GM60
Gaseous Product Line
208-600 Volt
60 Hz / 1800 RPM
GM60-02
60 kWe
Standby
Ratings
240V
208V
240V
480V
600V
Phase
1
3
3
3
3
PF
1
0.8
0.8
0.8
0.8
Hz
60
60
60
60
60
Generator Model
362CSL1604
361CSL1602
361CSL1602
361CSL1601
361PSL1633
Connection
12 LEAD ZIG-ZAG
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe Nat (LP)
60 (60)
60 (60)
60 (60)
60 (60)
60 (60)
AMPS Nat (LP)
250 (250)
208 (208)
181 (181)
90 (90)
72 (72)
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
Standard Equipment
Additional
Generator
Engine
„„Radiator
Cooled Unit Mounted (50˚C)
„„Brushless
Single Bearing
„„UL
2200 Certified
Voltage Regulator
„„cUL
„„Blower
Fan & Fan Drive
„„Automatic
Certified
„„Starter
& Alternator
„„±
1% Voltage Regulation
„„Microprocessor
Pole, Rotating Field
„„Base
- Formed Steel
Line Circuit Breaker Mounted & Wired
Based Digital Control
„„Oil
Pump & Filter
„„4
„„Oil
Drain Extension w/Valve
„„130˚C
Standby Temperature Rise
„„Main
„„100%
of Rated Load - One Step
„„Critical
Grade Silencer Mounted
„„Battery
Charger 12V 6 Amp
„„Governor
- Electronic Isochronous
„„12V
Battery System & Cables
„„5%
„„SAE
Flywheel & Housing
„„NEMA
„„Air
Cleaner (Dry Single Stage)
„„Flexible
„„EPA
Fuel Connector
Certified
Maximum Harmonic Content
MG 1, IEEE and ANSI standards
compliance for temperature rise
„„Jacket
Water Heater -20˚F 1000W 120V
w/Isolation Valves
„„Vibration
Isolation Mounts
„„Radiator
Duct Flange (OPU Only)
„„Single
„„2YR
Source Supplier
/ 2000HR Standby Warranty
„„Standard
GM60-02
Colors - White / Tan / Gray
1
Gaseous Product Line
60 kWe
Application Data
Engine
Manufacturer:
Model:
General Motors
GM 5.7L EPA
Displacement - Cu. In. (lit):
Bore - in. (cm) x Stroke - in. (cm):
Type:
4-Cycle
Compression Ratio:
Aspiration:
Natural
Rated RPM:
Cylinder Arrangement:
8 Cylinder Vee
350 (5.70)
4.0 (10.2) x 3.5 (8.8)
9.4 : 1
1800
Max HP Stby (kWm):
105 (78.3)
Exhaust System
Gas Temp. (Stack): °F (°C)
1,350 (732)
Gas Volume at Stack Temp: CFM (m³/min)
589 (17)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.8 (10.2)
Cooling System
Ambient Capacity of Radiator: °F (°C)
122 (50)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
36.6 (138.5)
Heat Rejection to Coolant: BTUM (kW)
3,650 (64.2)
Heat Rejection to CAC: BTUM (kW)
N/A
Heat Radiated to Ambient: BTUM (kW)
854 (14.9)
Air Requirements
Aspirating: CFM (m³/min)
182 (5.20)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Fuel Consumption
7,400 (209)
Consult Factory For Remote Cooled Applications
Natural Gas
LP
At 100% of Power Rating: ft3/hr (m3/hr)
859 (24.3)
363 (10.3)
At 75% of Power Rating: ft3/hr (m3/hr)
725 (20.5)
305 (8.6)
At 50% of Power Rating: ft3/hr (m3/hr)
578 (16.4)
244 (6.9)
1.0”
1.0”
Fuel Inlet Size: NPT
Fluids Capacity
Total Oil System: gal (lit)
1.4 (5.3)
Engine Jacket Water Capacity: gal (lit)
2.0 (7.6)
System Coolant Capacity: gal (lit)
6.0 (22.7)
All calculations based on natural gas fuel.
Deration Factors: Temperature: Derate 1% Per 10oF Over 77oF Air Inlet Temperature | Altitude: Derate 3% Per 1000ft Over 328ft
GM60-02
2
Gaseous Product Line
60 kWe
DGC-2020 Control Panel
Standard Features
„„Digital
Metering
„„Engine
Parameters
„„Generator
„„Engine
„„CAN
Protection Functions
Protection
Bus ECU Communications
„„Windows-Based
„„Multilingual
„„Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
„„16
Programmable Contact Inputs
„„Up
to 15 Contact Outputs (7 standard)
„„UL
Recognized, CSA Certified, CE Approved
„„Event
„„IP
Recording
54 Front Panel Rating with Integrated Gasket
„„NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data
LxWxH
Weight lbs
OPU
80 x 38 x 52 in
1650
Level 1
80 x 38 x 60 in
2000
Level 2
80 x 38 x 76 in
2150
Level 3
110 x 38 x 68 in
2350
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
79 dBA
81 dBA
Level 1
77 dBA
79 dBA
Level 2
76 dBA
78 dBA
Level 3
72 dBA
75 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice.
Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
GM60-02
3
Gaseous Product Line
60 kWe
Optional Enclosures
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available).
**Level 2 & 3 enclosures are 150 MPH Wind Rated as standard.
***Enclosure height does not include unit base or exhaust stack.
*All specification sheet dimensions are represented in inches.
**All enclosures are based on the standard standby unit configuration. Any deviation can change dimensions.
***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice.
PowerDak Power Products LLC
Distributed By:
3350 Jet Dr. Rapid City SD 57703
Phone + 1 605-718-9960
www.dakgenerator.com
GM60-02
Rev1.0
4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement