 1
250
1
2
3
4
344
None
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 are specified. See page 9 for details of the 3UF7 basic units which
are also required.
116
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.7 Motor starter protector + star(wye)-delta starting + 3RU11 thermal overload relay
6.7
Motor starter protector + star(wye)-delta starting + 3RU11 thermal
overload relay
CLASS 5 and CLASS 10, types of coordination 2 and 1,
short-circuit breaking capacity Iq = 50 kA
M
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stan Motor starter
dard current protector
outpu (guide
t
value)
Motor starter Contactors2
protector
P
I
kW
A
A
Size
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
Overload
relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
Iq
Type of coordination 2
7,5
12,4
None
3RV13 314AC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
3RU11 361JB0
7,00 ... 10,0
50
11
17,6
None
3RV13 314BC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
3RU11 361KB0
9,00 ... 12,5
50
15
22
None
3RV13 314DC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
3RU11 364AB0
11,0 ... 16,0
50
18,5
29
None
3RV13 314EC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
3RU11 364BB0
14,0 ... 20,0
50
22
34
None
3RV13 314FC10
3RT10 351AP00
3RT10 241AP00
S2/S2/S0
3RU11 364DB0
18,0 ... 25,0
50
30
46
None
3RV13 314HC10
3RT10 361AP00
3RT10 261AP00
S2/S2/S0
3RU11 364EB0
22,0 ... 32,0
50
37
53
None
3RV13 414JC10
3RT10 441AP00
3RT10 341AP00
S3/S3/S2
3RU11 464FB0
28,0 ... 40,0
50
45
65
None
3RV13 414KC10
3RT10 441AP00
3RT10 341AP00
S3/S3/S2
3RU11 464HB0
36,0 ... 50,0
50
55
79
None
3RV13 414LC10
3RT10 451AP00
3RT10 341AP00
S3/S3/S2
36,0 ... 50,0
50
Type of coordination 1
7,5
12,4
None
3RV13 214AC10
3RT10 171AP01
3RT10 151AP01
S0/S0/S0
0
3RU11 161JB0
7,00 ... 10,0
50
11
17,6
None
3RV13 214BC10
3RT10 241AP00
3RT10 241AP00
S0/S0/S0
3RU11 261KB0
9,00 ... 12,5
50
15
22
None
3RV13 214DC10
3RT10 241AP00
3RT10 241AP00
S0/S0/S0
3RU11 264AB0
11,0 ... 16,0
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
117
Selection tables 500 V AC
6.7 Motor starter protector + star(wye)-delta starting + 3RU11 thermal overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
1
2
Setting
range
Overload
release
Motor
Stan Motor starter
dard current protector
outpu (guide
t
value)
Motor starter Contactors2
protector
P
I
kW
A
A
18,5
29
22
Size
Overload
relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
Iq
Line
contactor +
delta
contactor
Star
contactor
Order No.
Order No.
Order No.
None
3RV13 314EC10
3RT10 261AP00
3RT10 241AP00
S2/S0/S0
3RU11 264BB0
14,0 ... 20,0
50
34
None
3RV13 314FC10
3RT10 341AP00
3RT10 241AP00
S2/S2/S0
3RU11 364DB0
18,0 ... 25,0
50
30
46
None
3RV13 314HC10
3RT10 341AP00
3RT10 261AP00
S2/S2/S0
3RU11 364EB0
22,0 ... 32,0
50
37
53
None
3RV13 414JC10
3RT10 341AP00
3RT10 341AP00
S3/S2/S2
3RU11 364FB0
28,0 ... 40,0
50
45
65
None
3RV13 414KC10
3RT10 351AP00
3RT10 341AP00
S3/S2/S2
3RU11 364GB0
36,0 ... 45,0
50
55
79
None
3RV13 414LC10
3RT10 361AP00
3RT10 341AP00
S3/S2/S2
3RU11 364HB0
40,0 ... 50,0
50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
118
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.8 Motor starter protector / circuit breaker + star(wye)-delta starting + 3RB20/3RB21 solid-state overload relay
6.8
Motor starter protector / circuit breaker + star(wye)-delta starting +
3RB20/3RB21 solid-state overload relay
CLASS 5 and CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
M
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor
Contactors3
starter
protector /
circuit
breaker
kW
A
A
Order No. Order No.
Order No.
7,5
12,4
None
3RV13 31 3RT10 34-4AC10
1AP00
3RT10 241AP00
S2/S2/S0
3RB20 36-1QB0/ 6,00 ... 25,0 50
3RB21 23-4QB0
11
17,6
None
3RV13 31 3RT10 34-4BC10
1AP00
3RT10 241AP00
S2/S2/S0
50
15
22
None
3RV13 31 3RT10 34-4EC10
1AP00
3RT10 241AP00
S2/S2/S0
3RB20 36-1UB0/ 12,5 ... 50,0 50
3RB21 33-4UW1
18,5
28
28,0 ... 40,0 3RV10 31 3RT10 35-4FA10
1AP00
3RT10 241AP00
S2/S2/S0
50
22
33
40,0 ... 50,0 3RV10 31 3RT10 36-4HA10
1AP00
3RT10 241AP00
S2/S2/S0
50
30
44
None
3RV13 41 3RT10 44-4HC10
1AP00
3RT10 341AP00
S3/S3/S2
37
53
None
3RV13 41 3RT10 44-4JC10
1AP00
3RT10 341AP00
S3/S3/S2
50
45
64
57,0 ... 75,0 3RV10 41 3RT10 44-4KA10
1AP00
3RT10 341AP00
S3/S3/S2
50
55
78
70,0 ... 90,0 3RV10 41 3RT10 45-4LA10
1AP00
3RT10 341AP00
S3/S3/S2
50
75
106
None
3VL27 16- 3RT10 543DK33
1AP36
3RT10 441AP00
-/S6/S3
3RB20 56-1FW2/ 50,0 ... 200
3RB21 53-4FW2
50
90
128
None
3VL27 16- 3RT10 553DK33
1AP36
3RT10 441AP00
-/S6/S3
3RB20 56-1FC2/
3RB21 53-4FC2
50,0 ... 200
50
110
156
None
3VL27 16- 3RT10 563DK33
6AP36
3RT10 441AP00
-/S6/S3
50
110
156
None
3VL37 25- 3RT10 563DK36
6AP36
3RT10 441AP00
-/S6/S3
50
I
Line
contactor +
delta
contactor
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Size
Overload relay
Star
contactor
Order No.
3RB20 46-1EB0/
3RB21 43-4EB0
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
25,0 ... 100
Iq
50
119
Selection tables 500 V AC
6.8 Motor starter protector / circuit breaker + star(wye)-delta starting + 3RB20/3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
output (guide circuit
P
value) breaker2
Motor
Contactors3
starter
protector /
circuit
breaker
kW
A
A
Order No. Order No.
Order No.
132
184
None
3VL37 25- 3RT10 643DK36
6AP36
3RT10 541AP36
-/S10/S6
160
224
None
3VL37 25- 3RT10 653DK36
6AP36
3RT10 541AP36
-/S10/S6
50
160
224
None
3VL47 31- 3RT10 653DK36
6AP36
3RT10 541AP36
-/S10/S6
50
200
280
None
3VL47 31- 3RT10 663DK36
6AP36
3RT10 541AP36
-/S10/S6
250
344
None
3VL57 50- 3RT10 753DK36
6AP36
3RT10 646AP36
-/S12/S10
50
315
432
None
3VL57 50- 3RT10 753DK36
6AP36
3RT10 646AP36
-/S12/S10
50
355
488
None
3VL57 50- 3RT10 753DK36
6AP36
3RT10 646AP36
-/S12/S10
50
I
1
2
3
Line
contactor +
delta
contactor
Size
Overload relay
Star
contactor
Order No.
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
A
kA
3RB20 66-1GC2/ 55,0 ... 250
3RB21 63-4GC2
3RB20 66-1MC2/ 160 ... 630
3RB21 63-4MC2
Iq
50
50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
120
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 500 V AC
6.9 Motor starter protector / circuit breaker + star(wye)-delta starting + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state o
6.9
Motor starter protector / circuit breaker + star(wye)-delta starting +
SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
CLASS 5 and CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
M
$&9
Standard
three-phase
motor
4-pole at
500 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
outpu (guide circuit
t
value) breaker2
Motor
Contactors3
starter
protector /
circuit
breaker
P
I
kW
A
A
Order No. Order No.
Order No.
7,5
12,4
None
3RV13 31 3RT10 34-4AC10
1AP00
3RT10 241AP00
S2/S2/S0
11
17,6
None
3RV13 31 3RT10 34-4BC10
1AP00
3RT10 241AP00
S2/S2/S0
15
23
None
3RV13 31 3RT10 34-4EC10
1AP00
3RT10 241AP00
S2/S2/S0
18,5
28
None
3RV13 31 3RT10 35-4FC10
1AP00
3RT10 241AP00
S2/S2/S0
50
22
33
40,0 ... 50,0 3RV10 31 3RT10 36-4HA10
1AP00
3RT10 241AP00
S2/S2/S0
50
30
44
None
3RV13 41 3RT10 44-4HC10
1AP00
3RT10 341AP00
S3/S3/S2
50
37
53
None
3RV13 41 3RT10 44-4JC10
1AP00
3RT10 341AP00
S3/S3/S2
50
45
64
None
3RV13 41 3RT10 44-4KC10
1AP00
3RT10 341AP00
S3/S3/S2
50
55
78
70,0 ... 90,0 3RV10 41 3RT10 45-4LA10
1AP00
3RT10 341AP00
S3/S3/S2
50
Line
contactor +
delta
contactor
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Size
Overload relay or
SIMOCODE pro
(current
measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
3UF7 101-1AA0/
3RB29 06-2DG1
2,40 ... 25,0 50
Star
contactor
Iq
50
3UF7 102-1AA0/
3RB29 06-2JG1
10,0 ... 100 50
121
Selection tables 500 V AC
6.9 Motor starter protector / circuit breaker + star(wye)-delta starting + SIMOCODE pro 3UF7 / 3RB22/3RB23
solid-state overload relay
Standard
three-phase
motor
4-pole at
500 V AC1
1
2
3
4
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector /
outpu (guide circuit
t
value) breaker2
Motor
Contactors3
starter
protector /
circuit
breaker
P
I
kW
A
Order No. Order No.
A
Line
contactor +
delta
contactor
Size
Overload relay or
SIMOCODE pro
(current
measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
Order No.
A
kA
3UF7 103-1AA0/
3RB29 56-2TG2
20,0 ... 200 50
Star
contactor
Iq
75
106
None
3VL27 16- 3RT10 543DK33
1AP36
3RT10 441AP00
-/S6/S3
90
128
None
3VL27 16- 3RT10 553DK33
1AP36
3RT10 441AP00
-/S6/S3
50
110
156
None
3VL27 16- 3RT10 563DK33
6AP36
3RT10 441AP00
-/S6/S3
50
110
156
None
3VL27 25- 3RT10 563DK33
6AP36
3RT10 441AP00
-/S6/S3
50
132
184
None
3VL37 25- 3RT10 643DK36
6AP36
3RT10 541AP36
-/S10/S6
160
224
None
3VL37 25- 3RT10 653DK36
6AP36
3RT10 541AP36
-/S10/S6
50
160
224
None
3VL37 31- 3RT10 653DK36
6AP36
3RT10 541AP36
-/S10/S6
50
200
280
None
3VL47 31- 3RT10 663DK36
6AP36
3RT10 541AP36
-/S10/S6
50
250
344
None
3VL57 50- 3RT10 753DK36
6AP36
3RT10 646AP36
-/S12/S10
50
315
432
None
3VL57 50- 3RT10 753DK36
6AP36
3RT10 646AP36
-/S12/S10
50
355
488
None
3VL57 50- 3RT10 753DK36
6AP36
3RT10 646AP36
-/S12/S10
50
3UF7 104-1BA0/
3RB29 66-2WH2
63,0 ... 630 50
Guide value for 4-pole standard motors at 500 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
122
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
7
Selection tables 550 V AC
7.1
Motor starter protector + contactor + 3RB20/3RB21 solid-state
overload relay
CLASS 5 and CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard threephase motor
4-pole at
550 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
Overload relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
A
Iq
I
kW
A
Order No.
Order No.
0,37
0,8
None
3RV13 53-6AP10
3RT10 24-1AP00
-/S0
3RB21 13-4NB0/
3RB21 13-4NB0
0,32 ... 1,25
50
0,55
1,1
None
3RV13 53-6BP10
3RT10 24-1AP00
-/S0
1,00 ... 4,00
50
0,75
1,4
None
3RV13 53-6BP10
3RT10 26-1AP00
-/S0
3RB20 16-1PB0/
3RB21 13-4PB0
1,00 ... 4,00
50
1,10
2,0
None
3RV13 53-6CP10
3RT10 26-1AP00
-/S0
1,00 ... 4,00
50
1,50
2,6
None
3RV13 53-6DP10
3RT10 26-1AP00
-/S0
1,00 ... 4,00
50
2,20
3,6
None
3RV13 53-6EP10
3RT10 34-1AP00
-/S2
1,00 ... 4,00
50
3,00
4,7
None
3RV13 53-6FP10
3RT10 34-1AP00
-/S2
3,00 ... 12,0
50
4,00
6,2
None
3RV13 53-6GP10
3RT10 34-1AP00
-/S2
3,00 ... 12,0
50
5,50
8,4
None
3RV13 53-6HP10
3RT10 34-1AP00
-/S2
3,00 ... 12,0
50
7,50
11,3
None
3RV13 53-6JP10
3RT10 34-1AP00
-/S2
3RB20 26-1QB0/
3RB21 23-4QB0
6,00 ... 25,0
50
9,00
13,1
None
3RV13 53-6LM10
3RT10 34-1AP00
-/S2
50
16,0
None
3RV13 53-6LM10
3RT10 34-1AP00
-/S2
3RB20 46-1UB0/
3RB21 43-4UB0
12,5 ... 50,0
11,0
12,5 ... 50,0
50
3RB20 16-1SB0/
3RB21 13-4SB0
15,0
21
None
3RV13 53-6MM10 3RT10 34-1AP00
-/S2
12,5 ... 50,0
50
18,5
25
None
3RV13 53-6MM10 3RT10 34-1AP00
-/S2
12,5 ... 50,0
50
22,0
30
None
3RV13 53-6MM10 3RT10 35-1AP00
-/S2
12,5 ... 50,0
50
12,5 ... 50,0
50
12,5 ... 50,0
50
30
40
None
3RV13 63-7AN10
3RT10 54-1AP36
-/S6
37
48
None
3RV13 63-7AN10
3RT10 54-1AP36
-/S6
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
3RB20 46-1UB0/
3RB21 43-4UB0
123
Selection tables 550 V AC
7.1 Motor starter protector + contactor + 3RB20/3RB21 solid-state overload relay
Standard threephase motor
4-pole at
550 V AC1
Stand Motor
ard
current
output (guide
P
value)
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
Overload relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
A
3RB20 56-1FW2/
3RB21 53-4FW2
50,0 ... 200
50
Iq
I
1
2
kW
A
45
58
None
Order No.
Order No.
3RV13 63-7AN10
3RT10 54-1AP36
-/S6
55
71
None
3RV13 63-7AN10
3RT10 54-1AP36
-/S6
50,0 ... 200
50
75
96
None
3RV13 63-7CN10
3RT10 54-1AP36
-/S6
50,0 ... 200
50
90
116
None
3RV13 63-7CN10
3RT10 55-6AP36
-/S6
50,0 ... 200
50
110
142
None
3RV13 63-7EN10
3RT10 56-6AP36
-/S6
132
167
None
3RV13 63-7EN10
3RT10 64-6AP36
-/S10
160
204
None
3RV13 73-7GN10
3RT10 65-6AP36
-/S10
185
235
None
3RV13 73-7GN10
3RT10 66-6AP36
-/S10
200
255
None
3RV13 73-7JN10
3RT10 66-6AP36
-/S12
250
313
None
3RV13 73-7JN10
3RT10 75-6AP36
-/S12
315
393
None
3RV13 83-7JN10
3RT10 76-6AP36
-/S12
355
444
None
3RV13 83-7KN10
3RT10 76-6AP36
-/S12
50,0 ... 200
50
3RB20 66-1GC2/
3RB21 63-4GC2
55,0 ... 250
50
55,0 ... 250
50
55,0 ... 250
50
3RB20 66-1MC2/
3RB21 63-4MC2
160 ... 630
50
160 ... 630
50
160 ... 630
50
160 ... 630
50
Guide value for 4-pole standard motors at 550 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
124
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 550 V AC
7.2 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
7.2
Motor starter protector + contactor + SIMOCODE pro 3UF7 /
3RB22/3RB23 solid-state overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 kA
$&9
Standard
three-phase
motor
4-pole at
550 V AC1
Stand
ard
outpu
t
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
Overload relay or
SIMOCODE pro
(current
measuring
module)3
Setting
range
Overload
release
Motor starter
protector
Shortcircuit
breaking
capacity
Order No.
A
A
3UF7 100-1AA0/
3RB29 06-2BG1
0,30 ... 3,00
50
Iq
P
Motor
curre
nt
(guide
value)
kW
A
A
Order No.
Order No.
0,37
0,8
None
3RV13 53-6AP10
3RT10 24-1AP00
-/S0
0,55
1,1
None
3RV13 53-6BP10
3RT10 24-1AP00
-/S0
0,30 ... 3,00
50
0,75
1,4
None
3RV13 53-6BP10
3RT10 26-1AP00
-/S0
0,30 ... 3,00
50
1,10
2,0
None
3RV13 53-6CP10
3RT10 26-1AP00
-/S0
0,30 ... 3,00
50
1,50
2,6
None
3RV13 53-6DP10
3RT10 26-1AP00
-/S0
2,20
3,6
None
3RV13 53-6EP10
3RT10 34-1AP00
-/S2
3,00
4,7
None
3RV13 53-6FP10
3RT10 34-1AP00
-/S2
4,00
6,2
None
3RV13 53-6GP10
3RT10 34-1AP00
5,50
8,4
None
3RV13 53-6HP10
3RT10 34-1AP00
7,50
11,3
None
3RV13 53-6JP10
3RT10 34-1AP00
9,00
13,1
None
3RV13 53-6LM10
3RT10 34-1AP00
11,0
16,0
None
3RV13 53-6LM10
15,0
21
None
18,5
25
None
22,0
30
None
30
40
None
37
48
I
0,30 ... 3,00
50
2,40 ... 25,0
50
2,40 ... 25,0
50
-/S2
2,40 ... 25,0
50
-/S2
2,40 ... 25,0
50
-/S2
2,40 ... 25,0
50
-/S2
2,40 ... 25,0
50
3RT10 34-1AP00
-/S2
2,40 ... 25,0
50
3RV13 53-6MM10
3RT10 34-1AP00
-/S2
3RV13 53-6MM10
3RT10 34-1AP00
-/S2
3RV13 53-6MM10
3RT10 35-1AP00
-/S2
3RV13 63-7AN10
3RT10 54-1AP36
-/S6
None
3RV13 63-7AN10
3RT10 54-1AP36
3UF7 101-1AA0/
3RB29 06-2DG1
2,40 ... 25,0
50
10,0 ... 100
50
10,0 ... 100
50
10,0 ... 100
50
-/S6
10,0 ... 100
50
3UF7 102-1AA0/
3RB29 06-2JG1
45
58
None
3RV13 63-7AN10
3RT10 54-1AP36
-/S6
10,0 ... 100
50
55
71
None
3RV13 63-7AN10
3RT10 54-1AP36
-/S6
10,0 ... 100
50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
125
Selection tables 550 V AC
7.2 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
550 V AC1
Stand
ard
outpu
t
1
2
3
Setting
range
Overload
release
Motor
starter
protector
Motor starter
protector
Contactor2
Size
P
Motor
curre
nt
(guide
value)
kW
A
A
Order No.
Order No.
75
96
None
3RV13 63-7CN10
3RT10 54-1AP36
-/S6
90
116
None
3RV13 63-7CN10
3RT10 55-1AP36
-/S6
Overload relay or
SIMOCODE pro
(current
measuring
module)3
Setting
range
Overload
release
Motor starter
protector
Shortcircuit
breaking
capacity
Order No.
A
A
3UF7 103-1AA0/
3RB29 56-2TG2
20,0 ... 200
50
20,0 ... 200
50
Iq
I
110
142
None
3RV13 63-7EN10
3RT10 56-1AP36
-/S6
20,0 ... 200
50
132
167
None
3RV13 63-7EN10
3RT10 64-6AP36
-/S10
20,0 ... 200
50
160
204
None
3RV13 73-7GN10
3RT10 65-6AP36
-/S10
63,0 ... 630
50
185
235
None
3RV13 73-7GN10
3RT10 66-6AP36
-/S10
63,0 ... 630
50
200
255
None
3RV13 73-7JN10
3RT10 66-6AP36
-/S10
63,0 ... 630
50
250
313
None
3RV13 73-7JN10
3RT10 75-6AP36
-/S12
63,0 ... 630
50
315
393
None
3RV13 73-7JN10
3RT10 76-6AP36
-/S12
63,0 ... 630
50
355
444
None
3RV13 83-7KN10
3RT10 76-6AP36
-/S12
63,0 ... 630
50
3UF7 104-1BA0/
3RB29 66-2WH2
Guide value for 4-pole standard motors at 550 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
126
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
8
Selection tables 690 V AC
8.1
Motor starter protector + contactor
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 ... 100 kA
$&9
Standard threephase motor
4-pole at
690 V AC1
Setting
Standard motor
Motor starter
range
starter protector
protector3
with
limiter
function
Overload
release
Standa Motor Motor starter
rd
current protector
output (guide
P
value)
Contactor2
Size
Short-circuit
breaking
capacity
kW
A
A
Type
Order No.
Order No.
0,09
0,2
0,14 ... 0,20
Not required
3RV10 21-0BA10
3RT10 15-1AP01
S0/S00
100
0,12
0,2
0,18 ... 0,25
Not required
3RV10 21-0CA10
3RT10 15-1AP01
S0/S00
100
0,12
0,2
0,22 ... 0,32
Not required
3RV10 21-0DA10
3RT10 15-1AP01
S0/S00
100
0,18
0,4
0,28 ... 0,40
Not required
3RV10 21-0EA10
3RT10 15-1AP01
S0/S00
100
0,18
0,4
0,35 ... 0,50
Not required
3RV10 21-0FA10
3RT10 15-1AP01
S0/S00
100
0,25
0,5
0,45 ... 0,63
Not required
3RV10 21-0GA10
3RT10 15-1AP01
S0/S00
100
0,37
0,6
0,55 ... 0,80
Not required
3RV10 21-0HA10
3RT10 15-1AP01
S0/S00
100
0,55
0,9
0,70 ... 1,00
Not required
3RV10 21-0JA10
3RT10 15-1AP01
S0/S00
100
0,75
1,1
0,90 ... 1,25
Not required
3RV10 21-0KA10
3RT10 15-1AP01
S0/S00
100
0,75
1,1
1,10 ... 1,60
Not required
3RV10 21-1AA10
3RT10 15-1AP01
S0/S00
100
1,1
1,6
1,40 ... 2,00
3RT10 24-1AP00
S0/S0
100
2,1
1,80 ... 2,50
3RV10 21-1CA10
3RT10 24-1AP00
S0/S0
100
2,2
2,8
2,20 ... 3,20
3RV13 21-4DC10
Size S0
In = 25 A
3RV10 21-1BA10
1,5
3RV10 21-1DA10
3RT10 24-1AP00
S0/S0
100
3,0
3,8
3,50 ... 5,00
3RV10 21-1FA10
3RT10 24-1AP00
S0/S0
100
4,0
4,9
4,50 ... 6,30
3RV10 21-1GA10
3RT10 24-1AP00/
3RT10 34-1AP00
S0/S0
100
5,5
6,7
5,50 ... 8,00
3RV10 21-1HA10
3RT10 24-1AP00/
3RT10 34-1AP00
S0/S0
50/100
7,5
8,9
7,00 ... 10,0
3RV10 21-1JA10
3RT10 24-1AP00/
3RT10 34-1AP00
S0/S0
50/100
Iq
I
3RV13 31-4HC10
Size S2
In = 50 A
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
kA
127
Selection tables 690 V AC
8.1 Motor starter protector + contactor
Standard threephase motor
4-pole at
690 V AC1
Setting
Standard motor
Motor starter
range
starter protector
protector3
with
limiter
function
Overload
release
Standa Motor Motor starter
rd
current protector
output (guide
P
value)
Contactor2
Size
Short-circuit
breaking
capacity
kW
A
A
Order No.
Order No.
11
12,8
11,0 ... 16,0
3RV10 21-4AA10
3RT10 25-1AP00/
3RT10 34-1AP00
S0/S0
50/
100
11
12,8
11,0 ... 16,0
3RV10 31-4AA10
3RT10 34-1AP00
S2/S2
100
15
17
14,0 ... 20,0
3RV10 31-4BA10
3RT10 34-1AP00
S2/S2
100
18,5
21
18,0 ... 25,0
3RV10 31-4DA10
3RT10 35-1AP00
S2/S2
100
22
24
22,0 ... 32,0
3RV10 31-4EA10
3RT10 35-1AP00
S2/S2
80
30
32
28,0 ... 40,0
3RV10 31-4FA10
3RT10 44-1AP00
S2/S3
50
37
39
36,0 ... 45,0
3RV10 31-4GA10
3RT10 44-1AP00
S2/S3
50
45
47
40,0 ... 50,0
3RV13 31-4HC10
Size S2
In = 50 A
3RV10 31-4HA10
3RT10 45-1AP00
S2/S3
50
30
32
28,0 ... 40,0
3RV10 41-4FA10
3RT10 46-1AP00
S3/S3
100
37
39
36,0 ... 50,0
3RV10 41-4HA10
3RT10 46-1AP00
S3/S3
100
45
47
36,0 ... 50,0
3RV13 41-4HC10
Size S3
In = 50 A
3RV10 41-4HA10
3RT10 46-1AP00
S3/S3
100
55
57
40,0 ... 100
Not required
3RV10 63-7AL10
3RT10 55-6AP36
-/S6
100
75
77
40,0 ... 100
Not required
3RV10 63-7AL10
3RT10 55-6AP36
-/S6
100
90
93
64,0 ... 160
Not required
3RV10 63-7CL10
3RT10 55-6AP36
-/S6
100
110
113
64,0 ... 160
Not required
3RV10 63-7CL10
3RT10 56-6AP36
-/S6
100
132
134
80,0 ... 200
Not required
3RV10 63-7DL10
3RT10 64-6AP36
-/S10
80
Iq
I
1
2
3
Type
3RV13 31-4HC10
Size S2
In = 50 A
kA
160
162
80,0 ... 200
Not required
3RV10 63-7DL10
3RT10 64-6AP36
-/S10
80
200
203
160 ... 400
Not required
3RV10 73-7GL10
3RT10 64-6AP36
-/S10
70
250
250
160 ... 400
Not required
3RV10 73-7GL10
3RT10 65-6AP36
-/S10
70
315
316
252 ... 630
Not required
3RV10 83-7JL10
3RT10 75-6AP36
-/S12
35
355
354
252 ... 630
Not required
3RV10 83-7JL10
3RT10 75-6AP36
-/S12
35
400
400
252 ... 630
Not required
3RV10 83-7JL10
3RT10 75-6AP36
-/S12
35
500
493
252 ... 630
Not required
3RV10 83-7JL10
3RT10 76-6AP36
-/S12
35
Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
If the corresponding link module is not used, the distance between the motor starter protector and the contactor must
be at least 10 cm for sizes S00 to S3. (For link modules see Catalog LV 1, Chapter 5, 3RV Motor Starter Protectors up
to 100 A, Accessories, Mounting Accessories)
128
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 690 V AC
8.2 Motor starter protector + contactor + 3RU11 thermal overload relay
8.2
Motor starter protector + contactor + 3RU11 thermal overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 ... 100 kA
$&9
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector
output (guide
P
value)
Standard motor
starter protector
with limiter
function
Motor
starter
protector3
Contactor2
kW
A
A
Type
Order No.
Order No.
0,09
0,2
None
Not required
3RV13 210BC10
3RT10 151AP01
0,12
0,2
None
Not required
3RV13 210CC10
0,12
0,2
None
Not required
0,18
0,4
None
0,18
0,4
0,25
Size
Overload
relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
S0/S00
3RU11 160BB0
0,14 ... 0,20
100
3RT10 151AP01
S0/S00
3RU11 160CB0
0,18 ... 0,25
100
3RV13 210DC10
3RT10 151AP01
S0/S00
3RU11 160DB0
0,22 ... 0,32
100
Not required
3RV13 210EC10
3RT10 151AP01
S0/S00
3RU11 160EB0
0,28 ... 0,40
100
None
Not required
3RV13 210FC10
3RT10 151AP01
S0/S00
3RU11 160FB0
0,35 ... 0,50
100
0,5
None
Not required
3RV13 210GC10
3RT10 151AP01
S0/S00
3RU11 160GB0
0,45 ... 0,63
100
0,37
0,6
None
Not required
3RV13 210HC10
3RT10 151AP01
S0/S00
3RU11 160HB0
0,55 ... 0,80
100
0,55
0,9
None
Not required
3RV13 210JC10
3RT10 151AP01
S0/S00
3RU11 160JB0
0,70 ... 1,00
100
0,75
1,1
None
Not required
3RV13 210KC10
3RT10 151AP01
S0/S00
3RU11 160KB0
0,90 ... 1,25
100
0,75
1,1
None
Not required
3RV13 211AC10
3RT10 151AP01
S0/S00
3RU11 161AB0
1,10 ... 1,60
100
1,1
1,6
None
3RT10 241AP00
S0/S0
3RU11 161BB0
1,40 ... 2,00
100
1,5
2,1
None
3RV13 21-4DC10 3RV13 21Size S0
1BC10
In = 25 A
3RV13 211CC10
3RT10 261AP00
S0/S0
3RU11 261CB0
1,80 ... 2,50
100
2,2
2,8
None
3RV13 211DC10
3RT10 261AP00
S0/S0
3RU11 261DB0
2,20 ... 3,20
100
Iq
I
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
129
Selection tables 690 V AC
8.2 Motor starter protector + contactor + 3RU11 thermal overload relay
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector
output (guide
P
value)
Standard motor
starter protector
with limiter
function
Motor
starter
protector3
Contactor2
kW
A
A
Type
Order No.
Order No.
3,0
3,8
None
3RV13 211FC10
3RT10 341AP00
4,0
4,9
None
3RV13 211GC10
5,5
6,7
None
7,5
8,9
None
11
12,8
11
Size
Overload
relay
Setting range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
Order No.
A
kA
S0/S0
3RU11 261FB0
3,50 ... 5,00
100
3RT10 341AP00
S0/S0
3RU11 261GB0
4,50 ... 6,30
100
3RV13 31-4HC10 3RV13 211HC10
Size S2
In = 50 A
3RV13 211JC10
3RT10 341AP00
S2/S0
3RU11 261HB0
5,50 ... 8,00
100
3RT10 341AP00
S2/S0
3RU11 261JB0
7,00 ... 10,0
100
None
3RV13 214AC10
3RT10 341AP00
S2/S0
3RU11 261KB0
11,0 ... 16,0
100
12,8
None
3RT10 341AP00
S2/S2
3RU11 364AB0
11,0 ... 16,0
100
15
17
None
3RV13 31-4HC10 3RV13 31Size S2
4AC10
In = 50 A
3RV13 314BC10
3RT10 341AP00
S2/S2
3RU11 364BB0
14,0 ... 20,0
100
18,5
21
None
3RV13 314DC10
3RT10 351AP00
S2/S2
3RU11 364DB0
18,0 ... 25,0
100
22
24
None
3RV13 314EC10
3RT10 351AP00
S2/S2
3RU11 364EB0
22,0 ... 32,0
80
30
32
None
3RT10 441AP00
S2/S3
3RU11 464FB0
28,0 ... 40,0
50
37
39
None
3RV13 31-4HC10 3RV13 314FC10
Size S2
In = 50 A
3RV13 314GC10
3RT10 441AP00
S2/S3
3RU11 464HB0
36,0 ... 50,0
50
45
47
None
3RV13 314HC10
3RT10 451AP00
S2/S3
3RU11 464HB0
36,0 ... 50,0
50
30
32
None
3RV13 41-4HC10 3RV13 414FC10
3RT10 441AP00
S3/S3
3RU11 464FB0
28,0 ... 40,0
100
37
39
None
3RV13 41-4HC10 3RV13 414HC10
3RT10 441AP00
S3/S3
3RU11 464HB0
36,0 ... 50,0
100
45
47
None
3RV13 41-4HC10 3RV13 414HC10
3RT10 461AP00
S3/S3
3RU11 464HB0
36,0 ... 50,0
100
Iq
I
1
2
3
Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
If the corresponding link module is not used, the distance between the motor starter protector and the contactor must be
at least 10 cm for sizes S00 to S3. (For link modules see Catalog LV 1, Chapter 5, 3RV Motor Starter Protectors up to
100 A, Accessories, Mounting Accessories)
130
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 690 V AC
8.3 Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay
8.3
Motor starter protector + contactor + 3RB20 / 3RB21 solid-state
overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 ... 100 kA
$&9
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Standard
motor
starter
protector
with limiter
function
Motor
starter
protector4
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Type
Order No.
Order No.
Order No.
A
kA
0,09
0,2
None
Not
required
3RV13 210CC10
3RT10 151AP01
S0/S00
3RB20 16-1RB0/
3RB21 13-4RB0
0,10 ... 0,40 100
0,12
0,2
None
Not
required
3RV13 210EC10
3RT10 151AP01
S0/S00
0,10 ... 0,40 100
0,12
0,2
None
Not
required
3RV13 210EC10
3RT10 151AP01
S0/S00
0,10 ... 0,40 100
0,18
0,4
None
Not
required
3RV13 210HC10
3RT10 151AP01
S0/S00
0,10 ... 0,40 100
0,18
0,4
None
Not
required
3RV13 210HC10
3RT10 151AP01
S0/S00
0,25
0,5
None
Not
required
3RV13 210JC10
3RT10 151AP01
S0/S00
0,32 ... 1,25 100
0,37
0,6
None
Not
required
3RV13 210JC10
3RT10 151AP01
S0/S00
0,32 ... 1,25 100
0,55
0,9
None
Not
required
3RV13 210KC10
3RT10 151AP01
S0/S00
0,32 ... 1,25 100
0,75
1,1
None
Not
required
3RV13 211AC10
3RT10 241AP00
S0/S0
0,75
1,1
None
Not
required
3RV13 211AC10
3RT10 241AP00
S0/S0
1,00 ... 4,00 100
1,1
1,6
None
3RV13 214DC10
3RV13 211BC10
3RT10 241AP00
S0/S0/S0
1,00 ... 4,00 100
1,5
2,1
None
3RV13 214DC10
3RV13 211CC10
3RT10 241AP00
S0/S0/S0
1,00 ... 4,00 100
2,2
2,8
None
3RV13 214DC10
3RV13 211DC10
3RT10 261AP00
S0/S0/S0
1,00 ... 4,00 100
Iq
I
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
3RB20 16-1NB0/
3RB21 13-4NB0
3RB20 16-1PB0/
3RB21 13-4PB0
0,32 ... 1,25 100
1,00 ... 4,00 100
131
Selection tables 690 V AC
8.3 Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Standard
motor
starter
protector
with limiter
function
Motor
starter
protector4
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Type
Order No.
Order No.
Order No.
A
kA
3,0
3,8
None
3RV13 214DC10
3RV13 211EC10
3RT10 261AP00
S0/S0/S0
3RB20 26-1SB0/
3RB21 23-4SB0
3,00 ... 12,0 100
4,0
4,9
None
3RV13 214DC10
3RV13 211GC10
3RT10 341AP00
S0/S0/S2
3,00 ... 12,0 100
5,5
6,7
None
3RV13 314HC10
3RV13 211HC10
3RT10 341AP00
S2/S0/S2
3,00 ... 12,0 100
7,5
8,9
None
3RV13 314HC10
3RV13 211JC10
3RT10 341AP00
S2/S0/S2
3RB20 26-1QB0/ 6,00 ... 25,0 100
3RB21 23-4QB0
11
12,8
None
3RV13 314HC10
3RV13 214AC10
3RT10 341AP00
S2/S0/S2
6,00 ... 25,0 100
11
12,8
None
3RV13 314HC10
3RV13 314AC10
3RT10 341AP00
S2/S2/S2
3RB20 36-1QB0/ 6,00 ... 25,0 100
3RB21 33-4QB0
15
17
None
3RV13 314HC10
3RV13 314BC10
3RT10 341AP00
S2/S2/S2
3RB20 36-1UB0/
3RB21 33-4UB0
18,5
21
None
3RV13 314HC10
3RV13 314EC10
3RT10 351AP00
S2/S2/S2
12,5 ... 50,0 100
22
24
22,0 ... 32,0 3RV13 314HC10
3RV10 314EA10
3RT10 351AP00
S2/S2/S2
12,5 ... 50,0 80
30
32
28,0 ... 40,0 3RV13 314HC10
3RV10 314FB10
3RT10 441AP00
S2/S2/S3
30
32
None
3RV13 414HC10
3RV13 414FC10
3RT10 461AP00
S3/S3/S3
25,0 ... 100 100
37
39
36,0 ... 45,0 3RV10 314HB10
3RV10 314GB10
3RT10 441AP00
S2/S2/S3
25,0 ... 100 50
37
39
None
3RV13 414HC10
3RV13 414FC10
3RT10 461AP00
S3/S3/S3
25,0 ... 100 100
45
47
40,0 ... 50,0 3RV10 314HB10
3RV10 314HB10
3RT10 451AP00
S2/S2/S3
25,0 ... 100 50
45
47
None
3RV13 414HC10
3RV13 414HC10
3RT10 461AP00
S3/S3/S3
25,0 ... 100 100
55
57
None
Not
required
3RV13 647AN10
3RT10 556AP36
-/S6
3RB20 56-1FW2/ 50,0 ... 200 100
3RB21 53-4FW2
75
77
None
Not
required
3RV13 647AN10
3RT10 556AP36
-/S6
50,0 ... 200 100
90
93
None
Not
required
3RV13 647CN10
3RT10 556AP36
-/S6
50,0 ... 200 100
110
113
None
Not
required
3RV13 647CN10
3RT10 566AP36
-/S6
50,0 ... 200 100
Iq
I
132
3RB20 46-1EB0/
3RB21 43-4EB0
12,5 ... 50,0 100
25,0 ... 100 50
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 690 V AC
8.3 Motor starter protector + contactor + 3RB20 / 3RB21 solid-state overload relay
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Standard
motor
starter
protector
with limiter
function
Motor
starter
protector4
Contactor3
Size
Overload relay
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capacity
kW
A
A
Type
Order No.
Order No.
A
kA
132
134
None
Not
required
3RV13 647EN10
3RT10 646AP36
-/S10
3RB20 66-1GC2/ 55,0 ... 250 80
3RB21 63-4GC2
160
162
None
Not
required
3RV13 647EN10
3RT10 646AP36
-/S10
55,0 ... 250 80
200
203
None
Not
required
3RV13 747GN10
3RT10 646AP36
-/S10
55,0 ... 250 70
250
250
None
Not
required
3RV13 747GN10
3RT10 656AP36
-/S10
3RB20 66-1MC2/ 160 ... 630
3RB21 63-4MC2
70
315
316
None
Not
required
3RV13 737JN10
3RT10 756AP36
-/S12
160 ... 630
70
355
354
None
Not
required
3RV13 837JN10
3RT10 756AP36
-/S12
160 ... 630
35
400
400
None
Not
required
3RV13 837KN10
3RT10 756AP36
-/S12
160 ... 630
35
500
493
None
Not
required
3RV13 837KN10
3RT10 766AP36
-/S12
160 ... 630
35
Iq
I
1
2
3
4
Order No.
Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup and rated data of
the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
If the corresponding link module is not used, the distance between the motor starter protector and the contactor must be
at least 10 cm for sizes S00 to S3. (For link modules see Catalog LV 1, Chapter 5, 3RV Motor Starter Protectors up to
100 A, Accessories, Mounting Accessories)
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
133
Selection tables 690 V AC
8.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
8.4
Motor starter protector + contactor + SIMOCODE pro 3UF7 /
3RB22/3RB23 solid-state overload relay
CLASS 10, type of coordination 2,
short-circuit breaking capacity Iq = 50 ... 100 kA
$&9
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Motor
starter
protector
with limiter
function
Motor
starter
protector5
Overload relay or
SIMOCODE pro
(current
measuring
module)4
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
kW
A
A
Order No.
Order No.
Order No.
Order No.
A
kA
0,18
0,4
None
Not
required
3RV13 210HC10
3RT10 151AP01
S0/S00
3UF7 100-1AA0/
3RB29 06-2BG1
0,30 ... 3,00 100
0,18
0,4
None
Not
required
3RV13 210HC10
3RT10 151AP01
S0/S00
0,30 ... 3,00 100
0,25
0,5
None
Not
required
3RV13 210JC10
3RT10 151AP01
S0/S00
0,30 ... 3,00 100
0,37
0,6
None
Not
required
3RV13 210JC10
3RT10 151AP01
S0/S00
0,30 ... 3,00 100
0,55
0,9
None
Not
required
3RV13 210KC10
3RT10 151AP01
S0/S00
0,30 ... 3,00 100
0,75
1,1
None
Not
required
3RV13 211AC10
3RT10 241AP00
S0/S0
0,30 ... 3,00 100
0,75
1,1
None
Not
required
3RV13 211AC10
3RT10 241AP00
S0/S0
0,30 ... 3,00 100
1,1
1,6
None
3RV13 214DC10
3RV13 211BC10
3RT10 241AP00
S0/S0/S0
0,30 ... 3,00 100
1,5
2,1
None
3RV13 214DC10
3RV13 211CC10
3RT10 261AP00
S0/S0/S0
0,30 ... 3,00 100
2,2
2,8
None
3RV13 214DC10
3RV13 211DC10
3RT10 261AP00
S0/S0/S0
3
3,8
None
3RV13 214DC10
3RV13 211EC10
3RT10 261AP00
S0/S0/S0
2,40 ... 25,0 100
4
4,9
None
3RV13 214DC10
3RV13 211GC10
3RT10 341AP00
S0/S0/S2
2,40 ... 25,0 100
5,5
6,7
None
3RV13 314HC10
3RV13 211HC10
3RT10 341AP00
S2/S0/S2
2,40 ... 25,0 100
Line
contactor +
delta
contactor
I
134
Contactors3 Size
3UF7 101-1AA0/
3RB29 06-2DG1
Iq
2,40 ... 25,0 100
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Selection tables 690 V AC
8.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Motor
starter
protector
with limiter
function
Motor
starter
protector5
Contactors3 Size
Overload relay or
SIMOCODE pro
(current
measuring
module)4
kW
A
A
Order No.
Order No.
Order No.
7,5
8,9
None
3RV13 314HC10
3RV13 211JC10
3RT10 341AP00
S2/S0/S2
2,40 ... 25,0 100
11
12,8
None
3RV13 314HC10
3RV13 214AC10
3RT10 341AP00
S2/S0/S2
2,40 ... 25,0 100
11
12,8
None
3RV13 314HC10
3RV13 314AC10
3RT10 341AP00
S2/S2/S2
2,40 ... 25,0 100
15
17
None
3RV13 314HC10
3RV13 314BC10
3RT10 341AP00
S2/S2/S2
2,40 ... 25,0 100
18,5
21
None
3RV13 314HC10
3RV13 314EC10
3RT10 351AP00
S2/S2/S2
22
24
None
3RV13 314HC10
3RV13 314EC10
3RT10 351AP00
S2/S2/S2
10,0 ... 100 100
30
32
28,0 ... 40,0 3RV13 314HC10
3RV10 314FB10
3RT10 441AP00
S2/S2/S3
10,0 ... 100 50
30
32
None
3RV13 414HC10
3RV13 414FC10
3RT10 461AP00
S3/S3/S3
10,0 ... 100 100
37
39
36,0 ... 45,0 3RV10 314HB10
3RV10 314GB10
3RT10 441AP00
S2/S2/S3
10,0 ... 100 50
37
39
None
3RV13 414HC10
3RV13 414FC10
3RT10 461AP00
S3/S3/S3
10,0 ... 100 100
45
47
40,0 ... 50,0 3RV10 314HB10
3RV10 314HB10
3RT10 451AP00
S2/S2/S3
10,0 ... 100 50
45
47
None
3RV13 414HC10
3RV13 414HC10
3RT10 461AP00
S3/S3/S3
10,0 ... 100 100
55
57
None
Not
required
3RV13 647AN10
3RT10 556AP36
-/S6
75
77
None
Not
required
3RV13 647AN10
3RT10 556AP36
-/S6
20,0 ... 200 100
90
93
None
Not
required
3RV13 647CN10
3RT10 556AP36
-/S6
20,0 ... 200 100
Line
contactor +
delta
contactor
I
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Order No.
3UF7 102-1AA0/
3RB29 06-2JG1
3UF7 103-1AA0/
3RB29 56-2TG2
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
A
kA
Iq
10,0 ... 100 100
20,0 ... 200 100
135
Selection tables 690 V AC
8.4 Motor starter protector + contactor + SIMOCODE pro 3UF7 / 3RB22/3RB23 solid-state overload relay
Standard
three-phase
motor
4-pole at
690 V AC1
Setting
range
Overload
release
Motor
Stand Motor starter
ard
current protector2
output (guide
P
value)
Motor
starter
protector
with limiter
function
Motor
starter
protector5
Setting
range
Overload
release
Overload
relay
Shortcircuit
breaking
capaci
ty
kW
A
A
Order No.
Order No.
Order No.
110
113
None
Not
required
3RV13 647CN10
3RT10 566AP36
132
134
None
Not
required
3RV13 647EN10
160
162
None
Not
required
200
203
None
250
250
315
2
3
4
5
Overload relay or
SIMOCODE pro
(current
measuring
module)4
Order No.
A
kA
-/S6
3UF7 103-1AA0/
3RB29 56-2TG2
20,0 ... 200 100
3RT10 646AP36
-/S10
3UF7 104-1BA0/
3RB29 66-2WH2
63,0 ... 630 80
3RV13 647EN10
3RT10 646AP36
-/S10
63,0 ... 630 80
Not
required
3RV13 747GN10
3RT10 646AP36
-/S10
63,0 ... 630 70
None
Not
required
3RV13 747GN10
3RT10 656AP36
-/S10
63,0 ... 630 70
316
None
Not
required
3RV13 737JN10
3RT10 756AP36
-/S12
63,0 ... 630 70
355
354
None
Not
required
3RV13 837JN10
3RT10 756AP36
-/S12
63,0 ... 630 35
400
400
None
Not
required
3RV13 837KN10
3RT10 756AP36
-/S12
63,0 ... 630 35
500
493
None
Not
required
3RV13 837KN10
3RT10 766AP36
-/S12
63,0 ... 630 35
Line
contactor +
delta
contactor
I
1
Contactors3 Size
Iq
Guide value for 4-pole standard motors at 690 V AC, 50 Hz. Selection depends on the concrete startup and rated data
of the protected motor.
The motor starter protector / circuit breaker is to be set to maximum current value.
Rated control supply voltage 230 V AC, 50 Hz. Other control voltages are also possible.
The current measuring modules required for 3UF7 or 3RB22 / 3RB23 are specified in each case. See page 9 for details
of the 3UF7 or 3RB22 / 3RB23 basic units which are also required.
If the corresponding link module is not used, the distance between the motor starter protector and the contactor must be
at least 10 cm for sizes S00 to S3. (For link modules see Catalog LV 1, Chapter 5, 3RV Motor Starter Protectors up to
100 A, Accessories, Mounting Accessories)
136
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
9
Installation guidelines
9.1
Installation guidelines for all voltages
Distance to grounded parts for 3RT10/3RT12 contactors (sizes S6/S10/S12)
Contactor
Rated operational voltage
Distance to grounded or live parts
G
H
I
V
mm
mm
mm
3RT10 5
400 / 440 / 480 / 500 / 550 / 690
40
10
20
3RT10 6
400 / 440 / 480 / 500 / 550 / 690
20
10
20
3RT10 7
400 / 440 / 480 / 500 / 550 / 690
20
10
20
3RT12 6
400 / 440 / 480 / 500 / 550 / 690
20
10
20
3RT12 7
400 / 440 / 480 / 500 / 550 / 690
20
10
20
G
G
I
NSB0_01769
H
G = distance to the coil terminals. If using cables with cable lugs or busbar connection,
3RT19 56-4EA1 (S6) or 3RT19 66-4EA1 (S10 / S12) terminal covers must be used.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
137
Installation guidelines
9.1 Installation guidelines for all voltages
Distance to grounded parts for 3RT10/3RT12 contactors with mounted overload relay
Contactor
Rated operational voltage
Distance to grounded or live parts
G
H
I
K
V
mm
mm
mm
mm
3RT10 1
550
40
20
40
20
3RT10 2
550
40
20
40
20
3RT10 3
550
40
20
40
20
3RT10 4
550
40
20
40
20
3RT10 5
400 / 500 / 550 / 690
40
10
20
20
3RT10 6
400 / 500 / 550 / 690
20
10
20
20
3RT10 7
400 / 500 / 550 / 690
20
10
20
20
3RT12 6
400 / 500 / 550 / 690
20
10
20
20
3RT12 7
400 / 500 / 550 / 690
20
10
20
20
G
G
H
NSB0_01772
K
I
K
G = distance to the coil terminals. If using cables with cable lugs or busbar connection,
3RT19 56-4EA1 (S6) or 3RT19 66-4EA1 (S10 / S12) terminal covers must be used.
138
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Installation guidelines
9.2 Installation guidelines for combinations: 3RV1. 5 ... 3RV1. 8
9.2
Installation guidelines for combinations: 3RV1. 5 ... 3RV1. 8
Distances to grounded parts for 3RT10/3RT12 contactors
3RT19 66-4EA1 terminal covers must be used on the line side of the contactor. Do not use
box terminals for size S12 contactors.
Motor starter
protector
Contactor
Rated operational voltage
V
Distance to grounded or live
parts
A
B
G
mm
mm
mm
3RV1. 5
S00 ... S3
440 / 480 / 550 / 690
130
25
150
3RV1. 6/7/8
S3 ... S12
440 / 480 / 550 / 690
130
25
200
A
B
G
NSB0_01950
H
For all combinations of motor starter protectors 3RV1. 5 ... 3RV1. 8 with contactors, phase
barriers must be used.
Motor starter protector
Phase barrier
3RV1. 5
3RV19 55-5GA0
3RV1. 6 / 7
3RV19 75-5GA0
3RV1. 8
3RV19 85-5GA0
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
139
Installation guidelines
9.3 Installation guidelines for 400/440/480/500 V AC
9.3
Installation guidelines for 400/440/480/500 V AC
Distance to grounded parts for 3RV motor starter protectors + 3RT10 contactor (sizes S00/S0/S2/S3)
Motor starter
protector
Contactor
Rated operational voltage
Distance to grounded or live
parts
Y
X21)
Z
V
mm
mm
mm
3RV1. 1
3RT10 1
400 / 440 / 480 / 500
20
10
9
3RV1. 2
3RT10 1
400 / 440 / 480 / 500
30
10
9
3RT10 2
400 / 440 / 480 / 500
30
10
9
3RT10 3
400 / 440 / 480 / 500
30
10
9
3RF24 .
400
30
–
9
3RT10 2
400 / 440 / 480 / 500
50
10
10
3RT10 3
400 / 440 / 480 / 500
50
10
10
3RV1. 3
3RV1. 4
3RT10 4
400 / 440 / 480 / 500
50
10
10
3RT10 4
400
90
10
12
3RT10 4
500
220
10
20
1) Minimum distance to contactor at the front. In the case of motor starter protectors and
solid-state contactors, no minimum distance is required at the front.
Z
Y
Z
1L1
3L2 5L3
3RV1...
3RV1...
1
2T1 4T2 6T3
1L1
3L2 5L3
X2
1
3RT1...
3RT1...
2T1 4T2 6T3
NSB0_01030d
For combinations with S3 motor starter protectors and S6 contactors at 440/480 V, a
distance of 220 mm is required.
140
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Installation guidelines
9.3 Installation guidelines for 400/440/480/500 V AC
Distance to grounded parts for 3VL circuit breakers
Circuit breaker
3VL2/31)
Rated operational voltage
Distance to grounded or live parts
A
B
C
D
V
mm
mm
mm
mm
Ue
max. 400
100
25
30
87
3VL2/32)
400 ... 525
100
25
30
87
3VL4/51)
max. 525
100
35
30
106,5
phase barriers 3VL93 00-8CE00 (3VL2/3) or 3VL96 00-8CE00 (3VL4/5) must be used.
2) The
3VL93 00-8C.0 (3VL2/3) terminal cover must be used.
A
1) The
B
C
D
NSB0_01599
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
141
Installation guidelines
9.4 Installation guidelines for 690 V AC
9.4
Installation guidelines for 690 V AC
Distance to grounded parts for 3RV motor starter protectors + 3RT10 contactor (sizes S0/S2/S3)
Two motor starter protectors in combination with
contactors
Distance to grounded or live parts
Motor starter
protector
Rated operational
voltage
Y1
Y2
Y3
X1
X2
Z
V
mm
mm
mm
mm
mm
mm
Contactor
3RV1. 2 with
3RT10 1/
3RT10 2
690
80
10
95
20
14
20
3RV1. 3 with
3RT10 3
690
50
10
120
10
32
10
3RT10 4
690
50
10
120
10
40
10
3RT10 4
690
50
20
130
10
40
15
3RV1.
41)
with
1)
Terminal block for 3RV1.4 required, Order No.: 3RV19 48-1K.
In limiter circuits with motor starter protectors of different sizes (e. g. 3RV133 and 3RV1.2
with 3RT102 contactor) you must observe the respective distances to grounded parts for
both motor starter protectors.
Distance to grounded parts for 3RV1. 4 motor starter protectors (S3) 3RT10 4 contactors
Z
Y1
Z
1
1
SKDVHEXVEDU
6L]H659$%
6L]H659$
1L1
3L2 5L3
1L1 3L2 5L3
3RV1...
3RV1...
X1
2T1 4T2 6T3
3RV1...
2
2T1 4T2 6T3
X2
1L1 3L2 5L3
2
3RT1...
Y2
Y3
3RT1...
2T1 4T2 6T3
NSB0_01033d
,QFRPELQDWLRQZLWKVL]H
6PRWRUVWDUWHU
SURWHFWRUVDQGVL]H6
FRQWDFWRUVDVSDFLQJRI
PPPXVWEH
PDLQWDLQHG
The diagram also applies accordingly when motor starter protectors of different sizes are
used.
142
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Installation guidelines
9.4 Installation guidelines for 690 V AC
Mounting methods for 3RV motor starter protectors + 3RT10 contactors (sizes S0/S2/S3)
Mounting methods
S0:
Mounting on an insulated
base plate. If screws are
used for mounting, the
screws must not be
grounded. Alternatively, the
standard mounting rail
adapter can be used
without restriction.
S2/S3:
Mounting on an insulated
base plate.
Alternatively, the standard
mounting rail adapter can
also be used.
Standard mounting for size S0
... 5.5 kW, S2 and S3
SKDVHEXVEDU
1L1
3L2 5L3
1L1
3RV1...
2T1 4T2 6T3
,QIHHGVLGH
3L2 5L3
6L]H6
59$
3RV1...
6L]H6
59$
Mounting for size S0
from 7.5 ... 12 kW
,QIHHGVLGH
1L1
3L2 5L3
1L1
3L2 5L3
3RV1...
3RV1...
2T1 4T2 6T3
2T1 4T2 6T3
2T1 4T2 6T3
1L1
3L2 5L3
1L1
3L2 5L3
3RT1...
2T1 4T2 6T3
NSB0_01031d
Size
)RUOLQNPRGXOHVVHH
0RXQWLQJ$FFHVVRULHV
3RT1...
2T1 4T2 6T3
/RDGVLGH
/RDGVLGH
● For the distance to grounded parts for 3RT10/3RT12 contactor (sizes S6/S10/S12),
please refer to the installation guidelines for all voltages.
● For the distance to grounded parts for 3RT10/3RT12 contactors (sizes S6/S10/S12) with
mounted overload relays, please refer to the installation guidelines for all voltages.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
143
Installation guidelines
9.4 Installation guidelines for 690 V AC
144
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
10
Service and support
Information
Simply download catalogs and information material
Newsletter
The Siemens Information and Download Center contains all
the current catalogs, customer magazines, brochures,
demonstration software and promotion packages ready for
you to download. Alternatively, you can order them if you
prefer.
Always up to date:
Our regular newsletter gives you the latest information on
industrial controls and low-voltage power distribution.
Information (www.siemens.de/lowvoltage/kataloge)
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
You can register at Newsletter
(www.siemens.de/lowvoltage/newsletter)
145
Service and support
Orders
Configurators
E-business
Configurators to make your life easier
24/7 access to a comprehensive information and ordering
platform for products and systems of the low-voltage
controls and distribution portfolio? Comprehensive
information on our complete portfolio? Product selection,
order tracking, service, support and training information?
You can find everything on this topic under
Configurators (www.siemens.de/lowvoltage/konfiguratoren)
You can find everything you need to know in the A&D Mall
(www.siemens.de/lowvoltage/mall)
146
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Service and support
Commissioning/operation
Service
Online support
Technical Assistance
More detailed technical information on our low-voltage
switchgear and controlgear products and systems, as well
as product support, and the service and support we can
offer on the basis of helpful support tools is available at:
Online support (www.siemens.de/lowvoltage/support)
Are you looking for the right product to suit your application?
Do you have technical questions, require spare parts or
need a regional expert on site? We'll help you! Our
experienced team of engineers and technicians will be
happy to help:
• Speak to them in person by phone from Monday to
Friday between 8 a.m. and 5 p.m. (CET): +49(911) 8955900
• Send them an email:
mail to: [email protected])
• Send them a fax: +49(911) 895-5907
At Technical Assistance
(www.siemens.de/lowvoltage/technical-assistance) you can
also access the Siemens Automation and Drives Service &
Support Internet platform. This facility offers an FAQ
database where you can look for information and solutions
for your application around the clock. Alternatively, you can
send your question direct to a specialist support adviser via
the Support Request feature.
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
147
Service and support
Training
Our training centers at numerous sites worldwide offer individual training programs covering all fields of automation and
individual solutions. Our online courses and various teach-yourself software packages can help you acquire new
knowledge in a time and cost-effective manner. You can find everything you need to know about our comprehensive
SITRAIN training program online at: SITRAIN (www.siemens.de/sitrain-cd)
148
Configuring SIRIUS
Configuration Manual, 10/2009, A8E56203880002-01
Service & Support
Download catalogs and information material:
www.siemens.com/lowvoltage/catalogs
Newsletter – always up to date:
www.siemens.com/lowvoltage/newsletter
E-business in the Industry Mall:
www.siemens.com/lowvoltage/mall
Online Support:
www.siemens.com/lowvoltage/support
Contact for all technical information:
Technical Assistance
Tel.: +49 (911) 895-5900
e-mail: [email protected]
www.siemens.com/lowvoltage/technical-assistance
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
www.siemens.com/automation
Subject to change without prior notice
Order No.: 3ZX1012-0RA21-0AC0