OPERATION SERVICE AND INSTALLATION MANUAL DUCTAIR NJCK / NJHK NCCK / NCHK Congratulations you have made a wise choice with the purchase of your Lennox air conditioning set. This product has been designed, assembled and supplied in one of our world class manufacturing facilities and we feel sure that it will meet your expectations. Lennox an international organization with world wide distribution takes pride in supplying you with this product. 1.- UNIT SELECTION 1.1.- PRODUCT RANGE 1.2.- GENERAL DESCRIPTION 1.3.- SPECIFICATIONS 1.4.- TECHNICAL DATA 1.5.- ELECTRICAL DATA 1.6.- MOTOR FAN CHARACTERISTICS 1.7.- CAPACITY TABLES 1.8.- UNIT DIMENSIONS 1.9.- UNIT DESCRIPTION 1.10.- OPERATING LIMITS 1.11.- STANDARD/ OPTIONAL ENTRANCES 1.12.- OPTIONS 2 3 4-5 6-7 6-7 8 9-12 13-14 15 16 16-17 18-19 2.- INSTALLATION 2.1.2.2.2.3.2.4.2.5.- POINTS TO KEEP IN MIND INSTALLATION GUIDELINES UNIT RECEPTION INSTALLATION CLEARANCES OPTIONAL OPERATIONS PRIOR TO UNIT INSTALLATION: CHANGING THE POSITION OF BLOWERS AND AIR INTAKE 2.6.- DUCT INSTALLATION 2.7.- DRAINS 2.8.- SETTING UP TEMPLATES OF UNITS 2.9.- OPTIONAL OPERATIONS PRIOR TO UNIT INSTALLATION: CHANGING THE POSITION OF AIR INLET PANEL FOR INDOOR UNITS LNXO 2.10.- UNIT LOCATION OF INDOOR UNIT LNXO 2.11.- ELECTRICAL CONNECTIONS 2.12.- REFRIGERANT CONNECTIONS 20 21 21 21 22 22 23 24 25 25 26-27 28-29 3.- COMMISSIONING AND OPERATION 3.1.3.2.3.3.3.4.- DATA PAGE FOR UNIT COMMISSIONING PRECAUTIONS TO BE TAKEN ON INSTALLATION PRELIMINARY CHECKS STEPS TO FOLLOW FOR COMMISSIONING THE UNIT 30 31 31 32 4.- MAINTENANCE 33 34 34 4.1.- PREVENTIVE MAINTENANCE 4.2.- CORRECTIVE MAINTENANCE 4.3.- FAILURE DIAGNOSIS 1 1.- UNIT SELECTION R-407C 1.1.- PRODUCT RANGE COOLING ONLY LNXO INDOOR UNIT IN COMBINATION WITH AXIAL FAN OUTDOOR UNIT MODEL NJCK 018 NJCK 024 NJCK 030 NJCK 030 NJCK 036 NJCK 036 NJCK 036 NJCK 048 NJCK 048 NJCK 060 NJCK 060 NJCK 070 NJCK 070 NJCK 080 NJCK 080 OUTDOOR UNIT KJCK 018 KJCK 024 KJCK 030 KJCK 030 KJCK 036 KJCK 036 KJCK 036 KJCK 048 KJCK 048 KJCK 060 KJCK 060 KJCK 070 KJCK 070 KJCK 080 KJCK 080 INDOOR UNIT V / Ph / 50 Hz LNXO 018 LNXO 024 230V-1Ph 230V-1Ph 230V-1Ph 400V-3Ph 230V -1Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph LNXO 030 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 NOMINAL CAPACITY W COOLING 5.000 6.500 POWER INPUT kW COOLING 1,95 2,5 7.600 3,0 9.100 3,6 11.300 4,2 13.300 5,3 16.300 6,2 18.000 7,2 LNXO INDOOR UNIT IN COMBINATION WITH CENTRIFUGAL FAN OUTDOOR UNIT MODEL NCCK 018 NCCK 024 NCCK 030 NCCK 036 NCCK 036 NCCK 036 NCCK 048 NCCK 048 NCCK 060 NCCK 060 NCCK 070 NCCK 070 NCCK 080 NCCK 080 OUTDOOR UNIT KCCK 018 KCCK 024 KCCK 030 KCCK 036 KCCK 036 KCCK 036 KCCK 048 KCCK 048 KCCK 060 KCCK 060 KCCK 070 KCCK 070 KCCK 080 KCCK 080 INDOOR UNIT LNXO 018 LNXO 024 LNXO 030 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 NOMINAL CAPACITY W COOLING 5100 6600 7700 V / Ph / 50 Hz 230V-1Ph 230V-1Ph 230V-1Ph 230V -1Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph POWER INPUT kW COOLING 2,02 2,6 3,3 9000 3,87 11000 4,7 13500 5,8 16100 6,72 18300 7,84 HEAT PUMP LNXO INDOOR UNIT IN COMBINATION WITH AXIAL FAN OUTDOOR UNIT MODEL NJHK 018 NJHK 024 NJHK 030 NJHK 036 NJHK 036 NJHK 036 NJHK 048 NJHK 048 NJHK 060 NJHK 060 NJHK 070 NJHK 070 NJHK 080 NJHK 080 OUTDOOR UNIT KJHK 018 KJHK 024 KJHK 030 KJHK 036 KJHK 036 KJHK 036 KJHK 048 KJHK 048 KJHK 060 KJHK 060 KJHK 070 KJHK 070 KJHK 080 KJHK 080 INDOOR UNIT LNXO 018 LNXO 024 LNXO 030 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 V / Ph / 50 Hz 230V-1Ph 230V-1Ph 230V-1Ph 230V -1Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph NOMINAL CAPACITY W COOLING HEATING 5000 5150 6500 6500 7600 8000 POWER INPUT kW COOLING HEATING 1,95 1,85 2,5 2,38 3,0 2,9 9100 9300 3,6 3,35 11300 11900 4,2 4,2 13300 13600 5,3 4,9 16300 16700 6,2 5,9 18000 18200 7,2 6,7 LNXO INDOOR UNIT IN COMBINATION WITH CENTRIFUGAL FAN OUTDOOR UNIT MODEL NCHK 018 NCHK 024 NCHK 030 NCHK 036 NCHK 036 NCHK 036 NCHK 048 NCHK 048 NCHK 060 NCHK 060 NCHK 070 NCHK 070 NCHK 080 NCHK 080 OUTDOOR UNIT KCHK 018 KCHK 024 KCHK 030 KCHK 036 KCHK 036 KCHK 036 KCHK 048 KCHK 048 KCHK 060 KCHK 060 KCHK 070 KCHK 070 KCHK 080 KCHK 080 INDOOR UNIT LNXO 018 LNXO 024 LNXO 030 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 V / Ph / 50 Hz 230V-1Ph 230V-1Ph 230V-1Ph 230V -1Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph 230 V - 3Ph 400 V - 3Ph NOMINAL CAPACITY W COOLING HEATING 5400 5100 6850 6600 8400 7700 POWER INPUT kW COOLING HEATING 2,06 2,02 2,54 2,6 3,23 3,3 9000 9200 3,87 3,5 11000 11400 4,7 4,2 13500 14400 5,8 5,65 16100 16450 6,72 6,03 18300 19000 7,84 7,3 NOTE: The units at 230V-3Ph power supply are special. Ask for availability. 2 1.- UNIT SELECTION 1.2.-GENERAL DESCRIPTION INDOOR UNIT LNXO OUTDOOR UNIT KJCK/KJHK (axial fan unit) OUTDOOR UNIT KCCK/KCHK (centrifugal fan unit) The duct air conditioner split on version cooling only and heat pump, are units condensed by air, designed for small shopping center and housing. The indoor unit with direct air supply, cools, heats, dehumidifies, and cleans air of the sites. The indoor unit can be combined with condensing units provided with axial fan (KJCK/KJHK) for outside installation, or with condensing units provided with centrifugal fan (KCCK/KCHK) for installation inside buildings. A wide range of options, completed-factory assembled are also available, for easier installation. COOLING CIRCUIT CABINET The indoor unit chassis is made of galvanized steel and is fully insulated inside. The cabinet includes brackets for holding the unit. Made of welded dehydrated copper pipe with service port on the suction and liquid lines. Coupling valves on outdoor unit (all models) and flare connection on indoor unit (except models 070-080, with welded connections) to make easier the refrigerant connections. The expansion system for cooling and heating takes place on outdoor unit, except for models 070-080 which cooling expansion system is located on indoor unit. Heat pump units are equipped as well with unidirectional and four way reversing valves. The outdoor unit chassis is made of electrozinced steel with epoxy painted finished, able to work with outdoors under the worst conditions. The unit is completed with handles, which assist easy installation. Its compact dimensions and features allow the unit to be positioned in almost any location. HEAT EXCHANGERS ELECTRIC CIRCUIT Made-up with copper pipes and aluminium wings, designed to get a high heating transfer. Their dimensions and design of the circuits have been specially worked to obtain the maximum performance of the exchanger increasing the power of the unit and reducing the consumption. The electrical panel includes a printed board, which controls the operating of the unit, defrosting timer thermostat and system of reversing on heat pump cycle. The heat pump outdoor unit includes a printed board with a defrosting timer, for safety device. CONTROL COMPRESSOR The indoor unit is supplied with a digital wired thermostat with 3 speed and ON TIMER/OFF TIMER function (see manual supplied with the thermostat for details). All units are provided with scroll compressor, cooling by a suction gas with thermic protection inside the engine, so no other additional protection is required. It is mounted on anti-vibration devices both external and internal. The 400V-III units are supplied with a three phase detector which avoids the unit starts, unless the phase connections are right. In heat pump units, the compressors are provided with a crankcase heater to heat the oil in the compressor so that a suitable lubrication can take place; this is an option for cooling only units. AUTO SLEEP DRY AUTO COOL HEAT FAN SWING KEY LOCK MON TUE WED THU FRI SAT SUN TIMER ACTIVE SET TIMER SET CLOCK COOL TEMP. HEAT TEMP. ROOM TEMP. ON / OFF SLEEP SWING FAN MODE ON TIMER OFF TIMER DAY HOUR SET TEMP CLOCK HOLD MINUTE Control OLT-1X OPTIONS INDOOR UNIT • One step electrical heater. • Hot water coils. • Kit discharge plenum and Kit air inlet plenum. • Condensate pump. OUTDOOR UNIT TYPE KJCK/KJHK • ON/OFF Condensation pressure control. • Proportional condensing pressure control. • Kit compressor isolation. • Supporting unit brackets (depends on models). • Long distance unit version (50m of refrigerant connection). OUTDOOR UNIT TYPE KCCK/KCHK • ON/OFF Condensation pressure control. • Proportional condensing pressure control. • Main switch (depends on models). • Kit compressor isolation. FANS The indoor units include centrifugal motor fan of two / three speed, with high static pressure, to adapt the fan features to installation requirements. Depending on outdoor unit type, it includes one or two axial motor fan (units KJCK/KJHK), or one centrifugal fan (units KCCK/KCHK),with exceptional features in noise level and flow. AIR FILTER A polypropylene air filter is incorporated on models from 018 to 060. And a polyester extinguishable material air filter is incorporated for models 070-080. Both high efficiency filtrate, washable and easy to install. 3 1.- UNIT SELECTION 1.3.- SPECIFICATIONS SET WITH AXIAL FAN OUTDOOR UNIT MODEL NJCK / NJHK 018 NJCK / NJHK 024 NJCK / NJHK 030 NJCK / NJHK 036 NJCK / NJHK 048 NJCK / NJHK 060 NJCK / NJHK 070 NJCK / NJHK 080 Nominal cooling capacity (*) W 5000 6500 7600 9100 11300 13300 16300 18000 Nominal heating capacity NJHK (**) W 5150 6500 8000 9300 11900 13600 16700 18200 KJCK / KJHK 018 KJCK / KJHK 024 KJCK / KJHK 030 KJCK / KJHK 036 KJCK / KJHK 048 KJCK / KJHK 060 KJCK / KJHK 070 KJCK / KJHK 080 1 / Scroll 1 / Scroll 1800 2800 Capillary Capillary OUTDOOR UNIT COMPRESSOR Nr / Type 3 FAN Air flow m /h EXPANSION (cooling only / heat pump) 1 / Scroll 1 / Scroll 3100 3200 1 / Scroll 5500 1 / Scroll 1 / Scroll 5500 5200 1 / Scroll 5200 Capillary Restrictor Restrictor Restrictor --/Restrictor --/Restrictor Cooling only units Kg 53 57 70 73 99 109 130 131 Heat pump units Kg 55 60 72 76 102 112 135 136 WEIGHT DIMENSIONS Height (H) mm 629 629 781 931 1239 1239 1230 1230 Width (W) mm 773 773 973 973 973 973 998 998 Depth (D) mm 333 333 333 333 333 333 386 386 PACKING DIMENSIONS (HxWxD) mm REFRIGERANT COUPLING Liquid pipe 970x1072 1120x1072 x395 x395 679x860x385 1390x1072x395 1385x1102x452 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" 5/8" 5/8" 3/4" 3/4" 3/4" 7/8" 7/8" LNXO 018 LNXO 024 LNXO 030 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 Max 915 1200 1350 1725 2150 2450 3600 3950 Min 600 740 920 1000 1630 2060 2500 2900 Pa 60 60 100 120 100 100 160 140 -- -- -- -- -- -- Kg 35 35 43 44 57 58 85 86 (H) mm 235 235 287 287 315 315 415 415 Width (W) mm 1076 1076 1076 1076 1271 1271 1380 1380 Depth (D) mm 535 535 700 700 750 750 850 850 Gas pipe INDOOR UNIT FAN Air flow m3/h Available pressure max (2) EXPANSION WEIGHT DIMENSIONS Height 235x1170x665 290x1170x830 Liquid pipe 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" Gas pipe 1/2" 5/8" 5/8" 3/4" 3/4" 3/4" 7/8" 7/8" PACKING DIMENSIONS (HxWxD) mm 320x1365x875 Restrictor Restrictor 555x1460x975 REFRIGERANT COUPLING (*) Air intake temperature indoor interchange: 27°C DB / 19°C WB (*) Air intake temperature outdoor interchange: 35ºC DB (**) Air intake temperature indoor interchange: 20°C DB / 12ºC WB (**) Air intake temperature outdoor interchange: 7°C DB / 6ºC WB (2) With minimum admissible flow volumes and high speed fan 4 DB.- Dry bulb WB.- Wet bulb 1.- UNIT SELECTION 1.3.- SPECIFICATIONS SET WITH CENTRIFUGAL FAN OUTDOOR UNIT MODEL NCCK / NCHK 018 NCCK / NCHK 024 NCCK / NCHK 030 NCCK / NCHK 036 NCCK / NCHK 048 NCCK / NCHK 060 NCCK / NCHK 070 NCCK / NCHK 080 Nominal cooling capacity (*) W 5100 6600 7700 9000 11000 13500 16100 18300 Nominal heating capacity NCHK (**) W 5400 6850 8400 9200 11400 14400 16450 19000 KCCK / KCHK 018 KCCK / KCHK 024 KCCK / KCHK 030 KCCK / KCHK 036 KCCK / KCHK 048 KCCK / KCHK 060 KCCK / KCHK 070 KCCK / KCHK 080 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll 1 / Scroll Max Min 2600 2500 3150 3100 3400 4950 4950 5900 1800 1750 2000 2000 2400 3750 3750 4350 Pa (2) 70 90 100 100 90 120 120 150 Capillary Capillary OUTDOOR UNIT COMPRESSOR Nr / Type FAN Air flow m3/h. Available static pressure EXPANSION (cooling only / heat pump) Capillary Restrictor Restrictor Restrictor --/Restrictor --/Restrictor Cooling only units Kg 73 76 87 87 135 180 185 195 Heat pump units Kg 78 81 92 92 140 185 190 200 (H) mm 485 485 505 505 495 595 595 595 Width (W) mm 975 975 1050 1050 1250 1300 1300 1450 Depth (D) mm 625 625 750 750 820 830 830 WEIGHT DIMENSIONS Height PACKING DIMENSIONS (HxWxD) mm REFRIGERANT COUPLING Liquid pipe 655x1059x725 675x1140x870 625x1350 x919 720x1400x929 900 720x1550 x1000 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" 5/8" 5/8" 3/4" 3/4" 3/4" 7/8" 7/8" LNXO 018 LNXO 024 LNXO 030 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 Max 915 1200 1350 1725 2150 2450 3600 3950 Min 600 740 920 1000 1630 2060 2500 2900 Pa 60 60 100 120 100 100 160 140 -- -- -- -- -- -- Kg 35 35 43 44 57 58 85 86 mm 235 235 287 287 315 315 415 415 Width mm 1076 1076 1076 1076 1271 1271 1380 1380 Depth mm 535 535 700 700 750 750 850 850 Gas pipe INDOOR UNIT FAN Air flow m3/h. Available pressure max (2) EXPANSION WEIGHT DIMENSIONS Height PACKING DIMENSIONS (HxWxD) mm REFRIGERANT COUPLING Liquid pipe Gas pipe 235x1170x665 290x1170x830 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 1/2" 1/2" 1/2" 5/8" 5/8" 3/4" 3/4" 3/4" 7/8" 7/8" (*) Air intake temperature indoor interchange: 27°C DB / 19°C WB (*) Air intake temperature outdoor interchange: 35ºC DB (**) Air intake temperature indoor interchange: 20°C DB / 12ºC WB (**) Air intake temperature outdoor interchange: 7°C DB / 6ºC WB (2) With minimum admissible flow volumes and high speed fan 5 320x1365x875 Restrictor Restrictor 555x1460x975 DB.- Dry bulb WB.- Wet bulb 1.- UNIT SELECTION SET WITH AXIAL FAN OUTDOOR UNIT 1.4.- TECHNICAL DATA NJCK NJHK 018 SOUND LEVELS NJCK NJHK 024 NJCK NJHK 030 NJCK NJHK 036 NJCK NJHK 048 NJCK NJHK 060 NJCK NJHK 070 NJCK NJHK 080 44 47 47 50 47 47 NJCK NJHK 070 NJCK NJHK 080 dBA 34 37 37 38 37 40 Sound Indoor unit (1) High pressure (Lp) 38 40 40 42 40 43 Low dBA level 36 42 43 43 46 46 Outdoor unit (2) dBA (1) Sound pressure level measured to a distance of 2,5m from the unit, free space. (2) Sound pressure level measured to a distance of 10m from the unit, free space, directibility ±3db. 1.5.- ELECTRICAL DATA NJCK NJHK 018 Voltage V/f (50 Hz) NJCK NJCK NJHK NJHK 024 030 230V / 1 Ph NJCK NJHK 036 NJCK NJHK 048 230V-400V / 3 Ph 400V/3Ph (3) Nominal total input power cooling capacity Nominal total input power heat pump NJHK Max. current Kw 1,95 2,50 3,00 3,60 4,20 5,30 6,20 7,20 Kw 1,85 2,38 2,90 3,35 4,20 4,90 5,90 6,70 230V-1Ph 12,31 16,25 19,39 21,11 8,29 19,21 9,71 23,08 12,48 23,77 15,37 28,19 18,39 31,99 20,69 76 95 40 91 / 46 98 / 50 133 / 66 172 / 74 178 / 101 KJCK KJHK 030 KJCK KJHK 036 KJCK KJHK 048 KJCK KJHK 060 KJCK KJHK 070 KJCK KJHK 080 A 230V-3Ph 400V-3Ph 47 Starting current 61 A KJCK KJHK 018 OUTDOOR UNIT KJCK KJHK 024 230V / 1 Ph Voltage V/f (50 Hz) 230V-400V / 3 Ph 400V/3Ph (3) Nominal total input power cooling capacity Nominal total input power heat pump KJHK Max. current A Starting current Kw 1,83 2,33 2,68 3,22 3,69 4,77 5,57 6,50 Kw 1,73 2,21 2,58 2,97 3,69 4,37 5,27 6,00 230V-1Ph 11,79 15,52 18,02 19,44 6,92 17,54 8,04 20,85 10,25 21,45 13,05 25,45 15,65 28,95 17,65 76 95 40 91 / 46 98 / 50 133 / 66 172 / 74 178 / 101 LNXO 030 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 230V-3Ph 400V-3Ph A 47 LNXO 018 INDOOR UNIT Voltage NJCK NJHK 060 61 LNXO 024 V/f (50 Hz) Nominal total input power cooling capacity Nominal total input power heat pump Max. current Starting current 230V / 1 Ph Kw 0,12 0,17 0,32 0,38 0,51 0,53 0,63 0,70 Kw 0,12 0,17 0,32 0,38 0,51 0,53 0,63 0,70 A 0,52 0,73 1,37 1,67 2,23 2,32 2,74 3,04 A 2,08 2,92 5,48 6,68 8,92 9,28 10,96 12,16 (3) Voltage only for cooling only unit NJCK 6 1.- UNIT SELECTION SET WITH CENTRIFUGAL FAN OUTDOOR UNIT 1.4.- TECHNICAL DATA NCCK NCHK 018 SOUND LEVELS NCCK NCHK 024 NCCK NCHK 030 NCCK NCHK 036 NCCK NCHK 048 NCCK NCHK 060 NCCK NCHK 070 NCCK NCHK 080 dBA 34 37 37 38 37 40 44 47 Sound Indoor unit (1) High pressure (Lp) 38 40 40 42 40 43 47 50 dBA Low level 40 40 41 41 43 45 45 49 dBA Outdoor unit (2) (1) Sound pressure level measured to a distance of 2,5m from the unit. (2) Sound pressure level measured to a distance of 10m from the unit, free space, with discharge and inlet plenum installed. 1.5.- ELECTRICAL DATA NCCK NCHK 018 Voltage Max. current NCCK NCHK 030 NCCK NCHK 036 NCCK NCHK 048 NCCK NCHK 060 NCCK NCHK 070 NCCK NCHK 080 230V / 1 Ph V/f (50 Hz) Nominal total input power cooling capacity Nominal total input power heat pump NCHK NCCK NCHK 024 230V-400V / 3 Ph Kw 2,02 2,60 3,30 3,87 4,70 5,80 6,72 7,84 Kw 2,06 2,54 3,23 3,50 4,20 5,65 6,03 7,30 230V-1Ph 13,62 17,23 21,77 23,37 24,63 14,03 27,02 16,62 30,84 19,04 37,24 22,84 91 / 46 98 / 50 133 / 66 172 / 74 178 / 101 KCCK KCHK 036 KCCK KCHK 048 KCCK KCHK 060 KCCK KCHK 070 KCCK KCHK 080 A 230V-3Ph 400V-3Ph Starting current A 21,47 11,97 47 KCCK KCHK 018 OUTDOOR UNIT 61 76 KCCK KCHK 024 KCCK KCHK 030 95 230V / 1 Ph Voltage V/f (50 Hz) Nominal total input power cooling capacity Nominal total input power heat pump KCHK Max. current A Starting current Kw 1,90 2,43 2,98 3,49 4,19 5,27 6,09 7,14 Kw 1,94 2,37 2,91 3,12 3,69 5,12 5,40 6,60 230V-1Ph 13,10 16,50 20,40 21,70 22,40 11,80 24,70 14,30 28,10 16,30 34,20 19,80 91 / 46 98 / 50 133 / 66 172 / 74 178 / 101 LNXO 036 LNXO 048 LNXO 060 LNXO 070 LNXO 080 230V-3Ph 400V-3Ph A 19,80 10,30 47 LNXO 018 INDOOR UNIT Voltage 230V-400V / 3 Ph 61 76 LNXO 024 LNXO 030 V/f (50 Hz) Nominal total input power cooling capacity Nominal total input power heat pump 95 230V / 1 Ph Kw 0,12 0,17 0,32 0,38 0,51 0,53 0,63 0,70 Kw 0,12 0,17 0,32 0,38 0,51 0,53 0,63 0,70 Max. current A 0,52 0,73 1,37 1,67 2,23 2,32 2,74 3,04 Starting current A 2,08 2,92 5,48 6,68 8,92 9,28 10,96 12,16 7 1.- UNIT SELECTION 1.6.- MOTOR-FAN CHARACTERISTICS INDOOR UNIT MOTOR-FAN LNXO 018 m3/h HIGH SPEED MEDIUM SPEED LOW SPEED m3/h HIGH SPEED MEDIUM SPEED LOW SPEED m3/h HIGH SPEED MEDIUM SPEED LOW SPEED m3/h HIGH SPEED MEDIUM SPEED LOW SPEED m3/h HIGH SPEED LOW SPEED AIR FLOW m3/h HIGH SPEED LOW SPEED LNXO 070 AIR FLOW m3/h HIGH SPEED LOW SPEED m3/h HIGH SPEED LOW SPEED AIR FLOW LNXO 024 AIR FLOW LNXO 030 AIR FLOW LNXO 036 AIR FLOW LNXO 048 AIR FLOW LNXO 060 LNXO 080 AIR FLOW 0 ----750 0 ----915 0 ----1180 0 ----1155 0 ----0 ----0 ----0 ----- AVAILABLE STATIC PRESSURE 20 40 60 80 100 120 915 760 600 ------------820 680 --680 600 --------20 40 60 80 100 120 1200 1050 890 ------1050 890 740 ------------830 740 --20 40 60 80 100 120 --- 1300 1200 1100 920 --1215 1100 1000 ------1130 1000 --------20 40 60 80 100 120 --- 1700 1625 1530 1370 1150 1350 1270 1180 1070 ----1120 1050 --------20 40 60 80 100 120 --- 2150 2050 1950 1800 1630 1765 1700 1630 ------20 40 60 80 100 120 --- 2450 2400 2300 2160 --2155 2115 2060 ------20 40 60 80 100 120 --- 3600 3400 3225 3050 2850 3425 3250 3100 2900 2700 2500 20 40 60 80 100 120 --- 3950 3750 3600 3450 3250 3425 3250 3100 2900 ----- Pa 140 ------140 ------140 ------140 ------140 ----140 ----140 2675 --140 3050 --- 160 ------160 ------160 ------160 ------160 ----160 ----160 2500 --160 ----- --- Out of fan working limits OUTDOOR UNIT CENTRIFUGAL FAN AVAILABLE STATIC PRESSURE Pa MODELS 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 KCCK 018 KCHK 018 2600 2500 2400 2350 2300 2200 2150 1800 ------------------- KCCK 024 KCHK 024 2500 2400 2350 2300 2200 2150 2050 1950 1870 1750 --------------- KCCK 030 KCHK 030 3150 3000 2825 2700 2600 2525 2450 2350 2250 2125 2000 ------------- AIR FLOW KCCK 036 KCHK 036 3100 2900 2800 2700 2600 2500 2400 2300 2200 2100 2000 ------------- NOMINAL FLOW 8 m3/h KCCK 048 KCHK 048 3400 3325 3160 3075 2980 2890 2790 2690 2580 2400 --------------- KCCK 060/070 KCHK 060/070 4950 4850 4750 4625 4525 4425 4325 4225 4125 4040 3940 3840 3750 --------- KCCK 080 KCHK 080 5900 5800 5700 5600 5495 5390 5280 5180 5075 4975 4875 4775 4675 4575 4460 4350 --- 1.- UNIT SELECTION 1.7.- COOLING CAPACITIES SET WITH AXIAL FAN OUTDOOR UNIT NJCK / NJHK 018 AIR INLET CAPACITY TEMPERATURE POWER INPUT INDOOR UNIT IN kW 25°C 30°C 35°C TOTAL CAPACITY 4,67 4,51 4,33 21°C DB 15°C WB 24°C DB 17°C WB 27°C DB 19°C WB 29°C DB 21°C WB 32°C DB 23°C WB SENSIBLE CAP. 3,39 POWER INPUT 3,31 NJCK / NJHK 024 3,22 40°C 4,13 45°C 3,92 25°C 6,08 30°C 35°C 45°C 5,10 30°C 35°C 40°C 45°C 5,64 40°C 5,39 25°C 5,87 7,11 6,86 6,29 3,12 3,01 4,46 4,35 4,24 4,11 3,98 5,18 5,05 6,59 4,92 4,77 5,97 4,61 3,64 1,52 1,69 1,87 2,09 2,35 2,00 2,21 2,45 2,73 3,06 2,41 2,65 2,93 3,25 TOTAL CAPACITY 5,01 4,83 4,64 4,43 4,20 6,52 6,30 6,05 5,78 5,48 7,63 7,36 7,08 6,76 6,41 SENSIBLE CAP. 3,61 1,54 3,52 1,71 3,43 1,90 3,34 2,12 4,53 2,48 4,40 2,76 4,27 3,10 5,00 4,76 3,54 2,15 5,10 3,44 2,42 --- 5,39 2,68 7,91 5,72 2,71 8,49 5,26 2,96 7,60 5,60 3,00 8,16 4,95 3,68 6,89 5,27 1,57 TOTAL CAPACITY 5,76 3,65 1,95 5,34 5,52 2,43 8,19 5,85 5,11 3,29 3,73 1,73 5,56 4,75 2,02 7,00 5,04 4,65 2,23 5,18 3,23 2,39 4,51 7,80 7,40 3,82 1,59 3,73 1,76 3,64 1,96 3,54 2,19 --- TOTAL CAPACITY 6,17 5,96 5,72 POWER INPUT TOTAL CAPACITY 5,37 SENSIBLE CAP. 3,82 POWER INPUT SENSIBLE CAP. POWER INPUT SENSIBLE CAP. POWER INPUT 4,01 1,61 3,93 1,79 3,84 1,99 WB 24°C DB 17°C WB 27°C DB 19°C WB 29°C DB 21°C WB 32°C DB 23°C WB SENSIBLE CAP. 6,32 POWER INPUT 2,82 6,50 6,20 5,88 2,05 7,50 4,93 2,26 7,24 4,80 2,50 6,96 4,68 2,80 6,65 4,54 3,15 6,30 2,46 8,80 4,92 2,30 4,80 --- 5,03 2,08 2,55 4,68 2,85 4,53 3,19 5,85 2,50 5,72 2,75 5,58 3,04 5,43 3,38 5,27 3,78 5,47 --- 8,04 7,76 7,46 7,12 --- 9,44 9,11 8,76 8,37 --- 3,74 2,23 --- 5,30 6,16 6,03 5,89 5,74 --- --- 2,11 4,94 2,89 ----- 2,53 2,79 3,09 3,43 --- POWER INPUT 40°C 45°C 25°C 30°C 35°C 40°C 45°C 25°C 30°C 40°C 45°C 7,84 6,02 7,50 5,86 7,11 10,46 10,12 9,76 9,36 8,92 12,33 5,68 7,81 7,64 7,46 7,27 7,06 9,18 11,91 11,46 10,99 8,97 8,75 8,52 10,48 8,28 3,12 8,76 6,62 3,16 3,46 3,83 4,24 3,49 6,17 11,23 8,35 3,51 4,14 10,49 8,00 4,18 5,63 7,64 6,11 4,30 4,98 9,60 7,59 5,03 4,69 8,06 6,30 3,88 4,53 10,07 7,81 4,57 4,29 8,43 6,46 3,50 3,80 10,88 8,18 3,83 13,27 9,82 4,36 9,41 7,04 9,10 6,90 8,66 6,72 3,94 8,21 6,52 12,07 8,87 11,69 8,70 10,83 8,33 10,32 8,11 14,27 10,44 12,82 12,34 11,83 9,61 9,39 9,16 4,77 5,23 5,73 13,79 13,30 12,73 10,23 10,00 9,77 4,86 5,30 5,83 11,29 8,91 6,27 12,14 9,52 6,39 POWER INPUT 6,88 2,95 TOTAL CAPACITY 11,21 3,26 10,84 3,61 10,43 SENSIBLE CAP. 7,43 7,27 3,32 3,67 9,30 4,36 8,80 3,53 3,85 4,61 5,08 12,97 8,86 3,55 12,56 12,13 11,64 11,10 4,45 15,34 8,52 4,24 8,32 4,65 8,10 5,13 10,44 4,53 14,83 14,29 13,70 10,23 10,01 9,77 4,95 5,42 5,94 13,06 8,70 3,88 13,93 13,50 13,03 12,51 11,92 16,48 15,94 15,36 14,73 --- 7,10 --- 9,36 9,19 9,01 8,82 8,60 11,03 --- 4,06 --- 3,58 3,91 4,28 4,70 5,18 4,63 10,82 10,59 10,35 5,05 5,53 6,06 4,42 --- NJCK / NJHK 080 24°C DB 17°C WB 27°C DB 19°C WB 29°C DB 21°C WB 32°C DB 23°C WB 11,23 10,97 10,69 10,41 10,12 POWER INPUT 5,00 6,00 6,59 7,24 TOTAL CAPACITY 16,35 15,79 15,20 14,59 13,94 12,45 12,16 11,85 11,52 11,15 5,70 6,27 7,65 6,92 8,47 18,03 17,41 16,74 16,01 15,18 11,98 11,72 11,44 11,16 10,86 13,31 5,08 5,56 6,09 6,68 7,35 5,82 POWER INPUT TOTAL CAPACITY 17,54 16,93 16,30 15,65 14,97 19,38 SENSIBLE CAP. 12,70 12,44 12,20 11,87 11,58 14,14 13,02 12,71 12,37 12,00 6,40 7,05 7,78 8,61 SENSIBLE CAP. POWER INPUT 5,17 5,65 TOTAL CAPACITY 18,81 18,17 SENSIBLE CAP. 12,69 