- No category
advertisement
Sensing and Control
UDC2300
Universal Digital Indicator
Product Manual
Doc. No.:
Release:
Last Revision Date:
51-52-25-84
A
10/00
Copyright, Notices, and Trademarks
Printed in U.S.A. – © Copyright 2000 by Honeywell
Revision A – October 2000
WARRANTY/REMEDY
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer’s sole remedy and is in lieu of all other warranties, expressed or implied, including those
of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.
While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.
ii
Sensing and Control
Honeywell
11 West Spring Street
Freeport, Illinois 61032
UDC2300 is a trademark of Honeywell
UDC2300 Indicator Product Manual 10/00
About This Document
Abstract
This document provides descriptions and procedures for the installation, configuration, operation, and troubleshooting of your UDC2300 Indicator.
Contacts
World Wide Web
The following lists Honeywell’s World Wide Web sites that will be of interest to our customers.
Honeywell Organization
Corporate
Sensing and Control
International
WWW Address (URL)
http://www.honeywell.com
http://www.honeywell.com/sensing http://www.honeywell.com/Business/global.asp
Telephone
Contact us by telephone at the numbers listed below.
Organization
United States and
Canada
Honeywell
Asia Pacific
Europe
Latin America
Honeywell Asia Pacific
Hong Kong
Honeywell PACE, Brussels, Belgium
Honeywell, Sunrise, Florida U.S.A.
Phone Number
1-800-423-9883 Tech. Support
1-888-423-9883 Q&A Faxback
(TACFACS)
1-800-525-7439 Service
(852) 2829-8298
[32-2] 728-2111
(854) 845-2600
10/00 UDC2300 Indicator Product Manual iii
Symbol Definitions
The following table lists those symbols that may be used in this document to denote certain conditions.
Symbol Definition
This DANGER symbol indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
This WARNING symbol indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
This CAUTION symbol may be present on Control Product instrumentation and literature. If present on a product, the user must consult the appropriate part of the accompanying product literature for more information.
This CAUTION symbol indicates a potentially hazardous situation, which, if not avoided, may result in property damage.
WARNING
PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms,
42.4 Vpeak, or 60 Vdc may be accessible. Failure to comply with these
instructions could result in death or serious injury.
ATTENTION, Electrostatic Discharge (ESD) hazards. Observe precautions for handling electrostatic sensitive devices
Protective Earth (PE) terminal. Provided for connection of the protective earth (green or green/yellow) supply system conductor.
Functional earth terminal. Used for non-safety purposes such as noise immunity improvement. NOTE: This connection shall be bonded to protective earth at the source of supply in accordance with national local electrical code requirements.
Earth Ground. Functional earth connection. NOTE: This connection shall be bonded to Protective earth at the source of supply in accordance with national and local electrical code requirements.
Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
Earth Ground. Functional earth connection. NOTE: This connection shall be bonded to Protective earth at the source of supply in accordance with national and local electrical code requirements.
Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.
iv UDC2300 Indicator Product Manual 10/00
Contents
1 INTRODUCTION ................................................................................................... 1
1.1
Overview ........................................................................................................................................ 1
1.2
CE Conformity (Europe)................................................................................................................ 2
2 INSTALLATION .................................................................................................... 3
2.1
Overview ........................................................................................................................................ 3
2.2
Model Number Interpretation ........................................................................................................ 5
2.3
Preliminary Checks ........................................................................................................................ 6
2.4
Alarm Relay Contact Information.................................................................................................. 8
2.5
Mounting........................................................................................................................................ 9
2.6
Wiring .......................................................................................................................................... 11
2.7
Wiring Diagrams.......................................................................................................................... 12
3 INITIAL START-UP ............................................................................................. 17
3.1
Overview ...................................................................................................................................... 17
3.2
Powering Up the Indicator ........................................................................................................... 17
3.3
Operator Interface and Key Functions ......................................................................................... 18
3.4
Key Error Message....................................................................................................................... 18
4 CONFIGURATION .............................................................................................. 19
4.1
Overview ...................................................................................................................................... 19
4.2
Configuration Prompt Hierarchy ................................................................................................. 20
4.3
Configuration Procedure .............................................................................................................. 21
4.4
Lock Set Up Group ...................................................................................................................... 22
4.5
Input Set Up Group ..................................................................................................................... 23
4.6
Communications Set Up Group ................................................................................................... 27
4.7
Alarms Set Up Group................................................................................................................... 30
4.8
Configuration Record Sheet......................................................................................................... 32
5 MONITORING THE INDICATOR ........................................................................ 33
5.1
Overview ...................................................................................................................................... 33
5.2
Operator Interface ........................................................................................................................ 34
5.3
Entering a Security Code ............................................................................................................. 34
5.4
Lockout Feature ........................................................................................................................... 35
5.5
Monitoring Your Indicator........................................................................................................... 36
5.6
Alarm Setpoints............................................................................................................................ 37
10/00 UDC2300 Indicator Product Manual v
6 INPUT CALIBRATION ........................................................................................ 39
6.1
Overview ...................................................................................................................................... 39
6.2
Minimum and Maximum Range Values ...................................................................................... 40
6.3
Preliminary Information............................................................................................................... 41
6.4
Input Set Up Wiring..................................................................................................................... 43
6.5
Input Calibration Procedure ........................................................................................................ 45
6.6
Restore Factory Calibration ......................................................................................................... 47
7 TROUBLESHOOTING/SERVICE ....................................................................... 49
7.1
Overview ...................................................................................................................................... 49
7.2
Troubleshooting Aids................................................................................................................... 51
7.3
Power-up Tests............................................................................................................................. 53
7.4
Status Tests .................................................................................................................................. 53
7.5
Background Tests......................................................................................................................... 54
7.6
Indicator Failure Symptoms......................................................................................................... 55
7.7
Troubleshooting Procedures ........................................................................................................ 56
8 PARTS LIST........................................................................................................ 59
8.1
Exploded View............................................................................................................................. 59
9 INDEX ................................................................................................................. 61 vi UDC2300 Indicator Product Manual 10/00
Tables
Table 2-1 Condensed Specifications _____________________________________________________ 4
Table 2-2 Preliminary Checks __________________________________________________________ 6
Table 2-3 Alarm Relay Contact Information _______________________________________________ 8
Table 2-4 Mounting Procedure_________________________________________________________ 10
Table 2-5 Permissible Wiring Bundling__________________________________________________ 12
Table 4-1 Configuration Prompt Hierarchy _______________________________________________ 20
Table 4-2 Configuration Procedure _____________________________________________________ 21
Table 4-3 LOCK Group (Numeric Code 200) Function Prompts ______________________________ 22
Table 4-4 INPUT Group (Numeric Code 600) Function Prompts ______________________________ 23
Table 4-5 Communications Group (Numeric Code 1000) Function Prompts _____________________ 27
Table 4-6 ALARMS Group (Numeric Code 1100) Function Prompts __________________________ 30
Table 5-1 Procedure to Enter a Security Code _____________________________________________ 35
Table 5-2 Annunciators ______________________________________________________________ 36
Table 5-3 Error Messages_____________________________________________________________ 36
Table 5-4 Procedure for Displaying Alarm Setpoints _______________________________________ 37
Table 6-1 Voltage and Resistance Equivalents for Input Range Values _________________________ 40
Table 6-2 Equipment Needed __________________________________________________________ 42
Table 6-3 Set Up Wiring Procedure for Thermocouple Inputs Using an Ice Bath _________________ 43
Table 6-4 Set Up Wiring Procedure for Thermocouple Inputs using Thermocouple Source _________ 43
Table 6-5 Set Up Wiring Procedure for RTD Inputs ________________________________________ 44
Table 6-6 Set Up Wiring Procedure for Radiamatic, Milliampere, Millivolts, or Volts Inputs
(Except 0-10 Volts) _________________________________________________________ 44
Table 6-7 Set Up Wiring Procedure for 0 to 10 Volts _______________________________________ 45
Table 6-8 Input Calibration Procedure __________________________________________________ 46
Table 6-9 Restore Factory Calibration ___________________________________________________ 48
Table 7-1 Procedure for Identifying the Software Version ___________________________________ 52
Table 7-2 Procedure for Displaying the Status Test Results __________________________________ 53
Table 7-3 Background Tests___________________________________________________________ 54
Table 7-4 Indicator Failure Symptoms ___________________________________________________ 55
Table 7-5 Troubleshooting Power Failure Symptoms _______________________________________ 57
Table 7-6 Troubleshooting Alarm Relay Output Failure _____________________________________ 57
Table 7-7 Troubleshooting a Keyboard Failure ____________________________________________ 58
Table 8-1 Parts Identification __________________________________________________________ 59
Table 8-2 Parts Not Shown____________________________________________________________ 60
10/00 UDC2300 Indicator Product Manual vii
Figures
Figure 1-1 UDC2300 Indicator Operator Interface __________________________________________ 1
Figure 2-1 Indicator Model Number Interpretation __________________________________________ 5
Figure 2-2 Jumper Placements __________________________________________________________ 7
Figure 2-3 Mounting Dimensions (not to scale)_____________________________________________ 9
Figure 2-4 Mounting Method __________________________________________________________ 10
Figure 2-5 Composite Wiring Diagram __________________________________________________ 12
Figure 2-6 Mains Power Supply________________________________________________________ 13
Figure 2-7 Input Connections __________________________________________________________ 13
Figure 2-8 Alarm Relay Output Connections______________________________________________ 14
Figure 2-9 Open Collector Alarm Relay Output ___________________________________________ 14
Figure 2-10 External Interface Option Connections ________________________________________ 15
Figure 3-1 Operator Interface and Key Functions __________________________________________ 18
Figure 5-1 Operator Interface __________________________________________________________ 34
Figure 6-1 Input Wiring Terminals _____________________________________________________ 41
Figure 6-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath _____________________ 43
Figure 6-3 Wiring Connections for Thermocouple Inputs Using Thermocouple Source ____________ 43
Figure 6-4 Wiring Connections for RTD (Resistance Thermometer Device) _____________________ 44
Figure 6-5 Wiring Connections for Radiamatic, Milliampere, Millivolts, or Volts (Except 0 to 10
Volts) ___________________________________________________________________ 45
Figure 6-6 Wiring Connections for 0 to 10 Volts __________________________________________ 45
Figure 8-1 UDC2300 Exploded View ___________________________________________________ 59
viii UDC2300 Indicator Product Manual 10/00
Introduction
1 Introduction
1.1 Overview
The UDC2300 Indicator model provides only indication and alarms of Analog Inputs. No control functionality is included.
The UDC2300 Indicator monitors temperatures and other variables in applications such as environmental chambers, plastic processing machines, furnaces and ovens, and packaging machinery.
The Input type and range are completely field selectable. The indicator has a dedicated configuration display which provides prompts in various languages providing unmatched operating simplicity. Programmed sequence of displays assure quick and accurate entry of the configurable parameters. Simple keystrokes let you change alarm setpoints to meet your process needs.
The UDC2300 Indicator model is also downward compatible with existing UDC2000
Indicator model applications and installations except for RTD and 0-10 Volt inputs and
Open Collector outputs.
See wiring diagrams in Section 2 - Installation.
ALM
12
2300
F
C
PV
FUNCTION
DISPLAY
MAN-AUTO
RESET
SET UP
AUTO
TUNE
RUN
HOLD
Figure 1-1 UDC2300 Indicator Operator Interface
10/00 UDC2300 Indicator Product Manual 1
Introduction
1.2 CE Conformity (Europe)
This product is in conformity with the protection requirements of the following European
Council Directives: 73/23/EEC, the Low Voltage Directive, and 89/336/EEC, the EMC
Directive. Conformity of this product with any other “CE Mark” Directive(s) shall not be assumed.
Product Classification: Class I: Permanently connected, panel-mounted Industrial
Control Equipment with protective earthing (grounding). (EN61010-1).
Enclosure Rating: Panel-mounted equipment, IP 00. This indicator must be panelmounted. Terminals must be enclosed within the panel. Front panel IP 65 (IEC 529).
Installation Category (Overvoltage Category): Category II: Energy-consuming equipment supplied from the fixed installation, local level appliances, and Industrial
Control Equipment. (EN61010-1)
Pollution Degree: Pollution Degree 2: Normally non-conductive pollution with occasional conductivity caused by condensation. (Ref. IEC 664-1)
EMC Classification: Group 1, Class A, ISM Equipment (EN55011, emissions), Industrial
Equipment (EN50082-2, immunity)
Method of EMC Assessment: Technical File (TF)
Declaration of Conformity: 51309602-000
Deviation from the installation conditions specified in this manual, and the special conditions for CE conformity in Section 2.1, may invalidate this product’s conformity with the Low Voltage and EMC Directives.
2 UDC2300 Indicator Product Manual 10/00
Installation
2 Installation
2.1 Overview
Introduction
Installation of the UDC2300 consists of mounting and wiring the indicator according to the instructions given in this section. Read the pre-installation information, check the model number interpretation (Subsection 2.2), and become familiar with your model selections, then proceed with installation.
What’s in this section?
The following topics are covered in this section.
TOPIC
2.1
Overview
2.2
Model Number Interpretation
2.3
Preliminary Checks
2.4
Alarm Relay Contact Information
2.5
Mounting
2.6
Wiring
2.7
Wiring Diagrams
See Page
3
5
6
8
9
11
12
10/00 UDC2300 Indicator Product Manual 3
Installation
Pre-installation Information
If the indicator has not been removed from its shipping carton, inspect the carton for damage then remove the indicator.
•
Inspect the unit for any obvious shipping damage and report any damage due to transit to the carrier.
•
Make sure a bag containing mounting hardware is included in the carton with the indicator.
•
Check that the model number shown on the inside of the case agrees with what you have ordered.
Condensed Specifications
Honeywell recommends that you review and adhere to the operating limits listed in Table
2-1 when you install your indicator.
Table 2-1 Condensed Specifications
Operating Limits
Ambient Temperature: 32 °F to 131 °F (0 °C to 55 °C)
Relative Humidity: 5 % to 90 % RH up to 104 °F (40 °C)
Vibration:
Frequency: 0 Hz to 200 Hz
Acceleration: 0.6 g
Mechanical Shock:
Acceleration: 5 g
Duration: 30 ms
Power:
90 Vac to 264 Vac, 50/60 Hz
(CSA models rated to 250 Vac maximum)
Power Consumption: 12 VA maximum
Accuracy
CE Conformity Special
Conditions (Europe)
± 0.25 % of span typical
± 1 digit for display
15-bit resolution typical
Shielded twisted-pair cables are required for all analog I/O, process variable, RTD, thermocouple, dc millivolt, low level signal, 4-20 mA, digital I/O, and computer interface circuits.
Refer to 51-52-05-01, How to Apply Digital Instrumentation in
Severe Electrical Noise Environments, for additional information.
4 UDC2300 Indicator Product Manual 10/00
Installation
2.2 Model Number Interpretation
Introduction
Write the model number into the spaces provided in
Figure 2-1 and compare it to the model number interpretation. This information will also be useful when you wire your indicator.
D C 2 3 0
I = Digital Indicator Model
Output #1
0 _ =
None
Alarm #2 and Alarm #1
_ 0 = No additional outputs or alarms
_ E = Relay, E-M and Alarm #1
_ A = Relay, SS 1 amp and Alarm #1
_ S = Relay, SS 10 amp and Alarm #1
_ T = Open Collector Output and Alarm #1
External Interface
0 _ = None
1 _ = RS422/485 ASCII / Modbus
Software Options
_ 0 = Single Display
0
Manuals
0 _ = English
Certificate
_ 0 = None
_ C = Certificate of
Conformance (F3391)
Options
0 _ _ _ _ _ _
1 _ _ _ _ _ _
_ 0 _ _ _ _ _
_ A _ _ _ _ _
_ _ 0 _ _ _ _
_ _ T _ _ _ _
_ _ _ 0 _ _ _
_ _ _ F _ _ _
_ _ _ _ 0 _ _
_ _ _ _ B _ _
_ _ _ _ T _ _
_ _ _ _ _ 0 _
_ _ _ _ _ _ 0
= 90 to 264 Vac Power
= 24 Vac/dc Power
(requires Alarms plus IN 2)
= UL and CE
= UL, CE, CSA and (FM pending)
= None
= Customer ID Tag
= None
= Rear Terminal Cover
= Gray Elastomer Bezel
= Blue Elastomer Bezel
= Tan Elastomer Bezel
= Future
= Future
PV Input
1 _ = T/C, RTD, Radiamatic, mV, 0-5V, 0-20mA, 4-20mA
2_ = T/C, RTD, Radiamatic, mV, Volts, milliamps, 0-10 Volts
Optional Input 2
_ 0 = None
Figure 2-1 Indicator Model Number Interpretation
10/00 UDC2300 Indicator Product Manual 5
Installation
2.3 Preliminary Checks
Introduction
Before you install the indicator, remove the chassis and make any preliminary checks necessary that are listed in Table 2-2. Figure 2-2 shows the locations for jumper placements.
Check
Number
Table 2-2 Preliminary Checks
Preliminary Check Description
1
Input I Jumper Placement Check the internal jumper for INPUT 1 to make sure it is set for the correct input type. The jumper is located at position S101 on the printed wiring board. Figure 2-2 shows the location of the jumper and position selections.
4
Alarm Relay Action.
The indicator has been shipped with ALARM relays configured for N.C. (Normally Closed). If you want to change to N.O. refer to Figure 2-2, Jumper positions
W201 and W202:
W201 is the ALARM RELAY 1 jumper.
W202 is the jumper ALARM RELAY 2.
See Table 2-3 for Alarm Relay contact information.
See Alarm Relay Caution Note, Page 8.
6 UDC2300 Indicator Product Manual 10/00
Installation
Jumper Placements
Alarm Relay #1
W201
NO
NC (default)
NC
NO
NO
NC
Note: Jumpers enlarged for clarity
S201
2 1
W201
NO
NC
W202
NO
NC
S101
4 3 2
1
W101
NO
NC
Alarm Relay #2
W202
NO
NC (default)
NC
NO
NO
NC
S101
Input #1
4 3 2
1
Position 1: thermocouple (default)
Position 2: mV, Volt, RTD
Position 3: not used
Main
Board
Position 4: mA
No jumper: 0 -10 volts
Figure 2-2 Jumper Placements
10/00 UDC2300 Indicator Product Manual 7
Installation
2.4 Alarm Relay Contact Information
Alarm Relays
Alarm relays are designed to operate in a failsafe mode (that is, de-energized during alarm sate). This results in alarm actuation when power is OFF or when initially applied, until the unit completes self diagnostics. If power is lost to the unit, the alarms will function.
Unit
Power
Off
On
Table 2-3 Alarm Relay Contact Information
Alarm Relay
Wiring
N.O.
N.C.
N.O.
N.C.
Variable NOT in Alarm State
Relay
Contact
Indicators
Open
Closed
Closed
Open
Off
Off
Variable in Alarm State
Relay
Contact
Indicators
Open
Closed
Open
Closed
Off
On
8 UDC2300 Indicator Product Manual 10/00
Installation
2.5 Mounting
Physical Considerations
The indicator
can be mounted on either a vertical or tilted panel using the mounting kit supplied. Adequate access space must be available at the back of the panel for installation and servicing activities.
•
Overall dimensions and panel cutout requirements for mounting the indicator are shown in Figure 2-3.
•
The indicator’s mounting enclosure must be grounded according to CSA standard
C22.2 No. 0.4 or Factory Mutual Class No. 3820 paragraph 6.1.5.
•
The front panel is moisture rated NEMA 3/IP65 (IEC) when properly installed with panel gasket.
Overall Dimensions
96
3.780
92
+0.008
-0.0
+0.8
3.5906
+0.03
-0.0
96
3.780
Panel Cutout
+0.008
92 -0.0
3.622
+0.031
-0.0
24
.945
Max Panel
Thickness
10
.394
Max (2)
2.62
.103
with optional rear cover
90.7
3.57
10/00
21.0
.826
105.4
4.19
Dimensions:
Millimeters
Inches
20751
Figure 2-3 Mounting Dimensions (not to scale)
UDC2300 Indicator Product Manual 9
Installation
Mounting Method
Before mounting the indicator, refer to the nameplate on the outside of the case and make a note of the model number. It will help later when selecting the proper wiring configuration.
Panel
20752
Figure 2-4 Mounting Method
Mounting Procedure
Step
1
2
3
4
Table 2-4 Mounting Procedure
Action
Mark and cut out the indicator hole in the panel according to the dimension information in Figure 2-3.
Remove the screw cover and loosen the screw on the front of the indicator. Pull the chassis out of the case.
Orient the case properly and slide it through the panel hole from the front.
Remove the mounting kit from the shipping container and install the kit as follows:
•
Install the screws into the threaded holes of the clips.
•
Insert the prongs of the clips into the two holes in the top and bottom of the case.
•
Tighten both screws to secure the case against the panel.
•
Carefully slide the chassis assembly into the case, press to close, and tighten the screw. Replace the screw cover.
10 UDC2300 Indicator Product Manual 10/00
Installation
2.6 Wiring
Electrical Considerations
The indicator is considered “rack and panel mounted equipment” per EN61010-1, Safety
Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use,
Part 1: General Requirements. Conformity with 72/23/EEC, the Low Voltage Directive requires the user to provide adequate protection against a shock hazard. The user shall install this indicator in an enclosure that limits OPERATOR access to the rear terminals
.
Mains Power Supply
This equipment is suitable for connection to 90 Vac to 264 Vac, 50/60 Hz, power supply mains. It is the user’s responsibility to provide a switch and non-time delay (North
America), quick-acting, high breaking capacity, Type F (Europe), 1/2 A, 250 V fuse(s), or circuit-breaker, as part of the installation. The switch or circuit-breaker shall be located in close proximity to the indicator, within easy reach of the OPERATOR. The switch or circuit-breaker shall be marked as the disconnecting device for the indicator.
Indicator Grounding
PROTECTIVE BONDING (grounding) of this indicator and the enclosure in which it is installed shall be in accordance with National and Local electrical codes. To minimize electrical noise and transients that may adversely affect the system, supplementary bonding of the indicator enclosure to a local ground, using a No. 12 (4 mm
2
) copper conductor, is recommended.
Alarm Circuit Wiring
The insulation of wires connected to the Alarm terminals shall be rated for the highest voltage involved. Extra Low Voltage (ELV) wiring (input, and low voltage Alarm circuits) shall be separated from HAZARDOUS LIVE (>30 Vac, 42.4 Vpeak, or 60 Vdc) wiring per Permissible Wiring Bundling, Table 2-5.
Electrical Noise Precautions
Electrical noise is composed of unabated electrical signals which produce undesirable effects in measurements and control circuits.
Digital equipment is especially sensitive to the effects of electrical noise. Your indicator has built-in circuits to reduce the effect of electrical noise from various sources. If there is a need to further reduce these effects:
•
Separate External Wiring—Separate connecting wires into bundles
(See Permissible Wiring Bundling - Table 2-5) and route the individual bundles through separate conduit metal trays.
Use Suppression Devices—For additional noise protection, you may want to add suppression devices at the external source. Appropriate suppression devices are commercially available.
For additional noise information, refer to Document #51-52-05-01, How to Apply Digital Instrumentation in
Severe Electrical Noise Environments.
10/00 UDC2300 Indicator Product Manual 11
Installation
Permissible Wiring Bundling
Table 2-5 Permissible Wiring Bundling
Bundle No.
1
2
3
Wire Functions
•
Line power wiring
•
Earth ground wiring
•
Line voltage alarm wiring
Analog signal wire, such as:
•
Input signal wire (thermocouple, 4 to 20 mA, etc.)
•
Low voltage alarm relay output wiring
2.7 Wiring Diagrams
Identify Your Wiring Requirements
To determine the appropriate diagrams for wiring your indicator, refer to the model number interpretation in this section. The model number of the indicator can be found on the outside of the case.
Wiring the Indicator
Using the information contained in the model number, select the appropriate wiring diagrams from the composite wiring diagram below. Refer to the individual diagrams listed to wire the indicator according to your requirements.
Input
Terminals
See Figure 2-7
Mains Power
Supply
See Figure 2-6
8
5
4
7
6
L2 / N
L1
9
10
11
12
13
14
15
16
Alarm Output
Connections
See Figures 2-8 and 2-9
Communications
Options Terminals
See Figure 2-10
24855I
Figure 2-5 Composite Wiring Diagram
12 UDC2300 Indicator Product Manual 10/00
Installation
Mains power supply
2
Neutral
Hot
Ground
1
L2 / N
L1
24856
1
PROTECTIVE BONDING (grounding) of this indicator and the enclosure in which it is installed, shall be in accordance with National and Local electrical codes. To minimize electrical noise and transients that may adversely affect the system, supplementary bonding of the indicator enclosure to a local ground, using a No.
12 (4 mm
2
) copper conductor, is recommended.
Before powering the indicator, see “Preliminary
Checks” in this section of the Product manual for switch and jumper settings.
2 Provide a switch and non-time delay (North America), quick-acting, high breaking capacity, type F (Europe),
1/2 A, 250 V fuse(s), or circuit-breaker as part of the installation.
Figure 2-6 Mains Power Supply
Thermocouple
8
+
Use
Thermocouple extension wire only
0 to 10 Volts
7
-
6
R
Platinum
RTD
RTD
1
mV, Volts (except 0-10V),
Milliamperes, or Radiamatic
8
7
+
-
6
R
mV, Volt, or
Milliampere
Source
8
+
7 -
6 R
+
Volt
Source
_
1
2
3
8
7
+
_
6 R
The voltage divider for 0 to 10
Volts is supplied with the indicator when the input is specified. You must install it when you wire the indicator before start-up. 1
24857
1 These inputs are wired differently than the UDC2000
Figure 2-7 Input Connections
10/00 UDC2300 Indicator Product Manual 13
Installation
9
10
11
12
Alarm
Relay #2 Load
Alarm
Relay #1 Load
1
1
2
2
Load
Supply
Power
Load
Supply
Power
1
Alarm relays 1 and 2 are configured N.C. as shipped. N.O. or N.C.
configurations are selectable by jumpers on the I/O and Transformer/Option printed wiring boards.
See "Preliminary Checks" in this section of the Product Manual for details.
2 5 Amp fast blo or 1 Amp fast blo
The SPST relay is rated at 5 A, 120 Vac and 30 Vdc, 2.5 A, 240 Vac, or 1 Amp SS Relay is rated at 1 Amp at 25°C, linearily derated to 0.5 Amp at 55°C.
24867I
Figure 2-8 Alarm Relay Output Connections
Customer Supplied External
Electromechanical Relay
0-24 Vdc
1
–
ALARM 2
9 –
10+
Customer Supplied External
Solid State Relay
ALARM 2
1
–
+
9 –
10+
0-24 Vdc
1
CAUTION
+
24861IND
Open collector outputs are internally powered at 24 Vdc.
Connecting an external supply will damage the indicator.
External relays should be fused between power and relay load.
Figure 2-9 Open Collector Alarm Relay Output
14 UDC2300 Indicator Product Manual 10/00
Communications
COMMUNICATION MASTER
(A) (RTN) (B)
D+
SHLD
D–
2
13
14
D+
D–
120 OHMS
1
TO OTHER
COMMUNICATION
CONTROLLERS
D– D+
1
2
Connect shield wires together with Honeywell
supplied crimp part number 30755381-001
Do not run these lines in the same conduit as AC power.
120 OHMS ON LAST LEG
Figure 2-10 External Interface Option Connections
Installation
10/00 UDC2300 Indicator Product Manual 15
Installation
16 UDC2300 Indicator Product Manual 10/00
Initial Start-up
3.1 Overview
This section gives you the information necessary to start up your indicator prior to configuration. Review the Operator Interface portion to make sure you are familiar with the indicator definitions and key functions.
3.2 Powering Up the Indicator
Apply Power
When power is applied, the indicator
will run three diagnostic tests. After these tests are completed, “TEST DONE” is displayed.
Test Failures
If one or more of these tests fail, the indicator
will go to the Failsafe Manual Mode, and
FAILSF will flash in the lower display and a message indicating which test failed will appear in the lower display. Then, “DONE” will appear in the lower display.
10/00 UDC2300 Indicator Product Manual 17
18
Initial Start-up
3.3 Operator Interface and Key Functions
Upper Display - Four digits
• Normal operation - Process Variable
• Configuration mode - displays parameter
value or selection
ALM - Alarm conditions exist
ALM
12
2300
F
C
PV
F - °Fahrenheit being used
C - °Centigrade being used
Keys
FUNCTION
DISPLAY
MAN-AUTO
RESET
SET UP
AUTO
TUNE
RUN
HOLD
24868
FUNCTION
Selects functions within each configuration group.
DISPLAY
Returns Controller to PV display from Set Up mode.
MAN-AUTO
RESET
Manual or Auto mode not used on Indicator
In Set Up mode, used to restore original value or selection.
SET UP
Scrolls through the configuration Setup groups.
AUTO
TUNE
RUN
HOLD
Not Used
Increases the configuration values or changes functions in Configuration mode groups.
Decreases the configuration values or changes functions in Configuration mode groups.
Not used
Figure 3-1 Operator Interface and Key Functions
3.4 Key Error Message
When a key is pressed and the prompt KEYERR appears in the lower display, it will be for one of the following reasons:
• parameter is not available,
• not in Set Up mode, press
[SET UP]
key first,
• key malfunction.
UDC2300 Indicator Product Manual 10/00
Configuration
4 Configuration
4.1 Overview
Introduction
Configuration is a dedicated operation where you use straightforward keystroke sequences to select and establish (configure) pertinent data best suited for your application.
To assist you in the configuration process, there are prompts that appear in the upper and lower displays. These prompts let you know what group of configuration data (Set Up prompts) you are working with and also, the specific parameters (Function prompts) associated with each group.
Figure 3-1 shows you an overview of the prompt hierarchy as they appear in the Indicator.
As you will see, the configuration data is divided into 4 main Set Up groups plus prompts for calibration and prompts that show the status of the continuous background tests that are being performed.
What’s in this section?
The following topics are covered in this section.
TOPIC
4.1
Overview
4.2
Configuration Prompt Hierarchy
4.3
Configuration Procedure
4.4
Lock Set Up Group
4.5
Input 1 Set Up Group
4.6
Communications Set Up Group
4.7
Alarms Set Up Group
4.8
Configuration Record Sheet
See Page
19
20
21
22
23
27
30
32
10/00 UDC2300 Indicator Product Manual 19
Configuration
4.2 Configuration Prompt Hierarchy
Set Up Group
LOCK
INPUT1
Table 4-1 Configuration Prompt Hierarchy
Function Prompts
SECUR LOCK
DECMAL UNITS IN1TYP XMITR1 IN1 HI IN1 LO RATIO1
FILTR1 BRNOUT EMISS FREQ LNGUAG
BIAS 1
COM
ComSTA ComADR SDENAB SHDTIM PARITY BAUD TX DLY WS FLT
UNITS LOOPBK
ALARMS A1S1VA A1S2VA A2S1VA A2S2VA A1S1TY A1S2TY A2S1TY A2S2TY
A1S1HL A1S2HL A2S1HL A2S2HL ALHYST ALARM1 BLOCK
STATUS
VERSON FAILSF TESTS
20 UDC2300 Indicator Product Manual 10/00
Configuration
4.3 Configuration Procedure
Introduction
Each of the Set Up groups and their functions are pre-configured at the factory.
The factory settings are shown in Table 4-3 through Table 4-6 that follow this procedure.
If you want to change any of these selections or values, follow the procedure in Table 4-2.
This procedure tells you the keys to press to get to any Set Up group and any associated
Function parameter prompt.
Procedure
The prompting scrolls at a rate of 2/3 seconds when the [SET UP] or [FUNCTION] key is held in.
Also, [
▲
] [
▼
] keys will move group prompts forward or backward at a rate twice as fast.
Step
1
2
3
4
5
6
Table 4-2 Configuration Procedure
Operation Press Result
Enter Set Up
Mode
Select any Set Up
Group
Select a Function
Parameter
SET UP
Upper Display = SET
Lower Display = LOCK (This is the first Set Up Group title)
SET UP
Sequentially displays the other Set Up group titles shown in the prompt hierarchy in Table 4-1.
You can also use the [
▲
] [
▼
] keys to scan the Set Up groups in both directions. Stop at the Set Up group title that describes the group of parameters you want to configure.
Then proceed to the next step.
FUNCTION
Upper Display = the current value or selection for the first function prompt of the selected Set Up group.
Lower Display = the first Function prompt within that Set Up group.
Change the
Value or
Selection
[
▲
] [
▼
]
Sequentially displays the other function prompts of the Set
Up group you have selected. Stop at the function prompt that you want to change, then proceed to the next step.
Increments or decrements the value or selection that appears for the selected function prompt. If you change the value or selection of a parameter while in Set Up mode then decide not to enter it, press [MAN-AUTO/RESET] once—the original value or selection is recalled.
Enter the Value or Selection
FUNCTION
Enters value or selection made into memory after another key is pressed.
Exit Configuration
DISPLAY
Exits configuration mode and returns indicator to the same state it was in immediately preceding entry into the Set Up mode. It stores any changes you have made.
If you do not press any keys for 30 seconds, the indicator times out and reverts to the mode and display used prior to entry into Set Up mode.
10/00 UDC2300 Indicator Product Manual 21
Configuration
4.4 Lock Set Up Group
Introduction
The Lock Set Up group contains the Function parameters that will allow your indicator to protect Configuration and Calibration data.
Because this group contains functions that have to do with Security and Lockout, it is best to configure this group last, after all the other configuration data has been loaded.
Function Prompts
Table 4-3 LOCK Group (Numeric Code 200) Function Prompts
Prompt
English
Numeric
Code
Description Selection or Range of Setting Factory
Setting
SECUR 210
DIS
LOCK 211
Security Code
Configuration
Lockout
0 to 4095
When “Lock” is none, this number is displayed and can be changed using the raise/lower keys
Numeric
Code
0
1
2
4
English
NONE – all parameters are read/write
CAL - all parameters are read/write except Calibration
CONF – Lockout is available for
Read/Write, other configuration parameters are Read Only
ALL – Only the Lockout group is available for read/write. No other parameters are viewable.
CAL
22 UDC2300 Indicator Product Manual 10/00
Configuration
4.5 Input Set Up Group
Introduction
This data deals with various parameters required to configure the Input.
Function Prompts
Table 4-4 INPUT Group (Numeric Code 600) Function Prompts
Prompt
English
Numeric
Code
Description Selection or Range of Setting Factory
Setting
DECMAL
UNITS
IN1TYP
601
602
603
Decimal Point
Selection
Temperature
Units
Input 1
Actuation
Type
Numeric
0
1
2
1
2
0
Numeric
7
8
5
6
9
10
1
2
3
4
11
12
13
14
15
16
B
E H
E L
J H
J L
K H
K L
NNMH
NNML
N90H
N90L
NIC
R
S
T H
T L
English
This selection determines where the decimal point appears in the display.
8888 (none)
888.8
88.88
This selection will be indicated on the annunciator. (“What display of temperature do you want?”)
F
C
NONE
English Numeric English
21
22
23
24
25
26
17
18
19
20
27
28
29
30
31
33
W H
W L
100H
100L
200
500
RADH
RADI
0-20
4-20
10m
50m
0-5
1-5
0-10
100m
8888
F
K H
10/00 UDC2300 Indicator Product Manual 23
Configuration
Prompt
English
Numeric
Code
Description
XMITR1
IN1 HI
IN1 LO
RATIO1
604
605
606
607
Selection or Range of Setting
Transmitter
Characterization
Available on
Linear actuations only.
Input High
Range Value
Input Low
Range Value
Numeric English Numeric English
10
11
12
7
8
9
2
3
4
0
1
5
6
B
E H
E L
J H
J L
K H
K L
NNMH
NNML
N90H
N90L
NIC
R
13
14
15
16
17
18
19
20
21
22
23
24
25
This selection lets you the Input high range value in engineering units.
Linear or Square Root Inputs only.
S
T H
T L
W H
W L
100H
100L
200
500
RADH
RADI
LIN
SrT
Scale the input signal to the display value you want for 100 %.
EXAMPLE:
Actuation (Input) = 4 mA to 20 mA
Process Variable = Flow
Range of Flow = 0 to 250 Gal/Min
High Range display value = 250
Then 20 mA = 250 Gal/Min
Range of Setting:
−
999 to 9999. floating in engineering units
This selection lets you the Input low range value in engineering units.
Linear or Square Root Inputs only.
Scale the input signal to the display value you want for 0 %.
EXAMPLE:
Actuation (Input) = 4 mA to 20 mA
Process Variable = Flow
Range of Flow = 0 to 250 Gal/Min
Low Range display value = 0
Then 4 mA = 0 Gal/Min
Range of Setting:
–999 to 9999 floating in Engineering Units
Ratio on Input Select the Ratio value you want on the Input.
Range of Setting: –20.0 to 20.0
Factory
Setting
LIN
2400
0
0.0
24 UDC2300 Indicator Product Manual 10/00
Configuration
Prompt
English
Numeric
Code
Description
BIAS 1
FILTR1
BRNOUT
608
609
610
Selection or Range of Setting
Bias on Input
Numeric English
Bias is used to compensate the input for drift of an input value due to deterioration of a sensor, or some other cause. Select the bias value you want on the Input.
Range of Setting:
–999 to 9999 (Engineering Units)
Filter for Input A software digital filter is provided for the input to smooth the input signal. You can configure the first order lag time constant from 1 to 120 seconds
Range of Setting:
0 to 120 seconds
0 = No Filter
Burnout
Protection
(Sensor
Break)
0
1
2
3
BURNOUT PROTECTION (SENSOR
BREAK) provides most input types with upscale or downscale protection if the input fails. 1-5 V, 0-10 V, or 4-20 mA inputs require no burnout or
NONE selection.
NONE - Pre-configured Failsafe output applied if failed input is detected (does not apply for an input out of range).
Error message IN1FL is flashed on the lower display intermittently every 10 seconds.
UP - UPSCALE BURNOUT will make the PV signal increase to full scale,
+10 %, when a sensor fails, and flash
IN1FL on the lower display intermittently every 10 seconds.
DOWN - DOWNSCALE BURNOUT will make the PV signal decrease to the lower range value, –10 %, when a sensor fails, and flash IN1FL on the lower display intermittently every 10 seconds.
NOFS - NO FAILSAFE —This selection does not provide input failure detection and should only be used when an absolute accuracy is the most important criteria. (For this selection, no burnout signal went to the sensor.)
Factory
Setting
0.0
1.0
8888
10/00 UDC2300 Indicator Product Manual 25
Configuration
Prompt
English
Numeric
Code
Description
EMISS
FREQ
Selection or Range of Setting
611
Emissivity
612
Power Line
Frequency
Numeric English
Emissivity is a correction factor applied to the
Radiamatic input signal that is the ratio of the actual energy emitted from the target to the energy which would be emitted if the target were a perfect radiator.
Range of Setting:
0.01 to 1.00 (RADH and RADI only)
0
1
Select whether your indicator is operating at 60 Hz or 50 Hz.
60
50
Factory
Setting
1.0
1.0
LNGUAG 614
Language
Selection
2
3
0
1
4
5
For units powered by +24 Vdc, this configuration should be set to the
AC Line frequency used to produce the +24 Vdc Supply. Failure to set this parameter properly can cause normal mode noise problems in the input readings.
Select what the language will be for the displays.
ENGL
FREN
GERM
SPAN
ITAL
NUMB (Numeric)
ENGL
26 UDC2300 Indicator Product Manual 10/00
Configuration
4.6 Communications Set Up Group
Introduction
The Communications group lets you configure the indicator to be connected to a host computer via RS422/485 or Modbus® protocol.
Function Prompts
Table 4-5 Communications Group (Numeric Code 1000) Function Prompts
Prompt
English
Numeric
Code
Description Selection or Range of Setting Factory
Setting
COMSTA
ComADD
SDENAB
SHDTIM
PARITY
BAUD
1001
1002
1003
1004
1005
1006
Communications State
Station
Address
Shed Enable
Shed Time
Parity
Baud Rate
Numeric English
0
1
2
DIS
R422
Disable
RS-422/485
MODB
Modbus
This is a number that is assigned to a indicator that is to be used with the communications option. This number will be its address.
Range of Setting: 1 to 99
This selection enables/disables the
Communications Shed feature.
0
1
DIS
Disable
ENAB
Enable
This is the number that represents how many sample periods there will be before the indicator sheds from communications. Each period equals 1/3 seconds; 0 equals No shed.
Range of Setting: 0 to 255 Sample Periods
0
1
2
3
0
1
PARITY pertains to the use of a self-checking code employing binary digits in which the total number of ONE’s (or ZERO’s) in each permissible code expression is either
ODD or
EVEN
BAUD RATE is the transmission speed in bits per second
2400 Baud
4800 Baud
9600 Baud
19200 Baud
DIS
0
ENAB
0
ODD
2400
10/00 UDC2300 Indicator Product Manual 27
Configuration
Prompt
English
Numeric
Code
Description
TX_DLY
WS_FLT
UNITS
1007
1008
1010
Selection or Range of Setting
Response
Delay
Word/Byte
Order for floating point communicatio ns data
Communications Override
Units
Numeric English
Configurable response-delay timer allows you to force the UDC to delay its response for a time period of from 1 to 500 milliseconds compatible with the host system hardware/software.
Range of Setting: 1 to 500 milliseconds
1
2
Byte
0
3
Contents seeeeeee emmmmmmm mmmmmmmm mmmmmmmm
Choice
FP_B
FPBB
FP_L
FPLB
Byte Order
0123
1032
3210
2301
0
1
2
3
0
1
FP_B
Floating point big endian
FPBB
Floating point big endian with byte-swapped
FP_L
FPLB
Floating point little endian
Floating point little endian with byteswapped
This selection determines how the indicator values are expressed during communications.
PCT
Percent
Eng
Engineering Units
Factory
Setting
1
FP_B
ODD
28 UDC2300 Indicator Product Manual 10/00
Configuration
Prompt
English
Numeric
Code
Description
LOOPBK 1013
Selection or Range of Setting
Local
Loopback Test
Numeric English
Allows loopback test. The UDC goes into Loopback mode in which it sends and receives its own message. The UDC displays PASS or FAIL status in the upper display and LOOPBACK in the lower display while the test is running.
The UDC will go into manual mode. The test will run until the operator disables it here, or until power is turned off and on.
Factory
Setting
DIS
0
1
The UDC does not have to be connected to the RS-485 link to perform this test. If it is connected, only one UDC2300 should run the loopback test at a time. The computer should not be transmitting on the link while the loopback test is active.
DIS
Disable
EnAB
Enable
10/00 UDC2300 Indicator Product Manual 29
Configuration
4.7 Alarms Set Up Group
Introduction
An alarm is an indication that an event that you have configured (for example—Process
Variable) has exceeded one or more alarm limits. There are two alarms available. Each alarm has two setpoints. You can configure each of these two setpoints to alarm on various indicator parameters.
There are two alarm output selections, High and Low. You can configure each setpoint to alarm either High or Low. These are called single alarms.
You can also configure the two setpoints to alarm on the same event and to alarm both high and low. A single adjustable Hysteresis of 0 to 100% is configurable for the alarm setpoint.
See Table 2-3 in the Installation section for Alarm relay contact information.
The prompts for the Alarm Outputs appear whether or not the alarm relays are physically present. This allows the Alarm status to be shown on the display and/or sent via communications to a host computer.
Function Prompts
Table 4-6 ALARMS Group (Numeric Code 1100) Function Prompts
Prompt
English
Numeric
Code
Description Selection or Range of Setting Factory
Setting
AxSxVA
A1S1
A1S2
A2S1
A2S2
AxSxTY
A1S1
A1S2
A2S1
A2S2
AxSxHL
A1S1
A1S2
A2S1
A2S2
1101
1102
1103
1104
1105
1106
1107
1108
1109
1110
1111
1112
Alarmx
Setpointx
Value
X = 1 or 2
Alarmx
Setpointx
Type
X = 1 or 2
Alarmx
Setpoint x
State
X = 1 or 2
Numeric English
This is the value at which you want the alarm type chosen in Prompt "AxSxTY" to actuate.
The value depends on what the alarm setpoint has been configured to represent.
Range of Setting:
within the range of the selected parameter
0
3
6
12
Select what you want Setpoint x of
Alarm x to represent; it can represent the Process Variable or
Deviation.
NONE No Alarm
PROC Process Variable
SHED Shed Communications
PrRT
PV Rate of Change
0
1
Select whether you want the alarm type chosen in prompt "AxSxTY" to alarm High or Low.
LOW
HIGH
Low Alarm
High Alarm
90
NONE
HIGH
30 UDC2300 Indicator Product Manual 10/00
Configuration
Prompt
English
Numeric
Code
Description
ALHYST
ALARM1
1113
1114
Selection or Range of Setting
Alarm
Hysteresis
Latching
Alarm Output
Numeric English
A single adjustable hysteresis is provided on alarms such that when the alarm is OFF it activates at exactly the alarm setpoint; when the alarm is ON, it will not deactivate until the variable is 0.0 % to 100 % away from the alarm setpoint.
Configure the hysteresis of the alarms based on INPUT signals as a % of input range span.
Range of Setting:
0.0 % to 100.0 % of span
When configured for latching, the alarm will stay on, after the alarm condition ends, until the
[RUN/HOLD] key is pressed.
0
1
BLOCK 1115
Alarm
Blocking
NO L
Non Latching
LACH Latching
Alarm Blocking prevents nuisance alarms when the indicator is first powered up. The alarm is suppressed until the parameter gets to the non-alarm limit or band.
Alarm blocking affects both alarm setpoints.
2
3
0
1
DIS
BK1
BK2
BK12
Disable Blocking
Block Alarm 1 only
Block Alarm 2 only
Blocks both Alarms
Factory
Setting
0.0
HIGH
DIS
10/00 UDC2300 Indicator Product Manual 31
Configuration
4.8 Configuration Record Sheet
Enter the value or selection for each prompt on this sheet so you will have a record of how your indicator was configured.
Group
Prompt Function Prompt
Value or
Selection
Factory
Setting
Group
Prompt
Function
Prompt
Value or
Selection
Factory
Setting
LOCK
INPUT1
SECUR
LOCK
DECIMAL
UNITS
IN1TYP
XMITR1
IN1 HI
IN1 LO
RATIO1
BIAS 1
RILTR1
BRNOUT
EMIS
FREQ
DISPLY
LNGUAG
_______
_______
DIS
CAL
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
8888
DegF
KH
LIN
2400
0
1.00
0.0
1.0
UP
1.0
60
SP
ENGL
ALARMS
A1S1VA
A1S2VA
A2S1VA
A2S2VA
A1S1TY
A1S1TY
A2S1TY
A2S2TY
A1S1HL
A1S2HL
A2S1HL
A2S2HL
ALHYST
ALARM1
BLOCK
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
90
90
90
90
NONE
NONE
NONE
NONE
HIGH
HIGH
HIGH
HIGH
0.0
NOL
DIS
COM
ComSTA
ComADR
SDENAB
SHDTIM
PARITY
BAUD
TX_DLY
WS_FLT
UNITS
LOOPBACK
_______
_______
_______
_______
_______
_______
_______
_______
_______
_______
Disable
0
Enable
0
Odd
9600
1
FP_B
PCT
Disable
32 UDC2300 Indicator Product Manual 10/00
Monitoring
5 Monitoring the Indicator
5.1 Overview
Introduction
This section gives you all the information necessary to help you monitor your Indicator including an Operator Interface overview, how to lockout changes to the Indicator, entering a security code, and monitoring the displays.
What’s in this section?
The following topics are covered in this section.
TOPIC
5.2
Operator Interface
5.3
Entering A Security Code
5.4
Lockout Feature
5.5
Monitoring The Indicator
5.6
Alarm Setpoints
See Page
34
34
35
36
37
10/00 UDC2300 Indicator Product Manual 33
Monitoring
5.2 Operator Interface
Introduction
Figure 5-1 is a view of the Operator Interface. A description of the displays and indicators is included.
Upper Display - Four digits
• Normal operation - Process Variable
• Configuration mode - displays parameter
value or selection
ALM - Alarm conditions exist
ALM
1 2
2300
F
C
PV
F - °Fahrenheit being used
C - °Centigrade being used
FUNCTION
DISPLAY
MAN-AUTO
RESET
SET UP
AUTO
TUNE
RUN
HOLD
Figure 5-1 Operator Interface
5.3 Entering a Security Code
Introduction
The level of keyboard lockout may be changed in the Set Up mode. However, knowledge of a security code number (0 to 4095) may be required to change from one level of lockout to another. When an Indicator leaves the factory, it has a security code of 0 which permits changing from one lockout level to another without entering any other code number.
Procedure
If you require the use of a security code, select a number from 0001 to 4095 and enter it when the lockout level is configured as NONE. Thereafter, that selected number must be used to change the lockout level from something other than NONE.
Write the number on the Configuration Record Sheet in the configuration section so you will have a permanent record.
34 UDC2300 Indicator Product Manual 10/00
Monitoring
Step
1
2
3
Operation
Table 5-1 Procedure to Enter a Security Code
Press Result
Enter Set Up
Mode
SET UP
Upper Display = SET UP
Lower Display = LOCK
Select SECUR
Security Code
Entry
FUNCTION
[
▲
] [
▼
]
Upper Display = 0
Lower Display = SECUR
To enter a four digit number in the upper display
(0001 to 4095)
This will be your security code.
5.4 Lockout Feature
Introduction
The lockout feature in the UDC2300 is used to inhibit changes (via keyboard) of certain functions or parameters by unauthorized personnel.
Lockout levels
There are different levels of Lockout depending on the level of security required. These levels are:
•
NONE
No Lockout. All groups Read/Write.
•
CAL
Calibration prompts are deleted from the Setup List.
•
CONF
Configuration Parameters are read only; no writes permitted
•
VIEW Timer, Tuning, and SP Ramp are Read/Write. No other parameters are available.
•
ALL
Only the Lockout group is available for read /write. No other parameters are viewable.
See Subsection 4.4 - LOCK Parameters Set Up Group prompts to select one of the above.
Security Code (see Section 5.3)
Key error
When a key is pressed and the prompt “Key Error” appears in the lower display, it will be for one of the following reasons:
• Parameter not available or locked out
• Not in setup mode, press
[SET UP]
key first
10/00 UDC2300 Indicator Product Manual 35
Monitoring
5.5 Monitoring Your Indicator
Annunciators
The following annunciator functions have been provided to help monitor the Indicator:
Annunciator
ALM 1 2
F or C
Table 5-2 Annunciators
Indication
A visual indication of each alarm
Blinking 1 indicates alarm latched and needs to be acknowledged before extinguishing when the alarm condition ends
A visual indication of the temperature units
F—Degrees Fahrenheit
C—Degrees Celsius
The upper display is used to show other annunciator functions.
LOOPBK—Loopback Test running
Diagnostic Error Messages
The
UDC
2300 performs background tests to verify data and memory integrity. If there is a malfunction, an error message will be displayed. In the case of more than one simultaneous malfunction, the messages will be displayed sequentially on the lower display. If any of these error messages in Table 5-3 occur, refer to
Section 7 - Troubleshooting for information to correct the failure.
Table 5-3 Error Messages
Prompt
EEFAIL
Description
Unable to write to nonvolatile memory.
IN1FL
Two consecutive failures of input 1 integration.
IN1RNG
PV LIM
FAILSF
LOCK
Input 1 Out-of-Range
Out-of-range criteria:
Linear range: ± 10 % out-of-range
Characterized range: ± 1 % out-of-range
PV Out-of-Range
PV = (PV source x PV source ratio) + PV source bias
Failsafe — conditions for failsafe are:
… EEROM Test Failed
… Scratch Pad RAM Test Failed
… Configuration Test Failed
… Field or Factory Cal Test Failed
Check the “Status” group.
The lockout feature has been enabled to prevent unauthorized changes of certain functions or parameters.
36 UDC2300 Indicator Product Manual 10/00
Setpoint Rate/Ramp/Program Operation
Introduction
An alarm consists of a relay contact and an operator interface indication. The alarm relay is de-energized if setpoint 1 or setpoint 2 is exceeded.
The alarm relay is energized when the monitored value goes into the allowed region by more than the hysteresis.
The relay contacts can be wired for normally open (NO) energized or normally closed
(NC) de-energized using internal jumper placement. See Table 2-3 in the Section 2 –
Installation for alarm relay contact information.
There are four alarm setpoints, two for each alarm. The type and state (High or Low) is selected during configuration. See Subsection 4.6 – Configuration for details.
Alarm Setpoints Display
Table 5-4 Procedure for Displaying Alarm Setpoints
Step Operation Press Result
1
Select Alarm
Set-up Group
2
Access the Alarm
Setpoint Values
SET UP
Until you see:
Upper Display = SET
Lower Display = ALARMS
FUNCTION
To successively display the alarm setpoints and their values.
Their order of appearance is shown below.
Upper Display = (the alarm setpoint value)
Range values are within the range of the selected parameters except:
PV RATE OF CHANGE (PVRT) = The amount of PV change in one minute in engineering units.
[
▲
] [
▼
]
Lower Display = A1S1VA = Alarm 1, Setpoint 1
A1S2VA = Alarm 1, Setpoint 2
A2S1VA = Alarm 2, Setpoint 1
A2S2VA = Alarm 2, Setpoint 2
To change any alarm setpoint value in the upper display.
3
4
Change a value
Return to Normal
Display
DISPLAY
10/00 UDC2300 Indicator Product Manual 37
Setpoint Rate/Ramp/Program Operation
38 UDC2300 Indicator Product Manual 10/00
Input Calibration
6.1 Overview
Introduction
This section describes the field calibration procedures for the Input.
•
Every
UDC
2300 indicator contains all input actuation ranges which are fully factorycalibrated and ready for configuration to range by the user.
•
However, these procedures can be implemented if the factory calibration of the desired range is not within specification.
FIELD CALIBRATION WILL BE LOST
The field calibration will be lost if a change in input type configuration is implemented at a later time. The original factory calibration data remains available for later use after a field calibration is done. See subsection 6.6 if you want to restore factory calibration.
What’s in this section?
The following topics are covered in this section.
TOPIC
6.1
Overview
6.2
Minimum and Maximum Range Values
6.3
Preliminary Information
6.4
Input Set Up Wiring
6.5
Input Calibration Procedure
6.6
Restore Factory Calibration
See Page
39
40
41
43
45
47
!
WARNING—SHOCK HAZARD
INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND
SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN
ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.
Failure to comply with these instructions could result in death or serious injury.
10/00 UDC2300 Indicator Product Manual 39
Input Calibration
Calibration Steps
Use the following steps when calibrating an input.
Step Action
1
Find the minimum and maximum range values for your PV input range from Table 6-1.
2
3
4
Disconnect the field wiring and find out what equipment you will need to calibrate.
Wire the calibrating device to your indicator according to the set up wiring instructions for your particular input (Subsection 6.4).
Follow the calibration procedure given for the Input (Subsection 6.5).
6.2 Minimum and Maximum Range Values
Select the Range Values
You should calibrate the indicator for the minimum (0 %) and maximum (100 %) range values of your particular indicator. Select the Voltage or Resistance equivalent for 0 % and 100 % range values from Table 6-1. Use these values when calibrating your indicator.
Table 6-1 Voltage and Resistance Equivalents for Input Range Values
Sensor Type
°F
PV Input Range
°C 0 %
Range Values
100 %
Thermocouples
B
E
E (low)
J
J (low)
K
K (low)
NiNiMoly (NNM68)
NiNiMoly (low)
NiMo-NiCo (NM90)
NiMo-NiCo (low)
Nicrosil Nisil (Nic)
R
S
T
T (low)
0 to 3300
-454 to 1832
-200 to 1100
0 to 1600
20 to 770
0 to 2400
–20 to 1000
32 to 2500
32 to 1260
32 to 2500
32 to 1260
0 to 2372
0 to 3100
0 to 3100
-300 to 700
-200 to 500
–18 to 1816
–270 to1000
–129 to593
–18 to871
–7 to410
–18 to1816
–29 to538
0 to1371
0 to682
0 to1371
0 to682
–18 to1300
–18 to1704
–18 to1704
–184 to371
–129 to260
–0.100 mV
–9.835 mV
–6.472 mV
–0.886 mV
–0.334 mV
–0.692 mV
–1.114 mV
0.000 mV
0.000 mV
0.000 mV
0.000 mV
–0.461 mV
–0.090 mV
–0.092 mV
–5.341 mV
–4.149 mV
13.769 mV
76.373 mV
44.455 mV
50.060 mV
22.400 mV
52.952 mV
22.255 mV
71.330 mV
31.820 mV
71.773 mV
31.825 mV
47.513 mV
20.281 mV
17.998 mV
19.097 mV
12.574 mV
40 UDC2300 Indicator Product Manual 10/00
Input Calibration
Sensor Type
W5W26
W5W26 (low)
Honeywell
Radiamatic
Type RH
Type RI
RTD
(IEC Alpha=0.00385)
100 ohms
100 ohms (low)
200 ohms
500 ohms
Linear
Milliamps
(impedance – 249
Ω
)
Millivolts
Volts
°F
PV Input Range
0 to 4200
0 to 2240
0 to 3400
0 to 3200
-300 to 1200
-300 to 300
-300 to 900
-300 to 900
4 to 20 mA
0 to 20 mA
0 to 10 mV
0 to 50 mV
0 to 100 mV
1 to 5 Volts
0 to 2 Volts
0 to 5 Volts
0 to 10 Volts
°C
–18 to2315
–18 to1227
–18 to1871
–18 to1760
–184 to649
–184 to149
–184 to482
–184 to482
0 %
Range Values
100 %
–0.234 mV
–0.234 mV
37.075 mV
22.283 mV
0.00 mV
0.00 mV
25.18 ohms
25.18 ohms
50.36 ohms
125.90 ohms
4.00 mA
0.00 mA
0.00 mV
0.00 mV
0.00 mV
1.00 Volts
0.00 Volts
0.00 Volts
0.00 Volts
57.12 mV
60.08 mV
274.96 ohms
156.90 ohms
549.92 ohms
1374.80 ohms
20.00 mA
20.00 mA
10.00 mV
50.00 mV
100.00 mV
5.00 Volts
2.00 Volts
5.00 Volts
10.00 Volts
6.3 Preliminary Information
Disconnect the Field Wiring
Tag and disconnect any field wiring connected to the input terminals on the rear of the indicator.
Input
Connections
+
_
R
8
7
6
24869I
Figure 6-1 Input Wiring Terminals
Check the Jumper for Input
Before you calibrate the Input, check the internal jumper for the Input to make sure it is set for the correct input type. The jumper is located at position S101 on the printed wiring board. Figure 2-2 shows the location of the jumper and position selections.
10/00 UDC2300 Indicator Product Manual 41
Input Calibration
Equipment Needed
Table 6-2 lists the equipment you will need to calibrate the specific types of inputs that are listed in the table. You will need a screwdriver to connect these devices to your indicator.
Type of Input
Table 6-2 Equipment Needed
Equipment Needed
Thermocouple
Inputs (Ice Bath)
•
A calibrating device with ± 0.02 % accuracy for use as a signal source such as a millivolt source.
•
Thermocouple extension wire that corresponds with the type of thermocouple that will be used with the indicator input.
•
Two insulated copper leads for connecting the thermocouple extension wire from the ice baths to the mV source.
•
Two containers of crushed ice.
Thermocouple
Inputs (T/C Source)
RTD (Resistance
Thermometer
Device)
Milliampere,
Millivolt, Volts, and
Radiamatic
•
A calibrating device with ± 0.02 % accuracy for use as a signal source such as a millivolt source.
•
Thermocouple extension wire that corresponds with the type of thermocouple that will be used with indicator input.
•
A decade box, with ± 0.02 % accuracy, capable of providing stepped resistance values over a minimum range of 0 to 1400 ohms with a resolution of 0.1 ohm.
•
Three insulated copper leads of equal length for connecting the decade box to the indicator.
•
A calibrating device with ± 0.02 % accuracy for use as a signal source.
•
Two insulated copper leads for connecting the calibrator to the indicator.
•
Place current source at zero before switching ON.
•
Do not switch current sources OFF/ON while connected to the
UDC2300 input.
For Radiamatic inputs only, set Emissivity value to 1.0. See Section 4.5 –
Configuration Set Up prompt INPUT1, function prompt EMISS.
42 UDC2300 Indicator Product Manual 10/00
Input Calibration
6.4 Input Set Up Wiring
Thermocouple Inputs Using an Ice Bath
Refer to Figure 6-2 and wire the indicator according to the procedure given in Table 8-3.
Make sure the jumper at S101 is in the #1 position (Figure 2-2).
Step
Table 6-3 Set Up Wiring Procedure for Thermocouple Inputs
Using an Ice Bath
Action
1
Connect the copper leads to the calibrator.
2
3
Connect a length of thermocouple extension wire to the end of each copper lead and insert the junction points into the ice bath.
Connect the thermocouple extension wires to the terminals for Input #1.
See Figure 6-2.
Millivolt
Source
+
_
Copper Leads
Ice Bath
+
_
8
7
24872
Thermocouple
Extension Wire
Figure 6-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath
Thermocouple Inputs Using a Thermocouple Source
Refer to Figure 6-3 and wire the indicator according to the procedure given in Table 8-4.
Make sure the jumper at S101 is in the #1 position (Figure 2-2).
Step
Table 6-4 Set Up Wiring Procedure for Thermocouple Inputs using
Thermocouple Source
Action
1
Connect the thermocouple extension wires to the terminals for the Input as shown in
Figure 6-3.
Thermocouple
Source
+
_
8
7
+
_
24873
Thermocouple
Extension Wire
Figure 6-3 Wiring Connections for Thermocouple Inputs Using
Thermocouple Source
10/00 UDC2300 Indicator Product Manual 43
Input Calibration
RTD Inputs
Refer to Figure 6-4 and wire the indicator according to the procedure given in Table 6-5.
Make sure the jumper at S101 is in the #2 position (Figure 2-2).
Step
Table 6-5 Set Up Wiring Procedure for RTD Inputs
Action
1
Connect the copper leads from the calibrator to the Input terminals as shown in Figure
6-4.
2
Place current source at zero before switching on.
3
Do not switch current sources ON/OFF while connected to the UDC2300 input.
Decade
Resistance
Box
8
7
+
_
6
R
Copper Leads
Equal Length
24875
Figure 6-4 Wiring Connections for RTD (Resistance Thermometer Device)
Radiamatic, Millivolts, Milliamperes, or Volts
Refer to Figure 6-5 and wire the indicator according to the procedure given in Table 6-6.
Make sure the jumper at S101 is in the #2 position for, mV, Volts, or the #4 position for mA (Figure 2-2).
Table 6-6 Set Up Wiring Procedure for Radiamatic, Milliampere, Millivolts,
or Volts Inputs (Except 0-10 Volts)
Step Action
1
Connect the copper leads from the calibrator to the Input terminals as shown
in Figure 6-5.
2
Place current source at zero before switching on.
3
Do not switch current sources ON/OFF while connected to the UDC2300 input.
For Radiamatic inputs only, set Emissivity value to 1.0. See Section 4.5 – Configuration Set Up prompt
INPUT1, function prompt EMISS.
44 UDC2300 Indicator Product Manual 10/00
Input Calibration
Milliampere,
Millivolt, Volt
Source
+
_
8
7
+
_
24876
Figure 6-5 Wiring Connections for Radiamatic, Milliampere, Millivolts, or
Volts (Except 0 to 10 Volts)
0 to 10 Volts
Refer to Figure 6-6 and wire the indicator according to the procedure given in Table 6-7.
Make sure the jumper at S101 is in parked position (Figure 2-2).
Step
Table 6-7 Set Up Wiring Procedure for 0 to 10 Volts
Action
1
Connect the copper leads from the calibrator to the Input terminals as shown in
Figure 6-6.
2
Place current source at zero before switching on.
3
Do not switch current sources ON/OFF while connected to the UDC2300 input.
Volt
Source
+
_
1
2
3
8
7
+
_
6 R
24877
Figure 6-6 Wiring Connections for 0 to 10 Volts
6.5 Input Calibration Procedure
Preliminary Steps
•
Apply power and allow the indicator to warm up for 30 minutes before you calibrate.
•
Please read Subsection 6.4 “Input Set Up Wiring” before beginning the procedure.
•
Make sure you have LOCK set to NONE. See Section 4.4
See Table 6-1 for Voltage vs. Resistance equivalents or 0 % and 100 % range values.
For linear inputs, avoid step changes in inputs. Vary smoothly from initial value to final 100 % value.
10/00 UDC2300 Indicator Product Manual 45
Input Calibration
Procedure
The calibration procedure for the Input is listed in Table 6-8.
Table 6-8 Input Calibration Procedure
Step Operation Press Result
1
Enter Calibration
Mode
SET UP until you see
FUNCTION
Upper Display = CAL (
- - - -
)
Lower Display = INPUT1 (10000)
You will see:
Upper Display = DIS ( 0 )
Lower Display = CALIN1 (10001)
▲
The calibration sequence is enabled and you will see:
Upper Display = BEGN ( 1 )
Lower Display = CALIN1 (10001)
At the completion of the sequence, the selection automatically reverts to disable.
2
Calibrate 0 %
FUNCTION
3
Calibrate 100 %
FUNCTION
You will see:
Upper Display = APLY ( 2 )
Lower Display = IN1ZRO (10002)
•
Adjust your calibration device to an output signal equal to the 0 % range value for your particular input sensor. See
Table 6-1 for Voltage, Degrees, or Resistance equivalents for 0 % range values.
•
Wait 15 seconds, then go to the next step.
You will see:
Upper Display = APLY ( 2 )
Lower Display = IN1SPN (10003)
•
Adjust your calibration device to an output signal equal to the 100 % range value for your particular input sensor.
See Table 6-1 for Voltage, Degrees, or Resistance equivalents for 100 % range values.
•
Wait 15 seconds, and
If … Then …
you are calibrating a Thermocouple input go to step 4 you are calibrating other than a
Thermocouple input go to step 5
46 UDC2300 Indicator Product Manual 10/00
Input Calibration
Step
4
Operation
Check the Cold
Junction
Temperature
Press Result
FUNCTION
The calculations for zero and span are now stored and you will see:
Upper Display = The cold junction temperature at the rear terminals
Lower Display = CJTEMP (10004)
The value in the upper display is in tenths of a degree. It is the current reading of the temperature as measured at the thermocouple terminals and recognized by the indicator. You can change this value, if it is in error, using the
[
▲
] [
▼
] keys.
The accuracy of the controller is directly affected by the accuracy of this value. Change this value only if the zero and span calibration procedures did not bring the indicator within the specified accuracy requirements.
5
Exit the
Calibration Mode
FUNCTION
The indicator stores the calibration constants and exits the calibration mode.
then
DISPLAY
6.6 Restore Factory Calibration
Introduction
The factory calibration constants for all the input actuation types that can be used with the indicator are stored in its nonvolatile memory. Thus, you can quickly restore the “Factory
Calibration” for a given input actuation type by simply changing the actuation type to another type and then changing it back to the original type.
Refer to Table 6-9 Restore Factory Calibration for procedure.
A restored factory calibration overwrites any previous field calibration done for the input and may change the High and Low Range Limits. Be sure to protect any field calibration from accidental overwrites by configuring the appropriate LOCKOUT selection after calibration. See Section 4 - Configuration for specific instructions to set the lockout.
10/00 UDC2300 Indicator Product Manual 47
Input Calibration
Step
1
2
3
4
Operation
Set LOCKOUT to
NONE
Table 6-9 Restore Factory Calibration
Press Result
SET UP
FUNCTION until you see:
Upper Display = SET UP
Lower Display = LOCK
Until you see:
Upper Display = one of the following:
NONE – all parameters are read/write
CAL - all parameters are read/write except Calibration
CONF – configuration parameters are Read Only; no writes permitted
ALL – Only the Lockout group is available for read/write. No other parameters are viewable.
Lower Display = LOCK
[
▲
] [
▼
]
Enter INPUT 1
Setup Group
Scroll through
Functions
Return to Normal
Operation
SET UP
FUNCTION
[
▲
] [
▼
]
FUNCTION
[
▲
] [
▼
]
DISPLAY
Until NONE is in the upper display until you see:
Upper Display = SET UP
Lower Display = INPUT 1 until you see:
Upper Display = the current selection
Lower Display = INxTYP to change the current selection to another selection until the lower display rolls through the rest of the functions and returns to:
Upper Display = the new selection
Lower Display = INxTYP until you change the input selection in the upper display back to the proper selection. You will see:
Upper Display = Original Input Selection that matches your type of sensor.
Lower Display = INxTYP to return to Normal operating mode.
The factory calibration will be restored. If the problem is not corrected, contact the Honeywell Technical Assistance
Center.
1-800-423-9883 USA and Canada
48 UDC2300 Indicator Product Manual 10/00
Troubleshooting/Service
7 Troubleshooting/Service
7.1 Overview
Introduction
Instrument performance can be adversely affected by installation and application problems as well as by hardware problems. We recommend that you investigate the problems in the following order:
• installation related problems
• application related problems
• hardware and software related problems and use the information presented in this section to solve them.
What’s in this section?
The following topics are covered in this section.
TOPIC
7.1
Overview
7.2
Troubleshooting Aids
• Overall Error Messages
• Indicator Failure Symptoms
• Customer Support
• Determining the Software Version Number
7.3
Power-up Tests
7.4
Status Tests
7.5
Background Tests
7.6
Indicator Failure Symptoms
7.7
Troubleshooting Procedures
• Power Failure
• Alarm Relay Output Failure
• Keyboard Failure
See Page
49
51
53
53
54
55
56
10/00 UDC2300 Indicator Product Manual 49
Troubleshooting/Service
Installation related problems
Read the Installation section in this manual to make sure the
UDC
2300 has been properly installed. The installation section provides information on protection against electrical noise, connecting external equipment to the indicator, and shielding and routing external wiring.
System noise induced into the indicator will result in diagnostic error messages recurring. If the diagnostic error messages can be cleared, it indicates a “soft” failure and is probably noise related.
If system noise is suspected, completely isolate the controller from all field wiring. Use calibration sources to simulate PV and check all controller functions; i.e. Gain, Rate, Reset, Output, Alarms, etc.
Application related problems
Review the application of the indicator; then, if necessary, direct your questions to the local sales office.
Hardware and software related problems
Use the troubleshooting error message prompts and indicator failure symptoms to identify typical failures which may occur in the indicator.
Follow the troubleshooting procedures to correct them.
50 UDC2300 Indicator Product Manual 10/00
Troubleshooting/Service
7.2 Troubleshooting Aids
Overall error messages
An error message can occur
• at power-up, see Subsection 7.3
• when the Status Tests are requested, see Subsection 7.4
• during continuous background tests while in normal operation, see Subsection 7.5
Indicator failure symptoms
Other failures may occur that deal with the Power or Alarms.
Refer to the indicator failure symptoms in Table 7-4 to determine what is wrong and the troubleshooting procedures to use to correct the problem.
Check installation
If a set of symptoms still persists, refer to Section 2 - Installation and ensure proper installation and proper use of the indicator in the system.
Customer support
If you cannot solve the problem using the troubleshooting procedures listed in this section, you can get technical assistance by dialing 1-800-423-9883 USA and Canada.
An engineer will discuss your problem with you. Please have your complete model
number, serial number, and Software version available. The model and serial numbers can be found on the chassis nameplate. The software version can be viewed under Setup Group “Status.” See Table 7-1.
If it is determined that a hardware problem exists, a replacement indicator or part will be shipped with instructions for returning the defective unit.
Do not return your indicator without authorization from Honeywell’s Technical
Assistance Center or until the replacement has been received.
For a list of frequently asked questions and their answers, dial Honeywell’s Faxback 24 hour Service:
1-888-423-9883 USA
Or check out Honeywell’s web site at: http://www.honeywell.com/sensing
10/00 UDC2300 Indicator Product Manual 51
Troubleshooting/Service
Determining the software version
Table 7-1 lists the procedure for identifying the software version number.
Step
1
Table 7-1 Procedure for Identifying the Software Version
Operation Press Result
Select
STATUS
Set Up Group
SET UP
Upper Display = READ
Lower Display = STATUS
2
Read the software version
FUNCTION
You will see:
Upper Display = Software version number
Lower Display = A1xx Basic Controller and Indicator
A2xx Limit Controller
Please give this number to the Customer Support person. It will indicate which version of UDC2300 you have and help them determine a solution to your problem.
52 UDC2300 Indicator Product Manual 10/00
Troubleshooting/Service
7.3 Power-up Tests
What happens at power-up
When power is applied, the indicator will run three diagnostic tests. After these tests are completed, “TEST DONE” is displayed.
Test Failures
If one or more of these tests fail, the indicator will go to the Failsafe Manual Mode, and
FAILSF will flash in the lower display and a message indicating which test failed will appear in the lower display. Then, “DONE” will appear in the lower display.
Introduction
When required, the results of these tests can be checked to determine the reason the indicator has gone to Failsafe.
How to check the status tests
The procedure in Table 7-2 tells you how to display the results of the status tests.
Step
1
Table 7-2 Procedure for Displaying the Status Test Results
Operation Press Result
Select
STATUS
Set Up Group
SET UP
Upper Display = READ
Lower Display = STATUS
2
Read the test results
FUNCTION
You will see:
Upper Display = NO or YES YES indicates a failure
Lower Display = FAILSF
FUNCTION
Upper Display = PASS or FAIL
Lower Display = TEST
10/00 UDC2300 Indicator Product Manual 53
Troubleshooting/Service
Introduction
The UDC2300 performs ongoing background tests to verify data and memory integrity.
If there is a malfunction, an error message will be displayed (blinking) in the lower display.
In the case of simultaneously malfunctions, the messages will appear in sequence in the lower display. Table 7-3 lists these background tests, the reason for their failure, and how to correct the problem.
Table 7-3 Background Tests
Lower
Display
EE FAIL
Reason for Failure How to Correct the Problem
FAILSF
IN1FL
IN1RNG
PV LIM
Unable to write to non-volatile memory. Anytime you change a parameter and it is not accepted, you will see EE FAIL.
This error message shows whenever the indicator goes into a failsafe mode of operation. This will happen if:
• RAM test failed
• Configuration test failed
• Calibration test failed
• Burnout configured for none and the input failed.
Two consecutive failures of input 1 integration; i.e., cannot make analog to digital conversion. This will happen if:
• Upscale or Downscale burnout is selected
• Input not configured correctly
Input 1 out of range. The process input is outside the range limits.
PV out of range.
PV = INP1 x RATIO1+ INP1 BIAS
1. Check the accuracy of the parameter and reenter.
2. Try to change something in configuration.
3. Run through STATUS tests to re-write to
EEPROM.
1. Run through STATUS check to determine the reason for the failure.
2. Press the [SET UP] key until STATUS appears in the lower display.
3. Press the [FUNCTION] key to see whether the tests pass or fail, then run through the
STATUS codes a second time to see if the error cleared.
1. Make sure the actuation is configured correctly. See Section 4 - Configuration.
2. Make sure the input is correct.
3. Check for gross over-ranging. Check S101 jumper position (Figure 2-2).
4. Restore factory calibration. See Section 6.6
1. Make sure the range and actuation are configured properly.
2. Check the input source.
3. Restore the factory calibration.
(See Section 6.6.)
4. Field calibrate.
See Section 6 - Input Calibration.
1. Make sure the input signal is correct.
2. Make sure the Ratio and Bias settings are correct.
3. Recheck the calibration. Use Bias of 0.0
54 UDC2300 Indicator Product Manual 10/00
Troubleshooting/Service
7.6 Indicator Failure Symptoms
Introduction
In addition to the error message prompts, there are failure symptoms that can be identified by noting how the indicator displays and indicators are reacting.
Symptoms
Compare your symptoms with those shown in Table 7-4.
Upper
Display
Lower
Display
Table 7-4 Indicator Failure Symptoms
Indicators Indicator
Output
Probable
Cause
Blank
OK
Blank
OK
Off
OK
None
External Alarm function does not operate properly
Display does not function when a key is pressed
Power Failure
Malfunction in alarm output
Keyboard
Malfunction
Troubleshooting
Procedure
1
2
3
Other symptoms
If a set of symptoms or prompts other than the one you started with appears while troubleshooting, re-evaluate the symptoms. This may lead to a different troubleshooting procedure.
If the symptom still persists, refer to the installation section in this manual to ensure proper installation and proper use of the indicator in your system.
10/00 UDC2300 Indicator Product Manual 55
Troubleshooting/Service
7.7 Troubleshooting Procedures
Introduction
The troubleshooting procedures are listed in numerical order as they appear in Table 7-4.
Each procedure lists what to do if you have that particular failure and how to do it or where to find the data needed to accomplish the task.
WARNING—SHOCK HAZARD !
TROUBLESHOOTING MAY REQUIRE ACCESS TO HAZARDOUS
LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY
QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH
MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE SERVICING.
Failure to comply with these instructions could result in death or serious injury.
Equipment needed
You will need the following equipment in order to troubleshoot the symptoms listed in the tables that follow:
• DC Milliammeter – mAdc
• Calibration sources – T/C, mV, Volt, etc.
• Voltmeter
56 UDC2300 Indicator Product Manual 10/00
Troubleshooting/Service
Procedure #1
Table 7-5 explains how to troubleshoot power failure symptoms.
Step
1
2
3
4
Table 7-5 Troubleshooting Power Failure Symptoms
What to do
Check the AC line voltage.
Make sure the chassis plugs into the rear of the case properly.
Check the system for Brown-outs, heavy load switching, etc., and conformance to installation instructions.
Change Main board.
How to do it
Use a voltmeter to measure the AC voltage across terminals L1 and L2 on the rear terminal panel of the indicator.
Check the earth ground connection.
Withdraw the chassis and visually inspect the indicator board and the inside of the case.
Refer to Section 2 - Installation.
Installation instructions supplied with new board.
Procedure #2
Table 7-6 explains how to troubleshoot Alarm Relay Output failure.
Step
1
2
3
4
Table 7-6 Troubleshooting Alarm Relay Output Failure
What to do How to do it
Check the alarm configuration data. If it is correct, check the field wiring.
Reconfigure if necessary.
Refer to Section 4 - Configuration for details.
Check that the applicable alarm relay actuates properly depending on what you have set at prompt AxSxTYPE.
If it does, check the field wiring.
Check the contacts.
Change Main board.
If the alarm type is set for PV vary the input to raise and lower the PV around the alarm setpoint. Listen for a click from the relay as the
PV moves in either direction and note that the proper ALM1 or ALM2 is lit.
Make sure the NO or NC contact wiring is correct.
Refer to Section 2 - Installation for relay jumper placement and relay contact information.
Installation instructions supplied with new board.
10/00 UDC2300 Indicator Product Manual 57
Troubleshooting/Service
Procedure #3
Table 7-7 explains how to troubleshoot a Keyboard failure.
Step
1
2
Table 7-7 Troubleshooting a Keyboard Failure
What to do
Make sure the keyboard is connected properly.
Indicator Keyboard or specific keys may be LOCKED OUT via the security code.
How to do it
Withdraw the chassis from the case and visually inspect the connection.
Use your four-digit security code number to change the lockout level. Refer to Section 4 –
Configuration.
3
Using “1000” as a security code number will override the 4-digit code previously entered.
Replace the display/keyboard if any keys are not functioning.
Installation instructions supplied with new display/keyboard.
58 UDC2300 Indicator Product Manual 10/00
Parts List
Introduction
Figure 8-1 is an exploded view of the UDC2300 Indicator. Each part is labeled with a key number. The part numbers are listed by key number in Table 8-1.
Parts not shown are listed in Table 8-2.
10/00
3
Key
Number
1
2
3
4
2
1
Figure 8-1 UDC2300 Exploded View
Part Number
Table 8-1 Parts Identification
Description
30756667-503
51309766-501
51309831-501
51404896-501
Bezel Assembly (Gray)
Display/Keyboard
RS-422/485 Communications PWA
Case Assembly (includes 30755050-001 Mounting Kit)
4
UDC2300 Indicator Product Manual 59
Parts List
Part Number
30755223-003
30756683-001
30755050-001
30757215-001
30756764-002
30756018-001
30756725-501
30754465-501
30754142-003
30755306-501
Table 8-2 Parts Not Shown
Description
DIN Adaptor (Gray)
NEMA 3 Gasket (Panel to Case)
Mounting Kit
NEMA 4 Adaptor Kit
Rear Terminal Cover Kit
SS Relay 10 Amp (external)
SS Relay 1 Amp (internal)
0-10 Volt Input resistor assembly (100K pair)
Terminal Strip Assembly
Electro-mechanical Relay (5 Amp)
60 UDC2300 Indicator Product Manual 10/00
Index
A
Accuracy, 4
Alarm Blocking, 31
Alarm Circuit Wiring, 11
Alarm Hysteresis, 31
Alarm Relay Action., 6
Alarm Relay Output failure, 57
Alarm relays, 8
Alarm Setpoints, 37
Alarm Setpoints Display, 37
Alarms Set Up Group, 30
Alarmx Setpoint x State, 30
Alarmx Setpointx Type, 30
Alarmx Setpointx Value, 30
Ambient Temperature, 4
Annunciators, 36
Application related problems, 50
B
background tests, 54
Baud Rate, 27
Bias on Input 1, 25
Burnout Protection, 25
C
Calibration Mode, 48 calibration procedure, 46
Calibration Steps, 40
CE Conformity, 4
CE Conformity (Europe), 2
Cold Junction Temperature, 47
Communi-cations Override Units, 28
Communications State, 27
Composite Wiring Diagram, 12
Configuration, 19
Configuration Lockout, 22
Configuration Procedure, 21
Configuration Prompt Hierarchy, 20
Configuration Record Sheet, 32
Control and Alarm Relay Contact Information, 8
Controller Grounding, 11
Customer support, 51
D
Decimal Point Selection, 23
Dimensions, 9
DOWNSCALE BURNOUT, 25
9 Index
E
Electrical Considerations, 11
Electrical Noise Precautions, 11
Emissivity, 26
EMISSIVITY, 26 equipment you will need to calibrate, 42
Error Messages, 36
Exploded View, 59
External Interface Option Connections, 15
External Wiring, 11
F, G, H
Factory calibration, 47
FAILSAFE, 25
Failsafe Manual Mode, 17, 53
Field Wiring, 41
Filter for Input 1, 25
Function Prompts, 20
I
Indicator Failure Symptoms, 55
Initial Start-up, 17
Input 1 Actuation Type, 23, 24
Input 1 High Range Value, 24
Input 1 Low Range Value, 24
Input 1 Set Up Group, 23
Input Calibration, 39
Input Calibration Procedure, 45
Input Connections, 13
Input I Jumper Placement, 6
Input Set Up Wiring, 43
Input Wiring Terminals, 41
Installation, 3
Installation related problems, 50
J
Jumper for Input, 41
Jumper Placement, 7
K
Key error, 35
Key Error Message, 18
Key Functions, 18
Keyboard failure, 58
10/00 UDC2300 Indicator Product Manual 61
Index
Language Selection, 26
Latching Alarm Output, 31
Local Loopback Test, 29
Lock Set Up Group, 22 lockout feature, 35
Lockout levels, 35
L
M, N
Mains Power Supply, 11, 13
Mechanical Shock, 4
Minimum and Maximum Range Values, 40
Model Number Interpretation, 5
Monitoring t, 33
Mounting, 9
Mounting Method, 10
Mounting Procedure, 10
O
Open Collector Alarm Relay Output, 14
Operating Limits, 4
Operator Interface, 1, 18, 34
P, Q
Parity, 27
Parts Identification, 59
Parts List, 59
Permissible Wiring Bundling, 12
Physical Considerations, 9
Power, 4
Power Consumption, 4 power failure symptoms, 57
Power Line Frequency, 26
Powering Up, 17
Power-up Tests, 53
Pre-installation Information, 4
Preliminary Checks, 6
R
Ratio on Input, 24
Relative Humidity, 4
Response Delay, 28
Restore Factory Calibration, 47
RTD Inputs, 44
S
SECURITY CODE, 22, 34
Sensor Break, 25
Set Up Group, 20
Set Up groups, 19
Shed Enable, 27
Shed Time, 27
Shock hazard warning, 56 software version number, 52
Specifications, 4 start up, 17
Station Address, 27
Status Tests, 53
Suppression Devices, 11
T
Temperature Units, 23
Test Failures, 17, 53
Thermocouple Inputs Using a Thermocouple Source,
43
Thermocouple Inputs Using an Ice Bath, 43
Transmitter Character-ization, 24
Troubleshooting Aids, 51 troubleshooting procedures, 56
Troubleshooting/Service, 49
U
UPSCALE BURNOUT, 25
V
Vibration, 4
Voltage and Resistance Equivalents for 0% and 100%
Range Values, 40
W, X, Y, Z
WARNING—SHOCK HAZARD, 56
Wiring, 11
Wiring Bundling, 12
Wiring Connections for Radiamatic, Milliampere,
Millivolts, or Volts (Except 0 to 10 Volts), 45
Wiring Connections for RTD (Resistance
Thermometer Device), 44
Wiring Diagrams, 12
Wiring the Indicator, 12
62 UDC2300 Indicator Product Manual 10/00
HSM8
HONEYWELL SERVICE CENTERS
ARGENTINA
HONEYWELL S.A.I.C.
BELGRANO 1156
BUENOS AIRES
ARGENTINA
Tel. : 54 1 383 9290
BULGARIA
HONEYWELL EOOD
14, Iskarsko Chausse
POB 79
BG- 1592 Sofia
BULGARIA
Tel : 359-791512/ 794027/ 792198
GERMANY
HONEYWELL AG
Kaiserleistrasse 39
D-63067 OFFENBACH
GERMANY
Tel. : 49 69 80 640
ASIA PACIFIC
HONEYWELL ASIA PACIFIC Inc.
Room 3213-3225
Sun Kung Kai Centre
N° 30 Harbour Road
WANCHAI
HONG KONG
Tel. : 852 829 82 98
AUSTRALIA
HONEYWELL LIMITED
5 Thomas Holt Drive
North Ryde Sydney
NSW AUSTRALIA 2113
Tel. : 61 2 353 7000
AUSTRIA
HONEYWELL AUSTRIA G.m.b.H.
Handelskai 388
A1020 VIENNA
AUSTRIA
Tel. : 43 1 727 800
BELGIUM
HONEYWELL S.A.
3 Avenue de Bourget
B-1140 BRUSSELS
BELGIUM
Tel. : 32 2 728 27 11
CANADA
HONEYWELL LIMITED
THE HONEYWELL CENTRE
529 Mc Nicoll Avenue
M2H 2C9 NORTH YORK,
ONTARIO
CANADA
Tel. : 416 502 5200
CZECH REPUBLIC
HONEYWELL, Spol.s.r.o.
Budejovicka 1
140 21 Prague 4
Czech Republic
Tel. : 42 2 6112 3434
DENMARK
HONEYWELL A/S
Automatikvej 1
DK 2860 Soeborg
DENMARK
Tel. : 45 39 55 56 58
FINLAND
HONEYWELL OY
Ruukintie 8
FIN-02320 ESPOO 32
FINLAND
Tel. : 358 0 3480101
HUNGARY
HONEYWELL Kft
Gogol u 13
H-1133 BUDAPEST
HUNGARY
Tel. : 36 1 451 43 00
ICELAND
HONEYWELL
Hataekni .hf
Armuli 26
PO Box 8336
128 reykjavik
Iceland
Tel : 354 588 5000
ITALY
HONEYWELL S.p.A.
Via P. Gobetti, 2/b
20063 Cernusco Sul Naviglio
ITALY
Tel. : 39 02 92146 1
MEXICO
HONEYWELL S.A. DE CV
AV. CONSTITUYENTES 900
COL. LOMAS ALTAS
11950 MEXICO CITY
MEXICO
Tel : 52 5 259 1966
BRAZIL
HONEYWELL DO BRAZIL AND CIA
Rua Jose Alves Da Chunha
Lima 172
BUTANTA
05360.050 SAO PAULO SP
BRAZIL
Tel. : 55 11 819 3755
FRANCE THE NETHERLANDS
HONEYWELL S.A.
Bâtiment « le Mercury »
Parc Technologique de St Aubin
Route de l’Orme (CD 128)
91190 SAINT-AUBIN
FRANCE
Tel. from France: 01 60 19 80 00
From other countries: 33 1 60 19 80 00
HONEYWELL BV
Laaderhoogtweg 18
1101 EA AMSTERDAM ZO
THE NETHERLANDS
Tel : 31 20 56 56 911
HSM8
NORWAY
HONEYWELL A/S
Askerveien 61
PO Box 263
N-1371 ASKER
NORWAY
Tel. : 47 66 76 20 00
POLAND
HONEYWELL Sp.z.o.o
UI Domainewksa 41
02-672 WARSAW
POLAND
Tel. : 48 22 606 09 00
PORTUGAL
HONEYWELL PORTUGAL LDA
Edificio Suecia II
Av. do Forte nr 3 - Piso 3
2795 CARNAXIDE
PORTUGAL
Tel. : 351 1 424 50 00
REPUBLIC OF IRELAND
HONEYWELL
Unit 1
Robinhood Business Park
Robinhood Road
DUBLIN 22
Republic of Ireland
Tel. : 353 1 4565944
REP. OF SINGAPORE
HONEYWELL PTE LTD
BLOCK 750E CHAI CHEE ROAD
06-01 CHAI CHEE IND. PARK
1646 SINGAPORE
REP. OF SINGAPORE
Tel. : 65 2490 100
HONEYWELL SERVICE CENTERS
REPUBLIC OF SOUTH
AFRICA
HONEYWELL
Southern Africa
PO BOX 138
Milnerton 7435
REPUBLIC OF SOUTH AFRICA
Tel. : 27 11 805 12 01
ROMANIA
HONEYWELL Office
Bucharest
147 Aurel Vlaicu Str., Sc.Z.,
Apt 61/62
R-72921 Bucharest
ROMANIA
Tel : 40-1 211 00 76/ 211 79 43
RUSSIA
HONEYWELL INC
4 th
Floor Administrative
Builiding of AO "Luzhniki"
Management
24 Luzhniki
119048 Moscow
RUSSIA
Tel : 7 095 796 98 00/01
SLOVAKIA
HONEYWELL Ltd
Mlynske nivy 73
PO Box 75
820 07 BRATISLAVA 27
SLOVAKIA
Tel. : 421 7 52 47 400/425
SPAIN
HONEYWELL S.A
Factory
Josefa Valcarcel, 24
28027 MADRID
SPAIN
Tel. : 34 91 31 3 61 00
SWEDEN
HONEYWELL A.B.
S-127 86 Skarholmen
STOCKHOLM
SWEDEN
Tel. : 46 8 775 55 00
SWITZERLAND
HONEYWELL A.G.
Hertistrasse 2
8304 WALLISELLEN
SWITZERLAND
Tel. : 41 1 831 02 71
TURKEY
HONEYWELL Otomasyon ve
Kontrol
Sistemlen San ve Tic A.S.
(Honeywell Turkey A.S.)
Emirhan Cad No 144
Barbaros Plaza C. Blok Kat 18
Dikilitas 80700 Istanbul
TURKEY
Tel : 90-212 258 18 30
UNITED KINGDOM
HONEYWELL
Unit 1,2 &4 Zodiac House
Calleva Park
Aldermaston
Berkshire RG7 8HW
UNITED KINGDOM
Tel : 44 11 89 81 95 11
U.S.A.
HONEYWELL INC.
INDUSTRIAL CONTROLS DIV.
1100 VIRGINIA DRIVE
PA 19034-3260 FT. WASHINGTON
U.S.A.
Tel. : 215 641 3000
VENEZUELA
HONEYWELL CA
APARTADO 61314
1060 CARACAS
VENEZUELA
Tel. : 58 2 239 0211
Sensing and Control
Honeywell
11 West Spring Street
Freeport, IL 61032
51-52-25-84A 1000 Printed in USA
www.honeywell.com/sensing
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 9 INTRODUCTION
- 9 Overview
- 10 CE Conformity (Europe)
- 11 INSTALLATION
- 11 Overview
- 13 Model Number Interpretation
- 14 Preliminary Checks
- 16 Alarm Relay Contact Information
- 17 Mounting
- 19 Wiring
- 20 Wiring Diagrams
- 25 INITIAL START-UP
- 25 Overview
- 25 Powering Up the Indicator
- 26 Operator Interface and Key Functions
- 26 Key Error Message
- 27 CONFIGURATION
- 27 Overview
- 28 Configuration Prompt Hierarchy
- 29 Configuration Procedure
- 30 Lock Set Up Group
- 31 Input Set Up Group
- 35 Communications Set Up Group
- 38 Alarms Set Up Group
- 40 Configuration Record Sheet
- 41 MONITORING THE INDICATOR
- 41 Overview
- 42 Operator Interface
- 42 Entering a Security Code
- 43 Lockout Feature
- 44 Monitoring Your Indicator
- 45 Alarm Setpoints
- 47 INPUT CALIBRATION
- 47 Overview
- 48 Minimum and Maximum Range Values
- 49 Preliminary Information
- 51 Input Set Up Wiring
- 53 Input Calibration Procedure
- 55 Restore Factory Calibration
- 57 TROUBLESHOOTING/SERVICE
- 57 Overview
- 59 Troubleshooting Aids
- 61 Power-up Tests
- 61 Status Tests
- 62 Background Tests
- 63 Indicator Failure Symptoms
- 64 Troubleshooting Procedures
- 67 PARTS LIST
- 67 Exploded View
- 69 INDEX