Robertshaw Braeburn 7500 Thermostat Kit is a versatile and feature-rich thermostat that can be used to control a wide range of HVAC systems, including conventional systems with up to 2 stages of heating and 2 stages of cooling, heat pump systems with up to 3 stages of heating and 2 stages of cooling, and 2 or 3 wire hydronic zone systems.
In addition to its basic functionality, the Robertshaw Braeburn 7500 Thermostat Kit also offers a number of advanced features, such as:
- Wireless connectivity: The thermostat can be paired with a wireless remote sensor, which can be placed in a different room or even outdoors to provide more accurate temperature readings.
advertisement
®
Installer Guide
Universal Wireless Thermostat Kit
7500 Up to 3 Heat / 2 Cool Heat Pump
Up to 2 Heat / 2 Cool Conventional with wireless Humidity Control*
* Wireless Humidity Control requires accessory model 7330.
®
1 Specifications 2 Installation and Wireless Setup 3 Quick Reference
4 Installer Settings 5 Wireless Remote Sensors 6 System Testing
Warning
For installation by experienced service technicians only.
Caution
• Possible electric shock or damage to equipment can occur.
• Disconnect power before beginning installation.
This thermostat requires 2 properly installed “AA” Alkaline batteries for proper operation. When connecting optional 24 Volt AC power the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
1 Specifications
KIT INCLUDES: Wireless thermostat, control module, batteries and return air plenum sensor.
This thermostat is compatible with:
• Single stage heat / cool conventional and heat pump systems
• Conventional systems up to 2 stages of heating and 2 stages of cooling
• Heat pump systems up to 3 stages of heating and 2 stages of cooling
• 2 or 3 wire hydronic zone systems
Electrical and control specifications:
• Electrical Rating: 24 Volt AC
• 1 amp maximum load per terminal
• AC Power: 18 – 30 Volts AC
• DC Power: 3.0 Volt DC (2 “AA” Alkaline Batteries Included)
• Control Range: 45° – 90° F (7° – 32° C)
• Temperature Accuracy: +/- 1° F (+/- .5° C)
• Outdoor Temperature Display Range: -40° - 120° F (-40° - 49° C)
Terminations
Thermostat: R, C (optional 24 VAC power terminals)
Control Module: Rh, Rc, G, W1/E, W2/AUX, Y1, Y2, O/B/V3, L, C, P1, P2, S1, S2
7500-100-04
2 Installation and Wireless Setup
Install and Wire the Control Module
Warning
Disconnect power before beginning installation.
Control Module Location
Install the control module on a wall near HVAC equipment or on the HVAC equipment.
• Remove the cover of the control module.
• Mount the control module using the two mounting holes
and the appropriate type of screws for the application.
Install Return Air Sensor (required)
The Return Air Sensor maintains default temperature control if wireless communication is lost.
• Install the Return Air Sensor at least 12 inches upstream
of any humidification or ventilation equipment.
• Connect the Return Air Sensor to the P1 and P2
terminals on the control module.
• For hydronic applications, mount sensor in an area that
maintains living space temperature. Do not mount
on the supply pipes.
Wiring Terminations for Control Module
Terminal Conventional Systems Heat Pump Systems
Rh
Rc
G
W1/E
24 Volt AC Heating Transformer 24 Volt AC Transformer
24 Volt AC Cooling Transformer Not Used
System Fan Relay
(W1) 1st Stage Heat Relay
W2/AUX (W2) 2nd Stage Heat Relay
System Fan Relay
(E) Emergency Heat Relay
(AUX) Auxiliary Heat Relay
O/B/V3 (V3) Zone Valve Power Close
(Hydronic Systems Only)
Y1 1st Stage Cooling Relay
(O) Cool Active Reversing Valve
(B) Heat Active Reversing Valve
1st Stage Compressor Relay
2nd Stage Cooling Relay
Not Used
2nd Stage Compressor Relay
System Fault Indicator
Y2
L
C
S1
S2
P1
P2
24 Volt AC Transformer Common
Required Return Air Plenum
Sensor (must be installed)
24 Volt AC Transformer Common
Optional Wired Remote Sensor Optional Wired Remote Sensor
(Indoor or Outdoor) (Indoor or Outdoor)
Required Return Air Plenum
Sensor (must be installed)
Mounting
Hole
Connect
Button
Rc/Rh Terminal
Jumper (J3)
Wiring
Punchout
Mounting
Hole
Wiring
Punchout
Installer Guide 2
Conventional Systems
Typical Wiring Configurations
NOTE: The “System Type” option will be configured in Thermostat Installer Settings (section 4).
Heat Only
Set System Type to 11CONV
Rh 24 Volt AC Power (heating transformer) [note 1]
W1 Heat Relay
G Fan Relay [note 3]
C 24 Volt AC Transformer Common
Hydronic Heat Only
Set System Type to 1HD
Rh 24 Volt AC Power (heating transformer) [note 1]
W1 Zone Valve Power Open
V3 Zone Valve Power Close
G Fan Relay [note 3]
C 24 Volt AC Transformer Common
1 HEAT / 1 COOL Single or Dual Transformer
Set System Type to 11CONV
Rh 24 Volt AC Power (heating transformer) [note 1]
Rc 24 Volt AC Power (cooling transformer) [note 1]
W1 Heat Relay
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common [note 2]
Hydronic Heat / 1 Cool
Set System Type to 11HD
Rh 24 Volt AC Power (heating transformer) [note 1]
Rc 24 Volt AC Power (cooling transformer) [note 1]
W1 Zone Valve Power Open
V3 Zone Valve Power Close
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common [note 2]
2 HEAT / 2 COOL Single or Dual transformer
Set System Type to 22CONV
Rh 24 Volt AC Power (heating transformer) [note 1]
Rc 24 Volt AC Power (cooling transformer) [note 1]
W1 Heat Relay Stage 1
W2 Heat Relay Stage 2
Y1 Compressor Relay Stage 1
Y2 Compressor Relay Stage 2 [note 3]
G Fan Relay
C 24 Volt AC Transformer Common [note 2]
NOTES - Conventional Systems
[1] Open (J3) jumper for dual transformer installations.
[2] In dual transformer systems, transformer common must come from cooling transformer.
[3] If needed for system.
Provide disconnect and overload protection as required.
Additional Wiring Options
S1
S2
Indoor or Outdoor Remote Sensor [note 1]
NOTES - Additional Wiring Options
[1] These terminals can be used to connect a
Braeburn ® wired indoor or outdoor remote sensor.
Indoor remote sensor must be configured in Thermostat
Installer Settings (section 4).
3 Installer Guide
Heat Pump Systems
Typical Wiring Configurations
NOTE: The “System Type” option will be configured in Thermostat Installer Settings (section 4).
1 HEAT / 1 COOL - No Auxiliary Heat
Set System Type to 11HP
3 HEAT / 2 COOL – Including Auxiliary Heat
Set System Type to 32HP
Rh 24 Volt AC Power
O/B Changeover Valve [note 1]
Y1 Compressor Relay
G Fan Relay
C 24 Volt AC Transformer Common
2 HEAT / 2 COOL - No Auxiliary Heat
Set System Type to 32HP
Rh 24 Volt AC Power
O/B Changeover Valve [note 1]
Rh 24 Volt AC Power
O/B Changeover Valve [note 1]
Y1
Y2
Compressor 1 Relay (1st stage heating/cooling)
Compressor 2 Relay (2nd stage heating/cooling)
AUX Auxiliary Heat Relay (3rd stage heating) [note 2]
E
G
C
L
Emergency Heat
Fan Relay
[note 2]
24 Volt AC Transformer Common
Optional System Fault Monitor [note 3]
Y1 Compressor 1 Relay (1st stage heating/cooling)
Y2 Compressor 2 Relay (2nd stage heating/cooling)
G Fan Relay
C 24 Volt AC Transformer Common
L Optional System Fault Monitor [note 3]
NOTES - Heat Pump Systems
[1] O (cool active) or B (heat active) is selected in the Thermostat Installer Settings menu (section 4).
[2] Install a field supplied jumper between the
AUX and E terminals if there is no separate emergency heat relay installed.
[3] If the L terminal is used, the 24 Volt AC common must be connected ( C terminal).
Provide disconnect and overload protection as required.
2 HEAT / 1 COOL - Including Auxiliary Heat
Set System Type to 22HP
Rh 24 Volt AC Power
O/B Changeover Valve [note 1]
Y1 Compressor Relay (1st stage heating/cooling)
AUX Auxiliary Heat Relay (2nd stage heating) [note 2]
E Emergency Heat Relay [note 2]
G Fan Relay
C 24 Volt AC Transformer Common
L Optional System Fault Monitor [note 3]
Additional Wiring Options
S1
S2
Indoor or Outdoor Remote Sensor [note 1]
NOTES - Additional Wiring Options
[1] These terminals can be used to connect a
Braeburn ® wired indoor or outdoor remote sensor.
Indoor remote sensor must be configured in
Thermostat Installer Settings (section 4).
Installer Guide 4
Install the Thermostat
NOTE: Test location by pairing your thermostat before mounting (see page 7).
Thermostat Location
Install the thermostat approximately 5 feet (1.5m) above the floor in an area that has a good amount of air circulation and maintains an average room temperature.
Avoid installation in locations where the thermostat can be affected by drafts, dead air spots, hot or cold air ducts, sunlight, appliances, concealed pipes, chimneys and outside walls.
• Remove the sub-base from the body of the thermostat.
• Mount the sub-base as shown below:
Drill 3/16” pilot holes in your desired location. Use supplied anchors for drywall or plaster.
UP UP
5 Installer Guide
Provide Power to Thermostat
C
R
+
+
24VAC Power (optional)
Battery Power
• For optional 24 Volt AC power, you must connect R and C terminal to the thermostat sub-base.
• For battery power, insert the 2 supplied “AA” type alkaline batteries into the battery compartment located
in the rear housing of the thermostat. Make sure to position the Positive (+) and Negative (-) sides of the
batteries correctly with the +/- symbols in the battery compartment.
5
Attach Thermostat to Sub-Base
UP UP
INSTRUCTIONS
DAY/TIME
1) Line up the thermostat body with the sub-base.
2) Carefully push the thermostat body against the sub-base until it snaps in place.
3) Insert Quick Reference Card into slot on top of thermostat.
NOTE: This thermostat ships configured as a 1H/1C conventional thermostat. Confirm installer settings. See page 11.
Installer Guide 6
3) Insert Quick Reference Card into slot on top of thermostat.
6
Pairing the Thermostat with Control Module
Pairing the Thermostat and Control Module
1. On the thermostat, press and hold down the HOLD and
RETURN buttons for 3 seconds.
2. The word CMOD (control module) will appear in the
display and the symbol will flash (see Figure 1).
3. On the powered control module, press and hold the
CONNECT button for 3 seconds (see Figure 2).
4. The control module will enter pairing mode for 60
seconds. During this time the blue COMM indicator on
the control module will flash once every 2 seconds.
5. Once successfully paired, the symbol will stop
flashing and the blue COMM indicator on the control
module will turn on.
6. Press RETURN on the thermostat at any time to exit.
NOTE: In step 2, if the control module has already been paired, the symbol will not be flashing.
DAY/TIME
Figure 1
Replacing a Thermostat
If you are replacing a thermostat that is paired with an existing control module, you will need to clear the control module and pair it again with the newly installed thermostat.
1. Install the new thermostat.
2. On the control module, press and hold the CONNECT button
for 10 seconds until the red COMM indicator turns on.
3. Release the CONNECT button and the blue and red LED will
each flash once to indicate the control module was
successfully cleared.
4. Pair the new thermostat with the control module.
PWR
Connect
Button
COMM
Figure 2
Replacing a Control Module
If you are replacing a control module that is paired with an existing thermostat, you will need to clear the thermostat’s control module settings before pairing the new wireless control module.
1. Install the new control module.
2. Thermostat control module settings are cleared by adjusting Installer Setting #29 to CLR2. This setting clears
the connection between the thermostat and control module (see section 4).
NOTE: Be careful not to select CLR3 unless you want to clear all the thermostat settings.
3. Pair your new control module with the thermostat. See “Pairing the Thermostat with Control Module”.
Communication Loss
If communication between the thermostat and control module is lost, the red COMM indicator on the control module will begin to flash once every 10 seconds. The control module will attempt to reconnect to the thermostat several times automatically.
NOTE: To attempt to reconnect manually, press and hold the CONNECT button for 3 seconds.
The thermostat display will also indicate that communication has been lost by flashing COMM LOSS CMOD.
During communication loss the return air sensor is used to maintain the factory default heating and cooling temperatures.
7 Installer Guide
1 2 3 4 5
Control Module LED Indicators
Communication Indicator (COMM)
• Solid blue: Normal Operation
• Rapid blue flash: Sending Data to Thermostat
• 1 blue flash every 2 seconds: Control Module in Pairing Mode
• Flashing, then solid blue: Successfully Paired
• 1 red flash every 10 seconds: Lost Communication
Installer Guide 8
3 Quick Reference
1
8 9
2
Thermostat Display
3
BACK NEXT
HUMID
4 5 6 7
10
11
12
13
14
15
16
Fan Indicator ................................ Indicates when the system fan is running
Wireless Indicator ........................
Indicates a wireless connection (flashes when connection has been lost)
Day of the Week ........................... Displays the current day of the week
Program Event Indicator.............. Displays the program event
Time of Day ................................. Displays the current time of day
* BACK and NEXT are secondary functions of the PROG and HOLD buttons. When in programming or
configuration modes, BACK and NEXT appear in the display screen indicating that the PROG and
HOLD buttons now function as BACK and NEXT.
** Also see #24 on page 10.
9 Installer Guide
INSTRUCTIONS
22
23
15
BACK NEXT
DAY/TIME
16 17 18 19 20 21
24
Thermostat
25
Reset Button ............................... Resets current time, program and user settings
PROG Button................................. Selects programming mode or press for 3 seconds to select SpeedSet
BACK Button* ............................... Secondary function of the PROG button - moves back a setting
®
19
HOLD Button ................................. Enters/Exits the HOLD mode (program bypass)
NEXT Button* ............................... Secondary function of the HOLD button - moves to next setting
RETURN Button ............................ Returns to normal mode from program or setting modes
FAN Button ................................... Selects the system fan mode
SpeedBar
®
................................... Increases or decreases settings (time, temperature, etc.)
24 Outdoor Temperature ................... If a Braeburn ® outdoor sensor was connected you can view the outdoor
temperature by pressing the PROG and HOLD buttons at the same time.
25 Humidity Setpoint ........................ If a Braeburn wireless humidity sensor is connected you can view the
current humidity or make adjustments to the humidity setpoint by
pressing the DAY/TIME and RETURN buttons at the same time.
Battery Compartment ........................ Located in the back of thermostat
* BACK and NEXT are secondary functions of the PROG and HOLD buttons. When in programming or
configuration modes, BACK and NEXT appear in the display, indicating that the PROG and HOLD buttons
now function as BACK and NEXT.
Installer Guide 10
4 Installer Settings
The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer settings are indicated below with comments. More detail on each setting follows this table.
1. Press and hold down the RETURN and
buttons for 3 seconds.
2. Release both buttons and the first installer
setting will be displayed.
3. Change settings as required using the
or portion of the SpeedBar ® .
4. Press NEXT (HOLD) or BACK (PROG) to
move to the next or previous setting,
RETURN to exit.
BACK NEXT
INSTRUCTIONS
DAY/TIME
DAY/TIME
No. Installer Setting Factory Setting
( Notes follow this table) Default Options
1 Residential or
or Commercial Profile
2 Programming Mode
[note 1]
3 Clock Format
4 Temperature Scale
5 Auto Changeover
6 System Type
7 1st Stage Differential
8 2nd Stage Differential
[note 2]
9 3rd Stage Differential
[note 2]
RES
7 PROG
12 HR
F DEG oF AUTO
11CONV
0.5 DIF1
2.0 DIF2
2.0 DIF3
Comments
(More information follows this table)
RES
COMM
7 PROG
52 PROG
NO PROG
Select for Residential profile
Select for Commercial profile
Select for 7 day programming mode
Select for 5-2 day programming mode
Select for non-programmable mode
12 HR
24 HR
F DEG
C DEG
Select for 12 hour clock
Select for 24 hour clock
Select for Fahrenheit display
Select for Celsius display
oF AUTO
ON AUTO
11CONV
22CONV
11HP
22HP
32HP
1HD
11HD
Disables Auto Changeover mode
Enables Auto Changeover mode
Select for 1H/1C Conventional system
Select for 2H/2C Conventional system
Select for 1H/1C Heat Pump system
Select for 2H/2C Heat Pump system
Select for 3H/2C Heat Pump system
Select for Heat Only Hydronic system
Select for Hydronic Heat/1C system
0.5, 1.0 or Select a 1st stage temperature differential of .5°,
2.0 DIF1 1° or 2° F (.25°, .5° or 2° C)
1.0, 2.0, 3.0, Select a 2nd stage temperature differential of 1°,
4.0, 5.0 or 2°, 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3° C)
6.0 DIF2
1.0, 2.0, 3.0, Select a 3rd stage temperature differential of 1°, 2°,
4.0, 5.0 or 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3°C)
6.0 DIF3
11 Installer Guide
No. Installer Setting
( Notes follow this table)
Factory
Default
Setting
Options
Comments
(More information follows this table)
10 1st Stage Fan Control
11 Emergency Heat]
12 Reversing Valve
(O/B Terminal)
13 Fossil Fuel
[note 3]
Fan Control [note 4]
Backup Heat
HG FAN 1
HE EMER
REVO
[note 5]
AE AUX
[note 4]
HG FAN 1
HE FAN 1
HE EMER
HG EMER
REVO
REVB
AE AUX
AG AUX
Select for 1st stage Gas heating
Select for 1st stage Electric heating
Select for Electric Emergency Heat
Select for Gas Emergency Heat
Select for cool active Reversing Valve (O terminal)
Select for heat active Reversing Valve (B terminal)
Select for Electric Auxiliary heat (with compressor)
Select for Gas Auxiliary heat (without compressor)
14 Compressor Power Outage
Protection [notes 4, 6]
15 AC Power Interrupt
Warning [note 6] oF CPOP
16 Compressor Short 5 CSCP
Cycle Protection [note 7]
oF CPOP
on CPOP
Disables Power Outage Lockout Delay
Enables Power Outage Lockout Delay
AC oF MONR AC oF MONR Disables AC Power Interrupt Warning
AC on MONR Enables AC Power Interrupt Warning
5, 4, 3, 2 or Select a compressor short cycle protection delay of 5,
0 CSCP 4, 3, 2 or 0 minutes
17 Residual Cooling
Fan Delay [note 7]
60 FAN 90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60,
0 FAN 30 or 0 seconds.
18 Adaptive Recovery oF REC
Mode (ARM™) [note 8]
19 Indoor Remote Sensor
Control* [note 9]
I SENS
oF REC
on REC
I SENS
E SENS
A SENS
Disables Adaptive (early) Recovery mode
Enables Adaptive (early) Recovery mode
Temperature is sensed from thermostat only.
Temperature is sensed from remote sensor only.
Temperature is combined with the thermostat and
the remote sensor.
20 Lockout Security Level 2 LOCK
21 Auto Changeover
Dead Band
Point
[note 10]
22 Compressor Balance
[notes 4, 11]
3 BAND
NO BALC
23 Auxiliary Heat Balance NO BALA
Point [notes 4, 11]
2 LOCK
1 LOCK
If locked – Complete lockout is enabled
If locked – Partial lockout is enabled (SpeedBar ® still functional)
2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5˚ F
BAND (1°, 2° or 3° C) for Auto Changeover mode.
NO BALC Disables Balance Points
0-50 BALC Select a Compressor Balance Point of 0°- 50°F
is
NO BALA Disables Balance Points
70-40 BALA Select a Auxiliary Heat Balance Point of 70°- 40° F
90-60 LIM Select a Heat Set Point Upper Limit of 90°-45° F
45-80 LIM Select a Cool Set Point Lower Limit of 45°-90° F
24 Heat Set Point Upper Limit 90LIM
25 Cool Set Point Lower Limit 45LIM
[note 7]
26 Humidification
[note 12]
OFF
27 Auto Humidity Set AUTO
Point Limit [notes 11, 12]
28 Dehumidification
[note 12]
29 Installer Clear
OFF
CLR0
OFF
DEP
IND
AUTO
MAN
OFF
NI
NA
CLR0
CLR1
CLR2
CLR3
Disables Humidification
Enables Dependant Humidification
Enables Independent Humidification
Enables automatic humidity control based on outdoor temperature.
Enables manual humidity control from thermostat.
Disables Dehumidification
Normally inactive (open) relay
Normally active (closed) relay
Clear Off - No changes made to settings
Clears connection with wireless remote sensors
Clears connection with control module
Clears all thermostat settings (factory defaults)
Options (shaded) 26 - 28 only appear if optional wireless humidity sensor is installed. *When a Braeburn ® outdoor sensor is connected, the thermostat automatically recognizes it. Press PROG and HOLD at the same time to display outdoor temperature.
NOTE: Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings –
See User Manual for information on setting these options.
Installer Guide 12
NOTES - Installer Settings
1 Only available if Residential profile was selected in option 1.
2 Only available if a 2 or 3 stage system type was selected in option 6.
3 Only available if a Conventional system was selected in option 6.
4 Only available if a 2 or 3 stage Heat Pump system was selected in option 6.
5 Only available if a Heat Pump system was selected in option 6.
6 Only available if thermostat is 24 VAC powered (R and C terminals).
7 Not available if a heat only hydronic system is selected in option 6.
8 Only available if a programmable profile was selected in option 2.
9 Only available if a Braeburn
®
indoor remote sensor was connected.
10 Only available if auto changeover was enabled in option 5.
11 Only available if a Braeburn outdoor sensor was connected.
12 Only available if a Braeburn wireless humidity sensor was connected.
Detailed Explanation of Installer Settings (also see NOTES above):
1 Profile – Selects a residential (RES) or commercial (COMM) profile. If residential is selected, 4 programming events per day are available. If commercial is selected, 2 event, 7 day programming is available.
2 Programming Mode [note 1] – Selects the programming mode, either full 7 day or 5-2 day (weekday/ weekend) programming or non-programmable.
3 Clock Type – Selects either a 12 hour or 24 hour clock.
4 Temperature Scale – Selects a temperature scale of either °F or °C.
5 Auto Changeover – Selects auto changeover on or off. When auto changeover mode is enabled and when switching from heating to cooling or cooling to heating in auto changeover mode.
NOTE: Also see “Auto Changeover Dead Band” in option 21.
6 System Type – Selects the system type for your installation. NOTE: Changes made to this option will reset options 7 through 15 back to their default values dependant on the system type.
7 1st Stage Differential – Selects a 1st stage temperature differential.
8 2nd Stage Differential [note 2] – Selects a 2nd stage temperature differential.
9 3rd Stage Differential [note 2] – Selects a 3rd stage temperature differential.
10 1st Stage Fan Control [note 3] – Selects a 1st stage fan control of either gas or electric heat.
11 Emergency Heat Fan Control [note 4] – Selects emergency heat fan control of either gas or electric heat.
12 Reversing Valve [note 5] – Selects the output state of the O/B terminal. Select O for this terminal to be active in the cool mode or select B for this terminal to be active in the heat mode.
13 Auxiliary Fossil Fuel Heat Pump Control [note 4] – When set to electric (AE AUX), both the compressor
(1st stage) and auxiliary stage(s) will run when a call for auxiliary heat is made. When set to gas (AG AUX), the compressor stage(s) will be locked out one minute after a call for auxiliary heat. NOTE: This option can be overridden if setting an auxiliary heat balance point in Option 23.
14 Compressor Power Outage Protection [notes 4, 6] – Selects power outage protection on or off. When enabled, this thermostat will provide cold weather compressor protection by locking out the compressor stage(s) of heating for a period of time after a power outage greater than 60 minutes.
13 Installer Guide
15 AC Power Interrupt Warning [note 6] – When enabled, the thermostat will display an outage warning when AC power to the thermostat is lost.
16 Short Cycle Protection [note 7] – Selects the number of minutes the cooling compressor will be locked out after turning off. This short cycle protection is also active in the heat mode if a heat pump system was selected in Option 6.
17 Residual Cooling Fan Delay [note 7] – Selects a delay for the system fan after the cooling compressor has turned off. This delay will help remove the remaining cool air out of the ductwork providing additional efficiency.
18 Adaptive Recovery Mode (early recovery) [note 8] – Enables or disables the ARM TM (adaptive recovery mode) feature. During ARM, room temperature is recovered by turning on the heating or cooling before the end of the set back period. The set point temperature is changed to that of the upcoming program temperature.
19 Indoor Remote Sensor Control [note 9] – If a Braeburn ® indoor remote sensor is connected (wired) or paired (wireless) during installation, the thermostat will automatically detect the sensor. When an indoor sensor is detected, you may select between thermostat only (I SENS), remote sensor only (E SENS) or combining the thermostat and the remote sensor(s) (A SENS).
NOTE: This option does not apply to the Braeburn outdoor sensor. When an outdoor sensor is connected
(wired) or paired (wireless), the thermostat automatically recognizes it and no further configuration is necessary.
20 Lockout Security Level – Selects the level of keypad lockout when the thermostat is locked. Level 2 locks the entire thermostat (including the front reset button). Level 1 locks everything except the SpeedBar ® allowing for up and down temperature adjustment. NOTE: The lock code is set in the User Settings mode
(see User Manual).
21 Auto Changeover Dead Band [note 10] – When auto changeover mode is enabled in option 5 and selected, the system automatically switches between heating and cooling when the room temperature meets the normal criteria for either a heating or cooling call. There is a forced separation (dead band) between the heating and cooling set points so that the systems do not work against each other. This option selects the amount of this dead band in degrees with the default being 3° F.
22 Compressor Balance Point [notes 4, 11] – Locks out the use of the compressor heat stage when the outside air temperature is less than the selected setting of 0° F to 50° F.
23 Auxiliary Heat Balance Point [notes 4, 11] – Locks out the use of the auxiliary heat stage when the outside air temperature exceeds the selected setting of 70° F to 40° F. NOTE: This balance point over rides the fossil fuel compressor lockout in option 13. If this option is set to gas and the outdoor temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
24 Heat Set Point Upper Limit – Selects the heating set point upper adjustment limit.
25 Cool Set Point Lower Limit [note 7] – Selects the cooling set point lower adjustment limit.
Installer Guide 14
26 Humidification Mode [note 12] – For use with an external humidifier. Selects between disabling humidification (OFF), dependent control (DEP) or independent control (IND). The DEP setting controls humidification only during a call for heating. The IND setting allows humidification output in the heat mode, but does not require a call for heating. NOTE: It is recommended that the IND setting only be used with systems designed for low air temperature humidification such as steam humidification. Always ensure the heat exchanger or other system parts are not exposed to excess water from condensation or other sources.
When there is any doubt, use the OFF or DEP setting.
27 Auto Humidity Set Point Limit [notes 11, 12] – Select between turning the automatic humidity set point limit to auto (AUTO) or manual (MAN). When AUTO is selected, humidity control is provided automatically based on the outdoor temperature. Selecting MAN allows you to manually control the level of humidity.
28 Dehumidification [note 12] – For use with an external dehumidifier. Select between dehumidification disabled (OFF), a normally inactive (NI) or normally active (NA) relay, depending on the requirements of your external dehumidification equipment.
29 Installer Clear – Clears settings based on your selection. CLRO makes no changes, CLR1 clears all wireless remote sensor connections, CLR2 clears the connection to the control module and CLR3 clears ALL thermostat settings.
WARNING: If you press NEXT or RETURN after selecting CLR1, CLR2 or CLR3 the clear will take place and the appropriate settings will be returned to factory defaults. If you do not wish to make any changes, use the
SpeedBar ® to select CLRO.
15 Installer Guide
5 Wireless Remote Sensors
NOTE: See the wireless remote sensor manual for complete installation and use instructions.
Compatible Wireless Remote Sensors
Wireless Remote Indoor Sensor(s) – 4 sensors maximum
Wireless Remote Outdoor Sensor – 1 sensor maximum
Wireless Remote Humidity Sensor – 1 sensor maximum
NOTE: No more than 4 wireless remote sensors can be connected.
Pairing Wireless Remote Sensors
1 Press and hold the HOLD and RETURN buttons for 3 seconds.
2 Press NEXT until the word SENS appears in the display and the symbol flashes.
3 After the remote sensor is powered, press and hold the CONNECT button on the sensor for 3 seconds
and release.
4 The remote sensor will enter pairing mode for 60 seconds. During this time the blue indicator on the wireless
remote sensor will flash once every 2 seconds.
5 When paired, the thermostat display will change and indicate which remote sensor has been paired (see
Table 1). The symbol will stop flashing and the blue indicator on the remote sensor will turn on for
60 seconds.
6 To pair another wireless remote sensor, press NEXT and repeat steps 3 - 5.
7 Press RETURN at any time to exit.
NOTE: Sensors that have already been paired will appear in the thermostat display first, with a solid symbol.
IDS1, IDS2, IDS3 or IDS4 Remote Indoor Sensor 1-4
HMS
ODS
Remote Humidity Sensor
Remote Outdoor Sensor
Table 1
Using Wired Remote Sensors
• One wired indoor or wired outdoor remote sensor can also be connected to the thermostats S1 and S2
terminals on the control module using 2-wire thermostat cable.
• You cannot mix wired and wireless remote sensors of the same type (i.e. mixing an indoor wireless remote
sensor and an indoor wired remote sensor).
Replacing a Thermostat
If you are replacing a thermostat that is paired with an existing wireless sensor, you will need to clear the remote sensor and pair it again with the newly installed thermostat.
1 Install the new thermostat.
2 On the wireless remote sensor you want to clear, press and hold the CONNECT button for 10 seconds until the
red indicator turns on.
3 Release the CONNECT button and the blue and red indicator will each flash once to indicate the sensor was
successfully cleared.
4 Pair the remote sensor again.
Replacing a Sensor
If you are replacing a wireless remote sensor that is paired with an existing thermostat, you will need to clear the thermostat’s remote sensor connection before pairing the new wireless remote sensor.
1 Install the new wireless remote sensor.
2 Thermostat remote sensor settings are cleared by adjusting Installer Setting 29 to CLR1 (see section 4).
This setting clears all the remote sensors paired with the thermostat.
NOTE: Be careful not to select CLR3 unless you want to clear all the thermostat settings.
3 Once the remote sensor settings are cleared you will need to pair your new wireless remote sensor. You will
also need to pair any other existing wireless remote sensors that were previously connected.
Installer Guide 16
Wireless Remote Sensor Communication Loss
If communication between the remote sensor and thermostat is lost, the red indicator on the remote sensor will begin to flash once every 10 seconds. The sensor will attempt to reconnect to the thermostat several times automatically.
NOTE: To attempt to reconnect manually, press and hold the CONNECT button for 3 seconds.
The thermostat display will also indicate which wireless remote sensor has lost communication by flashing
COMM LOSS along with the remote sensor that has lost communication (see Table 2).
Wireless Remote Sensor Low Battery
If the batteries in a wireless remote sensor are low, the red indicator will flash 3 times every 30 seconds. The thermostat display will also indicate which wireless remote sensor has a low battery by flashing LOW BATT along with the remote sensor that has the low battery condition (see Table 2). Replace the remote sensor batteries immediately.
NOTE: After replacing batteries, allow up to 15 minutes for the wireless connection to re-establish.
IDS1, IDS2, IDS3 or IDS4 Remote Indoor Sensor 1-4
HMS Remote Humidity Sensor
ODS Remote Outdoor Sensor
Table 2
6 System Testing
Warning
Read Before Testing
• Do not short (or jumper) across terminals on the gas valve or at the heating or cooling system control board to test the thermostat installation. This could damage the thermostat and void the warranty.
• Do not select the COOL mode of operation if the outside temperature is below 50º F (10º C). This could possibly damage the controlled cooling system and may cause personal injury.
• This thermostat includes an automatic compressor protection feature to avoid potential damage to the compressor from short cycling. When testing the system, make sure to take this delay into account.
NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat.
All user settings will be returned to factory default, however all Installer settings will remain as originally programmed in section 4.
1 Press SYSTEM until the thermostat is in HEAT mode.
2 Using the SpeedBar
®
raise the set temperature a minimum of 3 degrees above the current room
temperature. The system should start within a few seconds. With a gas heating system, the fan may
not start right away.
3 Press SYSTEM until the thermostat is in the OFF mode. Allow the heating system to fully shut down.
4 Press SYSTEM until the thermostat is in the COOL mode.
5 Using the SpeedBar lower the set temperature a minimum of 3 degrees below the current room
temperature. The system should start within a few seconds (unless compressor short cycle protection
is active – See note above).
6 Press SYSTEM until the thermostat is in the OFF mode. Allow the cooling system to fully shut down.
7 Press FAN until the thermostat is in FAN ON mode. The system fan should start within a few seconds.
8 Press FAN until the thermostat is in FAN AUTO mode. Allow the system fan to turn off.
9 If the thermostat is controlling auxiliary equipment such as a humidifier, adjust the thermostat
settings to test these devices.
17 Installer Guide
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This device complies with Industry Canada’s licence-exempt RSSs. Operation is subject to the following two conditions:
(1) This device may not cause interference; and
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
Cet appareil est conforme aux CNR exempts de licence d’Industrie Canada. Son fonctionnement est soumis aux deux conditions suivantes :
(1) Ce dispositif ne peut causer des interf é rences ; et
(2) Ce dispositif doit accepter toute interf é rence , y compris les interf é rences qui peuvent causer un mauvais fonctionnement de l’appareil.
Installer Guide 18
Limited Warranty
When installed by a professional contractor, this product is backed by a 5 year limited warranty. Limitations apply. For limitations, terms and conditions, you may obtain a full copy of this warranty:
· Visit us online: www.braeburnonline.com/warranty
· Write us: Braeburn Systems LLC
2215 Cornell Avenue
Montgomery, IL 60538
5
YEAR
LIMITED
WARRANT Y
Store this manual for future reference.
www.braeburnonline.com
19 Installer Guide
®
®
Braeburn Systems LLC
2215 Cornell Avenue • Montgomery, IL 60538
Technical Assistance: www.braeburnonline.com
844-BLU-LINK (844-258-5465) (U.S.)
630-844-1968 (Outside the U.S.)
©2015 Braeburn Systems LLC • All Rights Reserved • Made in China.
7500-100-04