PROGRAMMING GUIDE
XR100 SERIES
COMMAND PROCESSOR™ PANEL
MODEL XR100 SERIES ACCESS CONTROL
COMMAND PROCESSOR™ PANEL
PROGRAMMING GUIDE
Contains programming instructions for use with the Model
XR100 and XR100N Access Control Command Processor™ Panel.
When using the XR100 Series panel for any UL, NFPA, CSFM, or other listing organization’s approved methods, refer to this
manual and the XR100 Series Installation Guide (LT-0899). These documents outline the installation and programming
requirements of all applications for which the XR100 Series is approved.
FCC NOTICE
This equipment generates and uses radio frequency energy and, if not installed and used properly in strict accordance
with the manufacturer’s instructions, may cause interference with radio and television reception. It has been type tested
and found to comply with the limits for a Class A computing device in accordance with the specification in Subpart J
of Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential
installation. If this equipment does cause interference to radio or television reception, which can be determined by
turning the equipment off and on, the installer is encouraged to try to correct the interference by one or more of the
following measures:
Reorient the receiving antenna
Relocate the computer with respect to the receiver
Move the computer away from the receiver
Plug the computer into a different outlet so that computer and receiver are on different branch circuits
If necessary, the installer should consult the dealer or an experienced radio/television technician for additional suggestions.
The installer may find the following booklet, prepared by the Federal Communications Commission, helpful:
“How to identify and Resolve Radio-TV Interference Problems.”
This booklet is available from the U.S. Government Printing Office, Washington D.C. 20402
Stock No. 004-000-00345-4
© 2006-2007 Digital Monitoring Products, Inc.
Information furnished by DMP is believed to be accurate and reliable.
This information is subject to change without notice.
TABLE OF CONTENTS
Revisions to This Document........................................... viii
Introduction......................................................................1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.10
1.11
1.12
Before you Begin ................................................................. 1
Internal Programmer............................................................ 1
Programming Information Sheet ........................................... 1
Getting Started .................................................................... 1
Accessing the Programmer ................................................... 1
Programmer Operation......................................................... 2
Programmer Lockout Codes.................................................. 2
Reset Timeout ..................................................................... 2
Power Up ............................................................................ 2
Keypads ............................................................................. 3
Special Keys ........................................................................ 3
COMMAND (CMD) Key.......................................................... 3
Back Arrow (<—) Key .......................................................... 3
Select Keys/Areas ................................................................ 3
Entering Alpha Characters .................................................... 4
Entering Non-Alpha Characters ............................................. 4
Keypad Displays Current Programming .................................. 5
Asterisks in Programming ..................................................... 5
Initialization .....................................................................6
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
Initialization ........................................................................ 6
Clear All Memory ................................................................. 6
Clear All Codes .................................................................... 6
Clear All Schedules .............................................................. 6
Clear Display Events Memory................................................ 6
Clear Zone Information ........................................................ 6
Clear Area Information......................................................... 6
Clear Output Information ..................................................... 6
Clear Communication and Remote Options ............................ 7
Set to Factory Defaults......................................................... 7
Communication .................................................................8
3.1
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.2.7
3.2.8
3.2.9
3.2.10
3.2.11
3.2.12
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
XR100 Series Programming Guide
Communication ................................................................... 8
Communication Type............................................................ 8
Retry Time .......................................................................... 8
Network Backup .................................................................. 8
Supervise Backup ................................................................ 8
Remote IP Address .............................................................. 9
Alarm Port........................................................................... 9
Modem Setup ...................................................................... 9
UL AA ................................................................................. 9
Disarm Checkin ................................................................... 9
Network Test .....................................................................10
Substitution Code ...............................................................10
Check In ............................................................................10
Fail Time ............................................................................10
Network Trouble .................................................................10
Second Line .......................................................................11
Test Frequency ...................................................................11
NET Fail Test ......................................................................12
Account Number.................................................................12
Transmit Delay ...................................................................12
DTMF.................................................................................12
Defer Test .........................................................................12
Test Frequency ...................................................................12
Digital Monitoring Products
i
TABLE OF CONTENTS
3.11
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19
3.20
3.21
3.22
3.23
3.24
3.25
3.26
3.27
3.28
3.29
3.30
Test Time...........................................................................12
Events Manager..................................................................13
Receiver One Programming .................................................13
Alarm Reports ....................................................................13
Supervisory/Trouble Reports ................................................13
Opening/Closing and User Reports .......................................13
Test Report ........................................................................13
Door Access Report.............................................................13
Backup Reporting ...............................................................13
First Telephone Number ......................................................14
Second Telephone Number ..................................................14
Receiver Two Programming .................................................14
Alarm Reports ....................................................................14
Supervisory/Trouble Reports ................................................14
Opening/Closing and User Reports .......................................15
Test Report ........................................................................15
Door Access Report.............................................................15
Backup Reporting ...............................................................15
First Telephone Number ......................................................15
Second Telephone Number ..................................................15
Network Options (XR100N only) ......................................16
4.1
4.2
4.3
4.4
4.5
4.6
DHCP Mode Enabled ...........................................................16
Local IP Address .................................................................16
Gateway Address ................................................................16
Subnet Mask ......................................................................16
Programming Port...............................................................16
TCP Comm Enabled ............................................................16
Device Setup ...................................................................17
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
Device Setup ......................................................................17
Device Number...................................................................17
Door Name .......................................................................17
Access Areas ......................................................................17
Egress Areas ......................................................................17
Display Areas .....................................................................18
Strike Time ........................................................................19
Strike Delay........................................................................19
Fire Exit Release .................................................................19
Output Group .....................................................................19
Schedule Override ..............................................................19
Auto Force Arm Device? ......................................................19
Remote Options ..............................................................20
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
Remote Options..................................................................20
Remote Key .......................................................................20
Manufacturer Authorization .................................................20
Armed Rings ......................................................................20
Disarmed Rings ..................................................................20
Alarm Receiver Authorization ...............................................20
Service Receiver Authorization .............................................21
PC Modem ........................................................................21
Remote Telephone Number .................................................21
Remote Disarm ..................................................................21
System Reports...............................................................22
7.1
7.2
7.3
7.4
Digital Monitoring Products
ii
System Reports ..................................................................22
Abort Report ......................................................................22
Restoral Reports .................................................................22
Bypass Reports...................................................................22
XR100 Series Programming Guide
TABLE OF CONTENTS
7.5
7.6
7.7
7.8
Schedule Change Reports....................................................22
Code Change Reports .........................................................22
Access Keypads ..................................................................22
Ambush ............................................................................22
System Options ...............................................................23
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
8.10
8.11
8.12
8.13
8.14
8.15
8.16
8.17
8.18
8.19
System Options ..................................................................23
System ..............................................................................23
Closing Wait .......................................................................23
Entry Delay 1 .....................................................................23
Cross Zone Time.................................................................23
Zone Retard Delay ..............................................................24
Power Fail Delay .................................................................24
Swinger Bypass Trips ..........................................................24
Reset Swinger Bypass .........................................................24
Video/Alarm Verification ......................................................24
Time Zone Changes ............................................................25
Latch Supervisory Zones .....................................................25
Programming Menu Language ............................................25
User Menu and Status List Language ...................................26
Bypass Limit.......................................................................26
House Code .......................................................................26
Detect Wireless Jamming ....................................................26
Enable Keypad Panic Keys ...................................................27
SIA CP-01 ..........................................................................27
Output Options ...............................................................28
9.1
9.2
9.3
9.4
9.4.1
9.4.2
9.4.3
9.4.4
9.4.5
9.4.6
9.4.7
9.5
9.5.1
9.5.2
9.5.3
9.5.4
9.5.5
9.5.6
9.5.7
9.5.8
9.5.9
9.5.10
9.5.11
9.5.12
9.5.13
9.5.14
9.5.15
9.6
9.6.1
9.6.2
XR100 Series Programming Guide
Output Options...................................................................28
Bell Cutoff Time..................................................................28
Automatic Bell Test ............................................................28
Bell Action..........................................................................28
Fire Bell Action ...................................................................28
Burglary Bell Action.............................................................28
Supervisory Bell Action........................................................28
Panic Bell Action .................................................................28
Emergency Bell Action.........................................................28
Auxiliary 1 Bell Action..........................................................28
Auxiliary 2 Bell Action..........................................................28
Output Action .....................................................................28
Cutoff Output ....................................................................29
Output Cutoff Time.............................................................29
Communication Fail Output .................................................29
Fire Alarm Output ...............................................................29
Fire Trouble Output.............................................................29
Panic Alarm Output.............................................................29
Ambush Output ..................................................................29
Entry Output ......................................................................29
Exit Output.........................................................................29
Ready Output .....................................................................29
Telephone Trouble Output ...................................................30
Late To Close Output ..........................................................30
Device Fail Output ..............................................................30
Sensor Reset Output ...........................................................30
Closing Wait Output ............................................................30
Output Names ....................................................................30
Output Number .................................................................30
Output Name .....................................................................30
Digital Monitoring Products
iii
TABLE OF CONTENTS
Output Groups ................................................................31
10.1
10.2
10.3
10.4
Output Groups....................................................................31
Group Number....................................................................31
Group Name ......................................................................31
Output Number ..................................................................31
Menu Display...................................................................32
11.1
11.2
11.3
11.4
Menu Display .....................................................................32
Armed Status .....................................................................32
Time .................................................................................32
Arm/Disarm........................................................................32
Status List .......................................................................33
12.1
12.2
12.3
12.4
12.5
12.6
12.7
12.8
12.9
12.10
Status List .........................................................................33
Display Keypads .................................................................33
System Monitor Troubles .....................................................33
Fire Zones ..........................................................................33
Burglary Zones ...................................................................34
Supervisory Zones ..............................................................34
Panic Zones........................................................................34
Emergency Zones ...............................................................34
Auxiliary 1 Zones ................................................................34
Auxiliary 2 Zones ................................................................34
PC Log Reports................................................................35
13.1
13.2
13.3
13.4
13.5
13.6
13.7
PC Log Reports...................................................................35
PC Log Address ..................................................................35
Arm and Disarm Reports .....................................................35
Zone Reports......................................................................35
User Command Reports ......................................................35
Door Access Reports ...........................................................35
Supervisory Reports ............................................................35
Area Information ............................................................36
14.1
14.2
14.3
14.4
14.5
14.6
14.7
14.8
14.9.1
14.9.2
14.9.3
14.10
14.11
14.12
14.13
14.14
14.15
14.16
14.17
14.18
14.19
Digital Monitoring Products
iv
Area Information ................................................................36
Exit Delay ..........................................................................36
Burglary Bell Output ...........................................................36
Opening/Closing Reports .....................................................36
Closing Check.....................................................................37
Closing Code ......................................................................37
Any Bypass ........................................................................37
Area Schedules...................................................................37
Area Number......................................................................37
All/Perimeter Programming..................................................37
Home/Sleep/Away Programming..........................................37
Area Name .........................................................................37
Account Number.................................................................38
Automatic Arming ...............................................................38
Bad Zones..........................................................................38
Automatic Disarming...........................................................38
Armed Output Number........................................................38
Late Output Number ...........................................................38
Late Arm Delay...................................................................38
Common Area ....................................................................39
Arm First Area ....................................................................39
XR100 Series Programming Guide
TABLE OF CONTENTS
Zone Information............................................................40
15.1
15.2
15.3
15.4
15.5
15.6
15.7
15.8
15.9
15.10
15.10.1
15.10.2
15.10.3
15.10.4
15.10.5
15.11.1
15.11.2
15.11.3
15.11.4
15.11.5
15.11.6
15.11.7
15.11.8
15.11.9
15.11.10
15.11.11
15.11.12
15.12
15.13
15.14
15.15
15.16
15.17
15.18
15.19
15.20
15.21
15.22
15.23
15.24
Zone Information................................................................40
Zone Number .....................................................................40
Zone Name ........................................................................40
Zone Type ..........................................................................41
Area Assignment ................................................................41
Fire Bell Output ..................................................................41
Arming Zone Area Assignment .............................................42
Style ..................................................................................42
Next Zone ..........................................................................43
Wireless .............................................................................43
Serial Number Entry............................................................43
Contact ..............................................................................43
Supervision Time ................................................................44
LED Operation ....................................................................44
Next Zone ..........................................................................44
Key Fob User Number .......................................................44
Key Fob Serial Number........................................................45
Key Fob Supervision Time ...................................................45
Number of Key Fob Buttons ...............................................45
Key Fob Button Selection (Four Buttons) ..............................45
Key Fob Button Selection (Two Buttons) ..............................45
Button Action .....................................................................45
Button Press Time ..............................................................46
Arm/Disarm Area Selection..................................................46
Output Number ..................................................................46
Output Action .....................................................................47
Next Zone ..........................................................................47
Alarm Action ......................................................................47
Disarmed Open .................................................................47
Report to Transmit ..............................................................48
Output Number ..................................................................48
Output Action .....................................................................48
Swinger Bypass ..................................................................49
Prewarn Keypad Addresses..................................................49
Entry Delay ........................................................................49
Zone Retard Delay ..............................................................49
Presignal Addresses ............................................................49
Fast Response ....................................................................49
Cross Zone .........................................................................50
Priority ..............................................................................50
Stop.................................................................................51
16.1
Stop ..................................................................................51
Set Lockout Code ............................................................51
17.1
Set Lockout Code................................................................51
Feature Upgrade .............................................................52
18.1
18.1.1
18.1.2
XR100 Series Programming Guide
Feature Upgrade.................................................................52
All No Yes Option................................................................52
Service User Authentication .................................................52
Purchasing Feature Upgrades ..............................................52
Digital Monitoring Products
v
TABLE OF CONTENTS
Appendix .........................................................................53
19.1
False Alarm Reduction.........................................................53
System Recently Armed report.............................................53
19.2
Diagnostics function............................................................53
Test LX-Bus ........................................................................53
Zone Finder........................................................................53
Zone State .........................................................................53
LX-Bus Status .....................................................................53
MAC Address ......................................................................54
Serial Number ....................................................................54
Current Flash......................................................................54
Send Test Message .............................................................54
Exiting the Diagnostics program...........................................54
19.3
Using the 984 Command Function........................................54
NBR...................................................................................54
RMT .................................................................................55
PICKUP ..............................................................................55
Keypad Displays .................................................................55
19.4
Using the Walk Test ............................................................55
Walk Test ..........................................................................55
Zone Types ........................................................................56
Bell Action..........................................................................56
Trip Counter .......................................................................56
Test End Warning ...............................................................56
Failed Zones Display ...........................................................56
19.5
Keypad Speaker Operation ..................................................57
19.6
Cross Zoning ......................................................................57
19.7
Events Manager..................................................................57
19.8
User Profiles.......................................................................58
19.9
User Profiles Record............................................................59
19.10
Zone Type Descriptions .......................................................60
19.11
Zone Type Specifications ....................................................61
19.11.1 Keypad Bus Zone Type Defaults ...........................................61
19.11.2 LX-Bus Zone Type Defaults ..................................................62
19.12
Common Keypad Messages .................................................63
Listings and Approvals ....................................................64
Digital Monitoring Products
vi
XR100 Series Programming Guide
TABLE OF CONTENTS
This page intentionally left blank.
XR100 Series Programming Guide
Digital Monitoring Products
vii
REVISIONS
Revisions to This Document
This section explains the changes made to this document during this revision. It lists the date and identifies
the change(s) made, the related section number and section heading, and a summary of the change.
Date Section Number and Heading
1/07 3.3 Second Line
8.6 Zone Retard Delay
Quick Explanation of Changes
Removed Telephone from title.
Added Panic as a zone type option.
11/06 1.6 Power Up
3.2.2 Network Backup
3.2.3 Supervise Backup
Revised for SIA CP-01 option operation.
Option revised for new programming operation.
Option added for new programming operation.
Note: Subsequent section numbers changed.
3.2.6 Modem Setup
Added Supervise Backup operation information.
3.2.9 Substitution Code
Added note regarding Net Backup and Supervise Backup operation.
3.2.10 Check In
Added note regarding Net Backup and Supervise Backup operation.
5.4 Access Areas
Added note regarding All/Perimeter, Home/Sleep/Away operation.
5.5 Egress Areas
Added note regarding All/Perimeter, Home/Sleep/Away operation.
5.6 Display Areas
Added note regarding All/Perimeter, Home/Sleep/Away operation.
8.2 System
Option added for new programming operation.
Note: Subsequent section numbers changed.
8.4 Entry Delay 1
Added note regarding SIA CP-01 option operation.
8.19 SIA CP-01
Option added to enable specific SIA CP-01 operations.
14.2 Exit Delay
Added note regarding SIA CP-01 option operation.
14.8 Area Schedules
Added note regarding All/Perimeter, Home/Sleep/Away operation.
14.9.1 Area Number
Added note regarding All/Perimeter, Home/Sleep/Away operation.
14.9.2 All/Perimeter Programming
Option added for new programming operation.
14.9.3 Home/Sleep/Away Programming Option added for new programming operation.
14.12 Automatic Arming
Added note regarding SIA CP-01 UL installations.
14.14 Automatic Disarming
Added note regarding SIA CP-01 UL installations.
15.5 Area Assignment
Added All/Perimeter, Home/Sleep/Away operation.
15.7 Arming Zone Area Assignment
Added All/Perimeter, Home/Sleep/Away operation.
15.11 1100 Series Key Fobs
Added information regarding Key Fob user operation.
15.11.9 Arm/Disarm Areas
Added All/Perimeter, Home/Sleep/Away operation.
16.1 Stop
Revised for SIA CP-01 option operation.
19.9 User Profiles
Added note regarding All/Perimeter, Home/Sleep/Away operation.
19.12.1 Keypad Bus Zone Type Defaults Added Keypad Bus Zone Information Table with All/Perimeter, Home/
Sleep/Away operation and related Defaults list.
19.12.2 LX-Bus Zone Type Defaults
Added All/Perimeter, Home/Sleep/Away operation to LX-Bus Zone
Information Table and related Defaults list.
10/06 8.15 House Code
8.16 Detect Wireless Jamming
8.17 Enable Keypad Panic Keys
15.2 Zone Number
15.9 Next Zone
15.10 DMP Wireless
15.11 1100 Series Wireless Key Fob
19.11 Zone Type Specifications
19.12 Common Keypad Messages
Digital Monitoring Products
viii
Option added for new wireless programming operation.
Option added for new wireless programming operation.
Option added to allow override of Keypad two-button panic function.
Added zone numbers for new wireless programming operation.
Revised to cover new wireless programming operation.
Section added for new wireless programming options.
Added note regarding UL installations.
Section added for new wireless programming options.
Added note regarding UL installations.
Note: Subsequent section numbers changed.
Added revised table and text to reflect new DMP Wireless options.
Added new wireless keypad messages.
XR100 Series Programming Guide
INTRODUCTION
Introduction
1.1
Before you Begin
This guide provides programming information for the DMP XR100 and XR100N Command Processor™ Panel.
After this Introduction, the remaining sections describe the functions of each programming menu item
along with the available options. Before starting to program, we recommend that you read through the
contents of this guide. The information contained here allows you to quickly learn the programming
options and operational capabilities of the XR100 and XR100N panels.
In addition to this guide, you should also read and be familiar with the following XR100 Series documents:
• XR100 Series Installation Guide (LT-0899)
• XR100 Series Programming Sheet (LT-0897)
• XR500/XR100 Security Command® User’s Guide (LT-0683)
Internal Programmer
The panel contains all of its programming information in an on-board processor and does not require an
external programmer. You can perform all programming tasks through a 32-character DMP alphanumeric
keypad set to address one.
Programming Information Sheet
Included with each panel are the Programming Information Sheets. These list the various programming
prompts and available options for programming the panel. Before starting to program, we recommend you
completely fill out each sheet with the programming options you intend to enter into the panel.
Having completed programming sheets available before entering data helps prevent errors and can shorten
the time you spend programming. Completed sheets also provide you with an accurate panel program
record you can keep on file for future system service or expansion. The remainder of this Introduction
provides instructions for starting and ending a programming session using the alphanumeric keypad.
1.2
Getting Started
Ground Yourself Before Handling the Panel! Touch any grounded metal, such as the enclosure, before
touching the panel to discharge static.
Remove All Power From the Panel! Remove all AC and Battery power from the panel before installing or
connecting any modules, cards, or wires to the panel.
Before starting to program the XR100 Series panel, make sure the panel is properly grounded and AC
and battery power is applied to the appropriate panel terminals. All wiring connections and grounding
instructions are detailed in the XR100 Series Installation Guide (LT-0899).
XR100 Series Programming Guide
��
����������
��
������
��������
������������
����������������������������
����������������������������
������������������������
��
��������
������ ���
��� ��
���
������
�
��������
���
��
���
��������
�����
��
��
����
��������
���� ����
Accessing the Programmer
1. Install the reset jumper across the two J16
reset pins for two seconds.
2. Remove the reset jumper and place it over
just one pin for future use.
3. Enter the code 6653 (PROG) into a
32-character alphanumeric keypad set
to address one, supervised mode. Press
COMMAND.
Note: If the keypad displays ENTER CODE:,
a lock out code is required.
4. The keypad displays PROGRAMMER.
You are now ready to start programming the panel.
�� �� �� �� ���� ��� ��� ��� ��� ��� ��� ��� �� ��� ��
�
�
�
�
�
�
�
�
�
��
��
�� ��
��
��
���
��
��
��
�
���
�����
�����������
�� ��� �� �� ��� ��
�� ��
�� ��
��
��
�� ��� �� ��� ��� ���� ����
�� ��
��
��
��
��
��
��
Figure 1: XR100 Series Panel Showing Reset
Digital Monitoring Products
1
INTRODUCTION
1.3
Programmer Operation
There are 17 programming sections to choose from:
Programming Item
Section in this manual Programming Item Section in this manual
Initialization
2
Menu Display
11
Communication
3
Status List
12
Network Options
4
PC Log Reports
13
Device Setup
5
Area Information
14
Remote Options
6
Zone Information
15
System Reports
7
Stop
16
System Options
8
Set Lockout Code
17
Output Options
9
Feature Upgrade
18
Output Groups
10
To choose a section for programming, press any top row Select key when the keypad displays the name of
that section. Sections 2 through 18 contain detailed instructions for each programming step.
1.4
Programmer Lockout Codes
The panel allows you to enter the programming function without entering a lockout code using steps
1 to 4 listed in Getting Started. We recommend, however, that you install a Lockout Code to restrict
programming to only those persons your company authorizes. You can do this by using the SET LOCKOUT
CODE feature in the Programmer. The Lockout Code restricts any unauthorized panel programming.
After resetting the panel and entering the code 6653, the keypad displays PROGRAMMER. Press COMMAND
to advance through the programming sections until SET LOCKOUT CODE displays (after STOP). Press any
top row Select key. The keypad displays ENTER CODE: – . Enter a 3 to 5 digit Programmer Lockout Code
and press COMMAND. The keypad displays ENTER AGAIN followed by ENTER CODE: –. Enter the same 3 to
5 digit code a second time and press COMMAND. The keypad displays CODE CHANGED.
Note: The panel will not accept a 5-digit Lockout Code higher than 65535.
Before accessing programmer functions enter the new code number.
Write the Lockout Code number down and keep it in a secure place with access limited to authorized
persons only. Lost Lockout Codes require the panel to be sent back to DMP for repair. You may cancel a
Lockout Code by entering 00000 at the Set Lockout Code command.
1.5
Reset Timeout
The panel has a feature that requires you to enter the Programmer within 30 minutes of resetting the
panel. After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad
displays: RESET PANEL. You must reset the panel and enter the program code then begin programming
within the next 30 minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30 minutes,
the panel terminates programming. All data entered up to that time is Not saved unless you run the Stop
routine.
Note: Use the Stop routine to exit panel Programming. Ensure the keypad displays “SAVING PROGRAM”
to save all programming changes entered.
1.6
Power Up
When the SIA CP-01 option in System Options is set to Yes, for 60 seconds after power up or after applying
the J16 reset on the XR100 Series panel, any zone transitions are not recognized. Normal zone processing
resumes at the end of the 60 seconds.
Digital Monitoring Products
2
XR100 Series Programming Guide
INTRODUCTION
1.7
Keypads
DMP offers multiple keypads in a variety of styles. All DMP keypads provide the same programming
capabilities. Each keypad and its operation are shown and described in the following sections.
32-Character Display
��������������������
���������
���������
�
�
�
Power LED
������������
� � ���� � � � �������
�
�
�
�����������
�
�
���
�
���
�
�
�
� �� ��
�
� � �
�
��� ��
�
���
ABC PRINTING
F R I 2 : 51 AM
Armed LED
Select Keys
�
1
2
3
4
5
6
7
8
9
0
���
�
� ��
�������
��
�����������
CMD
COMMAND Key
Back Arrow Key
��������������
Data Entry Digit keys
����������������������
Figure 3: Security Command Keypad
Figure 4: Thinline/Aqualite Keypad
AC Power/Armed LED
32-Character
Display with
Four Touch
Select Areas
Data Entry
Digit Keys
FRI
2 : 51 AM
Logo
Icon
Three Panic Icons
Back Arrow Key
COMMAND Key
Figure 5: Clear Touch Keypad
1.8
Special Keys
The following special keys/areas are common to all DMP keypads.
COMMAND (CMD) Key
Pressing the COMMAND key allows you to go forward through the programming menu and through each
step of a programming section. As you go through the programming, the keypad display shows any current
programming already stored in the panel memory. If no change is required for a prompt, press the
COMMAND key to advance to the next step.
The COMMAND key is also used to enter information into the panel’s memory such as phone numbers or
zone names. Press the COMMAND key after entering information.
Back Arrow (<—) Key
Use the Back Arrow key to back up one step while programming. The Back Arrow key is also used when
an error is made while entering information. Press the Back Arrow key once to erase the last character
entered.
Select Keys/Areas
The top row of keys are called the Select keys on Security Command, Thinline, and Aqualite keypads or
Select Areas on Clear Touch keypads. Each time you need to press a Select key, the keypad displays the
function or options above one of the keys or in the Select Area. Displaying choices above individual Select
keys or in Select Areas allows them to be used for many different applications. For example, you can enter
AM or PM when programming the automatic test time or answer YES or NO for a system option.
During programming, the Select keys/areas also allow you to change information currently in panel memory
by pressing the appropriate Select key/area under or on the display. You then enter the new information
using the keypad data entry digit keys.
XR100 Series Programming Guide
Digital Monitoring Products
3
INTRODUCTION
When there are more than four response options available, press the COMMAND key to display the next one
to four options. Pressing the Back Arrow key allows you to review the previous four choices.
The Select keys/areas are also used for choosing a section from the programming menu. Press any Select
key or touch the Select Area when the programming section name you want displays.
Note: On Security Command, Thinline and Aqualite keypads, when instructed to press the first Select
key, press the far left Select key; the second Select key is the second from the left; third Select key is
second from the right; and the fourth Select key is the far right key. See Figures 6 and 7.
On Clear Touch Keypads, when instructed to press the first Select key, touch Select Area 1; the second
Select key touch Select Area 2; third Select key touch Select Area 3; and the fourth Select key touch Select
Area 4. See Figure 8.
1.9
Entering Alpha Characters
Some options during programming require you to enter alpha characters. To enter an alpha character,
press or touch the key that has that letter written below it. The keypad displays the number digit of the
key. Next, press the Select key/area that corresponds to the location of the letter under the key. Pressing
a different Select key/area changes the letter. When another digit key is pressed, the last letter displayed
is retained and the process starts over.
�
�
������������ �������������
�
A
�
������������
B
C
(
First Letter
Third Letter
Second Letter
Special Character
������������������
Figure 6: Security Command Select Keys
Figure 7: Thinline/Aqualite Select Keys
Select Area 2
Select Area 1
Select Area 3
Select Area 4
32-Character Display
Figure 8: Clear Touch Select Areas
1.10
Entering Non-Alpha Characters
To enter a space in an alpha entry, press the 9 digit key followed by the third Select key/area. The three
characters on the 9 digit key are Y, Z, and space. You can also enter the following characters: – (dash),
. (period), * (asterisk), and # (pound sign) using the 0 (zero) key and the four Select keys/areas from left
to right. For example, to enter a – (dash), press the 0 (zero) key and then the left Select key/area. A dash
now appears in the keypad display. Figures 9 and 10 show the character location for
Security Command, Thinline, and Aqualite keypads. Figure 11 shows the character
locations for Clear Touch keypads.
�����
�
������������
�
�
�������
����������
Figure 9: Security Command
Special Characters
Digital Monitoring Products
4
5
MN
9
O
YZ
2
3
7
DE
6
PQ
0
F
R
*
-.
4
8
GH
ST
I
U
L
JK
?
�����
�
C
X
,
�����
�
AB
!
�����
�
1
$
�����
)
�����
&
�����
#
�����
ABC( DEF) GHI!
(
�
/
�
'
�
(s
pa
ce
)
�
VW
CMD
Figure 10: Thinline/Aqualite
Special Characters
JKL? MNO/ PQR&
STU$ VWX, YZ
'
(SPACE)
–.*#
Figure 11: Clear Touch
Special Characters
XR100 Series Programming Guide
INTRODUCTION
1.11
Keypad Displays Current Programming
Each programming prompt displayed at the keypad shows the currently selected option in the panel
memory. These options are either shown as a number, a blank, or a NO or YES. To change a number or
blank to a new number, press any top row Select key or touch any Select Area. The current option is
replaced with a dash. Press the number(s) on the keypad you want to enter as the new number for that
prompt. It is not necessary to enter numbers with leading zeros. The panel automatically right justifies
the number when you press the COMMAND key.
To change a programming prompt that requires a NO or YES response, press the Select key or touch the
Select Area for the response not selected. See Figure 12.
For example, if the current prompt is selected as YES and you want to change it to NO, on Security
Command, Thinline, or Aqualite keypads press the third top row Select key. On Clear Touch keypads touch
Select Area 3. The display changes to NO. Press the COMMAND key to display the next prompt.
����������������������������
��������������������
���������
�������
�������
��������
��������
�������
����������������������������
���������������������������������
����
��������
���
��������
��
��������
���
��������
��
�����
�����
�������
��������
��������
���
��
Figure 12: Changing the Current Programming Option
1.12
Asterisks in Programming
Asterisks display next to a programming option that is already selected. As shown in the example, options
that are selected to display the current programming selection have an asterisk next to the number. Those
that are not selected simply display the number. In the Devices example, keypads 3, 6, and 8 are not
selected. In the Areas example, areas 3, 6, and 8 are not selected. In both examples the numbers with
asterisks are selected.
Devices
Areas
*1
*2
3
*4
*1
*2
3
*4
*5
6
*7
8
*5
6
*7
8
To select or deselect a number, simply enter the number using the digit keys on the keypad. This same
scheme is used when viewing the panel armed status and other programming and operational functions.
Remember to press the COMMAND key to display the rest of the device or area numbers.
XR100 Series Programming Guide
Digital Monitoring Products
5
INITIALIZATION
Initialization
NOTE: WHEN ANY PANEL PROGRAMMING IS CHANGED, THE STOP ROUTINE MUST BE RUN AND ‘SAVING
PROGRAM’ MUST DISPLAY ON THE KEYPAD IN ORDER TO SAVE THE PROGRAMMING CHANGES. SEE SECTION 17.1.
2.1
INITIALIZATION
Initialization
This function allows you to clear selected parts of the panel program back to the
factory defaults in preparation for system programming. Run the initialization
function on all new installations.
������������������������������������������
�����������������������������������������������
������
��
���
������������������������������
����������������������
�����
����������������������
�����������������������
�������
2.2
INIT ALL?
SURE?
NO YES
YES NO
���
��
���������������������������������������������������������
������������������������������������������������
��
���
�����������������������������������������������������
�������������������������������������������������������
������������
Clear All Memory
NO - Leaves existing programming intact then displays Clear All Codes.
YES - Clears all memory then displays Reset Panel. Reset the panel by shorting J16
and re-enter programming mode to continue.
2.3
CODES?
SURE?
NO YES
YES NO
Clear All Codes
NO - Leaves existing codes intact.
YES - Clears the user code and user profile memory and assigns user code number 99
to the highest user position.
Note: The user name for the default user code is created using the current
programmed primary user language.
2.4
SCHEDS?
SURE?
NO YES
YES NO
Clear All Schedules
NO - Leaves existing schedules intact.
YES - Clears all shift, and output schedules.
2.5
EVENTS?
SURE?
NO YES
YES NO
Clear Display Events Memory
NO - Leaves existing event memory intact.
YES - Clears the events memory.
2.6
ZONES?
SURE?
NO YES
YES NO
Clear Zone Information
NO - Leaves existing zone information intact.
YES - Clears the zone information for all zones. All zones are marked * UNUSED *
and must be renamed before being able to display on any system keypad.
2.7
AREAS?
SURE?
NO YES
YES NO
Clear Area Information
NO - Leaves existing area information intact.
YES - Clears the area information for all areas. All areas are marked * UNUSED * and
must be renamed before being able to display on any system keypad.
2.8
OUTPUTS? NO YES
SURE?
YES NO
Clear Output Information
NO - Leaves existing output information intact.
YES - Clears all programmed Output names and any output cutoff assignment.
Digital Monitoring Products
6
XR100 Series Programming Guide
INITIALIZATION
2.9
COM/RMT? NO YES
SURE?
YES NO
Clear Communication and Remote Options
NO - Leaves existing communication and remote options intact.
YES - Clears communication and remote options programming to factory defaults.
2.10
DEFAULTS NO YES
SURE?
YES NO
Set to Factory Defaults
NO - Leaves existing panel programming intact.
YES - Sets the remainder of the panel programming back to the factory defaults.
Note: Sets the Programming and User language to English.
XR100 Series Programming Guide
Digital Monitoring Products
7
COMMUNICATION
Communication
3.1
COMMUNICATION
Communication
Configure the communication options for the panel. The information you program
varies with the Communication Type you select.
3.2
COMM TYPE:
DD
Communication Type
Specifies the communication method the panel uses to report system events to DMP
SCS-1R Receivers or non-DMP receivers. Press any Select key/area.
NONE DD NET CID
NONE - For local systems. Selecting NONE ends communication programming.
DD - Digital Dialer communications to a DMP SCS-1 or SCS-1R Receiver.
NET (Network) - Asynchronous communication using the panel onboard network
connection (XR100N). The DMP Network/Output reporting format is transmitted over
an asynchronous data network to the SCS-1 or SCS-1R Receiver. If you need to send
a duplicate signal to the central station and you have selected NET, use Receiver 2
programming to send a duplicate digital dialer signal.
Note: When NET is selected, 2ND LINE programming allows you to select D2 for two
line supervision when using a Model 893A Dual Phone Line Module.
There are extra options available if you selected NET for the communication type.
These options are explained in the following sections.
CID - This option allows the panel to communicate to non-DMP receivers using
the Ademco Contact ID format. When selected, the panel sends all of its alarm,
trouble, and supervisory reports to the receiver(s) programmed in Receiver 1 and 2
Programming.
Note: To automatically switch from DD to a backup CID receiver see Section 3.19.
3.2.1
RETRY TIME: -
Retry Time
After selecting NET, the keypad displays RETRY TIME: -. Enter the number of
seconds (3 to 15 seconds) the panel should wait before retrying to send a message
to the receiver if an acknowledgment was not received. The panel retries as many
times as possible for a period of one minute before sending a network trouble
message. For example, if retry time is set to 15, the panel retries four times. The
default Retry Time is 5 seconds.
Note: If TCP is enabled, the minimum Retry Time programmed is 6 seconds.
3.2.2
NET BCKUP NO YES
Network Backup
Select YES to enable Network Backup and require panel messages to be sent to a
backup IP Address if the messages fail to communicate to the remote (primary) IP
address. Select NO to disable Network Backup. Default is NO.
Note: When Network Backup is set to YES, a Modem Setup String is required to send
messages to a backup IP address. See Modem Setup.
Note: Second line programming is available for dialer communication types such as
CELL or DD to backup network communications.
3.2.3
SUPERVISE BACKUP
NO YES
Supervise Backup
When Network Backup is set to YES, the Supervise Backup option displays. Select
YES to enable supervised communication and send checkins to the network Central
Station receiver for Network Backup. Select NO to disable Supervise Backup. Default
is NO.
Programming options for supervision of Network Backup is provided by the same
options used by the Communications Type programming for UL AA, Check In Time,
and Fail Time. If Substitution Code is programmed YES, then it is automatically
enabled for Network Backup. When Supervise Backup is set to YES, Net Trouble
only displays on the keypad if both remote (primary) and backup IP address
communications fail.
Digital Monitoring Products
8
XR100 Series Programming Guide
COMMUNICATION
3.2.4
RMT IP ADDRESS: Remote IP Address
000.000.000.000 Enter the remote (primary) IP address where the panel sends network messages.
The Remote IP Address must be unique and cannot be duplicated on the network.
Enter all 12 digits and leave out the periods. For example, enter IP address
192.168.0.250 as 192168000250. The periods display automatically.
3.2.5
ALARM PORT: -
3.2.6
2001
MODEM SETUP:
-
Alarm Port
Enter the receiver port number. Default port number is 2001. If a different Port
number is needed, enter the new number. Valid range is 1 to 65,535.
Modem Setup
The keypad displays MODEM SETUP:. Press COMMAND. Enter up to two lines of 16
characters to equal up to 32 characters for the backup receiver string address.
When Network Backup is set to YES, enter the backup IP address to receive panel
messages and enter a Modem Setup String.
The Modem Setup String for the Network Backup should be entered as follows:
AT#UCXXX.XXX.XXX.XXX#PPPPP. Also enter the UDP Port Number in place of the Ps.
The default port number is 2001. To enter the # (pound sign), press 0 (zero) and the
far right top row Select key. To enter . (periods), press 0 (zero) and the second from
the left Select key. Enter the backup IP Address in place of the Xs.
Note: If the onboard network interface connection J1 (XR100N only) is being used for
the main network communication (Network Backup is NO), do NOT enter a Modem
Setup String here.
To use the Network Backup and Modem Setup features to send messages through the
backup Network use the onboard network interface connection J1 on the XR100N
and assign the Modem Setup String to route the backup messages through J1 to the
backup receiver.
3.2.7
UL AA
NO YES
UL AA
At the UL AA prompt, select Yes to enable AA Mode or NO to disable AA Mode. NO is
the default setting. UL AA involves check-in reports. Check-in reports are a method
of supervising the communication between the panel and the receiver. To be UL AA
compliant, panels must check-in with the receiver every 6 minutes when armed.
The SCS-1R Receiver verifies that the next Check-in report is received at the
appropriate time. SCS-1/805 or higher firmware is required in the SCS-1 Receiver.
When AA is selected and the check-in fails after one minute, the panel sends a
WARNING: NETWORK TROUBLE (S72) report on the 2ND LINE. The next time the NET
report is successfully sent, the panel sends a NETWORK RESTORED (S73) report over
the 2ND LINE.
If you select YES for UL AA, the DISARM CHKIN prompt displays.
DISARM CHKIN RND
MINUTES: RND
XR100 Series Programming Guide
Disarm Checkin
Press any Select key to display Minutes: - RND. Enter the number of minutes,
from 1 to 6, between disarmed check-in reports. If any area is armed, the
report is automatically sent every 6 minutes.
To select RND (Random), press the top right Select key. RND is the default
setting. Selecting RND causes the panel to send the Check-in report at random
times. When all areas are disarmed, the panel sends the report randomly but
always between 5 to 60 minutes. If any area is armed, the panel sends the
report every 6 minutes.
Note: NET TRBL, Network Fail Notification, is automatically enabled when UL
AA is enabled. NET TRBL allows the panel to detect a primary network failure,
send an S72, Network Trouble message, through the DD if it is programmed as
the second line. When the primary network restores the panel sends an S73,
Network Restored message.
Digital Monitoring Products
9
COMMUNICATION
3.2.8
3.2.9
NET TEST
NO YES
SUB CODE NO YES
Network Test
Select YES to send an S97 network test message to the Central Station receiver over
the network based on the Test Time and frequency programmed in Communication.
Select NO to not send an S97 network test message over the network. The default is
NO.
Note: The S97 test message is specific to network operation. The S88 and S07
messages are specific to and only sent using the digital dialer. Having separate
test messages for network and digital dialer operation allows the Central Station to
identify the communication path used to send the message.
Substitution Code
Select YES if the panel sends a Panel Substitution Code when communicating
with the receiver. The Panel Substitution Code increases the level of security
by helping to ensure that the panel sending the message to the receiver has not
been substituted by another panel. The default is NO. When UL AA is YES, the
substitution code is always sent.
When Substitution Code, Network Backup, and Supervise Backup are set to YES, the
Substitution Code is sent to both the remote (primary) and backup IP addresses.
When Substitution Code and Network Backup are set to YES and Supervise Backup is
set to NO the Substitution Code is only sent to the remote (primary) IP address.
3.2.10 CHECKIN:
6
Check In
Enter the number of minutes, from 0 to 240, between check-in reports when the
panel is armed or disarmed. Check-in reports are a method of supervising the panel
for communication with the receiver. Enter 0 (Zero) to disable the check-in. The
default is 6 minutes.
When Supervise Backup is set to YES, the Check In is sent to both the remote
(primary) and backup IP addresses. Set the Check In Time to a minimum of 3
minutes when Net Backup is set to YES. When Supervise Backup is set to NO the
Check In is only sent to the remote (primary) IP address.
Check In messages sent to the remote (primary) and backup IP addresses continue to
be sent at the same intervals over both communication paths.
Note: When used for Fire Protective Signaling, the Check-in Time should not exceed
1 minute.
3.2.11 FAIL TIME:
6
Fail Time
Entering a FAIL TIME allows the receiver to miss multiple check-ins before logging
that the panel is missing. For example, if CHECKIN is 10 and FAIL TIME is 30, the
receiver only indicates a Panel Not Responding after 30 minutes. The FAIL TIME must
be equal to or greater than the CHECKIN time: If the CHECKIN is 10 minutes, the
FAIL TIME must be 10 or more minutes. The maximum FAIL TIME is 240 minutes. The
default is 6 minutes.
3.2.12 NET TRBL NO YES Network Trouble
Select YES to enable Network Fail Notification. When UL AA is enabled, this feature
is automatically enabled.
When NET TRBL is YES and the panel detects a primary network communication
failure, the panel attempts to send an S72, Network Trouble message, through NET
then through digital dialer when it is programmed as the second line. Also, the
trouble keypads sound a continuous tone and displays “NETWORK -TRBL.” Press any
key to silence the tone.
When the primary network restores, the panel sends an S73, Network Restored
message, through NET then through the digital dialer if it is programmed as the
second line. The “NETWORK -TRBL” display is removed from the keypad and the
tone automatically silences.
Digital Monitoring Products
10
XR100 Series Programming Guide
COMMUNICATION
3.3
2ND LINE:
NONE
Second Line
Allows you to use a second communication line to send reports to the SCS-1R
Receiver should the first communication type fail. The default is NONE.
If 2ND LINE is DD and the Comm Type programming is DD, you need to install a DMP
893A Dual Phone Line Module to connect both the main and secondary phone lines to
the panel.
NONE DD CELL NET
NONE - A second line is not used.
DD - Dialer communication to a DMP SCS-1R Receiver. When using CID as the main
Communication Type, choose DD to communicate to a CID receiver on the 2ND LINE.
CELL - Cellular dialer communication with Cell-Miser™ restrictions. When Cell-Miser
is selected, the following call restrictions apply to the panel.
1. Only zone alarms, Ambush, Line 1 Trouble, Abort, Recall Test, and Delayed
Events are sent over the cellular system. Delayed Events are only sent if the
cellular call was made for one of the other allowed reports.
2. Line 1 Trouble is sent only once during each armed period.
3. The dialing sequence uses the first phone number on line 1 only and the second
phone number on line 2 only. This allows the panel to use the cellular phone
number for cellular calls only without needing prefixes or area codes for land
line dialing.
If 2ND LINE = DD
If 2ND LINE = CELL
Panel dials the 1st ph # twice on Line 1
Panel dials the 1st ph # twice on Line 1
Panel dials the 1st ph # twice on Line 2
Panel dials the 2nd ph # twice on Line 2
Panel dials the 2nd ph # twice on Line 1
Panel dials the 1st ph # twice on Line 1
Panel dials the 2nd ph # twice on Line 2
Panel dials the 2nd ph # twice on Line 2
Panel dials the 1st ph # twice on Line 1
Panel dials the 1st ph # twice on Line 1
NET (NETWORK) - DMP Asynchronous communication to a DMP SCS-1R Receiver or
Network automation system. If NET is selected as the main Communication Type,
NET does not display as an option in 2ND LINE. If NET is selected for 2ND LINE, all
zone alarms and restorals are duplicated on the asynchronous channel in addition to
the main communication method.
NONE DD
3.4
232
D2
232 is not supported in XR100 Series panels.
D2 only displays if NET is the main Communication type.
D2 - Select D2 to allow supervision of a second telephone line connected to a Model
893A Dual Phone Line Module.
TEST FREQ:
NONE
Test Frequency
NONE REG
7
NONE - No communication test is made on the second line. NONE is selected by
default.
REG - A 2ND LINE communication test is made each time the regular communication
test completes.
7 - A communication test is made every 7 days at the test time programmed for the
regular communication test. Test time deferrals are disregarded.
30 - A communication test is made every 30 days at the test time programmed for
the regular communication test. Test time deferrals are disregarded.
30
Specifies the communication test interval for the second phone line. This is
displayed if 2ND LINE is programmed as DD, CELL or NET.
If the 2ND LINE test fails to communicate after 10 attempts, the regular
communication channel sends a Warning: Panel Backup Communication Fail (S12)
report. The next time the panel sends a report over the 2ND LINE, the regular
communication channel sends a Backup Communication Line Restored (S04) report.
XR100 Series Programming Guide
Digital Monitoring Products
11
COMMUNICATION
3.5
3.6
NET FAIL TST : X
0 2HR 4HR 8HR
NET Fail Test
ACCOUNT NO: 12345
Account Number
The time programmed in NET Fail Test increases the dialer test frequency
programmed in Test Time during NET failure. Press any top row Select key to choose
a 2, 4, or 8-hour interval between digital dialer contact attempts. The digital dialer
sends an S88, Automatic Recall Unrestored System message or an S07, Automatic
Recall Test message at the programmed minutes indicated in the Automatic
Recall Test Time. Select 0 (zero) to disable a more frequent dialer test when NET
communications fail. The default is 0 (zero).
Enter the account number sent to the SCS-1R Receiver.
DD and NET - The range of valid account numbers for a panel using DD or NET is 1 to
65535. For accounts of four digits or less, do not enter leading zeros.
CID - Choose an account number between 1 to 9999.
3.7
30
XMIT DELAY:
Transmit Delay
Enter the number of seconds (15 to 45) the panel waits before sending burglary,
night, day, or exit reports to the receiver. Other zone type reports are sent
immediately. Alarm bells and relay outputs are not delayed during this period.
Program Burglary Outputs for pulsed or steady, and set Abort Reports to YES if
Opening and Closing reports are not being sent. Enter 0 (zero) to disable this
function. The default is 30.
If the area where the alarm occurred is disarmed during the Transmit Delay time,
only an Abort Report (S45) message is sent to the receiver. If the area where
the alarm occurred is disarmed after the alarm message is sent to the receiver
but before the Bell Cutoff time expires even if the alarm was silenced, an Alarm
Cancelled (S49) message is sent. The Alarm Cancelled report cannot be disabled.
Note: For UL Installations, the combined Transmit Delay (Abort Window) and
Entry Delay must not exceed one (1) minute.
3.8
DTMF
NO YES
DTMF
YES enables tone dialing by the panel. NO enables rotary dialing.
3.9
3.10
DFR TEST
NO YES
TEST FREQ
0
Defer Test
Select YES to allow the programmed test report to be deferred if the panel
communicates with a receiver within the time set in Test Frequency. Select NO to
send the test report as programmed regardless of previous panel communication.
Test Frequency
Allows you to set how often the panel sends a test report to the SCS-1R Receiver.
Enter from 1 to 60 days. This prompt does not display if Defer Test Time is NO.
3.11
TEST TIME
0:00 AM PM
TEST DAY:
ALL
Test Time
SUN MON TUE WED
THU FRI SAT ALL
Press the COMMAND key to display the first four days of the week. Press the
COMMAND key to display the last three days and ALL. Select the day of the week to
send the test report. Default is ALL days.
2HR 4HR 6HR 12HR
If more frequent testing is required, press the COMMAND key to display 2HR, 4HR,
8HR, or 12HR instead of making one of the daily selections. Select the number of
hours required between test reports. When programmed, the test occurs at the
programmed minutes indicated in the Automatic Recall Test Time.
Digital Monitoring Products
12
Enter the time of day the panel sends the test report to the SCS-1R Receiver. Use
entries between 12:00 to 11:59 and then choose AM or PM. When Defer Test Time is
set to NO, this option allows you to program the day of the week the test report is
sent.
XR100 Series Programming Guide
COMMUNICATION
3.12
EVENT MGR:
SEND
Events Manager
Specifies when non-alarm reports are sent to the receiver. This selection does not
affect zone alarm, zone trouble, zone restoral, supervisory, or serviceman messages.
Closing reports are not delayed if the Closing Wait option is YES. Contact ID does not
delay reports but send them as they occur.
SND DLY
KEEP
SND - All reports are sent to the receiver as they occur.
DLY - All non-alarm reports are held until the panel memory buffer contains 50
events or until the next panel communication with the receiver.
KEEP - All non-alarm reports are held in the panel memory buffer until they are
overwritten by new activity. You can view the contents of the memory buffer using
DMP Remote Link™ or System Link™. You can also use the display events feature in
the User Menu. Refer to the Appendix for a table listing the delayed report types.
3.13
3.14
RECEIVER 1 PROG
ALARM
NO YES
Receiver One Programming
Allows you to set the options for the first receiver the panel attempts to contact
when sending reports. The panel supports communication to two receivers.
Alarm Reports
YES sends Abort, Alarm, Alarm Restoral, Alarm Cancelled, Ambush, Exit Error, and
System Recently Armed reports to this receiver.
3.15
SPV/TRBL
NO YES
Supervisory/Trouble Reports
YES sends Supervisory, Trouble, Trouble Restoral, Force Armed, Zone Fault reports,
and Serviceman Messages to this receiver. The Supervisory/Trouble report is only
sent if the keypad number has also been selected in Access Keypads under the
SYSTEM REPORTS programming.
3.16
O/C USER
NO YES
Opening/Closing and User Reports
YES sends Opening, Closing, Late to Close, Unauthorized Entry, Schedule and Code
changes, Zone Reset, and Zone Bypass reports by user to this receiver.
3.17
TEST RPT
NO YES
Test Report
Enter YES to enable the system test report to be sent to this receiver. Reports are
sent according to the programming in Test Frequency and Test Time.
3.18
DOOR ACS NO YES
Door Access Report
YES enables Door Access Granted reports to this receiver whenever a door access is
granted to a user. The Door Access Granted report is only sent if the keypad number
has also been selected in Access Keypads under the SYSTEM REPORTS programming.
Note: The following three prompts and Receiver 2 programming prompts do not
display if COMM TYPE is NET, NET BACKUP is NO, and 2ND LINE is NONE.
3.19
BACKUP
NO YES
Backup Reporting
Enter YES to enable this receiver to be a backup to the other receiver in the event
the other receiver cannot be contacted.
XR100 Series Programming Guide
Digital Monitoring Products
13
COMMUNICATION
3.20
FIRST PHONE NO.
-
First Telephone Number
This is the first number the panel dials when sending reports to this receiver. Phone
numbers can have two lines of 16 characters each to equal up to 32 characters.
Enter a P to program a two second pause in the dialing sequence. The P character
counts as part of the 32 allowable characters. No dial tone detect “D” is required.
Dial tone detect is an automatic panel function.
Automatic CID communication: You can place a letter “T” in the telephone
number first position to allow a message to be sent to the receiver using CID
communications. Once the CID message is sent, subsequent messages are sent using
the communications method selected under Communication Type until another
telephone number with a “T” in the first position is encountered. This option allows
capture by AES radio or CID backup communication to a CID receiver using a specific
telephone number.
The automatic backup CID communication feature allows for the following
communication options:
DD with CID second number
NET with DD second line
NET with CID second line
NET with DD/CID second line
For example, program NET with second line DD and phone number T555-1212, and
you have NET with CID second line.
Call Waiting: You can place the “* 7 0 P” (Star, Seven, Zero, Pause) in the telephone
number first position to cancel Call Waiting. For example, program NET with second
line DD and phone number *70P555-1212, and you have NET with Call Waiting
cancelled on the second line.
Caution: A call waiting cancel programmed on a non-call waiting telephone line,
would prevent communication to the central station.
3.21
SECOND PHONE NO.
-
Second Telephone Number
The panel dials the second number when two successive tries using the first number
fail. If the panel cannot reach the receiver after two attempts using the second
number, it returns to the first number and makes two additional attempts. A total of
ten dialing attempts are made using the first and second phone numbers.
Each number can be up to 32 characters in length including any P, T, or
*70P characters entered for pause, area code for cellular connections, CID
communication, or call waiting cancel option.
Should all ten attempts fail, the panel clears the communication buffer and makes
one communication attempt each hour to send a TRANSMIT FAILED (S87) report
to the receiver. Access the User Menu Display Events feature to view the report
information not sent to the receiver or download the report with DMP Remote Link™
software.
3.22
3.23
RECEIVER 2 PROG
ALARM
NO YES
Receiver Two Programming
Allows you to set the options for the second receiver the panel attempts to contact
when sending reports. If you select YES for any of the second receiver options,
you must have at least one phone number programmed in Receiver 2 programming.
RECEIVER 2 PROG and the following prompts are not displayed if COMM TYPE is NET
and 2ND LINE is NONE.
Alarm Reports
See section Alarm Reports on previous page.
3.24
SPV/TRBL
NO YES
Supervisory/Trouble Reports
See section Supervisory/Trouble Reports on previous page.
Digital Monitoring Products
14
XR100 Series Programming Guide
COMMUNICATION
3.25
O/C USER
NO YES
Opening/Closing and User Reports
See Opening/Closing and User Reports on previous page.
3.26
TEST RPT
NO YES
Test Report
See Test Report on previous page.
3.27
DOOR ACS NO YES
Door Access Report
See Door Access Report on previous page.
3.28
BACKUP
NO YES
Backup Reporting
See Backup Reporting on previous page.
3.29
3.30
FIRST PHONE NO.
-
First Telephone Number
SECOND PHONE NO.
-
Second Telephone Number
XR100 Series Programming Guide
Enter the phone number the panel dials to send reports to the receiver.
Note: All phone numbers can be up to 32 characters. Enter the letter P to program
a two second pause in the dialing sequence. Enter the letter T as the string first
character to enable the CID message communication format option. Enter *70P as
the string first characters to cancel call waiting. These characters count as part of
the 32 allowable characters. No dial tone detect D is required. Dial tone detect is
an automatic panel function.
The panel dials the second number when 2 successive tries using the first number
have failed. If the panel cannot reach the receiver after two attempts using the
second number, it returns to the first number and makes two additional attempts.
A total of 10 dialing attempts are made using the first and second phone numbers.
Note: All phone numbers can be up to 32 characters. Enter the letter P to program
a two second pause in the dialing sequence. Enter the letter T as the string first
character to enable the CID message communication format option. Enter *70P as
the string first characters to cancel call waiting. These characters count as part of
the 32 allowable characters. No dial tone detect D is required. Dial tone detect is
an automatic panel function.
Digital Monitoring Products
15
NETWORK OPTIONS
Network Options (XR100N only)
Note: IP addresses and port numbers may need to be assigned by the network administrator. When
entering an IP, Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods.
For example, IP address 192.168.000.250 is entered as 192168000250.
4.1
DHCP
4.2
LOCAL IP ADDRESS
Local IP Address
192.168.5.227 Enter the local IP address. The Local IP Address must be unique and cannot be
duplicated. The default local IP address is 192.168.0.250.
4.3
GATEWAY ADDRESS
Gateway Address
0.0.0.0 Enter the local gateway address. The Gateway IP Address is needed to exit your
local network. The default gateway address is 192.168.0.125.
4.4
SUBNET MASK
Subnet Mask
255.255.255.0 Enter the local subnet mask assigned to the panel. The default subnet mask address
is 255.255.255.000.
4.5
PROGRAMMING PORT
2001
Programming Port
TCP COMM: NO YES
TCP Comm Enabled
4.6
NO YES
DHCP Mode Enabled
If the panel uses a dynamic IP address Select YES. When set to YES the panel must
operate in DHCP and must not use the Local IP Address number. When the DHCP
option is set to NO, the panel must use the IP address entered in Local IP Address.
The default value for DHCP mode is YES.
Enter the programming port number. The programming port identifies the port used
to communicate messages to and from the panel. The default Programming Port
setting is 2001.
When this option is set to NO, the panel communicates over the network using
standard UDP protocol. When this option is set to YES, the panel communicates
using TCP protocol. The TCP communications default value is NO.
Digital Monitoring Products
16
XR100 Series Programming Guide
DEVICE SETUP
Device Setup
5.1
Device Setup
DEVICE SETUP
This section allows you to define the XR100 Series panel physical configuration. You
can install and address up to sixteen supervised devices on the keypad data bus.
5.2
DEVICE NO:Device Number
DEVICE 1: STNDRD Enter the device number on the keypad bus you are programming. The keypad bus
can have up to 8 devices.
Note: After you program each option for the first device, repeat these programming
steps for each additional devices.
STD FIRE
NONE
STANDARD - The device is either a Security Command keypad, a zone expander
device, or a 733 Wiegand Interface Module or 734 Wiegand Interface Module.
FIRE - The device is a Model 630F Remote Fire Command Center.
NONE - No device is set for this address.
5.3
DOOR NAME 1
Door Name
The door name displays. To change the name, press any top row Select key then
enter up to 16 characters for the door name. Press COMMAND to continue device
setup programming.
5.4
5.5
ACCESS AREAS:
1
2
3
5
6
7
EGRESS AREAS:
1
2
3
5
6
7
XR100 Series Programming Guide
Access Areas
4 Press the COMMAND key to program Access Areas. To select an area, enter the area
8 number using the digit keys on the keypad. When an area is selected, an asterisk
appears next to the area number. Enter the number again to deselect the area.
Refer to the Multiple Displays section at the beginning of this document.
Users must have matching access area numbers assigned to their code to receive a
door access at this device.
If you do not enter any area numbers, all users with Door Access authority receives
a door access without regard to schedules. If the user code is programmed for
Anti-Pass YES, then the user is logged into all matching areas. This user is not
allowed to access these areas again until they have egressed the area. See Egress
Areas.
Note: For an All/Perimeter or Home/Sleep/Away system, Access Areas should be
left at factory default settings.
Egress Areas
4 Press the COMMAND key to program Egress Areas. To select an area, enter the area
8 number using the digit keys on the keypad. When an area is selected, an asterisk
appears next to the area number. Enter the number again to deselect the area.
Refer to the Multiple Displays section at the beginning of this document.
Note: For an All/Perimeter or Home/Sleep/Away system, Egress Areas should be
left at factory default settings.
Note: If an area is programmed as an access area, it cannot be programmed as an
egress area and therefore does not display during Egress Areas programming.
Use this option to detect Anti-passback violations. Anti-passback requires a user to
properly exit (egress) an area they have previously accessed. If users fail to exit
through the proper card reader location they are not granted access on their next
attempt. Users must have matching access area numbers assigned to their profile,
to receive a door access at this device. If the user is programmed for Anti-Pass
YES, then the user is logged out of all matching areas. This allows the user to again
access the area. See Access Areas section.
If you do not enter any area numbers, all users with Door Access authority receives a
door access without regard to schedules. If you are not using the Anti-Pass feature
leave Egress Areas blank.
Digital Monitoring Products
17
DEVICE SETUP
5.6
DISPLAY AREAS:
*1 *2
*3
*5 *6
*7
Display Areas
*4 Press the COMMAND key to program Display Areas. To select an area between 1 and
*8 8, enter the area number using the keypad digit keys. When an area is selected,
an asterisk appears next to the area number. Enter the number again to deselect
the area. Default is all area numbers. Refer to the Multiple Displays section at the
beginning of this document.
Display Areas allows the XR100 Series burglary activities to be segmented so that
only specific area(s) and their associated operation appear at a particular keypad.
Area number(s) selected in this field affect the way users interact with the system
from this particular device. For example: Program Device 1 to show only the zone
activities and armed status of Area 1.
Enter the area number(s) that this keypad is to display. This allows specific area
control from specific keypads, as well as annunciation of zones assigned to those
area(s). When Display Areas is left defaulted (all areas selected), Menu Display and
Status List items determine whether zone alarms and troubles display at this device,
regardless of area assignment. Also, all system areas may be armed and disarmed
from this device.
Note: For an All/Perimeter or Home/Sleep/Away system, Display Areas should be
left at factory default settings.
User Action Allowed
When an area(s) is selected, the following user actions are allowed:
• Arming or Disarming of the area(s) selected from the ARM or DISARM menu
• Zone Bypass of zones assigned to the area(s) selected
• Zone Monitor of zone assigned to the area(s) selected
• Shift schedule changes allowed for the area(s) selected
• Closing Check Schedule Extend is allowed for the area(s) selected
• Door Schedules changes are allowed for devices that have a matching area(s)
as defined in Device Access Areas
• Door On/Off Menu operation is allowed for devices that have a matching area(s)
as defined in Device Access Areas
Note: The previous user actions also require the matching area(s) be programmed in
User Profile: Arm/Disarm area(s).
Status Display Allowed
When an area(s) is chosen, the following displays are allowed:
• Armed Status of the selected area(s)
• Zone Alarms and troubles for burglary (NT, DY, EX, A1, A2) type zones assigned to
the selected area(s)
• Late to Close status of the selected area(s)
• Zone Status (normal/fault) of zones that are assigned to the selected area(s)
Options and Actions Not Affected
The following options are not affected by the Display Areas operation. The User
Code authority level controls access to these items.
• Alarm Silence
• Sensor Reset Menu
• Outputs On/Off Menu
• System Status Menu
• System Test/Panic Test
• User Profiles
• Forgive Anti-Passback • Set System Time and Date • Display Events
• Service Request
• Fire Drill
• 24-hour zones display at keypads based on Status List programming only
Note: A common area and its operations cannot be assigned to a specific keypad
Display Areas example: When Device 1 has Display Areas set to 3, 5, and 8, it
annunciates troubles and alarms only for zones assigned to those areas. When
arming/disarming from Device 1, only areas 3, 5, and 8 may be armed/disarmed,
even when the User Profile has authority to arm/disarm other system areas.
Exception: Disarming of other areas not selected in Display Areas can be
accomplished by presenting a card that has disarming authority and matching profile
areas with areas assigned in Device Access Areas.
Digital Monitoring Products
18
XR100 Series Programming Guide
DEVICE SETUP
5.7
STRIKE TIME:
5
Strike Time
Enter a door access time, between 1 and 250 seconds, during which a keypad or
access control device relay is activated. Magnetic locks or electric door strikes are
connected to the relay and released for the length of the strike time. Default is 5
seconds.
Enter 0 (zero) to activate the device relay with a toggle action. This allows the user
to activate or deactivate the device relay each time a valid user code is entered.
The device relay is activated or deactivated until a user code is entered again.
Note: The Request to Exit door access time of a keypad or Model 733 Wiegand
Interface Module is not affected by this selection. It remains at 5 seconds.
5.8
STRIKE DELAY:
0
Strike Delay
Enter the number of minutes, 0 to 9, to delay a door strike after a valid code is
entered or a card read occurs. When a valid code or card read or code is received,
the activation of the door strike is delayed for the number of minutes programmed.
The standard door strike message is sent to the Central Station receiver and logged
in the Display Events at the time of card read or code entry and is not delayed.
During this delay, all subsequent codes entered or cards presented to the reader for
a door strike are ignored and no record of the attempt is stored. Enter 0 (zero) to
disable. Default is 0 (zero).
5.9
FIRE EXIT
5.10
OUT GROUP NO YES
5.11
OVERRIDE NO YES
NO YES
Fire Exit Release
Select YES to allow the door access relay at this address to be released whenever
Fire panic keys are pressed or a Fire or Fire Verify zone alarm is in the Status List.
The relay is reset whenever a Sensor Reset is performed to remove all Fire and Fire
Verify zone alarms from the Status List. Select NO to not allow the door access relay
at this address to be released.
Output Group
Select YES to allow the output group (relays) assigned to the user profile to turn ON
when the device relay is activated for the programmed strike time. This could be
used to operate an elevator control. Default is NO. See the User Profiles section in
the Appendix of this document for more information about profiles.
Schedule Override
Use this option to allow door ON/OFF schedules to be overridden by the armed
condition of the system. Selecting YES causes the on time for a door schedule to be
ignored when all areas assigned to Access Areas for this device are armed. Should
any area become disarmed after the door schedule on time, the device output turns
on. A door output which is on during a disarmed period automatically turns off when
all access areas assigned to the device become armed, even if the scheduled off
time has not been reached. This feature can be used to keep doors locked when a
factory opens late, or is forced to close early, due to a snow storm or other cause.
Select NO to allow door schedules to operate independent of system armed status.
Note: When OVERRIDE is YES and there are no areas programmed in ACCESS AREAS,
the door schedule for that device does not work. Either set OVERRIDE to NO or
enter an area number in ACCESS AREAS.
5.12
AUTO FORCE ARM
DEVICE?
NO YES
XR100 Series Programming Guide
Auto Force Arm Device?
Select YES to have all Display Areas assigned to this keypad automatically arm and
force arm faulted zones at arming. The user is not prompted to select areas to
arm or force arm faulted zones after choosing ARM at the keypad. If Closing Code
is programmed as YES, only the matching areas between the Display Areas and
the User Code’s authorized areas arm. Also, when YES is selected, the user is not
prompted to select areas to disarm after entering a code at Entry Delay or after
choosing Disarm at the keypad. All matching areas assigned to the User Code and to
this keypad are automatically disarmed. When NO is selected, the user is prompted
to select areas (ALL NO YES) and choose to force arm or bypass at arming and
disarming. Default is NO.
Digital Monitoring Products
19
REMOTE OPTIONS
Remote Options
6.1
Remote Options
REMOTE OPTIONS
This section allows you to enter the information needed for Remote Command/
Remote Programming operation.
6.2
Remote Key
RMT KEY:
This option allows you to enter a code of up to eight digits for use in verifying
the authority of an alarm or service receiver to perform a remote command/
programming session. The Remote Link™ program must give the correct key to the
panel before being allowed any remote functions. All panels are shipped from the
factory with the key preset as blank.
To enter a remote key or change the current one, press a top row Select key and
enter any combination of up to eight digits. Press COMMAND. The current key never
displays.
6.3
MFG AUTH NO YES
Manufacturer Authorization
Select YES to allow DMP Technical Support technicians to access the panel during
system service or troubleshooting. This authorization automatically expires within
one hour.
DMP remote service is provided on a read only basis: DMP technicians can look
at the system programming and make suggestions only. Alterations can only be
accomplished by installing company service personnel.
6.4
ARM RINGS:
0
Armed Rings
Enter the number of rings the panel counts before answering the phone line when
all system areas are armed. Any number from 1 to 15 can be entered. If 0 (zero)
is entered, the panel does not answer the phone when all system areas are armed.
The default Armed Rings is 0 (zero).
Answering machine bypass procedure: Entering a number greater than 0 (zero) into
either Armed Rings or Disarmed Rings, allows a central station operator to connect
remotely with the panel.
How it works: The operator calls the panel, allows the telephone to ring one time,
and then hangs up. The panel stores this as an attempt to communicate. The
operator then calls back within 30 seconds. The panel seizes the telephone line to
allow remote programming.
Note: This feature does not interfere with the normal operation of the Arm Rings or
Disarm Rings functions.
6.5
DISARM RINGS:
0
Disarmed Rings
Enter the number of rings the panel counts before answering the phone line while
any system areas are disarmed. Any number from 1 to 15 can be entered. If 0 (zero)
is entered, the panel does not answer the phone when any system area is disarmed.
The default number of Disarmed Rings is 0 (zero).
6.6
ALR RCVR
NO YES
Alarm Receiver Authorization
Select YES to enable remote commands and programming to be accepted from the
alarm SCS-1R Receiver. The Remote Key option can also be required.
With YES selected, the panel requests the receiver key during its first communication
with the first SCS-1R Receiver. The panel retains this alarm receiver key in memory
and allows remote commands to be accepted from the alarm receiver. If an alarm
occurs during a remote connect, the alarm report is immediately sent to this
receiver only.
When NO is selected, remote commands and programming are not accepted from
the alarm SCS-1R Receiver.
Digital Monitoring Products
20
XR100 Series Programming Guide
REMOTE OPTIONS
6.7
SVC RCVR
NO YES
Service Receiver Authorization
YES enables remote commands and programming to be accepted from a secondary
service receiver other than the alarm SCS-1R Receiver. The Remote Key option can
also be required.
With YES selected, the panel requests the service receiver key the first time it is
contacted by the service receiver. The panel retains this service receiver key in
memory and accepts remote commands from the service receiver.
If an alarm occurs during a remote connect, the panel disconnects from the service
receiver and calls the alarm receiver. Alarm reports are only sent to the alarm
receiver. It is important that the alarm receiver key and the service receiver key
programmed at the central station are NOT the same so the panel can determine the
difference between receivers.
When NO is selected remote commands and programming are not accepted from a
secondary service receiver.
This option must be YES to allow programming from a directly connected computer
or an iCOM/iCOM-E.
6.8
PC MODEM NO YES
PC Modem
YES allows the panel to answer the telco link and connect with Remote Link through
the PC Modem at 2400 baud. NO disables PC Modem communication.
6.9
REMOTE PHONE NO.
-
Remote Telephone Number
Press COMMAND to enter the phone number the panel dials when requesting remote
programming. After entering a phone number, the panel allows remote commands
and programming only after it has first been called by the authorized receiver,
disconnected itself, and redialed the remote phone number.
If a Remote Phone Number is NOT entered, and Alarm Receiver and Service Receiver
is YES the panel allows remote commands and programming without disconnecting
and redialing. The phone number can have two lines of 16 characters each to
equal 32. Enter a P to program a two second pause in the dialing sequence. The
P character counts as part of the 32 allowable characters. Enter *70P as the string
first characters to cancel call waiting. No dial tone detect “D” is required. Dial
tone detect is an automatic panel function.
Note: When not in the Programming Menu, the function 984 + COMMAND can be
entered at the keypad, and a remote options menu appears. This menu contains the
following options:
NBR RMT
PICKUP
NUMBER - The panel allows you to enter into the keypad a phone number you want
the panel to dial. Enter any required prefixes and area codes.
REMOTE - The panel dials the phone number programmed in Remote Phone Number.
PICKUP - The panel picks up the phone line when Remote Link™ calls in. The phone
must be ringing before selecting PICKUP.
See the Appendix for more information about the 984 + COMMAND feature.
6.10
DISARM
NO YES
Remote Disarm
YES allows the panel to be disarmed remotely. NO disables remote disarming.
XR100 Series Programming Guide
Digital Monitoring Products
21
SYSTEM REPORTS
System Reports
7.1
SYSTEM REPORTS
System Reports
Select specific system reports the panel sends to the receiver.
7.2
ABORT
NO YES
Abort Report
YES allows the panel to send an alarm abort report to the receiver any time an area
is disarmed during Transmit Delay before an alarm report is sent and the Bell Cutoff
Time has not expired. After disarming an area, if any other area remains armed and
has zone(s) in alarm, the alarm abort report is not sent.
If the communication type is set to DD, a Warning: Alarm Bell Silenced report is also
sent if the alarm bell is silenced.
Note: Abort Reports are not sent for Fire, Fire Verify, or Supervisory type zones.
7.3
YES
RESTORAL:
Restoral Reports
This option allows you to control when and if a zone restoral report is sent to the
central station receiver. Press any Select key to display the following options:
NO
YES
DISARM NO - Disables the zone restoral report option. Zones continue to operate normally
but do not send restoral reports to the receiver.
YES - Enables the zone restoral report option. Zone restorals are sent whenever a
zone restores from a trouble or alarm condition.
DISARM - Causes the panel to send restoral reports for a non-24-hour zone whenever
a zone that has restored from a trouble or alarm condition is disarmed. All 24-hour
zones send restoral reports as they restore.
Note: For UL applications, Restoral Reports must be set to YES.
7.4
BYPASS
7.5
SCHD CHG NO YES
7.6
CODE CHG NO YES
NO YES
Bypass Reports
YES allows the panel to send all zone bypasses, resets, and force arm reports to the
receiver. The bypass report includes the zone number, zone name, and the user
name and number of the individual operating the system. Reports are only sent if
O/C User in Communications is set YES for Receiver 1 or Receiver 2.
Schedule Change Reports
YES allows the panel to send all schedule changes to the receiver. The report
includes the day, opening time, closing time, extend schedule time, and the user
name and number of the individual making the change. Schedule changes made
through Remote Link™ are not sent to the printer or Display Events.
Code Change Reports
YES allows the panel to send all code additions, changes, and deletions to the
receiver. The code change report includes the user name and number added or
deleted and the user name and number of the individual making the change. Code
changes made through Remote Link™ are not sent to the printer or Display Events.
Reports are only sent if O/C User in Communications is set YES for Receiver 1 or
Receiver 2. The default setting is YES.
7.7
ACCESS KEYPADS:
Access Keypads
Select the keypad addresses (1 through 8) that send door access reports to the
receiver. Enter the keypad number using the digit keys. An asterisk next to the
number indicates that the keypad is selected.
A report is sent with each door access made from the selected keypads. Keypads at
addresses not selected still operate the door relay but do not send access reports.
The report includes the user number, user name, keypad address, and device name.
7.8
AMBUSH
NO YES
Ambush
YES allows an ambush report to be sent anytime user code number 1 is entered at
a keypad. NO disables the ambush report and allows user number 1 to operate the
same as all other codes.
Digital Monitoring Products
22
XR100 Series Programming Guide
SYSTEM OPTIONS
System Options
8.1
System Options
SYSTEM OPTIONS
This section allows you to select system-wide parameters.
8.2
System
SYSTEM:
AREA
This option allows you to program how the areas operate for arming and disarming.
The options you can choose are listed below:
AREA - All eight areas can be programmed and operated independently.
AREA
A/P H/A
ALL/PERIMETER - Area 1 is the Perimeter and Area 2 is the Interior.
HOME/SLEEP/AWAY - Area 1 is the Perimeter, Area 2 is the Interior, and Area 3 is the
Bedrooms. With the HOME/SLEEP/AWAY option, the user can:
1. Select HOME to arm just the perimeter.
2. Select SLEEP to arm the perimeter and interior (non bedroom areas).
3. Select AWAY to arm all three areas.
Note: A Home/Sleep/Away system can be configured to use all three areas or
only use the Home and Away areas.
When either All/Perimeter or Home/Sleep/Away is selected, the area names are
automatically assigned and cannot be modified.
Note: Areas 3-8 in an All/Perimeter system, and areas 4-8 in a Home/Sleep/Away
system are not available for use and are initialized.
8.3
CLS WAIT
NO YES
Closing Wait
When YES is selected, the keypad displays ONE MOMENT... while waiting for
an acknowledgement from the receiver before arming the selected area(s) and
performing a Bell Test (if selected). Exit delays begin after the Closing Wait.
Opening/Closing reports must be YES to enable Closing Wait.
8.4
ENTRY DLY 1:
ENTRY DLY 2:
ENTRY DLY 3:
ENTRY DLY 4:
30
60
90
120
Entry Delay 1
Enter the Entry Delay time for all Exit type zones programmed to use Entry Delay 1.
When an armed Exit type zone is faulted, the keypad prewarn tone begins sounding.
All keypads programmed to prewarn for that zone display ENTER CODE:- and the
name of the zone causing the entry delay. When the first digit of a code is entered,
the prewarn tone stops at that keypad. If an invalid code is entered, the prewarn
tone begins sounding again. The area must be disarmed before the delay expires
or an alarm report is sent to the receiver and an alarm sounds. All zones in that
area are delayed along with the Exit zone. Entry Delay times can be from 30 to 250
seconds. Repeat the above for each entry delay being used in the system.
Note: Specific Exit Error operation is based on the Entry Delay used (1-4) with an EX
type zone. See Exit Delay.
Note: When the SIA CP-01 option in System Options is set to NO, the first digit
entered at the keypad does not stop the prewarn tone.
Note: For UL Installations, the combined Transmit Delay (Abort Window) and
Entry Delay must not exceed one (1) minute.
8.5
CRS ZONE TM:
0
Cross Zone Time
Enter the time allowed between zone faults. When zones are cross zoned, the same
zone or a second cross zoned zone must fault within this time in order for an alarm
report for both zones to be sent to the receiver. If the cross zone time expires
without the second zone faulting, only a zone fault from the first zone is reported.
Cross-zone time can be from 4 to 250 seconds. Entering 0 (zero) disables this
function. Default is 0 (zero). See the Appendix.
XR100 Series Programming Guide
Digital Monitoring Products
23
SYSTEM OPTIONS
8.6
RETARD DELAY:
10
Zone Retard Delay
Enter the retard time assigned to Fire, Supervisory, Auxiliary 1, Auxiliary 2, Arming,
and Panic type zones. The retard delay only functions when the zone is shorted.
The zone must remain shorted for the entire length of the Retard Delay before being
recognized by the panel. The Zone Retard Delay can be from 1 to 250 seconds.
Entering a 0 (zero) disables this function.
8.7
PWR FAIL HRS:
1
Power Fail Delay
This option tracks the duration of an AC power failure. When the AC power is off for
the length of the programmed delay time, an AC power failure report is sent to the
receiver. The delay time can be from 1 to 15 hours. Entering a 0 (zero) sends the
power failure report after a 15-second delay. The default setting is 1.
Note: For UL burglary installations Power Fail Delay shall be programmed to 0
(zero).
Note: For UL fire installations, Power Fail Delay shall be programmed as required
by the service of the panel. For Central Station service: 6-12, for Remote Station
service: 12-15.
8.8
SWGRBYPS TRIPS: 1
Swinger Bypass Trips
Enter the number of times (1 or 2) a zone can go into an alarm or trouble condition
within one hour before being automatically bypassed. You can select one or two
trips. Bypassed zones are automatically reset when the area they are assigned to is
disarmed. All 24-hour zones are reset when any area of the system is disarmed. A
programming Stop operation restores a bypassed zone. Entering 0 (zero) disables
this function. Default is 1.
How it works
The panel hour timer starts at 59 minutes past the hour. If the hour timer expires
before the trip counter is exceeded, the trip counter returns to 0 (zero). If the trip
counter is exceeded before the hour expires, the zone is automatically bypassed by
the panel. A Bypass Report is sent to the receiver if Bypass Reports is YES.
Note: Not investigated by UL.
8.9
8.10
RST SBYP
NO YES
Reset Swinger Bypass
VIDEO
NO YES
Video/Alarm Verification
When YES is selected, an automatically bypassed zone is reset if it remains in a
normal condition for one complete hour after being bypassed. A report of the
automatic reset is sent to the receiver if Bypass Reports has been selected as YES.
Default is NO.
Note: Not investigated by UL.
Selecting YES forces the panel to wait for 60 seconds after a successful
communication with a central station receiver before making any additional
communication attempts. This 60-second period can be used to allow video
transmission or alarm verification (such as 2-way voice) equipment to use the phone
line. After the 60-second timer, the panel can once again seize the phone line and
send any reports being buffered.
The Video option must be set to NO if any fire protection is connected to the panel.
Note: Not investigated by UL.
Digital Monitoring Products
24
XR100 Series Programming Guide
SYSTEM OPTIONS
8.11
NO YES
TIME CHG
Time Zone Changes
This function allows the panel to request automatic time changes from the DMP
SCS-1R Receiver. For the receiver to send time changes, it must be programmed to
send time changes and must be receiving time change updates from the network
automation computer at least every 24 hours. Default is YES.
HRS FROM GMT:
GMT
8.12
6
When time zone is programmed YES, enter the number (0-23) that indicates the
Greenwich Time zone (GMT) where the panel is located. The default is 6.
City/Time Zone
GMT
City/Time Zone
0
London, Monrovia, Lisbon, Dublin, Casablanca, Edinburgh
13
New Cadelonia
1
Cape Verde Island, Azores
14
Guam, Sydney
2
Mid-Atlantic, Fernando de Noronha
15
Tokyo, Seoul
3
Buenos Aires, Georgetown, Brasilia, Rio de Janeiro
16
Hong Kong, Singapore
4
Atlantic Time (Canada), Caracas, La Paz, Santiago
17
Bangkok, Hanoi
5
Eastern Time (US, Canada) Bogota, Lima, Arequipa
18
Dhaka, Almaty
6
Central Time (US, Canada), Mexico City, Saskatchewan
19
Islamabad, Karachi
7
Mountain Time (US, Canada), Edmonton
20
Abu Dhabi, Kazan
8
Pacific Time (US, Canada), Tijuana
21
Moscow, Bagdad
9
Alaska
22
Eastern Europe
10
Hawaii
23
Rome, Paris, Berlin
11
Midway Island, Samoa
12
Fiji, Marshall Island, Wellington, Auckland, Kwajalein, Kamchatka
NO YES
LATCH SV
Latch Supervisory Zones
Selecting YES latches supervisory zone alarms on the keypad display until the sensor
reset operation is performed. Selecting NO automatically clears the alarm from the
keypad display when the supervisory zone restores to a normal condition. Default is
YES.
8.13
PROG LANGUAGE
Programming Menu Language
Press the COMMAND key to select the programming language(s). Any changes in
PROG LANGUAGE do not take effect until the STOP routine completes.
ENGLSH The current primary programming language displays. The default language is
English. Press a Select key to change the primary programming language.
PRI LANG:
ENG
SPN
SEC LANG:
FRN
NONE
Select the primary programming language.
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
The current secondary programming language displays. Selecting a secondary
language allows the installer to view programming in English, Spanish, or French.
When the Programming Menu is accessed, the installer is prompted to choose the
programming display language. If SEC LANG: is set to NONE, the option to choose
a language does not display. To select a secondary language, press the Select key
below the language. Default is NONE.
NONE ENG SPN FRN Select the secondary programming language.
NONE = No secondary language options are displayed
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
XR100 Series Programming Guide
Digital Monitoring Products
25
SYSTEM OPTIONS
8.14
User Menu and Status List Language
USER LANGUAGE
Press the COMMAND key to select User language(s).
ENGLSH The current primary user language displays. The default language is English. Press a
Select key to change the primary User language.
PRI LANG:
ENG
SPN
SEC LANG:
FRN
NONE
Select the primary user language.
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
The current secondary user language displays. Selecting a secondary user language
allows the user to view the User Menu and Status List text in English, Spanish, or
French. When the User Menu is accessed, the user is prompted to choose the display
language. Status List text displays in the selected language until another language
is chosen. If SEC LANG: is set to NONE, the option to choose a language does not
display. To select a secondary language, press the Select key below the language.
Default is NONE.
For example, when Spanish is selected at a keypad, the User Menu and Status List
text display in Spanish at that keypad. When the user later accesses the keypad,
pressing the COMMAND key once displays the option for English, Spanish, or French.
Pressing the COMMAND key again continues to display the Status List text in Spanish.
Later on, if English or French is selected at that keypad, the User Menu and Status
List text display in the selected language at that keypad.
NONE ENG SPN FRN Select the secondary user language.
NONE = No secondary language options are displayed
ENG = English (ENGLISH)
SPN = Spanish (ESPANOL)
FRN = French (FRANCAIS)
8.15
BYPASS LIMIT
0
Bypass Limit
Enter the maximum number of zones (0 to 8) that can be bypassed in any single area
when that area is being armed at a keypad. If more zones than the limit are in a
non-normal state or already bypassed at arming, arming does not occur and Arming
Stopped displays. The Bypass limit does not affect auto arming, keyswitch arming,
or remote arming. Entering 0 (zero) allows no limit. Default is 0 (zero).
8.16
WIRELESS
HOUSE CODE: XX
House Code
When using a DMP wireless system, enter a house code between 1 and 50. When
using FA Series wireless enter 99. See Wireless programming in Zone Information.
Default is 0 indicating no wireless system is being used.
The DMP house code identifies the panel, DMP receiver, and DMP transmitters to
each other. When operating, the DMP receiver listens for transmissions that have
the programmed house code and transmitter serial number.
Note: The flexibility of DMP two-way wireless operation allows an existing house
code to be changed in the panel at any time. The transmitters may take up to two
minutes to learn the new house code and continue operation.
Note: When any wireless zone programming is changed in the panel, wireless
receiver zone programming is updated. At that point, all wireless zones display as
normal for approximately 1 minute, regardless of the actual state of the zone.
8.17
DETECT WIRELESS
JAMMING: NO YES
Digital Monitoring Products
26
Detect Wireless Jamming
This option displays when the House Code entered is for a DMP 1100 Series Wireless
system (1-50). When enabled and the wireless receiver detects jamming, a trouble
or alarm message displays in the Status List and is sent to the central station
receiver. Select YES to enable jamming messages to display in the Status List.
Select NO to disable jamming messages. Default is NO.
XR100 Series Programming Guide
SYSTEM OPTIONS
8.18
KEYPAD PANIC KEYS
ENABLED: NO YES
8.19
Enable Keypad Panic Keys
This option allows the two-button panic key operation selected at the keypad to
send the Panic, Emergency, or Fire message to the central station receiver. Select
YES to enable the two-button panic operation to operate. To disable the two-button
panic operation, select NO. Default is YES.
SIA CP-01
SIA CP-01: NO YES
XR100 Series Programming Guide
Select YES to allow the panel to operate according to ANSI/SIA CP-01 standards for
the following operations. Select NO to enable standard DMP operation. Default is
YES. When YES is selected:
Power Up and Stop Routine
— the 60 second zone startup delay is turned on.
Keypress Alarm Silence
— during an alarm, the keypad alarm and bell output turn off when the first key is
pressed at a keypad.
Entry Delay
— entering the first digit of a code at the keypad stops the prewarn tone.
Exit Delay
— the keypad Exit Delay displays and annunciates a tone at 8 second intervals
until the last 10 seconds when annunciation is at 3 second intervals.
Exit Error Operation for Entry Delay 1
When the exit zone is faulted (door still open) at the end of the exit delay:
— the bell sounds for the length of time set in Bell Cutoff programming
— the Entry Delay operation starts, requiring code entry to disarm
— if not disarmed, a zone alarm and an Exit Error are sent to the receiver
Automatic Disarming Operation
— The Interior automatically disarms if a Perimeter exit zone is not tripped during
the Exit Delay time when arming All or Away.
Digital Monitoring Products
27
OUTPUT OPTIONS
Output Options
9.1
Output Options
OUTPUT OPTIONS
This function allows you to program the panel Bell Output functions and certain
Relay Output options. Dry contact relays and voltage outputs are available using
the output harness on the XR100 Series board. Refer to the XR100 Series Installation
Guide (LT-0899) for complete information.
Any Output Option can be used with output numbers 1 to 6, 500 to 599, D1 to D8,
and G1 to G20.
9.2
BELL CUTOFF:
15
Bell Cutoff Time
Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the
area is disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell
output. The default is 15 minutes.
Note: For SIA CP-01 False Alarm Reduction Installations, the Bell Cutoff Time must
be set to a minimum of six (6) minutes.
9.3
BELL TST
NO YES
Automatic Bell Test
Select YES to turn on the Bell Output for 2 seconds each time the system is
completely armed from a keypad. This test is delayed until the Closing Wait
acknowledge is received (if selected). If the Closing Wait acknowledge is not
received within 90 seconds, the bell test does not occur. Arming performed from an
Arming zone or from Remote Link™ does not activate the Bell Test.
9.4
Bell Action
BELL ACTION . . . . .
This section defines the type of Bell Output for zone alarms. Press COMMAND to
display the default Bell Output for each zone type. Press any Select key and enter S
for a Steady Bell Output, P for a Pulsed output, T for a Temporal Code 3 output, and
N for no Bell Output.
Note: Trouble conditions do not activate the Bell Output.
9.4.1
FIRE
TYPE:
P
Fire Bell Action
Defines Bell Action for Fire Type zones. The default is P.
9.4.2
BURGLARY TYPE:
S
Burglary Bell Action
Defines Bell Action for Burglary Type zones and Exit Error output. The default is set
at S.
9.4.3
SUPRVSRY TYPE:
N
Supervisory Bell Action
Defines Bell Action for Supervisory Type zones. The default is set at N.
9.4.4
PANIC
TYPE:
N
Panic Bell Action
Defines Bell Action for Panic Type zones. The default is set at N.
9.4.5
EMERGNCY TYPE:
N
Emergency Bell Action
Defines Bell Action for Emergency Type zones. The default is set at N.
9.4.6
AUXLRY 1 TYPE:
N
Auxiliary 1 Bell Action
Defines Bell Action for Auxiliary 1 Type zones. The default is set at N.
9.4.7
AUXLRY 2 TYPE:
N
Auxiliary 2 Bell Action
Defines Bell Action for Auxiliary 2 Type zones. The default is set at N.
9.5
OUTPUT ACTION . . .
Output Action
This option allows you to define the XR100 Series relay outputs operation. The panel
provides two Form C relays (1 and 2) and four open collector outputs numbered 3
to 6. Expand the system up to 100 additional relay outputs (numbered 500 to 599)
using J22 LX-Bus on the panel and multiple 716 Output Expander Modules. Program
keypad door strike relays by entering D1 to D8 for addresses 1 to 8. Program output
groups by entering G1 to G20.
Digital Monitoring Products
28
XR100 Series Programming Guide
OUTPUT OPTIONS
9.5.1
Cutoff Output
CO OUTS: - - - - - -
Outputs 1 to 6 can be entered here to turn off after a time specified in CUTOFF
TIME. To disable this option, press any Select key to clear the display then press
COMMAND. The Cutoff Output displays NONE when no outputs are selected.
9.5.2
CUTOFF TIME:
0
Output Cutoff Time
If a Cutoff Output is assigned, enter a Cutoff Time of 1 to 99 minutes for the output
to remain on. Enter 0 (zero) for continuous output.
9.5.3
COMM FAIL OUT:
0
Communication Fail Output
Enter the output number to turn on when a DD system fails to communicate on three
successive dial attempts or if the backup communication line transmits a report.
The Communication Fail Output also turns on when NET is selected as the primary
communication method and NET communication fails after one minute. When NET
communication is restored the Communication Fail Output automatically turns off.
To manually turn the output off, disarm any area or select Off for the output number
in the User Menu Outputs On/Off section. Enter 0 (zero) to disable this output.
9.5.4
FIRE ALR OUT:
0
Fire Alarm Output
Enter the output number to turn on when a fire type zone is placed in alarm. The
output is turned off using the Sensor Reset option while no additional fire type zones
are in alarm. Enter 0 (zero) to disable. This output is not compatible with Cutoff
Outputs.
9.5.5
FIRE TRB OUT:
0
Fire Trouble Output
Enter the output number to turn on when a fire type zone is placed in trouble, when
a supervisory type zone is placed in alarm or trouble, or when any system monitor
(AC, Battery, Phone Line 1 or Phone Line 2) is placed in trouble. The output turns off
when all fire and supervisory type zones, or system monitors are restored to normal.
Enter 0 (zero) to disable this output. This output is not compatible with Cutoff
Outputs. This output can be connected to a lamp, LED, or buzzer using the DMP
Model 716 Output Expansion Module.
9.5.6
PANIC ALM OUT:
0
Panic Alarm Output
Enter the output number to turn on when any Panic type zone is placed in an alarm
condition. The output is turned off after all Panic zones are restored from an alarm
condition and a Sensor Reset is performed. Enter 0 (zero) to disable.
9.5.7
AMBUSH OUT:
0
Ambush Output
Enter the output number to turn on when an Ambush code is entered at a keypad.
The output is turned off using the Sensor Reset option. Enter 0 (zero) to disable.
9.5.8
ENTRY OUT:
0
Entry Output
Enter the output number to turn on at the start of the entry delay time. The output
turns off when the area is disarmed or the entry delay time expires. Enter 0 (zero)
to disable.
9.5.9
EXIT OUT:
0
Exit Output
Enter the output number to turn on when an exit delay time starts in any area of
the system. The output turns off when the area arms or when the arming has been
stopped. Enter 0 (zero) to disable.
9.5.10 READY OUT:
0
Ready Output
Enter the output number to turn on when all disarmed burglary zones are in a
normal state. The output is turned off when any disarmed burglary type zone is in
a bad state. Enter 0 (zero) to disable. This output is not compatible with Cutoff
Outputs.
XR100 Series Programming Guide
Digital Monitoring Products
29
OUTPUT OPTIONS
9.5.11 PH TRBL OUT:
0
Telephone Trouble Output
Enter the output number to turn on when the phone line monitor detects a voltage
below 3 VDC. The output is turned off when phone voltage rises above 3 VDC. Enter
0 (zero) to disable this output. This output can be connected to a lamp, LED, or
buzzer using the DMP Model 716 Output Expansion Module.
9.5.12 LATE CLS OUT:
0
Late To Close Output
Enter the output number to turn on at the expiration of a Closing schedule. The
output activates simultaneously with the CLOSING TIME! keypad display. The output
is turned off when the area is armed, the Closing is extended, or the schedule is
changed. Enter 0 (zero) to disable this output.
9.5.13 DVC FAIL OUT:
0
Device Fail Output
Enter the output number to turn on when an addressed device fails to respond to
polling from the panel. A Missing Device report is sent to the receiver. The output is
turned off when the device responds to polling or is removed from the system. Enter
0 (zero) to disable this output and LX-Bus™ device fail reporting to the receiver. If
any addressed device is unsupervised, this output cannot be used.
9.5.14 SNSR RST OUT:
0
Sensor Reset Output
Enter the output number to turn on when a Sensor Reset is performed at a keypad.
The output turns off automatically 5 seconds later. This function can be used to
reset smoke detectors that are operated by an external power supply through a
Model 716 Output Expander Module. Enter 0 (zero) to disable this output.
9.5.15 CLS WAIT OUT:
0
Closing Wait Output
Enter the output number to turn on for approximately four (4) seconds when Closing
Wait is programmed as YES and the panel successfully communicates the closing
message at arming. If the closing message does not communicate successfully, this
output does not turn on.
9.6
OUTPUT NAMES . . .
Output Names
This section allows you to define a 16 character alphanumeric name for any or all
506 output numbers. The name can display on the keypad when a user performs the
browser feature at Outputs On/Off. See the XR500/XR100 User’s Guide (LT-0683)
Appendix for browser operation.
9.6.1
OUTPUT NO: -
Output Number
Enter an output number (1 to 6, 500 to 599).
9.6.2
OUTPUT NAME X X X
Output Name
The output name displays. To change the default name, press any top row Select
key then enter up to 16 characters for the output name. Press COMMAND to enter
the next output number.
Digital Monitoring Products
30
XR100 Series Programming Guide
OUTPUT GROUPS
Output Groups
10.1
Output Groups
OUTPUT GROUPS
This function allows you to assign outputs to groups. Output groups can be assigned
to other areas of programming such as Output Options or Alarm Action of Zone
Information, just like single outputs are assigned. This allows the entire group of
outputs to turn on and off as required by the programming option.
10.2
Group Number
GROUP NO: -
Enter a group number from 1 to 20. Up to 20 different groups may be assigned.
10.3
Group Name
GROUP NAME X X
The group name displays. To change the default name, press any top row Select key
then enter up to 16 characters for the group name. Press COMMAND to enter the
outputs to be assigned to the group.
10.4
OUTPUT NO 1:
OUTPUT NO 2:
OUTPUT NO 3:
OUTPUT NO 4:
OUTPUT NO 5:
OUTPUT NO 6:
OUTPUT NO 7:
OUTPUT NO 8:
0
0
0
0
0
0
0
0
Output Number
Enter the Output number. Entry range is 1 to 6, 500 to 599 (outputs), D1 to D8
(doors), and G1 to G20 (groups). The maximum number of outputs that can be
assigned to a specific group is eight.
An output group may be assigned as one of the output numbers in another output
group.
Example: Output Group 1 consists of only four assigned outputs. Output Group
1 could be assigned as one output in Output Group 2. Output Group 2 could still
have 7 other outputs assigned to that group. When Output Group 2 is turned on, 11
outputs could be turned on. This allows Output Groups to be assigned within other
Output Groups providing many combinations.
Output groups 1 to 10 can be assigned by a user profile for applications such as
elevator control. See the XR500/XR100 User’s Guide (LT-0683) Output Group section
for additional information.
Output groups 11 to 20 cannot be assigned to a profile and are available for
installation applications such as special lighting, etc. To assign these groups to a
profile, use Remote Link™ or System Link™ software from DMP.
XR100 Series Programming Guide
Digital Monitoring Products
31
MENU DISPLAY
Menu Display
11.1
Menu Display
MENU DISPLAY
Menu Display allows you to select at which keypad addresses the user can access the
following functions.
To select a keypad, enter the device number (keypad address) using the digit keys
on the keypad. When a keypad is selected, an asterisk appears next to the keypad
address. Enter the number again to deselect the keypad. Refer to the Multiple
Displays section at the beginning of this document.
11.2
1
5
11.3
Armed Status
ARMED STATUS:
2
6
3
7
TIME DISPLAY:
4
8
Enter the keypad addresses (1 through 8) that show the armed areas. The User
Menu Armed Areas function also displays the custom area name you enter in Area
Information.
Time
Enter the keypad addresses that can display the time and day of the week.
11.4
ARM/DIS DISPLAY:
Arm/Disarm
Enter the keypad addresses from which users can arm and disarm areas.
Digital Monitoring Products
32
XR100 Series Programming Guide
STATUS LIST
Status List
12.1
Status List
STATUS LIST
This function allows you to select the zone alarms and troubles, and system monitor
troubles displayed at the keypads. The Status List function operates automatically
when the keypad is not performing any other function.
The keypad stays in the Status List until the user arms or disarms or selects a menu
option. Status List alternates with the Armed Status on keypad addresses selected
in the Menu Display - Armed Status section. You can choose to have System Monitor
troubles placed in the list, the different zone types placed in the list, and at which
keypad addresses they display.
To select a keypad, enter the device number (keypad address) using the digit keys
on the keypad. When a keypad is selected, an asterisk appears next to the keypad
address. Enter the number again to deselect the keypad. Refer to the Multiple
Displays section at the beginning of this document.
12.2
Display Keypads
DISPLAY KEYPADS:
This option defines which keypad addresses display the various status information.
Any combination of addresses can be entered to display the status items that follow.
If you do not want a particular status item to display, do not enter any addresses.
12.3
SYSTEM TROUBLES:
1
5
2
6
3
7
4
8
System Monitor Troubles
Specifies the keypad addresses (1 through 8) where any trouble on a System Monitor
displays. The System Monitors include the following:
• AC Power
• Battery Power
• Closing Check
• Panel Box Tamper
• Phone Line 1
• Phone Line 2
(requires the 893A Dual Phone Line Module)
• Wireless Trouble
• Wireless Jamming Trouble
• Wireless Jamming Alarm
The System Monitor name is placed in the Status List and the keypad steady trouble
buzzer sounds. The buzzer remains on until any keypad top row Select key is
pressed. The name remains in the list until the condition is restored. The buzzer
sounds at 10:00 am daily until the system trouble is cleared from the Status List.
12.4
Fire Zones
FIRE ZONES:
1
5
2
6
3
7
4
8
Specifies the keypad addresses (1 through 8) where all fire zone alarms and troubles
display. The zone name displays and, if it is a trouble condition, the keypad steady
trouble buzzer sounds. The buzzer remains on until any top row Select key is
pressed and a user code is entered. If a trouble condition remains in the display, the
buzzer sounds at 10:00 am daily until the trouble is cleared from the Status List.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad
for Fire:
On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off - Alarm Silence
XR100 Series Programming Guide
Digital Monitoring Products
33
STATUS LIST
12.5
Burglary Zones
BURGLARY ZONES:
1
5
2
6
3
7
4
8
Specifies the keypad addresses (1 through 8) where all burglary zone alarms and
troubles display. Burglary zones include Night, Day, and Exit type zones. Burglary
zone troubles remain in the list until the zone restores. All keypads are selected by
default.
For zone alarms, only the last burglary zone tripped remains in the list. The alarm
remains in the list until another burglary zone goes into alarm, any area of the
system is disarmed. This ensures that if a burglary is in progress the last zone
tripped remains in the list even if the zone is restored.
The keypad buzzer sounds for one second on burglary alarms.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad
for Burglary:
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
You can further define which keypad address shows a Burglary Zone event by
entering that area number in the Display Areas menu during Device Setup.
12.6
SPRVISORY ZONES:
1
5
12.7
4
8
2
6
3
7
2
6
3
7
4
8
4
8
2
6
3
7
Specifies the keypad addresses (1 through 8) where all panic zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for panic alarms or troubles.
Emergency Zones
Specifies the keypad addresses (1 through 8) where all emergency zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for emergency alarms or troubles.
Auxiliary 1 Zones
AUX 1 ZONES:
1
5
Specifies the keypad addresses (1 through 8) where all supervisory zone alarms and
troubles display. Supervisory zones are entered in the status list and sound the
keypad buzzer until a valid user code is entered at any keypad address. If a trouble
condition remains in the display, the buzzer sounds at 10:00 am daily until the
supervisory trouble is cleared from the Status List.
Panic Zones
EMERGENCY ZONES:
1
5
12.9
3
7
PANIC ZONES:
1
5
12.8
2
6
Supervisory Zones
4
8
Specifies the keypad addresses (1 through 8) where all Auxiliary 1 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for Auxiliary 1 alarms or troubles.
You can further define which keypad address shows an Auxiliary 1 Zone event by
entering that area number in the Display Areas menu during Device Setup.
12.10 AUX 2 ZONES:
1
5
2
6
3
7
Auxiliary 2 Zones
4
8
Specifies the keypad addresses (1 through 8) where all Auxiliary 2 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for Auxiliary 2 alarms or troubles.
You can further define which keypad address shows an Auxiliary 2 Zone event by
entering that area number in the Display Areas menu during Device Setup.
Digital Monitoring Products
34
XR100 Series Programming Guide
PC LOG REPORTS
PC Log Reports
13.1
PC LOG REPORTS
PC Log Reports
This section allows you to program the types of PC Log Reports the panel sends
through the J1 network connector directly on the XR100N panel. The reports include
information such as the type of activity, time and date of the activity, and user name
and number. These data reports can be accessed from a PC using the Advanced
Reporting Module.
Note: The network connection that sends PC Log Reports is not monitored for
network trouble. The PC Log Reports option should NOT replace the primary
communication method or act as a backup communication method.
If there is trouble with the network connection, the panel continues to attempt to
send the PC Log Reports until the connection is reestablished. The panel then sends
the reports. A Network Trouble message is NOT sent if the connection is lost since
this report tool is not designed to be monitored by a receiver. The PC Log Reports
have the lowest priority of panel reports sent.
13.2
PC LOG ADDRESS:
-
PC Log Address
Press COMMAND to enter up to two lines of 16 characters to equal up to 32
characters for the IP address string that is sent to the network device. This option
allows PC Log messages to be sent to a PC through an IP Network.
Note: The PC Log Address String entered CANNOT be the same as that entered in
Communication.
13.3
ARM/DIS
NO YES
Arm and Disarm Reports
Sends arming, disarming and Late to Close events. Includes the area number, name
and action, the user number and name, and the time and date.
13.4
ZONE
NO YES
Zone Reports
Sends changes in the status of active zones. Includes the zone number, name, type,
the action (alarm, trouble, bypass, etc.), user number (if applicable), and area
name. For a Walk Test, Verify and Fail messages are sent for each zone.
13.5
USR CMDS NO YES
User Command Reports
Sends user code changes, schedule changes, and door access denied events.
13.6
DOOR ACS NO YES
Door Access Reports
Sends door access activity: door number, user number and name, and time and date.
13.7
SUPV MSG NO YES
Supervisory Reports
Sends system monitor reports, such as AC and battery, and system event reports.
Supervisory Reports also sends the following reports:
• Abort
• Exit Error
• Ambush
• System Recently Armed
• Alarm Bell Silenced
• Unauthorized Entry
• *Late to Close
* Only sent as a Supervisory Report if Area Schedules is not enabled, Closing
Check is enabled, and an opening/closing schedule has been programmed.
Note: To send these reports to the PC Log, you must enable SUPV MSG.
XR100 Series Programming Guide
Digital Monitoring Products
35
AREA INFORMATION
Area Information
14.1
AREA INFORMATION
Area Information
Allows you to assign functions to the different areas in the system. All non-24-hour
zones must be assigned to an active area. See Zone Information.
You activate an area by assigning it a name. See Area Name. A name is given to
each active area in place of a number to assist the user during arming and disarming.
The Armed Status display is 1 2 3 4 5 6 7 8.
14.2
EXIT DELAY:
60
Exit Delay
Enter the exit delay time for all Exit type zones in this area. When the exit delay
time starts, all activity on that zone and other non-24-hour zone types in the area
is ignored until the exit delay expires. The keypad displays the Exit Delay time
countdown and annunciates the Exit Delay tone at 8 second intervals until the last
10 seconds when annunciation is at 3 second intervals.
The exit delay can be from 45 to 250 seconds. Default is 60 seconds.
During Exit Delay, if an exit zone trips, then restores, and trips again, the Exit Delay
timer restarts. This restart can occur only once. The Exit Delay restart is disabled
when programmed for ULAA High Line Security operation.
Note: When the SIA CP-01 option in System Options is set to NO, the exit delay
countdown displays but progress annunciation does not occur.
Exit Error Operation: At arming, when an entry/exit zone (EX) is faulted at the end
of the exit delay then one of two sequences occur:
For Entry Delay 1 EX type zones:
• the bell sounds for the length of time set in Bell Cutoff programming.
• the Entry Delay operation starts requiring code entry to disarm
• if not disarmed, a zone alarm and an exit error are sent to the receiver.
For Entry Delay 2-4 EX type zones:
• the zone is force armed and a zone force arm message is sent to the receiver
• an Exit Error is sent to the receiver
• the bell sounds for two (2) seconds.
Note: When the SIA CP-01 option in System Options is set to NO, Entry Delay 1
operates as described for Entry Delay 2-4 above.
14.3
BURG BELL OUT:
0
Burglary Bell Output
Enter the output number (0 to 6, 500 to 599, G1 to G20, or D1 to D8) that is turned
on any time a Burglary type zone is placed in alarm. The output is turned off when
you disarm any area and no other Burglary type zones are in alarm. The output can
also be turned off using the Alarm Silence option in the User Menu or by entering
a user code with the authority to silence alarms. The duration of this bell output
follows the time entered in the System Options/Bell Cutoff Time prompt. See the
Output Options - Bell Cutoff Time section. If Bell Test is selected YES, the Burglary
Bell Output entered here is turned on for two seconds each time the system is
armed.
14.4
O/C RPTS
NO YES
Digital Monitoring Products
36
Opening/Closing Reports
This option allows an Opening report to be sent to the receiver whenever any area is
disarmed. A Closing report is also sent to the receiver when any area is armed.
XR100 Series Programming Guide
AREA INFORMATION
14.5
CLS CHK
NO YES
Closing Check
Select YES to enable the panel to verify that all areas in the system are armed
after permanent or extended schedules expire. If the Closing Check finds any areas
disarmed past the scheduled time, the keypads selected to display System Trouble
Status displays CLOSING TIME! and emits a steady beep. When Area Schedules is set
to YES in Area Information, the specific area and name display followed by — LATE.
When Auto Arm is NO, if within ten minutes the system is not armed or if the
schedule is not extended, a Late to Close report is sent to the SCS-1/SCS-1R
Receiver. When Auto Arm is YES, the area arms. See Automatic Arming section.
If the area becomes disarmed outside of any schedule, the Closing Check sequence
occurs after the Late Arm Delay time. See Late Arm Delay.
When Closing Check is NO and Auto Arm is YES, the system immediately arms when
the schedule expires. No warning tone occurs.
In addition, when Closing Check is NO, the option to extend a schedule does not
display when the schedule expires.
14.6
CLS CODE
NO YES
Closing Code
When YES is selected, a code number is required for system arming. If NO is
selected, a code number is not required for system arming.
14.7
ANY BYPS
NO YES
Any Bypass
When YES is selected, zones can be bypassed without a code number during the
arming sequence. A code number is always required to use the Bypass Zones option
from the menu.
14.8
AREA SCH
NO YES
Area Schedules
Select YES to allow each area to set its own shift schedules 1 to 4. Enter NO to
provide one set of schedules for this system.
Note: Area Schedules are not designed to operate with All/Perimeter or Home/
Sleep/Away systems.
14.9.1
Area Number
Enter the number of the area to programming. After entering the area number,
press COMMAND to enter the area name.
AREA NO: -
Note: When All/Perimeter or Home/Sleep/Away is selected as the system type, the
Area Number does not display.
14.9.2
All/Perimeter Programming
INT
PERIM
INT
BDRM PERIM
14.9.3
When All/Perimeter is selected as the system type, program the Interior and
Perimeter areas as needed.
Home/Sleep/Away Programming
14.10 * UNUSED *
When Home/Sleep/Away is selected as the system type, program the Interior,
Bedroom, and Perimeter areas as needed.
Area Name
The area name can be up to 16 alphanumeric characters. To add an area name to
the system, press any Select key and then enter up to 16 characters for the new
area name. Press COMMAND to continue. For instructions on entering alphanumeric
characters see section 1.7 Entering Alpha Characters. Inactive areas are marked
* UNUSED *.
To mark an active area unused, press any top row Select key to delete the old name,
then press the COMMAND key. The programmer automatically programs the name
as *UNUSED*. If you have already cleared Area Information during Initialization, all
areas are marked * UNUSED *. See Initialization section.
XR100 Series Programming Guide
Digital Monitoring Products
37
AREA INFORMATION
14.11 ACCOUNT NO: 12345
Account Number
Enter the account number to be sent to the receiver for this area. Choose
an account number compatible with the Communication Type selected in
Communications. The default Account Number is the one previously entered.
14.12 AUTO ARM NO YES Automatic Arming
Select YES to allow this area to arm automatically according to permanent,
temporary, or extended schedules. If no schedules are programmed, the area auto
arms every hour.
If closing check is selected as YES, the automatic arming function does not take
place until the expiration of a ten minute Closing Check delay. See Closing Check.
If the area has been disarmed outside of any permanent or temporary schedule, the
closing check sequence occurs one hour after the area is disarmed.
At arming, bad zones are handled according to the option selected in section Bad
Zones. If a closing report is sent, the user number is indicated as SCH on the SCS-1R
Receiver. NO disables automatic arming for this area.
Note: For ANSI/SIA CP-01 UL installations, Automatic Arming cannot be used for
arming.
14.13 BAD ZONES:
BYP
Bad Zones
At the time of automatic arming, some zones in the area may not be in a normal
condition. This option allows you to program the panel response to these bad zones.
This option does not display if AUTO ARM is NO.
BYP FORC
REF
BYP - All bad zones are bypassed. A report of the bypass is sent to the receiver if
Bypass Reports is YES. The report indicates SCH as the user number.
FORC - All bad zones are force armed. Zones force armed in a bad condition are
capable of restoring and reporting an alarm if tripped. A forced zone report is
transmitted if Bypass Reports is YES. The report indicates SCH as the user number.
REF - The automatic arming is refused and no arming takes place. A No Closing
report is sent to the receiver regardless of the Closing Check selection.
14.14 AUTO DIS NO YES Automatic Disarming
NO disables automatic disarming by schedule for this area. When YES is selected,
the area automatically disarms according to permanent or temporary schedules. If
an opening report is sent to the receiver, the user number is indicated as SCH.
Note: For ANSI/SIA CP-01 UL installations, Automatic Disarming cannot be used for
disarming.
14.15 ARMED OUTPUT:
0
Armed Output Number
14.16 LATE OUTPUT:
0
Late Output Number
Enter the output to turn on when this area is armed. If an exit delay is used for
this area, the Armed Output will turn on at the start of the exit delay. The output
is turned off when this area is disarmed. The output cannot be turned on from the
User Menu Outputs On/Off option.
Enter the output to turn on when this area is not armed by its scheduled time and
Area Late or Closing Time displays at a keypad and the keypad buzzer is on. The
output is turned off when the keypad buzzer is silenced by pressing any key. Default
is 0 (zero).
14.17 LATE/ARM DLY:
60
Late Arm Delay
Enter 4 to 250 minutes to delay before automatic re-arming occurs after the area
becomes disarmed outside of schedules. See Closing Check. Default is 60 minutes.
Note: The Late Arm Delay can be superseded by the Re Arm Delay setting of the
User Profile assigned to the user who disarmed the area. Refer to the Re Arm Delay
section in the XR100 Series User’s Guide (LT-0683).
Digital Monitoring Products
38
XR100 Series Programming Guide
AREA INFORMATION
14.18 COMMON
NO YES
Common Area
Select YES to enable this area to operate as a common area. This area is armed
when the last area in the system is armed and is disarmed when the first area in the
system is disarmed. You can have multiple common areas in each system. For the
common area to work properly, do not assign the common area to any user code.
When a user code can arm and disarm the common area from a keypad at any time,
the common area does not function as a common area.
14.19 ARM FIRST NO YES Arm First Area
Select YES to enable this area to operate as an Arm First area. This area is
automatically armed when any non-Arm First area assigned to the same keypad is
armed but does not disarm when other areas become disarmed. Assign areas to
keypads using the Display Areas option in Device Setup programming. You can have
multiple Arm First areas in a system and divide them among keypads if needed. If
an Arm First area has faulted zones that cannot be bypassed, arming stops and the
areas are not armed. Correct the problem with the Arm First area and then begin
the arming process again. Default value is NO.
Note: The Arm First automatic arming only occurs when arming from a keypad.
Arming from a zone, schedule, or remotely is not affected and Arm First areas do not
automatically arm.
XR100 Series Programming Guide
Digital Monitoring Products
39
ZONE INFORMATION
Zone Information
15.1
ZONE INFORMATION
Zone Information
Zone Information allows you to define the operation of each protection zone used in
the system. All protection zones, whether located on a command processor panel,
Security Command keypad, or zone expander are programmed the same way.
15.2
ZONE NO: -
Zone Number
Enter the number of the zone you intend to program. Available zone numbers are
shown in the table below. The keypad zone numbers begin with the keypad address
and are followed by the particular zone from that keypad. For example, a 7073 at
keypad address 7 would provide zones 71, 72, 73, and 74.
Press COMMAND to enter a zone name.
Address
Programming Zone Number
Panel
1-10
1
11-14
2
21-24
3
31-34
4
41-44
5
51-54
6
61-64
7
71-74
8
81-84
1100 Series Key Fob
400-449
LX-Bus 1
500-599
Note: For 1100 Series Key Fob zones (400-449), programming continues at the 1100
Series Key Fobs Section.
15.3
* UNUSED *
Zone Name
Zone names can have up to 16 alphanumeric characters. A name must be given to
each zone in the system. The name can display at the keypads during arming and
disarming so the user does not have to memorize zone numbers. Users can associate
a zone name with a particular protection point. A zone that is not part of the system
must be marked unused.
To add a zone name to the system, press any Select key and then enter up to 16
characters for the new zone name. Press COMMAND to continue.
To mark a zone unused, delete the old name by pressing a top row Select key, then
press the COMMAND key. The programmer automatically programs the name as *
UNUSED *. If you have already cleared Zone Information during Initialization, the
zones will be marked * UNUSED *.
Digital Monitoring Products
40
XR100 Series Programming Guide
ZONE INFORMATION
15.4
ZONE TYPE:
BLANK
Zone Type
The Zone Type defines the panel response to the zone being opened or shorted.
This is called the Alarm Action. There are up to 13 possible alarm action responses
depending on the zone type and any restrictions it may have. See the Zone Type
chart in the Appendix.
When you assign a Zone Type to a zone, automatic zone responses are made. There
are 12 Zone Types to choose from. Application descriptions for each zone type can
be found in the Appendix of this manual.
To enter a new Zone Type, press any Select key. The display lists all of the available
Zone Types four at a time.
--
NT
DY
EX
Blank, Night, Day, or Exit. Press COMMAND for additional zone types.
FI
PN
EM
SV
Fire, Panic, Emergency, or Supervisory. Press COMMAND for additional zone types.
A1
A2
FV
AR
Auxiliary 1, Auxiliary 2, Fire Verify, or Arming (keyswitch). Press the Back Arrow key
to display the previous zone types. When the Zone Type you want displays, press the
Select key beneath it.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the Zone
Type, the zone must be assigned to an active area. If you select Fire, Fire Verify,
Panic, Emergency, or Supervisory as the Zone Type, it is a 24-hour zone that is always
armed and no area assignment is needed.
Zone Type Specifications
The panel contains 12 default zone types for use in configuring the system. These
zone types provide the most commonly selected functions for their applications. All
zone types except the Arming zone type can be customized by changing the options
listed below.
Refer to the Appendix for complete zone type descriptions.
15.5
Area Assignment
In an Area system, enter the area number where this zone is being assigned. Area
number 1-8 can be assigned for Night, Day, Emergency, Auxiliary 1 and Auxiliary 2
zones.
AREA NO: -
AREA:
INT
INT
15.6
In an All/Perimeter or Home/Sleep/Away system, the currently selected area,
PERIMETER Perimeter, Interior, Bedroom displays.
PERIM
BDRM PERIM
FIRE BELL OUT:
0
On an All/Perimeter system, select INT to program zones for the interior area and
select PERIM to program zones for the perimeter area.
On a Home/Sleep/Away system, select INT to program zones for the interior area,
select BDRM to program zones for the bedroom area, and select PERIM to program
zones for the perimeter area.
Fire Bell Output
This output (1 to 6, 500 to 599, G1 to G20, or D1 to D8) is turned on any time a Fire,
Fire Verify, or Supervisory zone is placed in alarm. The output is turned off by any
the following actions:
• When the User Menu Alarm Silence function is performed.
• When a valid user code is entered to silence the bell.
• When the Silence key is pressed on the 630F Remote Fire Command Center.
• Using the Outputs On/Off function in the User Menu.
• The expiration of the Bell Cutoff time.
This output can be connected to a lamp, LED, or buzzer using the DMP Model 716
Output Expansion Module.
XR100 Series Programming Guide
Digital Monitoring Products
41
ZONE INFORMATION
15.7
Arming Zone Area Assignment
In an Area system, if the zone has been programmed as an Arming Type (AR), enter the
areas that the zone controls.
ARM/DIS AREAS
When the zone changes from normal to shorted, the programmed areas toggle between
the armed or disarmed condition using the Style programming below. When restored to
normal, no action occurs. When the zone is opened from a normal (disarmed) state, a
trouble is reported. When opened from a shorted (armed) state, an alarm is reported and
the zone is disabled until you disarm the area(s) from either a keypad or Remote Link™
computer.
To visually indicate the armed state of the area(s), you can assign an Armed Output
to individual areas and use remote LEDs at the keyswitch. The LED turns on or off to
indicate to the user the armed state of the area(s).
ARM AREAS: PERIM
In an All/Perimeter or Home/Sleep/Away system, this option specifies the areas to be
armed by the Arming Type zone. For All/Perimeter systems, choose PERIM or ALL, for
Home/Sleep/Away or Home/Away systems, choose HOME, SLEEP, or AWAY.
PERIM
ALL
Perimeter/All - Specify whether the arming zone arms just the Perimeter (PERIM) or
the Perimeter and Interior areas (ALL) for All/Perimeter systems. When disarming, all
areas are disarmed.
HOME SLEEP AWAY
Home/Sleep/Away - Specify whether the arming zone arms the Perimeter (HOME), the
Perimeter and Interior (SLEEP), or all three areas (AWAY). When disarming, all areas
are disarmed.
Arming Zone Operation
If any bad zones are present when the Arming zone is shorted, the LED delays lighting
for 5 seconds. If during the 5-second delay the Arming zone is shorted again no arming
takes place. If 5 seconds expire without the zone shorting again or restoring to normal,
the areas arm and bad zones are force armed. To allow bad zones to be force armed,
the Any Bypass option must be set to YES. If Any Bypass option is set to NO, arming
does not occur. See the Area Information - Any Bypass section. A priority zone cannot
be force armed.
15.8
STYLE:
Style
This option specifies the style for the arming/disarming operation. The default style
is TGL (toggle). Press any Select key to display the STYLE options. To view more style
options press the COMMAND key.
TGL ARM DIS STEP TGL (Toggle) - When the zone changes from normal to shorted, the programmed areas
toggle between the armed or disarmed condition. When restored to normal, no action
occurs. When the zone opens from a normal (disarmed) state, a trouble is reported.
When opened from a shorted (armed) state, an alarm is reported and the zone is
disabled until you disarm the area(s) from either a keypad or Remote Link.
ARM - When the zone is shorted, the programmed areas are armed. When restored to
normal, no action occurs. When the zone is opened from a normal (disarmed) state, a
trouble is reported. When opened from a shorted (armed) state, an alarm is reported.
DIS (Disarm) - When programmed, a short disarms the programmed areas. When
restored to normal, no action occurs. When the zone is opened from a normal
(disarmed) state, a trouble is reported.
STEP - A short arms the areas and beeps the keypads once. A normal condition will
cause no action. An open condition will disarm the programmed areas and beep the
keypads for one second.
Note: This arming style is designed for wireless arming pendants. When using a
arming/disarming keyswitch locate the keyswitch within the protected area.
MNT
Digital Monitoring Products
42
MNT (Maintain) - When the zone is shorted, the programmed areas are armed. When
restored to normal, the programmed areas are disarmed and any alarm bells are
silenced. When the zone is opened from a normal (disarmed) state, a trouble is
reported. If opened from a shorted (armed) state, an alarm is reported and the zone is
disabled until you disarm the area(s) from either a keypad or Remote Link.
XR100 Series Programming Guide
ZONE INFORMATION
15.9
NEXT ZN?
NO YES
Next Zone
Select YES to terminate zone programming. The display returns to Zone Number,
allowing you to enter a new zone number. Select NO to make alterations to the
Alarm Action for a zone. Alarm Action is defined beginning with section 15.12.
To program zones for wireless operation, select NO at the NEXT ZONE - NO YES
option. The WIRELESS NO YES option displays. If the zone you are programming
is intended for wireless devices, select YES. Select NO to continue programming
non-wireless zones in the 500 to 599 range.
• Zones 400 to 449 can be programmed for 1100 Series Key Fobs.
• Zones 500 through 599 can be programmed for DMP Wireless.
DMP Wireless
For a DMP 1100X Wireless Receiver set the House Code to 1-50. See House Code programming in System
Options. Zones 500 through 599 can be programmed as Wireless zones. Set the XR100 Series panel J23
jumper to X to enable DMP Wireless operation. After power-up, briefly reset the panel using the J16
jumper to activate Wireless operation. Refer to the XR100 Series Installation Guide (LT-0899).
For an 1100 Series Key Fob see section 15.11.
NOTE: All wireless programming is stored in the XR100 Series panel. The 1100X Wireless Receiver obtains
the necessary programming information from the panel each time the receiver powers up, when the
programmer STOP routine is selected or the panel is reset. The receiver memory refresh takes up to 10
seconds to complete depending on the number of wireless zones programmed and the Red LED remains on
during this time. Normal receiver operation is inhibited during the memory refresh period.
15.10
15.10.1
ZONE INFORMATION Wireless
WIRELESS? NO YES Select YES to program this zone as a DMP wireless zone. You must program the
wireless House Code prior to adding DMP wireless zones to the system. See House
Code programming in System Options. Default is NO.
TRANSMITTER
SERIAL#: XXXXXXXX
Serial Number Entry
Enter the eight-digit serial number, including leading zeros, found on the
wireless device.
15.10.2
ALREADY IN USE
ZONE NUMBER: XXX
This prompt displays when the serial number is already programmed for another
zone. The programmed zone number displays.
TRANSMITTER
CONTACT:XXXXXXXX
Contact
This prompt displays if the serial number entered is for an 1101 or 1103
Universal Transmitter. Press any top row Select key to choose internal or
external contacts.
TRANSMTR CONTACT This option displays when programming an 1101 or 1103 Transmitter. Select INT
to use the internal reed switch contacts. Select EXT to connect an external
INT EXT
device to the 1101 or 1103 terminal block. Default is INT.
Note: The 1101 or 1103 Universal Transmitter serial number may be
programmed for two zones provided the Contact type (INT or EXT) is
programmed differently for each zone.
Note: When using the 1103 Universal Transmitter in a UL listed Commercial
Burglary installation, the external contact cannot be used.
XR100 Series Programming Guide
Digital Monitoring Products
43
ZONE INFORMATION
ALREADY IN USE
ZONE NUMBER: XXX
This prompt displays when the Contact type (INT or EXT) is already programmed
for another zone. The programmed zone number displays.
By allowing both of the Model 1101 or 1103 contacts (INT and EXT) to be used at
the same time, two zones may be programmed from one transmitter.
For example, program transmitter serial number 01345678 as Zone 521 with an
INT contact type. Then program transmitter serial number 01345678 as Zone
522 with an EXT contact type. The same serial number is used for both zones.
Note: When using both contacts, you must use consecutive zone numbers.
For example, zones 531 and 532 or zones 590 and 591 are acceptable zone
assignments.
ZONE INFORMATION
NORM OPN NO YES
This option only displays when EXT is selected as the Contact type. For external
devices connected to the 1101 or 1103 terminal block, select NO to use normally
closed (N/C) contacts. Select YES to use normally open (N/O) contacts. Default
is NO.
Note: For UL listed installations, set Normally Open to NO.
15.10.3
TRANSMITTER
SUPRVSN TIME: XXX
Supervision Time
Press any top row key to select the supervision time required for the wireless
zone. Press COMMAND to accept the default time. Default is 60 minutes.
Press the Select key under the required number of minutes. The transmitter
SELECT MINUTES:
0
3
15
60 must check in at least once during this time or a missing condition is indicated
for that zone. 1100 Series transmitters automatically checkin based on the
supervision time selected for the wireless zone, no additional programming
is needed. If two zones share the same transmitter, the last programmed
supervision time is stored as the supervision time for both zones. Zero (0)
indicates an unsupervised transmitter.
Note: When the panel is reset or a receiver is installed or powered down and
powered up, the supervision timer restarts for all wireless zones.
15.10.4
LED OPERATION
NO YES
LED Operation
Select YES to turn on a panic, pendant, or hold-up transmitter LED during
Panic or Emergency operation. Select NO to turn the LED off during Panic or
Emergency operation. The LED always operates when the transmitter case is
open and the tamper is faulted. Default is YES.
Note: For UL listed holdup installations, set LED Operation to NO.
15.10.5
NEXT ZONE NO YES
Next Zone
Select YES to return to the ZONE NO: - prompt to program a new zone. Select
NO to display the Alarm Action option.
1100 Series Key Fobs
For an 1100 Series Key Fob set the House Code to 1-50. See House Code programming in System Options.
Only zones 400 to 449 can be programmed as 1100 Series Key Fob zones. Refer to the 1100 Series Key Fob
Programming Sheet (LT-0706) and the 1100 Series Key Fob Install Guide (LT-0703) as needed. The following
programming continues from the Zone Number Section when zone 400-449 is selected.
To operate arming and disarming properly, the Key Fob should be assigned to a User Number with
appropriate area assignments, however, the User Number does not have to exist at the time the Key
Fob is programmed. The Key Fob User Number can be added later by the User.
Note: Key Fobs have not been investigated by UL and are not intended for UL listed applications.
15.11.1
KEY FOB USER
NUMBER: XXXX
Digital Monitoring Products
44
Key Fob User Number
Enter the User Number (1-9999) used to identify the Key Fob user and their
arming and disarming authority at the receiver and panel. This information can
be viewed in Display Events. Default is blank.
XR100 Series Programming Guide
ZONE INFORMATION
15.11.2
TRANSMITTER
SERIAL#: XXXXXXXX
Key Fob Serial Number
Enter the eight-digit serial number, including leading zeros, found on the
wireless device.
15.11.3
TRANSMITTER
SUPRVSN TIME: XX
Key Fob Supervision Time
SELECT MINUTES:
0
3
15
60
Press the Select key under the required number of minutes. The key fob must
check in at least once during this time or a missing condition is indicated for
that zone. 1100 Series key fobs automatically checkin based on the supervision
time selected for the wireless zone, no additional programming is needed.
Zero (0) indicates an unsupervised transmitter.
Press any top row key to select the supervision time required for the key fob
zone. Press COMMAND to accept the default time. Default is 0 for key fobs.
Note: When the panel is reset or a receiver is installed or powered down and
powered up, the supervision timer restarts for all wireless zones.
15.11.4
NO. OF KEY FOB
BUTTONS: X
Number of Key Fob Buttons
Enter the number of buttons (1, 2, or 4) on the Key Fob being programmed.
Note: Default button assignment for one-button key fobs is a Panic Alarm (PN)
with no output assigned.
15.11.5
15.11.6
15.11.7
BUTTON:
TOP BTM LFT RGT
Key Fob Button Selection (Four Buttons)
BUTTON:
TOP BTM
Key Fob Button Selection (Two Buttons)
BUTTON
ACTION: XXXXXXXX
Button Action
BUTTON ACTION?
ARM DIS TGL STA
ARM (Arm) - Arms selected areas and force arms bad zones.
This prompt only displays if the Key Fob being programmed is a four-button
model. Press the Select key under the Key Fob button to program. The
following list identifies the default button assignments:
TOP Arming
BTM Disarming
LFT Panic Alarm (PN) with no output assigned
RGT Arming Home, Perimeter, or Area 1 if assigned to the user number
This prompt only displays if the Key Fob being programmed is a two-button
model. Press the Select key under the Key Fob button to program. The
following list identifies the default button assignments:
TOP Arming
BTM Disarming
This option specifies the Button Action? for an individual Key Fob button. The
default action displays. Press any Select key to display the Button Action?
options. To view more options press the COMMAND key.
DIS (Disarm) - Disarms selected areas.
TGL (Togl Arm) - Toggles arm/disarm for selected areas and force arms bad
zones.
STA (Status) - Causes the Key Fob LED to indicate the arm/disarm status of the
system.
BUTTON ACTION?
PN PN2 EM EM2
PN (Panic) - Triggers a Panic zone type alarm with no restoral.
PN2 (Panic 2) - Triggers a Panic zone type alarm with no restoral when pressed
simultaneously with any other Panic 2 button. No action occurs when pressed
alone.
EM (Emerg) - Triggers an Emergency zone type alarm with no restoral.
EM2 (Emerg 2) - Triggers an Emergency zone type alarm with no restoral when
pressed simultaneously with any other Emergency 2 button. No action occurs
when pressed alone.
XR100 Series Programming Guide
Digital Monitoring Products
45
ZONE INFORMATION
OUT (Output) - Causes an output to turn on steady, pulse, momentary, toggle or
off.
BUTTON ACTION?
OUT RST
UN
RST (Snsr Rst) - Causes the panel to perform a standard Sensor Reset.
UN (Unused) - The button is not used and performs no action.
15.11.8
aaa BUTTON PRESS
TIME:
DDDDD
Button Press Time
This option specifies the amount of time (SHORT or LONG) the user must press
the button before the action initiates a message to the receiver. Press any
Select key to set the Button Press Time for Arm, Disarm, Toggle, Status, Output,
and Sensor Reset.
Note: The Button Press Time is not programmable on Panic (PN or PN2)
Emergency (EM or EM2) or Unused (UN) zones. For those zones the button press
time is two (2) seconds.
15.11.9
BUTTON PRESS:
SHORT
LONG
SHORT - Press the button for one-half (1/2) second to initiate the action.
ARM/DIS AREAS:
Arm/Disarm Area Selection
1
5
2
6
3
7
4
8
LONG - Press the button for two (2) seconds to initiate the action.
In an Area system, this specifies the areas to be armed/disarmed by the Key Fob
button being programmed. To select an area between 1 and 8, enter the area
number using the keypad digit keys. Default is no areas enabled.
In order to arm or disarm selected areas, the Profile assigned to the User
Number needs to have the same area numbers selected. Any area may be
selected at Arm/Disarm Areas but only matching area numbers are armed or
disarmed when the specific button is pressed. For example, in Areas selection,
areas 1, 3, and 7 are selected. In the User Profile Arm and Disarm Areas, areas
1, 2, 4, and 7 are selected. When the user presses the button to Arm or Disarm
area(s), only matching areas 1 and 7 Arm/Disarm.
Note: When more areas are selected at Arm/Disarm Areas than are authorized
in the User Profile, in the future the user can be given access authority to
additional areas through the User Profile without requiring additional panel
programming to select Arm/Disarm Areas. See User Profiles in the Appendix or
refer to the XR500 Series User’s Guide (LT-0683).
ARM AREAS: PERIM
In an All/Perimeter or Home/Sleep/Away system, this specifies the area to be
armed by the Key Fob button being programmed. For All/Perimeter systems,
choose PERIM or ALL, for Home/Sleep/Away or Home/Away systems, choose
HOME, SLEEP, or AWAY.
Note: Areas 3 and higher in an All/Perimeter system, and areas 4 and higher in a
Home/Sleep/Away system are not available for use.
After selecting the areas, for one-button key fobs the Zone No.: prompt
displays. For two-button or four-button key fobs, the Key Fob Button Selection
option displays to program additional buttons.
15.11.10
OUTPUT NO: XXX
Output Number
You can specify a relay output to operate when OUT (Output), PN (Panic), PN2
(Panic 2), EM (Emergency), or EM2 (Emergency 2) is selected for a key fob
Button Action and the button is pressed. Valid range is 1 to 6, 500 to 599,
D1 to D8, or G1 to G20. For an output turned on by a PN, PN2, EM, or EM2
button action, the output turns off when any area is disarmed.
To enter an output number, press a top row Select key followed by the output
number. Press the COMMAND key.
Digital Monitoring Products
46
XR100 Series Programming Guide
ZONE INFORMATION
15.11.11
ACTION: XXXXXXXX
Output Action
This option allows you to define the Key Fob output operation (STD, MOM, TGL,
OFF) when PN, PN2, EM, or EM2 is selected for a Key Fob Button Action and the
button is pressed. For an output turned on by a PN, PN2, EM, or EM2 button
action, the output turns off when any area is disarmed by Key Fob button press.
The currently programmed action displays.
OUTPUT ACTION?
STD PLS MOM TGL
STD (Steady) - The output is turned on and remains on until the area is
disarmed, an output cutoff time expires, or the output is reset from the keypad
menu.
PLS (Pulse) - The output alternates one second on and one second off. Note:
The pulsing rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
MOM (Momentary) - The output is turned on only once for one second.
TGL (Toggle) - The output alternates between the armed and disarmed
condition. When restored to normal, no action occurs. When the zone opens
from a normal (disarmed) state, a trouble is reported. When opened from a
shorted (armed) state, an alarm is reported and the zone is disabled until the
area(s) is disarmed from either a keypad or Remote Link.
OFF (Off) - The output is turned off. If programmed, the output was turned on
by some other means such as another button, a zone action, or a schedule.
OUTPUT ACTION?
OFF
15.11.12 NEXT ZONE NO YES
Next Zone
Select YES to return to the ZONE NO: - prompt to program a new zone. Select
NO to display the Alarm Action option.
15.12 ALARM ACTION . . . .
Alarm Action
This option allows you to change any Zone Type standard definitions. When the Zone
Type is specified, the Alarm Action for that zone is stored in memory.
If the Zone Type is Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 it is a
non-24-hour zone and the Alarm Action programing begins with Disarmed Open.
If the Zone Type is Fire, Panic, Emergency, or Supervisory it is a 24-hour zone that is
always armed and the Alarm Action programming begins with Armed Open.
The Fire Verify Zone Type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone initiates an alarm, the panel performs a Sensor
Reset. If any Fire Verify zone initiates an alarm within 120 seconds after the
reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the cycle is
repeated and a zone fault report is sent to the receiver.
Do NOT program Fire Verify Zone Types for Zone Retard.
15.13 DISARMED OPEN
Disarmed Open
Defines the action taken by the panel when the zone is opened while the area is
disarmed. There are three actions to define: Report to transmit, Relay Output to
activate, and Relay Output action.
You must also make these selections for the Disarmed Short, Armed Open, and Armed
Short zone conditions. Press COMMAND to continue.
XR100 Series Programming Guide
Digital Monitoring Products
47
ZONE INFORMATION
15.14 MSG:
A
TROUBLE
T
L
-
Report to Transmit
Press any Select key to display the following report options: A, T, L, S, and - (dash).
ALARM - Select A to send an alarm report to the receiver and activate the bell
output according to zone type. The zone name appears in the panel alarmed zones
and status lists.
TROUBLE - Select T to send a trouble report to the receiver. The zone name
appears in the panel alarmed zones and status lists.
Note: UL requirements prevent the Alarm (A) and Trouble (T) action for Fire (FI), and
Fire Verify (FV) zone types from being changed.
LOCAL - When you select L, an alarm report is NOT sent to the receiver. The bell
output activates and the zone name appears in the panel alarmed zones and status
lists.
- (Dash) - When you select a – (dash), reports are NOT sent to the receiver. The bell
output does not activate and there is no display in the panel alarmed zones or status
list. Only the relay output selected in the next section operates.
D
S
DOOR PROPPED - Selecting D allows the following operation: The time programmed
into ENTRY DLY 4 in the System Option section begins to count without displaying
on keypad. If the time expires and the zone has not returned to normal, the keypad
trouble buzzer starts and CLOSE THE DOOR appears on the keypads programmed into
the PREWARN ADDRESS section. The time programmed into ENTRY DLY 4 begins to
count down again internally. If the time expires a second time and the zone has not
returned to normal, a fault report is sent to the receiver and the zone name - OPEN
message displays on the keypads until a code is entered. The bell output does not
activate for the Door Propped operation.
SILENCE/RESET - Select S when the zone (not FI, SV, or FV) is connected to a DMP
Model 303 Silence/Reset switch, the zone can be used to silence the alarm bell and
perform a sensor reset without using a keypad. A report is NOT sent to the receiver
except for the bell silence report.
15.15 OUTPUT NO:
0
Output Number
You can specify any of the Relay Outputs on the XR100 Series panel to be activated
by a zone condition (1 to 6, 500 to 599 if Model 716 used, D1 to D8, G1 to G20). The
output can be activated regardless of the report to transmit or whether or not the
zone is programmed as local. An output activated by an armed zone is turned off
when the zone area is disarmed by a user.
To enter an output number, press a top row Select key followed by the output
number. Press the COMMAND key.
15.16 OUTPUT:
NONE
Output Action
Entering an Output Number displays this prompt. This prompt allows you to assign
an output action to the relay: Steady, Pulse, Momentary, or Follow.
STD PLS MOM FOLW STEADY - The output is turned on and remains on until the area is disarmed, an
output cutoff time expires, or the output is reset from the keypad menu.
PULSE - The output alternates one second on and one second off. Note: The pulsing
rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an off
normal, or bad condition. When the zone restores, the output is turned off.
After you make the three selections in the sections above, the display prompts you for the same three
selections for Disarmed Short, Armed Open, and Armed Short conditions. If the zone is a 24-hour type,
only the Armed Open and Armed Short conditions display. When you have programmed all of the zone
conditions, the Swinger Bypass selection then displays.
Digital Monitoring Products
48
XR100 Series Programming Guide
ZONE INFORMATION
15.17 SWGR BYP NO YES Swinger Bypass
YES allows the zone to be swinger bypassed by the panel according to the
specifications programmed in Swinger Bypass Trips and Reset Swinger Bypass. The
Bypass condition displays in the keypad Status List. Selecting NO disables swinger
bypassing for this zone.
How it works
If within one hour, a zone trips the total number of times AS specified in Swinger
Bypass Trips, the panel bypasses it until the following conditions occur; the area
in which the zone is assigned is disarmed, the zone is manually reset through the
Bypass Zones? keypad User Menu function, the zone remains normal for one hour and
the Reset Swinger Bypass is YES.
If the zone trips fewer than the specified times within one hour, the bypass trip
counter returns to 0 (zero) and the process must be repeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES.
Note: Not investigated by UL.
15.18 PREWARN KEYPADS:
Prewarn Keypad Addresses
At the entry delay start, all keypad addresses selected here display ENTER CODE:-.
If you want the prewarn to sound at all 8 addresses, leave the default setting.
To delete an address, press the matching number on the keypad. To disable
prewarning at all keypads, press a top row Select key to clear the addresses shown.
Press the COMMAND key when the address selection is complete.
The prewarn tone stops at the keypad where the first user code digit is entered. If
no keys are pressed for five seconds or an invalid user code is entered, the prewarn
tone resumes at that keypad.
15.19 ENTRY DELAY:
1
Entry Delay
Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System
Options.
15.20 RETARD
NO YES
Zone Retard Delay
When you select YES, the zone operates with the zone retard delay. The retard
functions only in zone short conditions.
The zone must remain shorted for the full length of the retard delay before the
panel recognizes its condition. If you select NO, the zone operates without a retard
delay.
Note: For UL installations, Zone Retard Delay shall not be used for burglary
zones.
15.21 PRESGNL:
NONE
Presignal Addresses
You can enable any combination of keypad addresses to sound a presignal tone
during the time a zone is in retard delay. The presignal tone silences when the zone
restores or the retard delay expires.
To enable a presignal address, press any top row Select key followed by the number
of the keypad address. You can enable the presignal for all eight keypad addresses.
To disable a presignal address press the matching number digit again. Press the
COMMAND key when the address selection is complete. The Presignal prompt is only
displayed when Retard is selected as YES.
15.22 FAST RSP
NO YES
Fast Response
Select YES to provide a zone response time of 167ms. Select NO to provide a normal
zone response time of 500ms. Zones 500 to 599 have a fixed response time and do
not display this prompt.
XR100 Series Programming Guide
Digital Monitoring Products
49
ZONE INFORMATION
15.23 CRS ZONE NO YES Cross Zone
Select YES to enable cross zoning for this zone. Cross zoning requires one or more
armed zones to fault within a programmed time before an alarm report is sent to the
receiver.
When the first cross zoned zone trips, the cross zone time specified in System
Options begins to count down. When a second cross zoned zone trips or the first
zone trips a second time before the end of the count down, the bell action assigned
to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel
sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types: You can not enable cross zoning
for Fire verify zones or for any Fire zones that have Retard Delay enabled.
Note: For UL Installations, Cross Zoned zones must protect the same area.
15.24 PRIORITY NO YES Priority
Select YES to provide additional protection for the premises by requiring this zone to
be in a normal condition before its assigned area can be armed.
ZONE NO: -
Digital Monitoring Products
50
ZONE NUMBER - Enter the zone number to program next. Follow the descriptions of
each programming prompt. If all zones are programmed, press the Back Arrow key
at the ZONE NO: – display to continue.
XR100 Series Programming Guide
STOP
Stop
16.1
STOP
Stop
Save Programming
WHEN ANY PANEL PROGRAMMING IS CHANGED, THE STOP ROUTINE MUST BE RUN
AND ‘SAVING PROGRAM’ MUST DISPLAY ON THE KEYPAD IN ORDER TO SAVE THE
PROGRAMMING CHANGES.
At the STOP prompt, pressing any Select key allows you to exit the Programmer
function of the panel. When selected, the panel performs an internal reset and
exits the programmer.
The STOP routine causes the following conditions to occur:
• All areas are DISARMED
• All zones are DISARMED
• The panel Status List displays CLEARED
During the reset, all keypad displays are momentarily blank for two seconds. After
the reset, the programming function terminates and the keypads return to the status
list display.
Power Up
When the SIA CP-01 option in System Options is set to Yes, for 60 seconds after
power up or after applying the J16 reset on the XR100 Series panel, any zone
transitions are not recognized. Normal zone processing resumes at the end of the
60 seconds.
SET LOCKOUT CODE
Set Lockout Code
17.1
SET LOCKOUT CODE
Set Lockout Code
Pressing COMMAND at the STOP prompt displays SET LOCKOUT CODE. This allows
you to program a code that is then required to gain access to the panel internal
Programmer through the keypad. You can change this code at any time to any
combination of numbers from three to five digits long. You do not need to enter
leading zeros when using the lockout code. Initializing the panel does not clear a
Lockout Code. Lockout Codes can be changed through Remote Link.
Once you have changed the code, it is important to write it down somewhere and
store it in a safe place. Lost Lockout Codes require the panel to be sent back to
DMP for repair. You may cancel a Lockout Code by entering 00000 at the Set Lockout
Code command.
Lockout Code restriction
Do not set a Lockout Code higher than 65535.
XR100 Series Programming Guide
Digital Monitoring Products
51
FEATURE UPGRADE
Feature Upgrade
18.1
FEATURE UPGRADE
Feature Upgrade
In the Programming Menu, pressing COMMAND at the SET LOCKOUT CODE prompt
displays FEATURE UPGRADE. This allows you to enable additional features in the
panel. Press any top row Select key to display the first available feature. ENABLED
or DISABLED displays indicating whether this feature is currently used in this panel.
Press the COMMAND key to display additional feature(s).
ENTER KEY
-
To enable a feature, press any top row Select key anywhere in the features list to
display the ENTER KEY prompt.
Enter the factory-supplied feature key for the specific panel and press the COMMAND
key. The feature specific to the key displays as ENABLED.
Note: XR100 Series version 106 or higher panels require a six (6) character feature
key. Version 105 panels require a 16-character feature key.
If the feature key entered is not accepted, the ENTER KEY prompt displays again.
Re-enter the feature key and press the COMMAND key.
18.1.1 ALL NO YES OPTN All No Yes Option
DISABLED
18.1.2 SVC USER AUTH
DISABLED
This feature offers the ability to disable the ALL NO YES option at arming or
disarming. When this feature is enabled, the ALL NO YES option does not display
at any system keypad during arming or disarming. Each area assigned to the user
profile is chosen to be armed or disarmed independently.
Service User Authentication
This feature offers the ability to authenticate service personnel before allowing
access to panel programming or performing any user operations. When this feature
is enabled and a valid Service User code is entered for system operation or 6653 is
entered for programming, the Service Code entry option displays.
When the service person enters the Service Code, the panel authenticates the code
with the Service Code preprogrammed in the SCS-1R receiver, and access to panel
programming or the User Menu is granted. The Service Code can be used for system
operation for 30 minutes before authenticating again. If the code entered is not
validated, access to programming or the User Menu using the Service User code is
denied.
Note: The Service User code is user number zero (0) and can only be created in the
panel remotely. The SCS-1R receiver must have firmware version 902 or higher to
authenticate service personnel.
Purchasing Feature Upgrades
To purchase a feature upgrade, you may contact DMP Customer Service with the
feature you would like to enable and the panel serial number. The serial number(s)
should be sent in writing via e-mail or fax. A separate feature key is issued for each
panel. The feature key only enables the requested feature on the specified panel.
The panel serial number can be located several different ways:
• Printed on a label located on the right side of the XR100 Series PCB.
• Using panel diagnostics. See the Appendix.
• Using Remote Link™ (version 1.18 or greater). See the Remote Link User’s
Guide (LT-0565).
— Initial Panel Connection screen
— System Information screen.
Digital Monitoring Products
52
XR100 Series Programming Guide
APPENDIX
Appendix
19.1
False Alarm Reduction
19.2
Diagnostics function
System Recently Armed report
The System Recently Armed report (S78) is sent to the receiver when a burglary zone goes into alarm within
two minutes of the system being armed.
The XR100 Series panel contains a Diagnostics function that allows you to test the communication integrity
of the LX-Bus™, identify individual zones, and also display the present electrical state of any zone. To use
Diagnostics, reset the panel, enter the Diagnostics code 2313 (DIAG), and press COMMAND.
Test LX-Bus
The first Diagnostic function you displayed is: TEST LX-BUS. This function allows you to test the ability of the
LX-Bus to communicate with zone and output expander modules connected to their LX-Bus circuits.
To continue, press any top row Select key. The keypad displays LX-BUS:. Using the digit keys, enter the LXBus number 1 to test that LX-Bus circuit. The keypad now displays ADDRESS: - . Enter a 2-digit LX-Bus device
address and press COMMAND. When testing LX-Bus devices, enter only the addresses to which the modules
have been set.
Important Note: A device address is not the same as a zone number. If you are testing 714 or 715 Zone
Expander Modules, which each contain four zones, the device address is the first zone number. When the
panel polls a 714 on the LX-Bus, it recognizes it as a four zone device and does not poll the remaining three
zones. The 714 module internally polls the remaining zones and transmits any status changes to the panel.
This greatly reduces the amount of time it takes the panel to poll all LX-Bus devices.
The keypad next displays TESTING . . . STOP during the device testing. At any time, you can Select STOP to
end polling. The panel records the number of no responses from the device. If all polls are received back by
the panel correctly, the keypad displays 00000/65535 FAIL.
If one or more polling attempts fail, the keypad displays * * * * */65535 FAIL with the * representing the
number of failed polling attempts. A display of 65535/65535 FAIL indicates a problem with the interface
card or its LX-Bus wiring such as a bad or broken wire, harness not properly connected, or excessive noise or
distance. It can also mean that a zone number was entered that did not match a device address. Press the
Back Arrow key to enter a new device address or press COMMAND to exit the TEST LX-BUS.
Zone Finder
The second Diagnostic function is the Zone Finder. Press COMMAND to display ZONE FINDER. This function
allows you to identify individual zones on devices connected to the LX-Bus of an interface card, the panel, or
any zones on the keypad data bus. To use ZONE FINDER, press any top row Select key. The display changes
to FAULT ZONE. The next zone on the system that changes from a normal to an open or shorted state is
displayed as ZONE NO: * * *. To continue, press the Back Arrow key.
Zone State
Press the COMMAND to display the third Diagnostic function: ZONE STATE. This function allows you to enter
any zone number and check its current electrical state (Normal, Open, or Shorted). Press any Select key. The
display changes to ZONE NUMBER: _ . Enter in the zone number you want to check and press COMMAND. The
panel displays the current state of the zone as NRML (normal), OPEN, or SHORT.
LX-Bus Status
The fourth Diagnostic function is the LX-BUS STATUS. This function allows the panel to poll all devices
connected to the LX-Bus of an interface card and check for any Overlapped, Missing, or Extra addresses.
Below is a description of each status item:
Overlap - An overlap occurs when one device address is the same as any of the last three zones on another
714 or 715. The overlap feature cannot determine when two devices have the same address.
Example: Model 714 Address 00 = Zones 500 501 502 503, and the Model 711 Address 02 = Zone 502.
Zone 502 would report as an Overlap because both the 714 and 711 have devices set to 502.
Missing - A missing occurs when a zone between 500 and 599 has been programmed in ZONE INFORMATION
and no device with that zone address has been installed on the LX-Bus. To correct the problem, check your
zone programming and zone expansion module addressing.
Extra - A device is installed on the LX-Bus but none of its zones are programmed into the system.
XR100 Series Programming Guide
Digital Monitoring Products
53
APPENDIX
MAC Address
Short for Media Access Control address. This hardware address uniquely identifies each network node. Not to
be confused with an IP address, which is assignable. In the Diagnostics function, the MAC address is the panel
on-board network hardware address. Press any top row Select key to display the panel MAC address. Press
the COMMAND key to view the next prompt.
Serial Number
This number is the network communicator serial number. Reference this number for communicator date-ofmanufacture, hardware version, etc. Press any top row Select key to display the Serial Number. Press the
COMMAND key to view the next prompt.
Current Flash
This option displays Flash 1 or Flash 2 indicating which physical flash chip the panel is currently using. Press
any top row Select key to display the current flash information. Press the COMMAND key to view the next
prompt.
Send Test Message
To Send a Test Message press the COMMAND key until SEND TEST MSG displays. Press any top row Select
key/area to send a Device Missing message for the first available LX-Bus zone to the central station.
Note: A Restoral message is NOT sent.
Exiting the Diagnostics program
To exit the Diagnostics function, press the COMMAND key until STOP displays. Press any Select key to exit the
diagnostics function. The keypad returns to the Status List display.
19.3
Using the 984 Command Function
This feature allows you to connect to a service receiver, is used primarily to bring a new account on-line and
upload panel programming completed in Remote Link™. There are three options to allow manual phone line
seizure: Number, Remote, and Pickup.
NBR
After completing panel programming in Remote Link, set a trap to seize the panel when it calls. Traps are set
by selecting Panel > Trap. Refer to the Remote Link User’s Guide (LT-0565), or the Remote Link Help File.
Then, from the panel, enter 984 and press the COMMAND key, while the panel is in the Status List. The
keypad display changes to NBR RMT PICKUP. Press the Select key under NBR. Enter the phone number for
the service receiver connected to the Remote Link computer. Press each number key slowly and deliberately.
The panel dials each number as it is pressed. If you make a mistake, press the Back Arrow key. The panel will
stop dialing and return to the Status List.
You can enter up to 32 characters for the phone number. Once you have entered 16 characters the LCD
display is full: Press the COMMAND key to enter the final 16 characters. To enter a # (pound sign) press the
fourth (far right) Select key, and to enter an * (asterisk) press the third Select key. Program a pause by
entering the letter P. Program CID message communication by entering the letter T in the first position.
Cancel call waiting by entering *70P as the first characters. These characters are counted as part of the
allowable 32 characters. Press COMMAND after you enter the phone number.
The panel calls the receiver connected to Remote Link to download the new programming. Remote Link then
traps the panel.
Note: The panel makes ten attempts to reach the receiver. While attempting to contact the receiver, if the
panel needs to send an alarm report, the panel stops dialing and uses the phone line to send its report.
Digital Monitoring Products
54
XR100 Series Programming Guide
APPENDIX
RMT
Select RMT if you want the panel to immediately seize the phone line and dial the remote phone number
programmed into the panel programming Remote Options section. The Remote Options phone number
connects to the modem used by the DMP Remote Link™ software program.
After completing panel programming in Remote Link, set a trap to seize the panel when it calls. Traps are
set by selecting Panel > Trap. Refer to the Remote Link User’s Guide (LT-0565), or Remote Link Help File
for complete information about setting traps.
While the panel displays in the Status List, enter 984 and press the COMMAND key. The keypad display
changes to NBR RMT PICKUP. Press the Select key under RMT. The panel automatically calls the receiver
connected to Remote Link to download the new programming. Remote Link then traps the panel.
Note: The panel makes ten attempts to reach the receiver. While attempting to contact the receiver, if
the panel needs to send an alarm report, the panel stops dialing and uses the phone line to send its report.
PICKUP
After completing panel programming in Remote Link, connect to the panel by selecting Panel > Connect.
Refer to the Remote Link User’s Guide (LT-0565), or Remote Link Help File for complete information about
connecting to panels.
While the panel displays in the status list and the telephone line at the panel rings, enter 984 and press
the COMMAND key. The keypad display changes to NBR PICKUP. Press the Select key under PICKUP to
allow the panel to seize the line. The panel immediately seizes the phone line and sends a carrier tone
to the receiver. A verification process occurs and, if successful, the panel grants remote access to its
programming and Event Buffer.
After the panel has seized the line, send the file from Remote Link by selecting Panel > Send. Remote
Link then uploads the new programming into the panel. You may also Request Events by selecting Panel >
Request Events in Remote Link. The panel begins sending the first event or access that occurred on or after
the start date specified by Remote Link and finishes by sending the last event or access that occurred on
or before the end date specified by Remote Link. If necessary, a Request Events upload in progress can be
cancelled.
Keypad Displays
When either the RMT or PICKUP options are used, the keypad displays LINE SEIZED. This indicates that
the panel has seized the line and is executing its program. If the line cannot be accessed, or if the RMT or
PICKUP options are used before all connects attempts are made, the keypad displays SYSTEM BUSY.
19.4
Using the Walk Test
The XR100 Series panel provides a walk test feature that allows a single technician to test the protection
devices connected to zones on the system. Conduct the Walk Test within 30 minutes of resetting the panel.
The Walk Test automatically ends if no zones are tripped for 20 minutes. TEST IN PROGRESS displays at all
keypads programmed with the same Area Display features. When five minutes remain, TEST END WARNING
displays. The Walk Test only tests zones assigned to the areas programmed into the keypad in Area Display.
If any areas are armed the Walk Test does not start and SYSTEM ARMED displays.
WALK TEST
Walk Test
To conduct the Walk Test, reset the control panel by momentarily placing a
jumper on J16. From the keypad, enter the code 8144 and press COMMAND. The
keypad displays WALK TEST for four seconds. If the system is monitored and the
communication type is DD or NET, the system sends a System Test Begin report to the
central station. After four seconds, the keypad displays the zone type choices for
testing.
XR100 Series Programming Guide
Digital Monitoring Products
55
APPENDIX
*BG
Zone Types
*FI *PN *SV
Select the zone type you want to test. An asterisk next to the zone type indicates
the zone type chosen for testing. Press the Select key again to deselect the zone
type. When you have selected all the zone types you want for testing, press the
COMMAND key to display the next Walk Test option. Pressing the Back Arrow key
exits the Walk Test.
BG (Burglary zones) - Select BG to test burglary zones. Includes all NT, DY, EX, A1,
and A2 zones.
FI (Fire zones) - Select FI to test fire zones. Includes all FI and FV zones.
PN (Panic zones) - Select PN to test panic zones. Includes all PN and EM zones.
You do NOT have to hold the zones for 2 seconds in normal mode. You are only
required to hold the panic during the Walk Test because the zone takes additional
time to report when the system is in test mode.
SV (Supervisory zones) - Select SV to test supervisory zones. Includes all SV zones.
Note: During the Walk Test, trip each zone device or button on the system for 1 to 2
seconds.
BELL
NO YES
Bell Action
This option selects the bell output action when a zone under test faults. This option
allows the panel bell, and/or burglary bell, and/or fire bell to turn ON and then OFF
each time a zone is tripped (opened or shorted).
NO - Select NO for no bell output action during Walk Test.
YES - Select YES to turn on any bell output for 2 seconds during Walk Test.
PULS - Select PULS to turn on any bell output for 1/4 second during Walk Test. Any
LX-Bus device output will turn on for 1.6 seconds due to the polling cycle.
Once in the Walk Test, walk around and trip each protective device. As each device
trips, the panel sounds the alarm bells as programmed in Bell Action and then
performs an automatic Sensor Reset. Continue tripping devices until the entire
system is tested. The trip counter on the keypad display increments by one each
time a device is opened or shorted.
TRIPS: XXX
END
Trip Counter
Displays the number of zone trips during the Walk Test.
• Each time a selected zone trips, the keypad buzzes for two seconds.
• Each time a FI, FV, or SV zone trips, a Sensor Reset occurs.
END - Select END to stop the Walk Test. When the Walk Test ends or a 20 minute
time-out expires, a final Sensor Reset occurs. The System Test End message is
sent to the receiver along with Verify and Fail messages for each zone under test.
Faulted zones then display on the keypad.
TEST END WARNING
Test End Warning
When five minutes remain on the 20 minute Walk Test timer, the keypad displays
TEST END WARNING . If no additional test zone trips occur, the test ends and a final
Sensor Reset automatically occurs. The System Test End message is sent to the
receiver along with Verify and Fail messages for each zone under test. Faulted zones
then display on the keypad.
SOUTH LOBBY
ZONE: 10
-FAIL
Digital Monitoring Products
56
Failed Zones Display
For each zone that did not trip (failed) at least once during the Walk Test, all
keypads with matching Area Display programming display the zone name and number
and buzz for one second. Any selected (*FI *PN *SV) 24-hour zone that is faulted at
the end of the Walk Test displays a trouble condition for that zone regardless of the
message programmed for the open or short condition of the zone and a zone trouble
is sent to the receiver. Press the COMMAND key to display the next failed zone.
XR100 Series Programming Guide
APPENDIX
19.5
Keypad Speaker Operation
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire, Burglary,
Zone Monitor, and Prewarn events. The list below details the conditions under which the speaker is turned
on and off for each event.
Fire
On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off - Alarm Silence.
Burglary
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
Zone Monitor On - One time only when a monitored zone is tripped.
Off - After one tone.
Prewarn
On - During Entry Delay.
Off - When Entry Delay expires.
19.6
Cross Zoning
Caution must be taken when cross zoning devices to ensure that the Cross Zone Time is long enough to
allow an intruder to trip both devices before it expires. A Cross Zone Time that is too short may allow an
intruder to trip the devices and allow only a zone fault report be sent to the central station.
When a Cross Zoned zone trips a FAULT report is sent to the SCS-1R Receiver. When two Cross Zoned zones
trip within the Cross Zone Time, both zones send ALARM signals to the receiver. For example, if zones 1
and 2 are Cross Zoned zones, and only zone 1 trips, a FAULT report is sent to the receiver for zone 1. If
zone 1 trips and zone 2 trips within the Cross Zone Time, an ALARM report is sent to the receiver for zone 1
and zone 2.
19.7
Events Manager
The Events Manager allows you to delay sending certain reports to the central station receiver. Reports can
be kept in the panel memory until overwritten by new activity or held until the memory buffer reaches 50
events or 50 door access granted events. When the buffer is full, the panel automatically sends the stored
reports to the central station receiver. Below is a list of panel reports you can delay using the Events
Manager option.
Report Type
Immediately
Alarm
Y
Trouble
Y
Restore
Y
Delayed
Opening
Y
Closing
Y
Bypass
Y
Reset
Y
Supervisory
Y
Add Codes
Y
Delete Codes
Y
Change Codes
Y
Permanent Schedule Change
Y
Temporary Schedule Change
Y
Door Access
Y
Door Access Denied
Y
Late to Close
Y
Force Armed Zone
Y
XR100 Series Programming Guide
Digital Monitoring Products
57
APPENDIX
19.8
User Profiles
A profile defines the authority of each user code in the system. Profiles are programmed in the Keypad
User Menu. Several characteristics associated with each User Profile define its authority within the system.
To effectively program an XR100 Series system, you must understand the interrelationship between profiles,
devices, output groups, and areas. Below is a brief explanation of the User Profile elements. For more
information about user profiles, refer to the XR500/XR100 User’s Guide (LT-0683).
Profile Number - Each profile may be assigned a unique number from 1 to 99.
Note: Profiles cannot be changed via keypad in an All/Perimeter or Home/Sleep/Away system. Use
the default profiles 1 through 10. Refer to the User Profiles Record and the XR500/XR100 User’s Guide
(LT-0683).
Profile Name - Each profile may be assigned a 16-character name. The Profile Number is the default name.
Area Number - Each profile may be assigned specific areas of the system for arming and disarming. When
creating profiles 1 to 98, NO areas are assigned by default. The default for profile 99 is ALL areas assigned.
Profile 99 is preprogrammed in the system at the factory.
Access Area Number - Each profile may be assigned door access area assignments. Default for profile 1 to
98 is NO areas assigned. Default for profile 99 is ALL areas assigned. Profile 99 is preprogrammed at the
factory.
Output Group Assignment - Each profile may be assigned an output group number from 1 to 10. Default
for profile 1 to 98 is NO output group assigned. Default for profile 99 is output group 10. Your system may
by programmed to turn on an output group at certain keypads when door access occurs.
User Menu Assignments - Each user profile may have any of the menus assigned to it as shown in the
User Profile Record below. The User Profile Record lists the user menu profile assignments and the system
functions users are allowed to access based on the profile numbers assigned to their codes.
Always make sure that at least one administrator in your system has a profile with all authorities and all
areas.
Digital Monitoring Products
58
XR100 Series Programming Guide
APPENDIX
19.9
User Profiles Record
Re Arm Delay
Shift/Time
Access
Anti-passback
Temp User Code
Extend
Fire Drill
Service Request
Display Events
Time
Schedules
User Codes
User Profiles
System Test
System Status
Zone Monitor
Bypass Zones
Zone Status
Outputs On/Off
Armed Area
Output
Group
Door Access
Access Areas
Sensor Reset
Arm/Disarm
Areas
Alarm Silence
Profile Name
Disarm
Profile
#
Arm
This User Profiles Record can be used as a tool when programming Devices, Profiles, Areas, and Output
Groups. Because these programming options are interrelated, use this sheet to plan the system before you
begin the installation and programming process.
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
1234A
XR100 Series Programming Guide
Digital Monitoring Products
59
APPENDIX
19.10 Zone Type Descriptions
This section describes applications for the default zone types in Zone Information programming.
-- (Blank Zone)
Customizable zone type. By default, no actions are programmed to occur with Blank Zone. A zone name
must be entered to use this zone type: This zone type is not the same as an *UNUSED* zone.
NT (Night Zone)
Controlled instant zone used for perimeter doors and windows and interior devices such as PIRs and
Glassbreak detectors.
DY (Day zone)
Used for emergency doors or fire doors to sound the keypad buzzer and display the zone name when the
zone is faulted. Day zones also send alarm reports to the receiver during the system armed periods.
EX (Exit zone)
Initiates the entry delay timer when its assigned area is fully armed. Also, can initiate an exit delay timer
to allow a user to exit an area after the arming process starts.
PN (Panic zone)
Used for connecting to mechanical devices that allow a user to signal an emergency alarm. Panic zones can
provide either a silent or audible alarm with or without reporting to a central station receiver.
EM (Emergency zone)
These are used for reporting medical or other non-panic emergencies to the central station receiver.
SV (Supervisory zone)
Used to provide 24-hour zone supervision to devices associated with fire systems. Typical applications are
tamper switches on Post Indicator Valves (PIVs), gate valves, and low and high temperature gauges.
FI (Fire zone)
Used for any type of powered or mechanical fire detection device. Typical applications are for smoke
detectors, sprinkler flowswitches, manual pull stations, and beam detectors. Retard, cross zoning, and
presignal options are available for the Fire zone type.
FV (Fire Verify zone)
Used primarily for smoke detector circuits to verify the existence of an actual fire condition. When a Fire
Verify zone initiates an alarm, the panel performs a Fire Reset. If any Fire Verify zone initiates an alarm
within 120 seconds after the reset, an alarm is indicated. If an alarm is initiated after 120 seconds, the
cycle repeats.
A1 and A2 (Auxiliary 1 and Auxiliary 2)
These zones are similar to a Night zone and are typically used to protect restricted areas within a
protected premises.
AR (Arming zone)
This zone allows you to connect a keyswitch to a zone and use it to arm and disarm one or more areas.
Digital Monitoring Products
60
XR100 Series Programming Guide
APPENDIX
19.11
Zone Type Specifications
Zone Name
0
0
0
0
0
T
T
0
0
0
…
…
A
A
0
0
…
…
0
0
0
0
0
0
0
0
0
0
…
…
…
…
…
…
…
…
…
…
0
0
0
0
0
0
0
0
0
0
S
P
M
F
N
1
1
N
1
N
N
N
or
to
or or to or or or
Y
8
4
…
…
…
…
…
…
…
…
…
…
Y
Y
Y
N
N
N
N
N
N
N
Prewarn
Output *
Message
Action
Output *
Message
Action
…
…
…
A
T
L
D
S
A
A
A
A
A
A
A
A
A
A
Priority
…
…
…
S
P
M
F
Cross Zone
0
0
0
A
T
L
D
S
A
A
A
T
T
T
T
T
T
T
Fast Response
NT
DY
EX
FI
PN
EM
SV
A1
A2
FV
AR
S
P
M
F
Presignal
Night
Day
Exit
Fire
Panic
Emergency
Supervisory
Auxiliary 1
Auxiliary 2
Fire Verify
Arming
A
T
L
D
S
T
-
Retard Delay
FV AR
or
1 to 8
S
P
M
F
Entry Delay
A1 A2
A
T
L
D
S
T
-
Armed
Short
Swinger
Zone Type Defaults
BDRM
Armed
Open
Action
EM SV
INT
Output *
FI PN
Assign Retard and Presignal for FI, SV,
A1, and A2 only
PERIM
Disarmed
Short
Message
DY EX
Action
-- NT
Fire Disarmed
Bell Open
Output *
Assign Prewarn and Entry Delay for EX
only
Area
Message
Assign Disarm condition of NT, DY, EX,
A1, and A2 only
Type
Output *
Keypad Bus Zone Information
1-8
Y
8
1
N
+
N
N
N
+
+
+
Y
Y
Y
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
Style
The XR100 Series panel contains multiple default zone types for use in configuring the system. These
zone types provide the most commonly selected functions for their applications. All zone types can be
customized by changing the variable options listed below. The Keypad Bus Zone Information table below
reflects the zone types for Keypad Bus Zones. The XR100 Series LX-Bus Zone Information table on the
next page reflects the zone types for LX-Bus Zones.
TGL
ARM
DIS
STEP
MNT
TGL
* Output Options: 1 to 6, 500 to 599, D1 to D8, G1 to G20. … = Output action defaults to S. + = Set retard to YES before selecting presignal.  = Zone functions not available.
19.11.1 Keypad Bus Zone Type Defaults
These are complete spellings of the abbreviations used for the zone types, such as Night and Exit.
Type - These are the abbreviations used for the zone types, such as NT and EX.
Area - For an Area system this is 1 to 8. For an All/Perimeter or Home/Sleep/Away system, this is the
Interior, Bedroom, or Perimeter. Select the area for NT, DY, EX, A1, A2, and AR types.
Fire Bell Out - Only available for FI, FV, and SV zones. Use any output zone number listed.
Message - A = alarm report, T = trouble report, L = local, no report, — (dash) = no report, D = door
propped (When SV zone is connected to 303 Silence/Reset Switch), S = sensor reset/alarm silence,
C = early morning ambush cancel.
Output - These are the 6 on-board and 500 off-board relay outputs, D1 to D16, and G1 to G20.
Action - This selects the action of the output: S = steady, P = pulse, M = momentary, and F = follow
Swinger - The zone can be automatically shunted after a programmed number of trips.
Prewarn - This selects the keypad address that sounds the entry prewarn for this zone.
Entry Delay - This is the entry delay timer selected as the default for this zone.
Retard Delay - Provides a programmed retard time before an alarm initiates from a shorted zone. When
used on an arming zone, the retard delay occurs when the zone is shorted before the armed state has
changed. If the arming zone has Maintain as the Style, the retard delay also occurs when the zone returns
to a normal state.
Presignal - Provides a keypad tone for zones in retard delay. Retard must be YES before Presignal can be
selected.
Fast Response - Provides a 167ms zone response instead of the normal 500ms response.
Cross Zone - Provides cross zoning with any of the 574 zones.
Priority - Requires this zone to be in a normal condition before the area can be armed.
Style - The abbreviations for arming zone style:
TGL = Toggle, ARM = Arm only, DIS = Disarm only, STEP = Wireless arming, MNT = Maintain
XR100 Series Programming Guide
Digital Monitoring Products
61
TGL
0
= Zone functions not available.
+
+
+
…
…
0
0
0
0
A
A
A
A
…
…
0
0
0
0
Zone Name
NIGHT
DAY
EXIT
FIRE
PANIC
EMERGENCY
SUPERVISORY
AUXILIARY 1
AUXILIARY 2
FIRE VERIFY
ARMING
Serial Number
FV
Zone Type Defaults
A1
NT
DY
EX
FI
PN
EM
SV
A1
A2
FV
AR
1 to 8
Zones 500 to 599
A2
or
SV
PN
EM
INT
BDRM
EX
Assign Retard and Presignal for FI, SV, A1, and A2 only.
FI
NT PERIM
Output *
DY
T
T
–
T
–
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
N
N
N
N
N
N
N
N
N
N
N
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
INT
N
N
N
N
N
N
N
N
N
N
N
Wireless
Assign Prewarn and Entry Delay for EX only.
60
60
60
60
60
60
60
60
60
60
60
Y
60
Y
EXT
3
or
or
INT
Contact
N
Y
EXT Contact N/O?
N
or
Supervision Time
0
15
N
LED Operation
--
or
A
T
L
–D
S
Message
Assign Disarm condition for NT, DY, EX, A1, and A2 only.
1
1-8
Y
Y
Y
N
N
N
N
N
N
N
…
…
…
…
…
…
…
…
…
…
0
0
0
0
0
0
0
0
0
0
…
…
…
…
…
…
…
…
…
…
0
0
0
0
0
0
0
0
0
0
…
…
…
0
0
0
–
T
–
…
…
…
0
0
0
Output *
Type Area Fire
N
N
N
+
N
8
Y
4
8
Y
A
T
L
–
D
S
A
A
A
A
A
A
A
A
A
A
S
P
M
F
A
T
L
–
D
S
A
A
A
A
A
A
A
A
A
A
S
P
M
F
A
T
L
–D
S
S
P
M
F
Action
XR100 Series LX-Bus Zone Information
* Output Options: 1 to 6, 500 to 999, D1 to D16, G1 to G20. … = Output action defaults to S. + = Set retard to YES before selecting presignal.
N
N
N
N
N
N
N
N
N
N
Y
N
N
N
N
N
N
N
N
N
N
Y
N
N
N
N
N
N
N
N
N
Y
or
or
or
to
or
1
N
1
1
N
S
P
M
F
Armed
Short
Message
Disarmed Armed
DMP Wireless Disarmed
Open
Short
Open
Output *
Digital Monitoring Products
62
Action
Style - The abbreviations for arming zone style:
TGL = Toggle, ARM = Arm only, DIS = Disarm only,
STEP = Wireless arming, MNT = Maintain
Message
Priority - Requires this zone to be in a normal
condition before the area can be armed.
Output *
Cross Zone - Provides cross zoning with any of
the 142 zones.
Action
Fast Response - Provides a 167ms zone response
instead of the normal 500ms response.
Message
Presignal - Provides a keypad tone for zones
in retard delay. Retard must be YES before
Presignal can be selected.
Output *
Retard Delay - Provides a programmed retard
time before an alarm initiates from a shorted
zone. When used on an arming zone, the retard
delay occurs when the zone is shorted before the
armed state has changed. If the arming zone
has Maintain as the Style, the retard delay also
occurs when the zone returns to a normal state.
Action
Entry Delay - This is the entry delay timer
selected as the default for this zone.
Swinger
Prewarn - This selects the keypad address that
sounds the entry prewarn for this zone.
Prewarn
Swinger - The zone can be automatically shunted
after a programmed number of trips.
Entry Delay
Action - This selects the action of the output:
S = steady, P = pulse, M = momentary, and
F = follow
Retard Delay
Output - These are the 6 on-board and 100
off-board relay outputs, D1 to D8, and G1 to G20.
Presignal
Message - A = alarm report, T = trouble report,
L = local, no report, - (dash) = no report,
D = door propped (When SV zone is connected to
303 Silence/Reset Switch), S = sensor reset/alarm
silence.
N
Fast Response
DMP Wireless - These options are for use with
the DMP 1100X Wireless Receiver.
N
Cross Zone
Wireless - This indicates wireless equipment is
being used.
N
Priority
Area - For an Area system this is 1 to 8. For an
All/Perimeter or Home/Sleep/Away system, this
is the Interior, Bedroom, or Perimeter. Select the
area for NT, DY, EX, A1, A2, and AR types.
Fire Bell Out - Only available for FI, FV, and S
zones. Use any output zone number listed.
to
Style
Type - These are the abbreviations used for the
zone types, such as NT and EX.
or
These are complete spellings of the abbreviations
used for the zone types, such as Night and Exit.
2
3
or
19.11.2 LX-Bus Zone Type Defaults
TGL
ARM
DIS
STEP
MNT
APPENDIX
XR100 Series Programming Guide
APPENDIX
19.12 Common Keypad Messages
There are several common keypad messages that the keypad displays to inform the technician and
end-user. The common messages are described below. Possible solutions are also provided.
Message
Meaning
Possible Solutions
INVALID AREA
The user has attempted a door access for an
area they are not assigned.
Change the user access areas if access to the
area is needed. If access is not needed, the
user cannot enter the area.
INVALID CODE
The user code you entered is not recognized
by the system.
Check the user code and try again.
INVALID PROFILE
A user attempted a function that is outside of
the assigned profile.
Check the user profile settings.
INVALID TIME
A user code assigned to a specific schedule
has entered outside of the valid schedule.
See Schedules and User Codes.
CLOSING TIME
The scheduled has expired but the area is not
armed.
Users still on the premise should arm the
system or extend the schedule to a later time.
LATE TO CLOSE
The system was not armed at its scheduled
closing time.
Users still on the premise should arm the
system or extend the schedule to a later time.
FAILED TO EXIT
A user assigned the anti-passback option has
attempted to re-enter an area from which
they did not exit properly.
The user must exit the area through the
proper door. If not possible, your system
administrator should select the Forgive option
in the User Codes menu.
AC TROUBLE
The system is not getting proper power.
Check that all AC connections are good.
BATTERY TROUBLE
The battery is either low or missing.
Check that the battery connections are good
and the battery is still good.
PHONE LINE 1
TROUBLE
There is trouble with the phone line
supervision.
Plug in the phone line.
There is a problem with one or more
components in the system.
Make sure the J16 jumper is removed from
the panel. Make sure there is not a short or
open condition on the green data wire to the
keypad. You may also need to check that all
of the keypads and expansion modules on the
bus are good.
The system is performing another task with a
higher priority.
Wait a few moments for the system to
complete the task. Make sure the J16 jumper
is not on the panel. If the message displays
for a long period of time, the processor could
be locked up.
There is not a supervised device on the bus.
Program a device to be supervised.
There is low voltage or an open yellow wire.
Make sure all wires are connected.
Two devices share the same address.
Program one of the devices to a unique
address.
TRANSMIT FAIL
The panel has attempted to communicate
with the central station 10 times and has not
succeeded.
Verify your communication type, account
number, and phone number. Make sure the
telephone line is connected and working
properly.
NON-POLLED ADDRESS
The device is not set to STD or FIRE in Device Program the device as STD or FIRE in Device
Setup during programming.
Setup.
ENTER CODE (entering
Programming)
A lockout code has been programmed for the
panel.
WIRELESS TROUBLE
The panel is unable to communicate with the
wireless receiver.
SYSTEM TROUBLE or
SERVICE REQUIRED
SYSTEM BUSY
4-WIRE BUS TROUBLE
The wireless receiver is missing.
XR100 Series Programming Guide
Enter the lockout code.
Verify the receiver is properly connected to
the panel. Verify the correct House Code is
programmed in System Options.
Digital Monitoring Products
63
Underwriters Laboratories (UL) Listed
UL 294
Access Control System Units
UL 365
Police Connected Burglar
UL 609
Local Burglar
UL 1023 Household Burglar
UL 1076 Proprietary Burglar
UL 1610 Central Station Burglar
UL 1635 Digital Burglar
UL 985
Household Fire Warning
UL 864
Fire Protective Signaling
UL AA High Line Security
Underwriters Laboratories Canada (ULC) Listed
ULC 5545
Household Fire
ULC Subject-C1023 Household Burglar
ULC/ORD-C1076
Proprietary Burglar
ULC S304
Central Station Burglar
ANSI/SIA CP-01-2000 False Alarm Reduction
FCC Part 15
FCC Part 68 Registration ID CCKAL00BXR500
California State Fire Marshall (CSFM)
800-641-4282
INTRUSION • FIRE • ACCESS • NETWORKS
www.dmp.com
2500 North Partnership Boulevard
Made in the USA
Springfield, Missouri 65803-8877
LT-0896 (1/07) © 2007 Digital Monitoring Products, Inc.