HWS Analog

HWS Analog
Installation Guide
Humidity
TM
HWS Series
LCD Wall Mount with Analog Setpoints,
Humidistat Control
Product Overview
The HWS analog series measures humidity of the air inside a room. Devices are designed for use in hospital rooms,
laboratories, and other spaces that require precise environmental control. The keypad allows control of setpoint
values. The slide switch position determines the output type (amp or volt). To maintain accuracy, keep vents clear
of dust, debris, etc. The HWS is warranted for period of five years.
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classified locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Product Identification
Accuracy
Setpoint
A
NIST
HWS
1 = 1%
2 = 2%
3 = 3%
5 = 5%
N = NIST (1 & 2% only)
X = No (2, 3, 5% only)
= Analog
S
= CE
Specifications
Input Power
Outputs
15 to 30VDC/24VAC, 100mA max.
Switch-selectable amp or volt
If volt is selected, the configuration menu allows selection
between 0-5V or 0-10V
RH Sensor*
Digitally profiled thin-film capacitive (32-bit mathematics)
U.S. Patent 5,844,138
RH Accuracy at 25°C from 10-80% RH**
(Multi-point Calibration NIST traceable)
Reset Rate***
Stability
Hysteresis
Linearity
Operating Humidity Range
Temperature Coefficient
Operating Temperature Range
Analog Output Scaling
Calibration Offset
Setpoint Range
±2%, 3%, or 5% models, ±1% at 20-50% RH
24 hours
±1% @ 20°C (68°F) annually, for two years
1.5% (typical)
Included in Accuracy spec.
0-100% RH (non-condensing)
± 0.1%RH/°C above or below 25°C (typical)
10° to 35°C (50° to 95°F)
0-100% RH
Adjustable ±9.9% in 0.1% increments
10-80% RH in 1% increments
* The HS sensing element has a 1-year warranty. The element is not a part of the 5-year product warranty.
** Accuracy is specified with 24 VDC supplied power with rising humidity.
*** Reset Rate is the time required to recover to 50% RH after exposure to 90% RH for 24 hours.
One side of the transformer secondary is connected to the signal common, so an isolation transformer or
dedicated power supply may be required.
RTD/Thermistors in wall packages are not compensated for internal heating of the product.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper
surge protection (EN 61000-6-1:2007 specification requirements).
Z204453-0E
Page 1 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HWS Series
TM
Dimensions
4.75"
(121 mm)
-
+
3.5"
(89 mm)
Installation
1.2"
(29 mm)
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Locate the tab at the top of the sensor housing. Using only the minimum required force, press this tab down and pull the cover
outward from the top. Set the cover aside.
Housing, Top View
Tab
2. Remove the backplate by unfastening the sensor from the bottom of the backplate and pivoting the sensor outward.
3. Punch out wire opening in the backplate.
4. Position the backplate vertically on the wall, 4 ½ feet (1.4 m) above the floor. Locate away from windows, vents, and other
sources of draft.
Z204453-0E
Page 2 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HWS Series
Installation (cont.)
TM
5. Mount the backplate onto the wall using the screws provided.
Five screwholes available; use a minimum
of two for secure mounting.
6. Wire the backplate.
RH Output
RH Setpoint Output
+
POWER SOURCE
15 to 30VDC or 24VAC DIGITAL CONTROL
RH Input
GND
-
RH Setpoint Input
7. Install and configure the sensor.
RH YES/NO Jumper:
YES - allows user to change RH setpoint
NO - user can NOT change RH setpoint
RH
NO
AMP
VOLT
–
Minus
RUN
CAL
YES
+
Select
Plus
RUN/CAL Jumper:
CAL Mode - allows full access to all features.
RUN Mode - allows access to setpoint ONLY.
RH
SENSOR
NOTICE
RISK OF EQUIPMENT DAMAGE
. Ensure that the output selection is correct before applying power.
Failure to follow these instructions may result in permanent
equipment damage.
8. When the installation is complete, replace the cover and snap it into position.
Z204453-0E
Page 3 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Humidity
HWS Series
Calibration
Instructions
TM
1. To calibrate, move the RUN/CAL jumper to the CAL position.
2. Relative humidity allows for a calibration offset of ±9.9% RH, at the user’s discretion.
Menu Options
NORMAL MODE
4 5 .
Display screen
Scroll down
Select
Scroll up
-
5
% R H
SETPOINT MODE
(Enter by any keypress when
RH Yes/No jumper is in Yes position)
Press +/- to change, press Select button to select.
+
S E T P
4 5
O I N T
% R H
Press +/- to change, press Select button to select.
CONFIG/CAL MODE
(Enter by any keypress when
Run/Cal jumper is in Cal position)
C A L
+ 0 . 0
R H
%
Press +/- to change, press Select button to select.
Only if switch is in
Volts position
O U T P
0 - 1 0
U T
V
Press +/- to change, press Select button to select.
Replacing the
HS Element
Observe precautions for handling static sensitive
devices to avoid damage to the circuitry that
is not covered under the factory warranty.
1. Disconnect power to the unit.
2. Remove the faceplate.
3. Remove the HS element by gently pulling from the pin connector.
4. Place a new HS element onto the pin connector. Orient as shown, or the unit will not function. Ensure that the four HS pin holes
are inserted fully onto the unit pin connectors.
Top
Side
Bottom
Side
5. Replace the faceplate.
Z204453-0E
Page 4 of 4
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.