Ex1s2AD (connect to 2nd communication port)

Ex1s2AD (connect to 2nd communication port)
ÁÁÁ
PROGRAMMABLE LOGIC CONTROLLER
ÁÁÁ
Connection with PLC
1) The blocks not occupy any points.
2) Applicable PLC : Ex1s, Ex1n, Ex2n series.
3) The Ex1s2AD and the main unit are connected
with the cable at the left of the main unit.
EX1N,1S
Ex1s2AD
Ex1s2AD USER’S GUIDE
Ex1n32MR
Ex1n2DA Ex1n16ER Ex1n2DA
Ex1n32ER
X20-X27
X30 - X47
X00 -X17
$This manual contains text, diagrams and explanations
which will guide the reader in the correct installation
and operation of the Ex1s2AD special function block.
Y00-Y17
1) The Ex1s2AD type analog input block (Hereafter
referred to as the Ex1s2AD) converts 2 points of
analog input values (voltage output and current
output) into digital values, and transfers them to the
PLC main unit.
2) The analog input is selected from the voltage input or the
current input by the method of connecting wires.
ÁÁÁ
External Dimensions
87
39.6
48
ÁÁÁ
51KΩ
V2+
*3
500Ω
51KΩ
I2+
COM2
V1+
Voltage input
*2
Item
Content
Directric Withstand 500V AC 1min(Between analog input terminals
voltage
and case)
Environmental specifications other than the abovementioned are the same as the main unit of the
Programmable controller. (Refer to the manual of the
Programmable controller)
Isolation
*1 Shielded cable
Current input
1. Environment specification
Item
Analog circuits
Digital circuits
90
Wiring
CH2
CH1
51KΩ
Item
Range of analog
input
Resolution
Voltage input
Current input
-10 to 10V DC
-20 to 20mA
(External load resistance (External load resistance
2K to 1MΩ)
500Ω or less)
11bit (the 12th bit is positive and negative sign bit)
5Mv{10-(-10V)}/4000
10µA{20-(-20)}/4000
Integrated accuracy ±1%(full scale –10V to 10V) ±1%(full scale -20 to20mA)
COM1
1CH / 2 scantime
A/D conversion time
AG
+15V
24+
24-
Content
24V DC±10% 85mA (supplied from the External)
5V DC 30mA (supplied from main unit)
Photo-coupler isolation between analog and
digital circuits.
3. Defining gain and offset
Digital output
51KΩ
500Ω
I1+
ÁÁÁ
Specifications
2. Power supply specification and others
Unit : mm
ÁÁÁ
ÁÁÁ
DC/DC
converter
AG
-15V
*4
*1 Use a two-core, twisted, shielded cable for the
analog input line, and separate it from other power
lines or a lines easily induced.
*2 If there is voltage ripple in the input or there is noise in the
external wiring, connect a capacitor of approximately 0.1 to
0.47 µF, 25V.
*3 For the current input, make sure to short-circuit the
“Vn+” terminal and the “In+” terminal (n: input
channel No.).
*4 Make sure to connect the
terminal to the
terminal of the PLC main unit to which Class D
grounding (100 Ω or less) is performed.
Analogue value:-10V to 10V Analogue value: -20mAto +20mA
Input characteristics
Digital value -2000 to 2000
Digital value:-2000 to 2000
+2000
-10V
10V
-2000
Analog input
Digital output
ÁÁÁ
Y70-Y107
ÁÁÁ
Introduction
Digital output
ÁÁÁ
Y20-Y37 Y40-Y47 Y50-Y67
+2000
-20mA
20mA
-2000
Analog input
ÁÁÁ
Program Example
ÁÁÁ
♦Voltage Mode
M8002
[MOV K0 D8120] enable analog module
M8000
(M8112) : CH1 be selection
(M8110) : voltage mode M8110=0
CH1 Digital value that is converted from analog
values and stored in D8112.
If the digital value wanted to display in the range
of –20.000mA ~ 20.000mA and stored in any D register,
please see below program,
D200 = 10 × (D8112 or D8113)
M8002
[MOV K0 D8120] enable analog module
M8000
(M8113)
(M8111)
MUL
K10
D8113
D200
M8002
[MOV K0 D8120] enable analog module
M8000
(M8113) : CH2 be selection
(M8111) : voltage mode M8111=0
CH2 Digital value that is converted from analog
values and stored in D8113.
CH1 real voltage input = 10V × (D8112/2000)
CH2 real voltage input = 10V × (D8113/2000)
♦ M8110 : CH1 voltage or current mode selection flag
♦ M8111 : CH2 voltage or current mode selection flag
♦ M8112 : CH1 of 2AD enable flag
♦ M8113 : CH2 of 2AD enable flag
♦ D8110 : CH1 Immediate Data
♦ D8111 : CH2 Immediate Data
♦ D8112 : CH1 data buffer (Average data)
♦ D8113 : CH2 data buffer (Average data)
♦ D8114 : CH1 offset value
♦ D8115 : CH2 offset value
If the digital value wanted to display in the range
of –10,000 ~ +10,000 and stored in any D register,
please see below program,
D100 = 10,000 × (D8112 or D8113) ÷ 2000
M8002
[MOV K0 D8120] enable analog module
M8000
(M8112)
(M8110)
MUL
K10000
D8112
D104
DDIV
D104
K2000
D100
♦Current Mode
M8002
[MOV K0 D8120] enable analog module
M8002
[MOV K0 D8114] : CH1 offset value
M8000
(M8112) : CH1 be selection
(M8110) : CH1 is current mode, M8110=1
CH1 Digital value that is converted from analog
values and stored in D8112. (resolution 0.01mA)
M8002
[MOV K0 D8120] enable analog module
M8002
[MOV K0
D8115] : CH2 offset value
Ex1s2AD-edoc0309v100b
M8000
(M8113) : CH2 be selection
(M8111) : CH2 is current mode, M8111=1
CH2 Digital value that is converted from analog
values and stored in D8113. (resolution 0.01mA)
LIYAN ELECTRIC INDUSTRIAL LTD.
TEL: 886-4-25613700
FAX: 886-4-25613408
WEBSITE: http://www.liyanplc.com
E-MAIL: [email protected]