12,42 5,26 5,75 POWER INPUT 6,20 6,79 7,46 5,95 17,50 16,79 16,06 20,83 12,14 11,85 11,56 14,14 6,10 6,30 6,91 7,59 18,72 18,00 17,21 16,33 13,85 13,50 13,19 12,81 6,54 7,20 7,94 8,76 20,12 19,36 18,51 --13,85 13,53 13,18 --6,69 8,10 7,36 --- TOTAL CAPACITY 20,17 19,48 18,76 18,01 17,22 22,38 21,62 20,79 19,88 --- 13,37 13,10 12,82 12,53 12,24 14,93 5,37 5,86 6,41 7,03 7,72 6,26 14,63 14,31 13,96 7,54 6,87 8,29 --- SENSIBLE CAP. POWER INPUT 9,51 6,51 6,51 SENSIBLE CAP. 5,47 5,14 6,70 4,00 9,97 NJCK / NJHK 070 WB 35°C 11,30 8,50 4,20 AIR INLET CAPACITY AIR INLET TEMPERATURE OUTDOOR UNIT ºC DRY BULB TEMPERATURE POWER INPUT INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C 12,98 13,59 15,24 14,71 14,16 16,77 TOTAL CAPACITY 16,19 15,57 14,88 14,11 21°C DB 15°C NJCK / NJHK 060 35°C 3,60 9,72 3,00 NJCK / NJHK 048 30°C 3,21 TOTAL CAPACITY 10,45 10,11 SENSIBLE CAP. 7,18 7,03 POWER INPUT 5,07 2,59 8,15 6,18 7,18 2,90 7,57 5,19 2,33 3,73 AIR INLET TEMPERATURE OUTDOOR UNIT ºC DRY BULB TOTAL CAPACITY 9,06 SENSIBLE CAP. 6,76 2,86 POWER INPUT TOTAL CAPACITY 9,73 SENSIBLE CAP. 7,26 5,43 3,33 6,75 NJCK / NJHK 036 AIR INLET CAPACITY TEMPERATURE POWER INPUT INDOOR UNIT IN kW 25°C TOTAL CAPACITY 8,43 21°C DB 15°C NJCK / NJHK 030 AIR INLET TEMPERATURE OUTDOOR UNIT ºC DRY BULB --- --- CALCULATION OF COOLING CAPACITY DEPENDING ON AIR FLOW Data based on the following nominal indoor fan air flow: MODELS 018 024 030 036 048 060 070 080 INDOOR AIR FLOW 800 1100 1250 1650 2050 2400 3400 3750 M3/H CORRECTION COEFFICIENT TO FIX TO THE CAPACITY OF DIFFERENT INDOOR AIR FLOW: % NOMINAL AIR FLOW 70% 80% 90% 100% Total capacity 0,96 0,97 0,98 1 Sensible capacity Power input 0,9 0,98 0,93 0,96 0,99 1 1 1 Data based on the following nominal outdoor fan air flow: MODELS 018 024 030 036 048 060 070 080 DB - Dry bulb WB - Wet bulb Nominal capacities 9 OUTDOOR AIR FLOW 1800 2800 3100 3200 5500 5500 5200 5200 M3/H 1.- UNIT SELECTION 1.7.- COOLING CAPACITIES SET WITH CENTRIFUGAL FAN OUTDOOR UNIT NCCK / NCHK 018 NCCK / NCHK 024 NCCK / NCHK 030 AIR INLET CAPACITY TEMPERATURE POWER INPUT INDOOR UNIT IN kW 25°C 4,75 TOTAL CAPACITY 21°C DB 30°C 4,59 35°C 4,42 40°C 4,24 45°C 4,03 25°C 6,17 30°C 35°C 45°C 5,21 30°C 35°C 40°C 45°C 5,73 40°C 5,48 25°C 5,96 7,15 6,90 6,35 3,43 3,35 3,26 3,17 3,07 4,50 4,40 4,28 4,16 4,03 5,20 5,07 6,64 4,94 4,80 6,02 4,64 15°C 24°C WB DB 17°C WB 27°C DB 19°C 29°C 21°C 32°C 23°C WB DB WB DB WB SENSIBLE CAP. AIR INLET TEMPERATURE OUTDOOR UNIT ºC DRY BULB POWER INPUT 1,67 1,81 1,98 2,18 2,41 2,12 2,32 2,54 2,81 3,13 2,72 2,95 3,22 3,53 3,90 TOTAL CAPACITY 5,10 4,93 4,75 4,55 4,34 6,62 6,39 6,15 5,89 5,59 7,68 7,41 7,13 6,82 6,48 3,65 SENSIBLE CAP. 1,68 POWER INPUT TOTAL CAPACITY 5,47 SENSIBLE CAP. 3,87 3,57 1,83 3,48 2,00 3,39 2,20 3,29 2,43 4,66 4,80 2,14 4,69 2,34 4,58 2,57 4,45 2,84 4,32 3,16 5,54 2,75 5,42 2,98 5,28 3,25 5,14 3,57 4,98 3,94 6,86 6,60 6,32 6,01 4,85 2,60 7,08 4,74 2,87 6,78 4,60 3,19 8,25 5,87 7,97 5,75 3,01 7,33 5,46 3,60 6,96 5,30 8,56 7,70 5,60 3,30 8,23 7,88 7,49 4,59 3,23 --- 5,87 2,80 5,74 3,04 5,61 3,32 5,46 3,64 5,30 4,03 9,51 9,19 8,84 8,46 --- --- 6,19 6,06 5,92 5,77 --- --- 2,83 3,08 3,36 3,69 --- 5,29 5,10 4,89 3,70 2,02 5,48 3,60 2,22 5,25 3,50 7,10 5,08 1,69 5,88 3,78 1,84 5,69 2,45 --- 2,16 7,62 4,98 2,36 7,36 3,78 1,86 3,70 2,04 3,60 2,24 ----- 5,08 2,19 4,97 2,39 4,86 POWER INPUT 3,87 1,71 2,63 4,73 2,91 TOTAL CAPACITY 6,31 6,10 5,88 5,64 --- 8,17 7,90 7,60 7,28 SENSIBLE CAP. 4,07 1,72 3,99 1,88 3,90 2,06 3,80 2,26 --- 5,35 --- 2,21 POWER INPUT TOTAL CAPACITY SENSIBLE CAP. POWER INPUT NCCK / NCHK 036 AIR INLET CAPACITY TEMPERATURE POWER INPUT INDOOR UNIT IN kW 25°C 21°C DB 15°C WB 24°C DB 17°C WB 27°C DB 19°C WB 29°C DB 21°C WB 32°C DB 23°C WB 5,24 2,42 5,12 2,66 5,00 2,95 NCCK / NCHK 048 15°C WB 24°C DB 17°C WB 27°C DB 19°C WB 29°C DB 21°C WB 32°C DB 23°C WB 3,98 NCCK / NCHK 060 30°C 35°C 40°C 45°C 25°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C TOTAL CAPACITY 8,40 6,30 SENSIBLE CAP. 8,11 7,45 5,84 7,06 10,29 9,93 9,54 9,11 8,62 12,50 12,08 6,16 7,80 6,00 5,65 7,72 7,55 7,36 7,15 6,91 9,27 9,06 11,63 11,17 8,84 8,61 10,67 8,37 3,15 3,44 3,77 4,14 4,54 3,88 4,21 4,58 5,00 5,50 5,21 5,64 TOTAL CAPACITY 9,02 8,71 8,38 8,01 11,04 10,66 10,24 9,78 9,25 13,01 12,53 12,03 11,49 SENSIBLE CAP. 6,60 3,49 9,36 7,02 6,44 6,27 4,19 8,60 6,69 4,25 7,58 6,08 4,83 13,45 8,26 8,08 7,89 7,67 7,44 4,60 8,14 6,49 3,92 11,84 8,77 4,25 11,43 8,59 5,07 10,49 8,18 5,57 9,91 7,94 9,91 4,89 14,47 10,54 3,96 4,30 5,14 5,65 9,25 6,20 13,50 12,96 10,10 9,87 5,80 6,29 9,01 6,72 12,38 9,62 6,82 12,70 12,27 8,76 8,58 4,01 4,36 11,79 11,25 10,62 4,97 15,57 9,70 5,28 14,00 10,32 5,36 9,48 5,72 4,66 8,72 4,63 11,00 8,40 4,70 15,07 14,53 13,95 13,33 8,38 4,75 8,16 5,21 7,91 5,73 10,54 5,04 10,33 5,44 10,11 5,89 9,62 6,93 15,63 15,01 --- POWER INPUT 6,74 3,19 POWER INPUT TOTAL CAPACITY 9,69 7,16 SENSIBLE CAP. 3,24 POWER INPUT TOTAL CAPACITY 10,40 7,15 SENSIBLE CAP. 3,82 9,00 6,85 3,54 3,87 10,05 9,66 7,01 9,23 6,85 6,68 4,31 9,88 6,47 30°C 6,11 6,63 9,87 6,38 3,28 TOTAL CAPACITY 11,15 7,55 SENSIBLE CAP. 3,59 13,62 13,15 12,64 12,05 11,36 16,74 16,20 7,41 7,25 7,07 --- 9,24 9,06 8,86 8,64 8,39 11,13 10,92 10,70 10,46 --- POWER INPUT 3,65 3,99 4,37 --- 4,05 4,41 4,82 5,29 5,82 5,12 5,53 5,98 --- POWER INPUT 3,34 3,93 10,78 10,36 4,72 --- NCCK / NCHK 070 DB 2,77 8,86 AIR INLET TEMPERATURE OUTDOOR UNIT ºC DRY BULB NCCK / NCHK 080 AIR INLET CAPACITY AIR INLET TEMPERATURE OUTDOOR UNIT ºC DRY BULB TEMPERATURE POWER INPUT INDOOR UNIT IN kW 25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C 21°C 6,45 TOTAL CAPACITY 15,09 14,56 14,00 13,42 12,80 SENSIBLE CAP. 11,16 10,89 10,61 10,33 10,03 POWER INPUT 5,52 5,99 6,51 TOTAL CAPACITY 16,18 15,61 15,02 SENSIBLE CAP. 11,90 11,63 11,36 5,60 6,08 6,61 POWER INPUT TOTAL CAPACITY 17,34 16,73 16,10 SENSIBLE CAP. 12,62 12,35 12,10 5,70 6,18 6,72 POWER INPUT 7,10 7,76 14,40 13,74 11,07 10,77 7,21 7,88 15,44 14,74 11,78 11,48 7,33 8,00 TOTAL CAPACITY 18,59 17,94 17,26 16,55 15,81 SENSIBLE CAP. 12,60 12,32 12,04 11,75 11,46 5,80 6,29 6,84 7,46 8,14 POWER INPUT TOTAL CAPACITY 19,92 19,22 18,49 17,73 16,94 SENSIBLE CAP. 13,27 13,00 12,72 12,43 12,13 POWER INPUT Nominal capacities 5,92 6,41 6,97 7,60 8,29 6,48 CALCULATION OF COOLING CAPACITY DEPENDING ON AIR FLOW Data based on the following nominal indoor fan air flow: 16,97 16,40 15,79 12,55 12,27 11,96 15,12 11,64 14,38 11,28 6,47 7,00 7,60 18,25 17,64 16,99 8,29 9,06 16,28 15,49 12,50 8,41 17,53 13,33 8,54 12,14 9,18 16,68 12,96 9,31 18,87 --- 14,26 13,97 13,66 6,81 7,36 7,98 13,33 8,68 --- 22,70 21,96 21,17 20,29 --- MODELS 018 024 030 036 048 060 070 080 15,05 14,76 14,45 14,12 --- OUTDOOR AIR FLOW 2200 2150 2525 2500 2890 4425 4425 5390 M3/H 13,42 6,57 19,62 14,25 13,13 7,11 18,98 13,97 7,23 12,83 7,72 18,30 13,65 7,84 6,68 21,11 20,42 19,68 6,95 7,51 8,14 8,84 --- --- CORRECTION COEFFICIENT TO FIX TO THE CAPACITY OF DIFFERENT OUTDOOR AIR FLOW: DB - Dry bulb WB - Wet bulb MODELS 018 024 030 036 048 060 070 080 INDOOR AIR FLOW 800 1100 1250 1650 2050 2400 3400 3750 M3/H CORRECTION COEFFICIENT TO FIX TO THE CAPACITY OF DIFFERENT INDOOR AIR FLOW: % NOMINAL AIR FLOW 70% 80% 90% 100% Total capacity 0,96 0,97 0,98 1 Sensible capacity Power input 0,93 0,96 0,99 1 1 1 Data based on the following nominal outdoor fan air flow: % NOMINAL AIR FLOW 80% 90% 100% Total capacity 0,97 0,98 1 Sensible capacity Power input 10 0,9 0,98 0,93 0,96 0,99 1 1 1 1.- UNIT SELECTION 1.7.- HEATING CAPACITIES SET WITH AXIAL FAN OUTDOOR UNIT NJHK 018 AIR INLET TEMPERATURE INDOOR UNIT 15°C DB 18°C DB 20°C DB kW -10°C -5°C 0°C 6°C 10°C 14°C 18°C -10°C -5°C 0°C 6°C 10°C 14°C 18°C 5,34 6,06 6,89 8,06 8,95 9,94 11,02 Power input 1,39 1,46 1,54 1,67 1,77 1,90 2,05 1,82 1,90 2,00 2,15 2,27 2,42 2,61 2,24 2,34 2,47 2,65 2,81 3,00 3,23 Total capacity 3,39 3,86 4,39 5,13 5,70 6,33 7,02 4,30 4,89 5,56 6,50 7,22 8,03 8,92 5,35 6,07 6,89 8,03 8,91 9,88 10,94 Power input 1,47 1,55 1,64 1,77 1,88 2,02 2,18 1,93 2,02 2,12 2,28 2,41 2,58 2,77 2,36 2,47 2,61 2,81 2,98 Total capacity 3,40 3,86 4,39 5,15 5,69 6,31 6,99 4,31 4,89 5,56 6,50 7,21 8,01 8,88 5,36 6,07 6,89 8,00 8,89 9,85 10,89 Power input 1,53 1,61 1,71 1,85 1,97 2,11 2,28 3,45 3,90 4,41 5,12 --- 1,78 1,88 1,99 2,16 --- --- NJHK 036 kW -10°C -5°C Total capacity 6,08 Power input 2,53 Total capacity 6,08 Power input 2,68 Total capacity 6,09 Power input 2,79 Total capacity 6,12 Power input 3,02 Total capacity 6,16 Power input 3,21 kW 3,10 3,32 3,57 8,85 9,78 --- --- 2,17 2,27 2,40 2,59 2,74 2,93 3,15 2,65 2,78 2,94 3,18 3,37 3,61 --- --- 4,38 4,94 5,59 6,49 7,18 7,94 --- 5,42 6,12 6,91 8,00 8,83 --- --- --- 2,32 2,43 2,56 2,76 2,93 3,13 --- 2,82 2,96 3,13 3,39 3,60 --- --- NJHK 048 AIR INLET TEMPERATURE OUTDOOR UNIT ºC WET BULB 0°C 6°C 10°C 14°C 18°C -10°C -5°C 0°C 6°C 10°C 14°C 18°C -10°C -5°C 2,65 2,80 3,02 3,21 3,43 3,68 18°C DB 20°C DB 24°C DB 2,81 2,97 3,21 3,40 3,63 3,89 3,32 3,48 3,65 3,90 4,09 4,31 4,57 3,68 3,89 3,49 3,65 3,84 4,09 4,30 4,54 4,82 3,87 4,09 2,92 3,09 3,35 3,54 3,77 4,04 10°C 14°C 18°C 4,14 4,51 4,82 5,18 5,60 4,36 4,75 5,07 5,45 5,88 3,61 3,77 3,96 4,20 4,45 4,70 4,99 4,00 4,24 4,51 4,90 5,25 5,64 6,08 6,94 7,91 9,27 10,30 11,43 12,63 7,91 8,99 10,20 11,86 13,10 14,47 15,94 8,80 10,08 11,55 13,59 15,15 16,87 --- 3,17 3,35 3,61 3,83 4,07 4,35 5,62 6,03 --- 8,85 10,11 11,55 13,56 15,09 16,76 --- 3,65 3,92 --- 3,85 4,03 4,24 4,53 4,77 5,04 5,36 6,97 7,92 9,26 10,26 11,35 --- 7,92 8,99 10,18 11,81 13,03 14,35 --- 3,37 3,56 3,84 4,06 4,31 --- --- 4,05 4,24 4,46 4,78 5,03 5,32 4,28 4,53 NJHK 070 NJHK 080 AIR INLET TEMPERATURE OUTDOOR UNIT ºC WET BULB -10°C -5°C 0°C 6°C 10°C 14°C 18°C -10°C -5°C 0°C Power input 4,49 4,72 5,00 6°C 10°C 14°C 18°C 5,41 5,75 6,14 6,60 4,96 5,24 5,58 6,07 6,49 Power input 4,72 4,98 5,27 5,71 6,05 6,46 6,94 5,25 5,55 5,91 6,43 6,87 6,98 7,58 7,38 8,00 Total capacity 10,90 12,47 14,24 16,70 18,56 20,62 22,89 11,56 13,36 15,38 18,20 20,37 22,78 25,44 Power input 4,89 5,15 5,46 5,90 6,27 6,69 7,18 5,46 5,78 6,15 6,70 7,14 7,67 8,29 Total capacity 10,85 12,42 14,17 16,60 18,43 20,45 22,66 11,59 13,37 15,37 18,15 20,26 22,59 25,15 6,35 6,73 7,18 7,70 5,93 6,27 6,67 7,25 7,72 Total capacity 10,82 12,39 14,14 16,54 18,35 20,33 Power input 5,52 5,83 6,19 6,70 7,11 7,58 8,27 8,91 --- 11,63 13,40 15,39 18,11 20,18 22,45 --- --- 6,32 6,68 7,10 7,70 8,19 --- 8,76 CALCULATION OF HEATING CAPACITY DEPENDING ON AIR FLOW Data based on the following nominal indoor fan air flow: Data based on the following nominal outdoor fan air flow: MODELS 018 024 030 036 048 060 070 080 MODELS 018 024 030 036 048 060 070 080 INDOOR AIR FLOW 800 1100 1250 1650 2050 2400 3400 3750 M3/H CORRECTION COEFFICIENT TO FIX TO THE CAPACITY OF DIFFERENT INDOOR AIR FLOW: % NOMINAL AIR FLOW 70% 80% 90% 100% Total capacity 0,96 0,97 0,98 1 OUTDOOR AIR FLOW 1800 2800 3100 3200 5500 5500 5200 5200 M3/H 0,9 0,98 0,93 0,96 0,99 1 1 1 11 4,83 4,24 5,27 4,70 5,07 5,49 Nominal capacities Total capacity 10,93 12,50 14,27 16,75 18,63 20,72 23,01 11,56 13,36 15,39 18,24 20,43 22,87 25,57 Sensible capacity Power input 6°C 6,92 7,90 9,30 10,35 11,52 12,78 7,91 9,00 10,23 11,90 13,21 14,62 16,15 8,77 10,07 11,56 13,60 15,24 17,00 18,93 Power input 5,24 5,53 5,87 27°C DB 0°C 6,92 7,90 9,30 10,38 11,57 12,85 7,91 9,01 10,25 11,96 13,26 14,69 16,26 8,77 10,07 11,57 13,67 15,28 17,07 19,02 Total capacity 10,98 12,54 14,33 16,83 18,74 20,86 23,20 11,57 13,37 15,42 18,30 20,52 23,00 25,77 15°C DB NJHK 060 6,91 7,90 9,32 10,42 11,63 12,95 7,91 9,03 10,28 12,02 13,34 14,80 16,40 8,78 10,08 11,59 13,72 15,35 17,17 19,17 27°C DB AIR INLET TEMPERATURE INDOOR UNIT 2,45 2,57 2,71 2,90 5,39 6,09 6,89 8,01 1,67 1,75 1,86 2,02 2,15 2,30 Power input AIR INLET TEMPERATURE INDOOR UNIT 2,00 2,10 2,21 2,38 2,52 2,69 2,89 --- Total capacity 3,18 3,43 4,35 4,92 5,57 6,49 7,19 7,96 8,81 3,42 3,88 4,40 5,12 5,67 6,27 --- 27°C DB 24°C DB 6°C 10°C 14°C 18°C 4,29 4,88 5,56 6,51 7,25 8,07 8,98 Power input 20°C DB 0°C 3,39 3,86 4,39 5,15 5,72 6,37 7,07 24°C DB 18°C DB -10°C -5°C NJHK 030 Total capacity Total capacity 15°C DB NJHK 024 AIR INLET TEMPERATURE OUTDOOR UNIT ºC WET BULB DB - Dry bulb WB - Wet bulb 1.- UNIT SELECTION 1.7.- HEATING CAPACITIES SET WITH CENTRIFUGAL FAN OUTDOOR UNIT NCHK 018 AIR INLET TEMPERATURE INDOOR UNIT 15°C DB 18°C DB 20°C DB kW NCHK 024 AIR INLET TEMPERATURE OUTDOOR UNIT ºC WET BULB -10°C -5°C 0°C 6°C 10°C 14°C 18°C -10°C -5°C 0°C NCHK 030 6°C 10°C 14°C 18°C -10°C -5°C 0°C 6°C 10°C 14°C 18°C 6,89 7,66 8,51 9,45 5,59 6,35 7,23 8,45 9,38 10,40 11,52 2,32 2,45 2,60 2,79 2,61 2,72 2,85 3,04 3,20 3,39 6,86 7,62 8,46 9,37 5,59 6,35 7,21 8,42 9,33 10,33 11,43 2,08 2,17 2,28 2,45 2,59 2,75 2,95 2,74 2,85 2,99 3,19 3,37 3,57 Total capacity 3,57 4,06 4,62 5,40 5,98 6,62 7,32 4,53 5,15 5,86 6,85 7,60 8,42 9,32 5,60 6,35 7,21 8,40 9,30 10,29 11,37 Power input 1,75 1,82 1,92 2,06 2,18 2,33 2,50 Total capacity 3,56 4,06 4,63 5,43 6,03 6,70 7,42 4,52 5,16 5,88 Power input 1,61 1,68 1,76 1,89 1,99 2,12 2,27 1,97 2,06 2,16 Total capacity 3,57 4,06 4,62 5,41 6,00 6,65 7,36 4,53 5,15 5,87 Power input 1,69 1,76 1,85 1,99 2,10 2,24 2,40 3,62 3,82 2,15 2,25 2,36 2,54 2,69 2,86 3,07 2,83 2,94 3,09 3,23 3,49 3,70 3,96 Total capacity 3,59 4,07 4,62 5,37 5,94 6,57 --- 4,55 5,17 5,86 6,83 7,56 8,36 9,22 5,62 6,36 7,20 8,37 9,25 10,21 --- Power input 1,87 1,96 2,07 2,23 2,36 2,52 --- 2,31 2,42 2,55 2,75 2,91 3,10 3,32 3,02 3,15 3,31 3,55 3,75 3,99 --- 4,58 5,18 5,87 6,82 7,53 8,31 --- 5,65 6,38 7,21 8,35 9,21 --- --- 2,92 3,09 3,30 --- 3,51 3,77 3,98 --- --- 24°C DB Total capacity 3,60 4,08 4,62 5,37 --- --- --- Power input 1,98 2,08 2,19 2,37 --- --- --- 27°C DB NCHK 036 AIR INLET TEMPERATURE INDOOR UNIT kW -10°C -5°C 0°C 2,45 2,57 2,71 3,19 3,33 NCHK 048 AIR INLET TEMPERATURE OUTDOOR UNIT ºC WET BULB 6°C 10°C 14°C 18°C -10°C -5°C 0°C 6°C NCHK 060 10°C 14°C 18°C -10°C -5°C 0°C 6°C 10°C 14°C 18°C Total capacity 6,05 6,87 7,85 9,26 10,35 11,56 12,88 7,57 8,63 9,82 11,48 12,75 14,17 15,73 9,26 10,65 12,26 14,50 16,22 18,11 20,17 15°C DB 18°C DB 20°C DB 24°C DB Power input 2,75 2,86 2,99 3,20 3,36 3,56 3,79 3,38 3,52 3,68 3,91 4,41 4,62 4,88 Power input 2,89 3,01 3,15 3,36 3,54 3,75 3,99 3,54 3,69 3,86 4,09 4,28 4,49 4,75 4,60 4,82 5,09 Power input 2,99 3,11 3,26 3,50 3,67 3,88 4,13 3,65 3,81 3,98 4,20 4,42 4,64 4,91 4,73 4,96 5,24 4,72 4,97 5,26 5,00 5,25 5,55 24°C DB 5,81 6,19 6,62 5,65 5,98 6,37 6,00 6,81 --- 6,35 6,75 --- --- 7,63 8,64 9,78 11,34 12,53 13,83 --- 9,30 10,63 12,16 14,27 15,86 17,59 --- Power input 3,38 3,52 3,69 3,95 4,15 4,38 --- 4,08 4,25 4,45 4,74 --- 5,21 5,48 5,80 --- kW 4,97 5,24 NCHK 070 NCHK 080 AIR INLET TEMPERATURE OUTDOOR UNIT ºC WET BULB -10°C -5°C 0°C 6°C 10°C 14°C 18°C -10°C -5°C 0°C Power input 4,74 4,96 5,21 5,57 5,87 Total capacity 10,78 12,31 14,05 16,49 18,36 20,43 22,72 12,07 13,96 16,09 19,07 21,34 23,88 26,67 Power input 4,96 5,19 5,45 5,84 6,15 6,52 6,95 Power input 5,11 5,35 5,63 6,03 6,35 5,98 6,26 6,59 7,07 7,47 7,95 8,51 6,73 7,17 6,17 6,46 6,80 7,30 7,71 8,20 8,77 Total capacity 10,71 12,25 13,98 16,37 18,19 20,20 22,40 12,08 13,95 16,05 18,94 21,13 23,55 26,18 Power input 5,43 5,70 6,00 6,43 6,78 Power input 5,69 5,98 6,30 6,76 7,12 7,18 7,65 6,59 6,90 7,27 7,80 8,23 8,73 9,32 7,55 --- 12,12 13,97 16,04 18,88 21,02 23,37 --- --- 6,93 7,27 7,65 8,21 8,65 9,17 --- CALCULATION OF HEATING CAPACITY DEPENDING ON AIR FLOW Data based on the following nominal indoor fan air flow: Data based on the following nominal outdoor fan air flow: MODELS 018 024 030 036 048 060 070 080 MODELS 018 024 030 036 048 060 070 080 INDOOR AIR FLOW 800 1100 1250 1650 2050 2400 3400 3750 M3/H OUTDOOR AIR FLOW 2200 2150 2525 2500 2890 4425 4425 5390 M3/H CORRECTION COEFFICIENT TO FIX TO THE CAPACITY OF DIFFERENT INDOOR AIR FLOW: % NOMINAL AIR FLOW 70% 80% 90% 100% Total capacity 0,96 0,97 0,98 1 Sensible capacity Power input 0,9 0,98 0,93 0,96 0,99 1 1 1 CORRECTION COEFFICIENT TO FIX TO THE CAPACITY OF DIFFERENT OUTDOOR AIR FLOW: % NOMINAL AIR FLOW 80% 90% 100% Total capacity 0,97 0,98 1 Sensible capacity Power input 12 0,93 0,96 0,99 1 6,27 6,63 7,05 Nominal capacities 6°C 10°C 14°C 18°C 6,22 6,63 5,72 5,98 6,29 6,75 7,13 7,59 8,14 Total capacity 10,69 12,22 13,95 16,32 18,11 20,09 27°C DB 6,34 Total capacity 6,14 6,94 7,88 9,21 10,22 11,32 Total capacity 10,76 12,29 14,02 16,45 18,30 20,35 22,61 12,07 13,95 16,07 19,00 21,27 23,77 26,51 20°C DB 5,49 Total capacity 6,11 6,91 7,87 9,22 10,25 11,38 12,59 7,61 8,63 9,78 11,37 12,58 13,91 15,37 9,26 10,62 12,17 14,32 15,95 17,73 Total capacity 10,83 12,35 14,10 16,56 18,45 20,56 22,89 12,09 13,98 16,13 19,14 21,45 24,04 26,89 18°C DB 5,56 5,92 Total capacity 6,07 6,89 7,85 9,20 10,29 11,47 12,73 7,59 8,62 9,79 11,40 12,65 14,03 15,54 9,24 10,62 12,20 14,40 16,06 17,90 19,88 AIR INLET TEMPERATURE INDOOR UNIT 15°C DB 5,26 Total capacity 6,06 6,88 7,85 9,24 10,32 11,50 12,80 7,58 8,62 9,80 11,44 12,69 14,08 15,62 9,24 10,63 12,22 14,44 16,12 17,98 20,00 Power input 3,20 3,34 3,50 3,74 3,94 4,16 4,41 3,89 4,05 4,24 4,50 27°C DB 4,08 4,28 4,52 1 1 DB - Dry bulb WB - Wet bulb 1.- UNIT SELECTION 1.8.- UNIT DIMENSIONS (mm) OUTDOOR UNIT WITH CENTRIFUGAL FAN Electrical box 975 36,5 24 45 ,5 34 5 41 0 Unit anchor support 530 78 Refrigerant connection valves 470 133 25 400 470 25 490 370 41,5 Refrigerant connection valves 410 78 Electrical box 1050 750 400 625 370 41,5 MODELS KCCK- 030-036 KCHK- 030-036 36,5 MODELS KCCK- 018-024 KCHK- 018-024 35 0 47 0 Unit anchor support 660 35 ,5 Refrigerant connection valves 1250 32 820 27 495 25 184 Drainage outside thread 3/4'' Male 1,6 71 452 Distance between holes:13 00 349 123 Refrigerant connection valves 1300 32 830 25 Electrical box Power supply connection Drainage outside thread 3/4'' Male 1,6 72 Detail drawing of unit anchor support 355 500 27 6 333 Unit anchor support 422 Distanc e betwe en hole s:1350 324 20 x12 Oval hole 123 50 25 40 249 Electrical box MODELS KCCK/ KCHK- 080 Refrigerant connection valves 36,5 900 25 25 Drainage outside thread 3/4'' Male 355 497 47 1450 595 MODELS KCCK- 060-070 KCHK- 060-070 Power supply connection 333 6 303 425 Unit anchor support Electrical box 595 MODELS KCCK/ KCHK- 048 Power supply connection 262 79 462 Distanc e betwe en hole s:1500 13 324 92 1 Unit anchor support 60 80 1.- UNIT SELECTION 1.8.- UNIT DIMENSIONS (mm) OUTDOOR UNIT WITH AXIAL FAN KJCK KJHK C B A B C A KJCK KJHK 018 KJCK KJHK 024 KJCK KJHK 030 773 629 333 773 629 333 973 781 333 KJCK KJHK 036 973 KJCK KJHK 048 973 KJCK KJHK 060 931 333 1239 1239 333 KJCK KJCK KJHK KJHK 070 080 998 1230 386 973 333 INDOOR UNIT LNXO 018-024-030-036-048-060 G A J D L A H C E F I C B K H I Ø INT. 20mm / Ø EXT. 25 mm INDOOR UNIT LNXO 070-080 B C C I E F J D K A G A L H Ø INT. 20mm / Ø EXT. 25 mm LNXO 018-024 LNXO 030-036 LNXO 048-060 LNXO 070-080 mm. mm. mm. mm. A B C D E F G H I J K L 1000 1000 1195 1300 535 700 750 850 235 287 315 415 880 880 1050 1060 153 203 228 275 40 40 40 121 60 60 72 120 885 885 1055 80 175 225 255 356 76 76 76 34 27 28 26 1240 58 58 70 30 14 998 1230 386 1.- UNIT SELECTION 1.9.- UNIT DESCRIPTION OUTDOOR UNIT KCCK/ KCHK 018-024-030-036 11 7 6 5 1 FAN 2 EXCHANGER 3 COMPRESSOR 4 ELECTRICAL BOX 4 3 10 4A Mod. 048-060-070 4B Mod. 080 5 2 14 ACCESS PANEL TO COMPRESSOR AND PIPE COMPONENTS 13 1 12 6 CONNECTION PIPE 7 ACCESS PANEL TO ELECTRICAL BOX 8 MAIN SWITCH (OPTIONAL, depending on model) 8B Mod. 080 8A Mod. 048-060-070 14 9 13 9 OUTDOOR UNIT KCCK/ KCHK 048-060-070-080 POWER SUPPLY ENTRY 9A Mod. 048-060-070 9B Mod. 080 6 10 DRAINAGE Models 018 to 036: Ø 16 EXTERIOR Models 048 to 080: OUTSIDE THREAD 3/4" MALE 10 11 INTAKE PRESSURE (Mod. 030-036) 1 13 14 12 CONDENSATE PUMP 13 DISCHARGE AIR 2 5 4B STANDARD POSITION 8A OPTIONAL POSITION 4A 3 7 14 INLET AIR STANDARD POSITION 8B OPTIONAL POSITION 5 9B 13 14 9A INDOOR UNIT LNXO 018-024-030-036-048-060 AIR INDOOR UNIT LNXO 070-080 8 1 2 AIR AIR 11 8 2 AIR 7 7 6 6 5 8 11 9 9 10 10 5 12 12 13B 6 8 AIR 2 1 6 AIR 7 8 AIR 2 1 AIR 7 13 13A 3 3 5 11 4 1 FAN-MOTOR 6 DRIP TRAY 2 EXCHANGER 7 DISCHARGE AIR ELECTRICAL BOX 8 INLET AIR STANDARD POSITION 3 4 5 CONNECTION PIPE DRAIN WITH ADAPTOR Ø20 mm INSIDE Ø25 mm OUTSIDE OPTIONAL POSITION (Mod. 018 to 060) 15 4 5 9 ACCESS PANEL TO FAN-MOTOR 10 AIR FILTER 11 ELECTRICAL HEATERS OR HOT WATER COILS (OPTIONS) 12 OUTDOOR AIR INTAKE 13 CONDENSATE PUMP (OPTIONAL) 13A Mod. 018-024 13B Mod. 030-036-048-060 1.- UNIT SELECTION 1.10.- OPERATING LIMITS OPERATING LIMITS FOR (COOLING ONLY) UNITS MAXIMUM TEMPERATURES COOLING CYCLE OPERATION INDOOR TEMPERATURE OUTDOOR TEMPERATURE MINIMUM TEMPERATURES 32º C DB / 23º C WB 21º C DB / 15º C WB + 19º C STANDARD UNIT +15º C WITH MINIMUM INDOOR TEMPERATURES 24º C DB/ 18º C WB 0º C WITH OPTIONAL ON/OFF CPC -10º C WITH OPTIONAL PROPORT. CPC DEPENDING ON MODEL (see Tables for cooling capacities) OPERATING LIMITS FOR (HEATING PUMP) UNITS MAXIMUM TEMPERATURES COOLING CYCLE OPERATION INDOOR TEMPERATURE OUTDOOR TEMPERATURE HEATING CYCLE OPERATION 32º C DB / 23º C WB 21º C DB / 15º C WB + 19º C STANDARD UNIT +15º C WITH MINIMUM INDOOR TEMPERATURES 24º C DB/ 18º C WB 0º C WITH OPTIONAL ON/OFF CPC -10º C WITH OPTIONAL PROPORT. CPC DEPENDING ON MODEL (see Tables for cooling capacities) INDOOR TEMPERATURE OUTDOOR TEMPERATURE MINIMUM TEMPERATURES 27º C DB 15º C DB DEPENDING ON MODEL (See Tables for heating capacities) -10º C DB / -11º C WB DB.- Dry Bulb Temperature WB.- Wet Bulb Temperature 1.11.- STANDARD/ OPTIONAL INLET AIR PANEL OF INDOOR UNIT LNXO 018-024-030-036-048-060 (to be made by the installer) STANDARD POSITION E OPTIONAL POSITION E A Service panel Air filter B D A C C F D D B C F C Profiles for fixing air filter Service panel LNXO 018-024 mm. LNXO 030-036 mm. LNXO 048-060 mm. A B 1000 1000 1195 235 287 315 D Air filter C 16 D 885 175 885 225 1055 255 E F 58 58 70 27 28 26 1.- UNIT SELECTION 1.11.- STANDARD/ OPTIONAL ENTRANCE OF OUTDOOR UNIT KCCK / KCHK (to be made by the installer) MODELS 018-024 133 78 400 490 STANDARD EXTRACTOR ENTRANCE 400 490 400 490 350 B1 67,5 OPTIONAL EXTRACTOR ENTRANCE 53,5 53,5 STANDARD CONFIGURATION 470 35,5 B0 118,5 58,5 58,5 A1 B1 OPTIONAL EXTRACTOR ENTRANCE 45,5 B0 STANDARD EXTRACTOR ENTRANCE 370 470 24 470 OPTIONAL BLOWER ENTRANCE 350 345 370 A0 370 410 345 53,5 78 A1 STANDARD BLOWER ENTRANCE 470 COMPRESSOR IL OPTIONAL BLOWER ENTRANCE 58,5 410 470 STANDARD BLOWER ENTRANCE 58,5 C O 370 470 FAN A0 A1 400 A0 53,5 B0 MODELS 030-036 490 B1 OPTIONAL CONFIGURATION ELECTRIC BOX MODELS 048 MODELS 060-070 B1 IL O 123 A1 E.B. OPTIONAL BLOWER ENTRANCE 58 595 324 355 355 324 213 OPTIONAL BLOWER ENTRANCE 595 A1 E.B. 495 123 349 428 STANDARD BLOWER ENTRANCE 38 C A0 349 303 COMPRESSOR 368 170 B0 495 303 A0 STANDARD BLOWER ENTRANCE FAN MODELS 080 IL O 324 A1 92 OPTIONAL BLOWER ENTRANCE 193 C 324 595 595 B0 391,5 STANDARD BLOWER ENTRANCE 355 355 A0 193 B1 FAN 595 497 B1 OPTIONAL EXTRACTOR ENTRANCE 61 STANDARD CONFIGURATION STANDARD EXTRACTOR ENTRANCE 497 595 B0 A1 462 462 61 262 A0 OPTIONAL CONFIGURATION ELECTRIC BOX 17 384 595 500 B1 OPTIONAL EXTRACTOR ENTRANCE 63 STANDARD EXTRACTOR ENTRANCE 500 595 OPTIONAL EXTRACTOR ENTRANCE OPTIONAL CONFIGURATION ELECTRIC BOX COMPRESSOR 422 422 B0 43 43 STANDARD CONFIGURATION 249 B1 63 STANDARD EXTRACTOR ENTRANCE 495 425 B0 A1 269 452 452 425 495 184 A0 304 1.- UNIT SELECTION 1.12.- OUTDOOR UNIT OPTIONS ON/OFF CONDENSATION PRESSURE CONTROL (outdoor unit) The condensation pressure control consists of one pressure switch, which starts and stops the outdoor fan, regulating the condensation temperature; thus the unit will be able to operate in the cooling cycle when the outdoor temperature is below 19ºC (until 0ºC). It includes crankcase heater for cooling only units. The purpose of the heater is to keep the oil in the compressor at the correct temperature while the compressor is stopped, so that it can be properly lubricated when starts again. When the unit is operating at low outdoor temperatures (below 19ºC), it is advisable to fit a crankcase heater. For long distances applications, proportional winter control must be installed. PROPORTIONAL CONDENSING PRESSURE CONTROL (outdoor unit. Not available for MODELS 060-070080 with centrifugal fan) It is an element that regulates outdoor fan speed, in order to control condensation temperature. Thus, the unit will be able to operate in the cooling cycles when the outdoor temperature is below 19ºC. This kit includes crankcase heater for cooling only units. MAIN SWITCH (only MODELS 048-060-070-080 with centrifugal fan) The main switch is located on the access panel to the electrical box, in such a way that the unit is disconnected when the panel is opened, for the models KCCK / KCHK. COMPRESSOR ACOUSTIC JACKET (outdoor unit) Each compressor is fitted with a compressor acoustic jacket this provides attenuation of the compressor noise that radiates from the unit when in operation. 1.12.- INDOOR UNIT OPTIONS KIT CONDENSATE PUMP As an option, a condensate pump is available to ensure condensate removal; also the kit is supplied with a float switch which makes the unit stops in case the pump is broken or the drain is choking (see unit description of page 15, for condensate pump position). To ensure that the condensate flows, the drain tube must be installed with a fall of 2% without obstructions, or without rising sections. To avoid any unpleasant odours from the drainage system, a trap must be fitted with a trap depth of no less than 50mm. The condensate pump has a maximum lift of 200mm. The rising tube must always be vertical. On completion the drain line must be insulated. The condensate pump is supplied with a cover panel which can be removed from the unit in case could be necessary. KIT AIR INLET PLENUM AND KIT DISCHARGE PLENUM DISCHARGE PLENUM B DISCHARGE PLENUM C mm. A B C D E LNXO 018-024 890 102 235 152 293 LNXO 030-036 LNXO 048-060 890 102 242 152 293 1060 102 267 137 262 LNXO 070-080 1248 300 320 114 255 C A C D A E mm. F G H LNXO 018-024 892 100 237 151 295 LNXO 030-036 LNXO 048-060 892 100 260 151 295 1062 100 288 135 264 LNXO 070-080 1246 88,5 350 113 255 D E D E J J J I E E E D I AIR INLET PLENUM A E E E LNXO 018-024 030-036 I B B LNXO 048-060 D D LNXO 070-080 G F I J J J H I G I F H J J J J I G F H LNXO 018-024 030-036 LNXO 048-060 Ø DUCT FLANGE EXTERNAL DIAMETER 195 mm AIR INLET PLENUM 18 LNXO 070-080 1.- UNIT SELECTION 1.12.- INDOOR UNIT OPTIONS ELECTRICAL HEATER AND HOT WATER COIL INSTALLATION INSTRUCTIONS NOTE: Electrical heater and water coil are supplied mounted on the unit. Also, it is possible to install them on site, always before the unit is installed on the ceiling. BEFORE ATTEMPTING TO PERFORM ANY SERVICE OR MAINTENANCE, TURN OFF THE ELECTRICAL POWER, AND CHECK THAT THE FAN HAS STOPPED LNXO 018-024-030-036-048-060 • The electrical heater or hot water coil should be installed into the impulsion fan of the unit. • Fit them on the unit using the screws supplied as the drawing shows. • Remove on side cover (disposable), then slide the electrical heater or hot water coil to the backstop through the provided rail. • Fit them on the unit side using two screws. Make the electrical connection between the electrical heater and the electrical box of the unit following the wiring diagram supplied, or make the water connections if a hot water coil is being installed. Finally, place the end cover. LNXO 070-080 ELECTRICAL HEATER TECHNICAL DATA SET/ INDOOR UNIT LNXO 018 LNXO 024 LNXO 030 LNXO 036 Only Cooling / Heat Pump C/H.Pump C/H.Pump C/H.Pump 230V 1Ph-50Hz Power (kW) 5 / 2,5 5 / 2,5 400V 3Ph-50Hz Power (kW) --- --- LNXO 060 LNXO 070 LNXO 080 C/H.Pump C/H.Pump C/H.Pump C/H.Pump C/H.Pump 7,5 / 3,75 7,5 / 3,75 7,5 / --- LNXO 048 7,5 / 3,75 --- --- --- --- 12 / 6 12 / 6 15 / 7,5 15 / 7,5 HOT WATER COIL (2 ROWS) TECHNICAL DATA WATER FLOW WATER COIL PRESSURE DROP AIR FLOW AIR PRESSURE DROP (*) 70 ºC L/h Kpa m3/h Pa 7350 452 13 800 13 10990 675 36 1250 17 16660 1023 33 2050 24 29960 1840 13 3400 16 DIFFERENCE IN TEMPERATURES BETWEEN HOT WATER INTAKE AND THE AIR THAT ENTERS THE COIL 50 ºC 60 ºC CAPACITY IN W LNXO 018-024 5250 6300 CAPACITY IN W LNXO 030-036 7850 9420 CAPACITY IN W LNXO 048-060 11900 14280 CAPACITY IN W LNXO 070-080 21400 25680 (*) NOMINAL AIR FLOW VOLUME For different air flow volumes from the table above, apply the following coefficients: Relation between air flow from the table x 0,75 x 0,85 x1 x 1,15 x 1,35 Capacity Water flow x 0,84 x 0,92 x1 x 1,08 x 1,20 x 0,84 x 0,92 x1 x 1,08 x 1,20 19 Water Air pressure pressure drop drop x 0,73 x 0,63 x 0,83 x 0,73 x1 x1 x 1,13 x 1,30 x 1,42 x 1,70 2.- INSTALLATION 2.1.- POINTS TO KEEP IN MIND DANGER AND WARNING SIGNS Abrasive surfaces Low temperatures High temperatures Risk of injury with moving objects WARNING Electric shock hazard can cause injury or death. Before attempting to perform any service or maintenance on the unit, turn OFF the electrical power, and check that the fan has stopped. Electrical voltage Risk of injury with rotating objects The air filter cleaning operations do not require technical service; however when an electrical or mechanical operation is required call an Engineer. FILTER CLEANING Check the air filter and make sure it is not blocked with dust or dirt. If the filter is dirty, wash it in a bowl with neutral soap and water, drying it in the shade before inserting it in the unit. Standard Guidelines to Lennox equipment All technical data contained in these operating instructions including the diagrams and technical description remains the property of Lennox and may not be used (except for the purpose of familiarizing the user with the equipment), reproduced, photocopied, transferred or transmitted to third parties without prior written authorization from Lennox . The data published in the operating instructions is based on the latest information available. We reserve the right to make modifications without notice. We reserve the right to modify our products without notice without obligation to modify previously supplied goods. These operating instructions contain useful and important information for the smooth operation and maintenance of your equipment. The instructions also include guidelines on how to avoid accidents and serious damage before commissioning the equipment and during its operation and how to ensure smooth and fault-free operation. Read the operating instructions carefully before starting the equipment, familiarize yourself with the equipment and handling of the installation and carefully follow the instructions. It is very important to be properly trained in handling the equipment. These operating instructions must be kept in a safe place near the equipment. Like most equipment, the unit requires regular maintenance. This section concerns the maintenance personnel and management. If you have any queries or would like to receive further information on any aspect relating to your equipment, do not hesitate to contact us. 20 2.- INSTALLATION 2.2.- INSTALLATION GUIDELINES All INSTALLATION, SERVICE and MAINTENANCE operations must be carried out by QUALIFIED PERSONNEL. The unit must be transported in a HORIZONTAL POSITION; any other position may cause serious damage to the machine. When the unit is received, it should be checked to assure that there are no bumps or other damage, following the instructions on the packaging. If there is damage, the unit may be rejected by notifying the LENNOX Distribution Department and reporting why the machine is unacceptable on the transport agent’s delivery notice. Any later complaint or claim made to the LENNOX Distribution Department, for this type of anomaly, cannot be considered under the Guarantee. Sufficient space must be allowed to facilitate placement of the unit. When positioning the unit, be sure that the Rating Plate will always be visible since this data will be necessary to assure proper maintenance. The KCCK-KCHK indoor and outdoor unit are designed to be installed with ducts, calculated by qualified technical staff. The joints to be used between ducts and the openings to the unit should be Elastic Joints. Avoid the use of BYPASS joints between the extraction air and input air in both the outdoor and indoor sections. The structure where the unit is placed must be able to support the weight of the unit during operation. 2.3.- UNIT RECEPTION The KCCK-KCHK 048-060-070-080 units have Metal Bedplate Profiles and Wooden Blocks for transportation. These wooden blocks must be removed when positioning the unit in its final position. PLACEMENT OF THE BEDPLATE AND TRANSPORTATION BLOCKS To remove the transportation blocks: remove the screw and slide the block along the metal profile. How to hoist the unit If unloading and placement require the use of a crane, then secure the suspension cables as shown in the figure. Use separators Bedplate profile Securing screw Wood block 2.4.- INSTALLATION CLEARANCES Clearance around the unit for service and maintenance. Min. 300 Min . 15 0 KJCK KJHK 1 mete 1 r 1 er et m 1 mete er et m r 21 Min. 300 2.- INSTALLATION 2.5.- OPTIONAL OPERATIONS PRIOR TO UNIT INSTALLATION: CHANGING THE POSITION OF BLOWERS AND AIR INTAKE FOR OUTDOOR UNITS KCCK-KCHK 048-060-070-080 STANDARD AIR INTAKE AND BLOWERS OPTIONAL AIR INTAKE AND BLOWERS Service Panel Intake Opening B1 Intake Opening B0 Service Panel Extension Collar A0 Motor Fan-motor assembly Blower Panel with Opening Service Panel Motor Fan-motor assembly A1 Blower Panel with Opening BLOWER: From the position A0 to the position A1 1) Remove the ceiling of the unit, the Blower Panel with Opening and the Service Panel. 2) Remove the motor-fan assembly from the unit unscrewing the supports from the base, and throwing away the extension collar, if there is one. 3) Unscrew the supports that have been left on the fan-motor assembly. 4) Turn the fan-motor assembly to its new position 90º horizontally and 180º on its shaft. The motor should now be accessible from the Service Panel in this new position. 5) Screw down the fan-motor assembly in its new position using the supports. 6) Assemble the Blower Panel with Opening and the Service Panel in its new position, taking special care with the weather striping. INLET: From the position B0 to the position B1 1) Remove the Intake Opening and the Service Panel. 2) Switch the position of the Opening and Service Panels. SEE LOCATIONS AND SIZES FOR THE OPENINGS IN THEIR STANDARD AND OPTIONAL POSITIONS ON THE GENERAL MEASUREMENT DRAWINGS. 2.6.- DUCT INSTALLATION Duct calculation and design must be effected by a qualified technician. The ductwork dimensions should be determined in accordance with the air flow circulating through it and with the available static pressure of the unit. This data appears in the corresponding Technical Documentation. Various suggestions are made here below, regarding the layout and design of the said ductwork: 1- Whatever type of duct is used, it should not be made of materials which are flammable, or which give off toxic gases in the event of a fire. The internal surfaces should be smooth , and not contaminate the air which passes through. It is advisable to use isolated sheet metal duct in order to avoid condensations and thermic charges. 2- At the points where the duct joins with the unit, it is advisable to use a flexible connection which absorbs vibration and prevents the transmission of noise inside the ductwork and allows the unit access. 3- Bends should be avoided as much as possible near the unit outlet. If unavoidable, they should be as slight as possible, and internal deflectors should be used when the duct is of large dimensions. 4- For heat pump indoor unit, room height has to be taken on account because for long heights the hot air should go on to the top, and this makes difficult conditioning the room. In this case, the return and discharge grilles should be positioned adequately and have the suitable dimensions. 22 2.- INSTALLATION 2.7.- DRAINS GENERAL RECOMMENDATIONS: For drain piping, it is advisable to use PVC copper and steel tube. For drain tube, use a sealing material. Do not make any drill on the unit base: the drip tray could be damage. Slightly tip the unit toward the drainage side as the picture shows. If heat pump outdoor unit is going to be installed for working with outdoor temperatures below 0ºC, an electrical heater must be installed around the drain pipe in order to avoid ice formed and not get obstructed. INDOOR UNITS LNXO: They are provided with two 1/2” male steel threaded drain pipe welded to the drip tray located at both sides of the unit, which can be used faintly to adapt the installation requirements. The units are also provided with a PVC 20mm inside diameter / 25mm outside diameter tamper and adaptor to connect the drain pipe as the picture shows. NOTE: it is necessary that at least one of the two drain tubes must be blind. UNITS LNXO 018-024-030-036-048-060 Drain tube UNITS LNXO 070-080 Drain tube UNIT UNIT 2% 2% 2% 2% Drain pipe PVC adaptor PVC adaptor Siphon Drain pipe It is not necessary to install a siphon to evacuate water Install siphon to avoid suction from fans. from the unit, but it is advisable to install it to avoid offensive odor. Slightly tip the units (2%) toward the drainage tube and check that the drip tray is clean and free from dirt and other debris from the works, and that the water drains correctly. HEAT PUMP OUTDOOR UNITS WITH AXIAL FAN KJHK: Unit models 018-024-030-036-048-060-070-80 are provided with a steel 16mm outdoor diameter drain tube welded to the unit base; for this application a siphon must be installed. Connect the siphon to the drain pipe of the unit, and mount the drain pipe with at least a 2% incline from the siphon. Slightly tip the unit (2%) toward the drainage tube and check that the drip tray is clean and free from dirt and other debris from the works, and that the water drains correctly. Drain tube UNIT 2% 2% Drain pipe Siphon HEAT PUMP OUTDOOR UNITS WITH CENTRIFUGAL FAN KCHK: Unit models 018-024-030-036 are provided with a steel 16mm outdoor diameter drain tube welded to the unit base; for this application a siphon is not necessary. Unit models 048-060-070-080 are provided with a 3/4" male steel threaded welded to the drip tray; for this application a siphon must be installed. Connect the siphon to the drain pipe of the unit, and mount the drain pipe with at least a 2% incline from the siphon. Slightly tip the unit (2%) toward the drainage tube and check that the drip tray is clean and free from dirt and other debris from the works, and that the water drains correctly. UNITS KCHK 048-060-070-080 UNITS KCHK 018-024-030-036 Drain tube Drain tube UNIT UNIT 2% 2% 2% Drain pipe Drain pipe Siphon It is not necessary to install siphon to evacuate water from the unit, but it is advisable to install it to avoid offensive odor. 23 2.- INSTALLATION 2.8.- SETTING UP TEMPLATES OF OUTDOOR UNIT OUTDOOR UNIT WITH CENTRIFUGAL FAN (mm) SETTING UP TEMPLATE UNITS 018-024-030-036 A SETTING UP TEMPLATE UNITS 048-060-070 Refrigerant connection valves A Refrigerant connection valves AIR OUT OPTIONAL B AIR IN OPTIONAL AIR IN STANDARD B AIR IN OPTIONAL AIR OUT OPTIONAL AIR OUT STANDARD AIR IN STANDARD AIR OUT STANDARD Use 4 rod of a diameter of 10mm if the unit is fixed in the roof , or screw M.10 if the unit is fixed on the ground. SETTING UP TEMPLATE UNITS 080 Refrigerant connection valves A B A AIR IN OPTIONAL B KCCK / KCHK KCCK / KCHK KCCK / KCHK KCCK /KCHK KCCK /KCHK 018-024 030-036 048 060-070 080 983 1064 1300 1350 1500 A AIR IN STANDARD AIR OUT STANDARD Dimensions recommended on point A and B are referred to the hole of support of the unit. AIR OUT OPTIONAL B 530 660 711,6 721,6 791 OUTDOOR UNIT WITH AXIAL FAN (mm) D E D KJCK KJCK KJCK KJCK KJCK KJCK KJCK KJCK KJHK KJHK KJHK KJHK KJHK KJHK KJHK KJHK 018 024 030 036 048 060 070 080 520 520 620 620 620 620 602 602 E 126,4 126,4 176,4 F E G KJCK KJHK Ø 12 10 10 10 176,4 176,4 176,4 10 10 10 198 198 12 12 386 386 F F G Ø Drain pipe 16 mm 343,5 343,5 343,5 343,5 343,5 343,5 2.8.- SETTING UP TEMPLATES OF INDOOR UNIT LNXO LNXO LNXO LNXO 018-024 030-036 048-060 070-080 B A C B LNXO 018-024-030-036-048-060 C B A 535 700 750 850 C B 49 55 62 32 C 354 472 515 409 D 132 173 173 1345 E 1000 1000 1195 1405 F 1038 1038 1233 1375 LNXO 070-080 A C D D E B D F E F 24 2.- INSTALLATION 2.9.- OPTIONAL OPERATIONS PRIOR TO UNIT INSTALLATION: CHANGING THE POSITION OF INLET AIR PANEL FOR UNITS LNXO 018-024-030-036-048-060 Air filter D0 Service panel Service panel From the position D1 Profiles for fixing air filter Air filter D0 to the position D1 1) Detach air filter profiles. 2) Detach service panel. 3) Interchange the position of air filter and service panel, and secure them with the screw supplied. SEE LOCATIONS AND SIZES FOR THE OPENINGS IN THEIR STANDARD AND OPTIONAL POSITIONS ON THE GENERAL MEASUREMENT DRAWINGS. 2.10.- UNIT LOCATION OF INDOOR UNIT LNXO (mm) INSTALL THE UNIT IN POSITION WHERE: 1. Where there is enough security to support weight of the indoor unit. 2. Where you can remove filters for maintenance purposes. Install always the filter. If the unit works without filter you will find problem on the unit because of dust. 3. Where connection pipes of the outdoor unit can have easily access. 4. Where drain pan can evacuate easily. 5. Assure that there is enough space around the unit for manipulation. 6. Where you can access easily the electrical box. 7. Where the coil cannot get dirty and obstructed because of dust. These units can work in normal radio electric conditions. Certain ambiental conditions may cause high electromagnetic emissions; for this kind of installation, please consult. Install the unit with rod M-8 with nuts and washers, as drawing shows. Install also rubbers to avoid noise transmissions. 1 Nut 2 Washer Suspension rod M-8 Rubbers 1 2 2 1 1 When lifting the unit into position, care should be taken not to lift the unit by the drip tray, refrigerant connections or drain tube; this could damage the unit. The unit should be lifted by the hanging brackets. Make sure all the panels are fitted and secured. The unit brackets hook over the washers. Tighten the unit with the lower nuts. Check to ensure the unit is level. Tighten the nuts on the suspended rods. Ensure there is sufficient space around the unit t service it. Where there is a false ceiling ensure that there is enough space to provide access. Where there is a false panelled ceiling, ensure that there is enough adjacent space to remove the panels. If there is enough space between unit and the ceiling, it is advisable to install a rubber sheet. In addition, an access panel under the unit should be left in order to carry out further maintenance operations. 25 2.- INSTALLATION 2.11.- ELECTRICAL CONNECTIONS IMPORTANT Prior of making the electrical connections, set the switch for heat pump unit or for cooling only unit. COOLING ONLY (factory setting) This unit is valid for operating as a cooling only or heat pump application. It should be configured prior to making the electrical connections, by setting the configuration switch located on the (P.C.B) at indoor unit as follows: JMODE JMODE HEAT PUMP P.C.B. JMODE SITUATION B Models 030(3ph)-036-048-060-070-080 SITUATION A Models 018-024-030(1ph) 1 OUTDOOR UNIT 2 3 OUTDOOR UNIT 2 3 1 Power supply 2 Remote control connection (max. length 15m.) 3 Indoor unit/Outdoor unit connection 1 VOLTAGE MODELS ONLY COOLING 1 POWER SUPPLY 230V SINGLE PHASE UNITS PE N L X1 NUMBER OF WIRES X SECTION HEAT PUMP 2 018 024 030 3x2,5mm 036 3x2,5mm 036 4x2,5mm 048 060 2 4x4mm 070 4x4mm 2 4x1mm shielded cable (supplied with the unit) 2 2 1N ~ 230V - 50 Hz + PE POWER SUPPLY 230V THREE-PHASE UNITS PE L1 L2 L3 X1 3 ~ 230V - 50 Hz + PE POWER SUPPLY 400V THREE-PHASE UNITS PE L1 L2 L3 N X1 2 5x1,5mm 2 2 5x2,5mm 2 5x2,5mm 2 5x4mm 4x1mm shielded cable (supplied with the unit) 2 4x2,5mm 2 4x1,5mm 2 4x1,5mm 4x2,5mm 3 4x4mm 2 4x1mm (supplied with the unit) 2 6x1,5mm 2 4x1mm (supplied with the unit) 2 5x1,5mm 4x1,5mm 2 5x2,5mm 2 2 2 6x2,5mm 2 6x1,5mm 2 4x4mm 2 2 4x1mm (supplied with the unit) 4x1mm (supplied with the unit) 2 4x6mm 2 4x1mm shielded cable (supplied with the unit) 2 3x2,5mm 2 2 4x1,5mm 2 4x1mm shielded cable (supplied with the unit) 2 3x2,5mm 2 2 4x1mm shielded cable (supplied with the unit) 4x1mm shielded cable (supplied with the unit) 030 036 080 2 2 2 2 4x6mm 060 070 3N ~ 400V - 50 Hz + PE 2 080 048 1 3 2 5x2,5mm 4x1,5mm 2 5x4mm 2 6x1,5mm 2 4x1mm (supplied with the unit) 2 6x1,5mm 2 4x1mm (supplied with the unit) 2 6x1,5mm NOTE: The sections have been calculated for a distance no longer than 35m, and a voltage drop of 10V. The wiring must comply with the regulations in force. Make sure the earth cable connection is correct. IN ORDER TO CARRY OUT THE ELECTRICAL CONNECTIONS, FOLLOW THE ELECTRICAL DIAGRAM SUPPLIED WITH THE UNIT REMEMBER THAT THE COMPRESSOR IS A SCROLL TYPE COMPRESSOR Scroll type compressors only compress in one direction of the rotation. Single phase models are always started up in the proper direction; however, the three phase models, turn in either direction depending on the order of the power supply phases. Therefore, it is essential that the phase connection for scroll-type three-phase compressors be carried out correctly, that is why these three-phase compressors are supplied as standard with a three-phase detector, which avoids the unit starts unless the connections are made on the right way. The direction of the rotation is right when an indicator-light turns ON. If the connection is wrong, this indicator will not light and the rotation will be reversed. If this occurs, the solution is to disconnect, switch the wires between two of the phases and connect again. VOLTAGE OPERATING LIMITS MODEL 018-024-030-036 030-036-048-060 070-080 230 V-1Ph-50Hz LIMIT 198-264 V -1Ph- 50Hz 230 V-3Ph-50Hz 180-242 V -3Ph- 50Hz 400 V-3Ph-50Hz 230 V-3Ph-50Hz 342-462 V -3Ph- 50Hz 180-242 V -3Ph- 50Hz 400 V-3Ph-50Hz 342-462 V -3Ph- 50Hz VOLTAGE 26 2.- INSTALLATION 2.11.- ELECTRICAL CONNECTIONS ACCESS TO ELECTRICAL COMPONENTS OF INDOOR UNIT The electric board, located outside of the unit, allows easy access to electrical components. To carry out wiring: power supply of the unit, connection to remote control, and connection with outdoor unit, get access to electrical panel removing electric board cover. For electrical connection refer to wiring diagram in the unit. For easier installation: The electrical panel can be folded 90º, so terminals will be easily accessed, and also can be removed from the unit 30cm. In case it is necessary to place the electric board away from the unit, the temperature sensor wire and fan wire may be extended up to a maximum of 25m using screened wire. The remote control terminal housing may be detached to ease its connection. COOLING ONLY UNITS LNXO 018-024-030 PE L N 1 2 3 PE L N N 1 2 LNXO 036-048-060 LNXO 036 PE L PE L N 1 2 3 PE L N N 1 2 OUTDOOR OUTDOOR UNIT UNIT N 1 2 3 PE L1 L2 L3 N L N 1 OUTDOOR UNIT 2 1N~230V-50Hz+PE 1N~230V-50Hz+PE PE L N 1 2 3 PE L1 L2 L3 N L N 3~230V-50Hz+PE LNXO 070-080 LNXO 030-036-048-60 1 2 PE L1 L2 L3 N LNXO 070-080 PE L N 1 2 PE L N N 1 OUTDOOR UNIT 3 PE L1 L2 L3 N 2 PE L N 1 PE L N N OUTDOOR UNIT 3N~400V-50Hz+PE 2 3 1 2 OUTDOOR UNIT 3~230V-50Hz+PE 3N~400V-50Hz+PE HEAT PUMP UNITS LNXO 018-024-030 PE L N 1 2 3 PE L N N 1 2 3 4 OUTDOOR UNIT 1N~230V-50Hz+PE LNXO 036-048-060 LNXO 036 PE L N 1 2 3 PE L N N 1 2 PE L 3 N 1 2 3 PE L1 L2 L3 N L 1 2 3 PE L1 L2 L3 N OUTDOOR UNIT 1N~230V-50Hz+PE L N 1 2 3 4 OUTDOOR UNIT 3~230V-50Hz+PE LNXO 070-080 LNXO 036-048-060 PE L 4 N N 1 2 3 4 PE L1 L2 L3 N PE L N 1 2 PE L N N 1 3 2 3 4 PE L1 L2 L3 N PE L N 1 2 3 PE L N N 1 OUTDOOR UNIT OUTDOOR UNIT 3N~400V-50Hz+PE LNXO 070-080 3~230V-50Hz+PE 27 2 3 4 OUTDOOR UNIT 3N~400V-50Hz+PE 2.- INSTALLATION 2.12.- REFRIGERANT CONNECTIONS UNIT CONNECTION MODELS 018 to 060 Insulated gas line UNIT CONNECTION MODELS 070 / 080 INDOOR UNIT Flared nuts Service valve Service valve Coupling OUTDOOR UNIT Coupling Insulation OUTDOOR UNIT Protective hoods INDOOR UNIT Insulated gas line Flared nuts Welded connection Insulation Liquid line without insulation Insulated liquid line REFRIGERANT CONNECTION INSTRUCTIONS FOR UNITS WITH COUPLINGS AND SERVICE VALVES NOTE: THE REFRIGERANT GAS AND LIQUID LINES MUST BE INSULATED FOR MODELS 018 TO 060. FOR MODELS 070 / 080 THE LIQUID LINE IS NOT NECESSARY TO BE INSULATED. Make the refrigerant connections between the outdoor and indoor unit, as follows: -With the valves closed on outdoor unit, unscrew the flare nuts, removing all the protective hoods. -Unscrew the flare nuts and the coupling on indoor unit (mod. 018 to 060), removing the protecting hoods. -Introduce the flare nuts in the corresponding union tubes, previously isolated. -Make the thread union of the tubes in valves and coupling using the keys, as shown in the picture. And welded on indoor unit for models 070 / 080. -To do vacuum, first close the valves on outdoor unit, second connect the plug of the vacuum pump to the suction valves service port 1/4”, do vacuum to get an absolute pressure of 0,5 mm Hg. This way the vacuum will be created in indoor unit and union pipes. -Remove the plugs and open the valves of outdoor unit. -Verify leakage in couplings. -Insulate pipes and service ports. CUT THE PIPE PROPERLY MAKE A CORRECT FLARE Pipe cutter YES Unpolished Bent FAULTY 90° NO Bent Damaged surface AVOID FROM METALLIC DUST ENTERING INTO THE PIPE Flawed Irregular 0-0.5 mm. CLEAN THE BURRS Copper pipe TIGHTENING TORQUE Apply the tightening torque shown in the table. Insufficient tightening torque could cause refrigerant leak, excessive tightening torque will damage pipe flare. PIPE DIAMETER TIGHTENING TORQUE 1/4'' 15-20 Nm 3/8'' 31-35 Nm 5/8'' 50-55 Nm 3/4'' 65-70 Nm Service port Gas line Liquid line 28 2.- INSTALLATION 2.12.- REFRIGERANT CONNECTIONS DISTANCES BETWEEN UNITS To locate the outdoor and the indoor units, refer to the following information: SYPHONS: Install syphons on the installation as the picture shows, on the upper and lower position of the suction line. No other syphons are necessary. The indoor units LNXO 070-080 are supplied with welded connections. OUTDOOR UNIT 2% OUTDOOR UNIT B 2% 1 INDOOR UNIT 2 2% INDOOR UNIT L A 2 1 2 L 1 A,B,C : Unit positions L : Total length 1 = Gas line 2 = Liquid line INDOOR UNIT L OUTDOOR UNIT C 2% 2% REFRIGERANT LINES SELECTION UNIT - MODEL REFRIGERANT LINES Ø Liquid 018 1/4" 024 1/4" 030 3/8" 036 3/8" 048 3/8" 060 3/8'' 070 1/2'' 080 1/2'' Ø Gas 1/2" 5/8" 5/8" 3/4" 3/4" 3/4" 7/8" 7/8" Maximum vertical line length (m) 15 15 15 15 15 15 15 15 Max. vertical line length + horizontal (m) Min. vertical line length + horizontal (m) 25 5 25 5 25 5 25 5 25 5 25 5 25 5 25 5 Maximum number of curves 12 12 12 12 12 12 12 12 Unit connections REFRIGERANT LINES SELECTION FOR LONG DISTANCES UNITS (only for applications as pictures A and B show; only cooling sets NJCK 018 to 060 standard units, and heat pump NJHK 0180 to 060 with a special outdoor unit LD). UNIT - MODEL REFRIGERANT LINES Ø Liquid 018 1/4" 024 1/4" 030 3/8" 036 3/8" 048 3/8" 060 3/8'' Ø Gas 1/2" 5/8" 5/8" 3/4" 3/4" 3/4" Maximum vertical line length (m) 30 30 30 30 30 30 Max. vertical line length + horizontal (m) Min. vertical line length + horizontal (m) NJHK-LD 55 25 55 25 55 25 55 25 55 25 55 25 Maximum number of curves 12 12 12 12 12 12 Unit connections NOTE: THE REFRIGERANT GAS AND LIQUID LINES MUST BE INSULATED FOR MODELS 018 TO 060. FOR MODELS 070 / 080 THE LIQUID LINE IS NOT NECESSARY TO BE INSULATED. For other positions and longer distances, consult the Lennox Technical Support Department for application assistance. The following data will be obtained from that estimation: pipe dimensions, suction traps, isolation, refrigerant charge. REFRIGERANT CHARGE: The outdoor unit is supplied with refrigerant R-407C factory precharged, for the set indoor+outdoor unit and for a line of 5 meter long. When the line length exceeds 5m, add the following amount of refrigerant per meter line: COOLING ONLY UNIT MODELS Refrigerant charge R-407C per meter (gr.) HEAT PUMP UNIT MODELS Refrigerant charge R-407C per meter (gr.) 018 024 030 036 048 060 070 080 10 10 20 20 20 20 85 85 018 024 030 036 048 060 070 080 20 20 45 45 45 45 85 85 29 3.- COMMISSIONING AND OPERATION 3.1.- DATA PAGE FOR UNIT COMMISSIONING UNIT: SERIAL No: CONTROL PANEL IDENTIFICATION CODE INSTALLATION ADDRESS: INSTALLER: INSTALLER TEL.: INSTALLER ADDRESS: DATE OF COMMISSIONING: CHECKS: SUPPLY VOLTAGE: RATED VOLTAGE OF THE UNIT: YES NO UNIT ON SHOCK ABSORBERS DRAINAGE WITH TRAP GENERAL POWER SUPPLY CONNECTION CONTROL PANEL CONNECTION COMPRESSOR OIL LEVEL INDICATOR DATA INPUT: HEATING CYCLE COOLING CYCLE Air Intake Temperature to the coil: ºC Air Intake Temperature to the coil: ºC Air Output Temperature to the Coil: ºC Air Output Temperature to the Coil: ºC High Pressure: High Pressure: Low Pressure: Low Pressure: ELECTRIC POWER CONSUMPTION (Amps) Compressor Compressor Fan Fan Options Installed: Comments: 30 3.- COMMISSIONING AND OPERATION 3.2.- PRECAUTIONS TO BE TAKEN ON INSTALLATION The refrigerant R407-C is a mixture of other three refrigerants that behave as pure compounds. This fact makes that the operations of installation, service and maintenance must be special, for the next operations: SYSTEM EVACUATION Vacuum must be done until the absolute pressure does rise -750mm Hg during an hour, since the compressor oil high hygroscopic degree can cause corrosion in some metallic materials. REFRIGERANT CHARGING To maintain the mixture composition, the refrigerant must be charged always in liquid phase. For what it is necessary to have special caution when it is little quantity of refrigerant in the bottle. LEAKS If a leak takes place in the system that has produced an important evacuation of the refrigerant charge, instead of recharging the system, it is convenient to eliminate the whole charge completely, the system must be evacuated and charged again or to introduce the charge according to an specified value. OPERATION On a system operated with refrigerant R407-C, during the evaporation phase at constant pressure the temperature increases; and during the condensation phase at constant pressure the temperature decreases a certain value. Consequently, the terms “evaporation temperature” and “condensation temperature” should be redefined. PRECAUTIONS TO BE TAKEN IN THE USE OF R-407C Refrigerant: R-407C Refrigerant is used in the unit; therefore, the following precautions characteristic of this gas should be taken: - The Vacuum Pump must have a Check Valve or Solenoid Valve. - Pressure Gauges and Hoses for the exclusive use with R-407C Refrigerant should be used. - The charge should be carried out in the Liquid Phase. - Always use scales to weight-in charge - Use the Leak Detector exclusive for R-407C Refrigerant. - Do not use mineral oil, only synthetic oil to ream, expand or make connections. - Keep pipes closed before using them and be very thorough about any possible dirt (dust, filings, burrs, etc.). - When there is a leak, gather what is left of the charge, create a vacuum in the unit and completely recharge with new R-407C Refrigerant. - Brazing should always be carried out in a nitrogen atmosphere. - Reamers should always be well sharpened. REMEMBER THAT THE COMPRESSOR IS A SCROLL TYPE COMPRESSOR: Scroll type compressors only compress in one direction of the rotation. Single phase models are always started up in the proper direction; however, the three phase models, turn in either direction depending on the order of the power supply phases. Therefore, it is essential that the phase connection for scroll-type three-phase compressors be carried out correctly, that is why these three-phase compressors are supplied as standard with a three-phase detector, which avoids the unit starts unless the connections are made on the right way. The direction of the rotation is right when an indicator-light turns ON. If the connection is wrong, this indicator will not light and the rotation will be reversed. If this occurs, the solution is to disconnect, switch the wires between two of the phases and connect again. 3.3.- PRELIMINARY CHECKS 1 Check that drain pipe connections, syphon installation, and their fixtures are secure and that the level of the unit is tipped toward the drain. 2 Inspect the state of the ducts and grilles (clean and open grilles, no breaks in the duct, etc.). 3 Check that the power supply is the same as stated on the Rating Plate which is in agreement with the electrical diagram for the unit and that cable sizes are correct. Check that tightness of the electrical connections to their terminals and to ground. 4 Check the control panel connections. (If the connection is wrong, the unit will not operate and the control panel display will not light). Inspect the Air Filter, which should be in its housing and correctly positioned (the metal grille should be toward inside). Air filter Air return duct 5 Check, with your hand, that the fans turn freely. FIGURE FOR THE STANDARD UNIT CONFIGURATION FOR MODELS 080 Power supply 3 Outdoor air intake duct 2 Close the unit and check that there are no loose panels. Discharge duct 1 Drain pipe 5 Fan access 1 Drain pipe Flexible joint at Openings Power supply 3 1 2 Outdoor discharge duct 31 Trap 2 Flexible joint at Openings 3 Power supply Drain pipe ON / OFF SLEEP FAN MODE SET TEMP OFF TIMER HOUR MINUTE 4 Control panel 3.- COMMISSIONING AND OPERATION 3.4.- STEPS TO FOLLOW FOR COMMISSIONING THE UNITS - On heat pump units, the compressor has a single phase electric heating element to assure a separation between the refrigerant and the oil in the housing. This heater is activated when the compressor is off and stops working when the compressor is on. About eight hours before start up or after a long shutdown period, voltage should be supplied to the unit so that this heater will be activated. - To start the unit, follow the instructions given in the Control Panel Manual supplied with the unit (requesting operation in any of the modes, cooling, heating, or automatic). After a time lapse, the unit will start. - With unit operating, check that the fans are turning freely and in the proper direction. REMEMBER THAT THE COMPRESSOR IS A SCROLL TYPE COMPRESSOR Scroll type compressors only compress in one direction of the rotation. Single phase models are always started up in the proper direction; however, the three phase models, turn in either direction depending on the order of the power supply phases. Therefore, it is essential that the phase connection for scroll-type three-phase compressors be carried out correctly, that is why these three-phase compressors are supplied as standard with a three-phase detector, which avoids the unit starts unless the connections are made on the right way. The direction of the rotation is right when an indicator-light turns ON. If the connection is wrong, this indicator will not light and the rotation will be reversed. If this occurs, the solution is to disconnect, switch the wires between two of the phases and connect again. - Connect high and low pressure gauges and check that operating pressure values are normal. - Measure electrical consumption for the unit and check that it is near what is indicated on the Rating Plate. - Check the electrical consumption of the compressor and the fans with what is specified in the physical data sheets. - In the case of a Heat Pump unit, make a cycle change on the Control Panel checking that the 4-way valves make the change correctly. Check the pressure values in the new cycle. - UNIT PROTECTIONS: 1.- Electrical protections: à Compressor start temporize 3 minutes. Avoid continued compressor starts. à Thermal compressor protection (three phase models). Protects from a high compressor absorbed power. To reset this protection, push the thermal protection button (located at the outdoor unit electrical box). à Three phase detector (three phase models). Explained before. à Protection fuses outdoor-indoor unit connection. 2.- Refrigerant protections: à Pressostats: RATED (kg/cm2) OFF ON DESCRIPTION UNITS EFFECT RESET Low pressure (LP) 030 to 080 0,5 1,5 Unit stops High pressure (HP) Low ambient control (HPC) 030 to 080 27,5 22 Unit stops on cooling mode Manual (electric) Heat pump units 26,5 22 Outdoor fan stops on heating mode Automatic/ Manual (electric) (1) Automatic (1) For heat pump units, when the unit is working during an hour, the 2 first resets are automatic, the third one is manual (electric). For cooling only units, the reset is always manual (electric). For electrical resets, disconnect power supply from the unit. Indication for pressostat alarms: For heat pump units, the PCB (located at the outdoor unit electrical box) has 2 indicators, HP and LP, which are low pressure and high pressure indicators. If any of those are lighted, indicates that the protection is activated; if any indicator is flashed, indicates that the protection has been reset, and it is waiting for disconnecting power supply. à Probes: • Anti-freeze protection: it comes on through the indoor unit coil probe (ID), avoids ice forms on cooling mode when temperature measures 0ºC, the unit stops. This protection has an automatic reset. • Overload heating mode protection: it comes on through the indoor unit coil probe (ID), avoids the unit works on heating mode with high condenser temperatures, when temperature measures 63ºC, the unit stops. This protection has an automatic reset at the first time, and manual (electric) for the second one. 3.- Defrost cycle: For heat pump units during the heating mode, it is possible the unit goes on to the defrost cycle. During this cycle, it is necessary to melt the ice on the outdoor coil, for that the unit will start working on cooling mode, and outdoor and indoor fans will stop. needed JMP5 JMP6 Function: the defrost cycle is controlled through the PCB (outdoor unit) and the Time for defrost temperature probe (TS) located on the outdoor coil. The defrost cycle begins when 30 min TS< -2ºC during 45 min. (not necessary on and on). This period can be changed 45 min (2) through jumpers JMP5 and JMP6 from PCB. The defrost cycle ends when 60 min TS> +18ºC or because the defrost cycle has exceeded 12 min. 75 min (2) Factory setting 32 4.- MAINTENANCE IMPORTANT: MAKE SURE THE UNIT IS COMPLETELY DISCONNECTED FROM THE POWER SUPPLY WHEN CARRYING OUT ANY TYPE OF WORK ON THE MACHINE. ALL MAINTENANCE SERVICE ON THE UNIT MUST BE CARRIED OUT BY QUALIFIED PEOPLE. ONLY COIL CLEANING AND FILTER REPLACEMENT CAN BE DONE BY NON-QUALIFIED PEOPLE. 4.1.- PREVENTIVE MAINTENANCE PREVENTIVE MAINTENANCE PREVENTS COSTLY REPAIRS. BECAUSE OF THIS, PERIODIC INSPECTIONS ARE REQUIRED: - GENERAL STATE OF THE CASING: Furniture, paint, deterioration due to bumps, rust spots, leveling and supporting, state of the shock absorbers, if installed, screwed panels, etc. - ELECTRICAL CONNECTIONS: State of hoses, tightness of screws, grounding, current draw of the compressor and fans and checking that the unit is receiving the correct voltage. - COOLING CIRCUIT: Check that pressure values are correct and that there are no leaks. Check that there is no damage to the pipe insulation, that the state of the batteries is correct and that there are no chips or clogs retained by the air flow, etc. - COMPRESSOR: Inspect the oil level, if sight glass is present. Inspect the state of the silent block fixtures. - DRAINS: Check that water drains correctly and that the drain trays are clean. - FANS: Check that fans turn freely and in the correct direction without excessive noises. - CONTROL: Check Set Points and normal operation. - AIR FILTER: Detachable for cleaning by sliding front and down side. A) ONE SIDE: filter can be removed sliding it out, from left or right side, as picture shows. B) FRONT SIDE: push air filter up and pull it out, as shown in the picture. The filter should be cleaned with a vacuum cleaner or washed in soapy water. The frequency for cleaning or changing the air filters will depend on the quality air in the area (fumes, vapors, suspended dust particles, etc.). - ACCESS TO INSIDE COMPONENTS: The whole unit will be accessed, without disassembling the ducts, through the cover located at the bottom of the unit. This allows: - To carry out an inspection, checking or replacing any internal component of the unit (motor-fan). - Cleaning the coil and drip tray. LNXO 018-024-030-036-048-060 LNXO 070-080 Drip tray Fan access panel Fan access panel It is very important cleaning the coil and the drip tray periodically. - For models 018 to 060 it is necessary to detach the drip tray to get the coil. This can be easily done by removing the screws which join the drip tray with unit sides. - For models 070 to 080, to get the coil, only have to detach fan access panel. 33 4.- MAINTENANCE 4.2.- CORRECTIVE MAINTENANCE If some component in the cooling circuit must be replaced, follow these recommendations: - Always use original replacement parts. - Remove the entire refrigerant charge from the unit. Create a slight vacuum as a safety measure. - Regulation prohibits the release on the refrigerant into the atmosphere. - If cuts must be made in the pipework, use pipe cutters. Do not use saws or any other tools that produce filings. - All brazing must be carried out in a nitrogen atmosphere to prevent corrosion from forming. Direction of the flame - Use silver alloy brazing rod. Wet rag - Take special care that the flame from the torch is aimed in Silver alloy welding rod the opposite direction from the component to be welded and Nitrogen is covered with a wet rag in order to avoid overheating. Component to be welded - If a compressor must be replaced, disconnect it electrically and un-braze the suction and discharge lines. Remove the securing screws and replace the old compressor with the new one. Check that the new compressor has the correct oil charge, screw it to the base and connect the lines and electrical connections. - Carry out the vacuum above and below until -750 mm Hg is reached. Once this level of vacuum has been reached, keep the pump in operation for at least one hour. DO NOT USE THE COMPRESSOR AS A VACUUM PUMP. - Charge the unit with refrigerant according to the data on the Rating Plate for the unit and check that there are no leaks. 4.3.- FAILURE DIAGNOSIS PROBLEM SOLUTION 1.- Unit does not work. • Check electrical supply of the unit. • Check electrical connection. • Check that remote controller and its parameters work correctly. 2.- The fan of the unit works too fast without any change on speed. • Check that the filter of the unit is clean. • Check electrical connection. • If the problem persists, check the function of the motor. 3.- Noise on pipe system. NOTE: Some noises are normal when unit stops and starts. • Check refrigerant charge is correct. • ¿was the vacuum made correctly? • Check internal temperature; it could be quite low. 4.- Excess of condensation in indoor unit. 5.- The indoor coil freezes continuously. • Check possible obstructions in the condensate pan, and also out of the pan. • Check correct level of the unit. • Check drainage pipe. • Check the air filter of the indoor unit. • Check the level of refrigerant. • Check strangulation air flow or recirculation. • If the freeze persists the expansion can be obstructed. • ¿Is the temperature below 21 ºC? • Check indoor temperature sensor. 6.- Unit works perfectly on cooling mode, but does not produce heat on heat pump mode. • Check if you have configured correctly the function mode of the unit. • Check inverter valve of the outdoor unit. • Check the plate PCB to the solenoid inverted valve. 7.-External fan stops. • Check that terminal connections are slack. • Check the motor. • Check the condenser situation. • Check that the unit is not on defrost cycle (heat pump units). 8.-Excessive pressure of condensation. (working on cooling mode). • • • • 9.-Low pressure condensation. (working on cooling mode). • Check that the refrigerant charge is correct. • Check possible obstruction on the expansion system, liquid pipe or exchanger. • Check that air filter is not dirty or wrong function of indoor fan. • 10.-Excessive pressure on return air. • (working on heat pump mode). • • 11.-Low pressure on return air. • (working on heat pump mode). • • Check that the external exchanger is not dirty and obstructed. Check that there is no condensable gas and air in the refrigerant circuit. Check that the external fan works correctly. Check that the refrigerant charge is correct Check that the refrigerant charge is correct. Check the situation of inverter valve. Check retention valve situation (if incorporated). Check that the refrigerant charge is correct. Check possible obstruction on the expansion system of the outdoor unit. Check that the external fan works correctly. Check the correct function of the defrost control. 34 GREAT BRITAIN, IRELAND: BELGIUM : CZECH REPUBLIC : FRANCE : GERMANY: NETHERLANDS : POLAND : PORTUGAL : RUSSIA : SLOVAKIA : SPAIN: UKRAINE : OTHER EUROPEAN COUNTRIES, AFRICA, MIDDLE-EAST : COD: MIL90E-0303 03-2003 LENNOX INDUSTRIES LTD tél. : + 44 1604 59 9400 fax : + 44 1604 594200 e-mail : marketing lennoxind.com LENNOX BENELUX N.V./S.A. tél. : + 32 3 633 30 45 fax : + 32 3 633 00 89 e-mail : info lennoxbenelux.com JANKA LENNOX tél. : + 420 2 510 88 111 fax : + 420 2 579 10 393 e-mail : janka janka.cz LENNOX FRANCE tél. : + 33 4 72 23 20 20 fax : + 33 4 78 20 07 76 e-mail : accueil lennoxfrance.com LENNOX DEUTSCHLAND Gmbh tél. : + 49 69 42 0979 0 fax : + 49 69 42 0979 40 e-mail : info lennoxdeutschland.com LENNOX BENELUX B.V. tél. : + 31 33 2471 800 fax : + 31 33 2459 220 e-mail : info lennoxbenelux.com LENNOX POLSKA SP z o.o. tél. : + 48 22 832 26 61 fax : + 48 22 832 26 62 e-mail : lennoxpolska inetia.pl LENNOX CLIMATIZAÇAO LDA. tél. : + 351 22 998 33 70 fax : + 351 22 998 33 79 e-mail : marketing lennoxportugal.com LENNOX DISTRIBUTION MOSCOW tél. : + 7 095 246 07 46 fax : + 7 502 933 29 55 e-mail : lennox.dist.moscow co.ru LENNOX SLOVAKIA tél. : + 421 7 44 88 92 16 fax : + 421 7 44 88 16 88 LENNOX REFAC S.A. tél. : + 34 902 400 405 fax : + 34 91 542 84 04 e-mail : marketing lennox-refac.com LENNOX DISTRIBUTION KIEV tél. : + 380 44 213 14 21 fax : + 380 44 213 14 21 e-mail : jankauk uct..kiev.ua LENNOX DISTRIBUTION tél. : + 33 4 72 23 20 14 fax : + 33 4 72 23 20 28 e-mail :marketing lennoxdist..com
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement