Manual 13262441

Manual 13262441
Tech News Letter : CCC/Dec/Tech/222
Author :Schneider Technical Support Team
Rev : 00
Last Modified On- 28 Dec 2015
th
SOFTWARE RELEASE
SUBJECT
Release of BMXNOC0401 Exec V2.09
TARGTED
AUDIENCE
System Integrator, End User, OEM, Tech Support
CONTENTS
FAMILY: ID PAC Platform
RANGE: Modicon M340
PICTURE
NEW
EVOLUTION
This Firmware release has been introduced with some enhancement.
Below enhancement has been done in this firmware release:
Removed a Remote Code Execution vulnerability in the websSecurityHandler (ICS-VU-587471)
CUSTOMER
VALUE
Click here to download the Firmware file.
Click here to download the Release Note.
1
Schneider Electric,
[email protected]
SOFTWARE RELEASE
SUBJECT
Release of BMXERT1604T SV1.2
TARGTED
AUDIENCE
System Integrator, End User, OEM, Tech Support
CONTENTS
FAMILY: ID PAC Platform
RANGE: Modicon M340
PICTURE
NEW
EVOLUTION
This Firmware release has been introduced with some enhancement.
The Following enhancement has been done in this firmware version:
ERT time stamping Applicative in Drop: EF will be locked with ACTIVE=1 if you active
READ_VAR on the same drop.
CUSTOMER
VALUE
UNITY00066012--- The local ERT under applicative mode, its status reports "0xFFFF" when
switch PLC running from System to Applicative
Click here to download the Firmware file.
Click here to download the Release Note.
2
Schneider Electric,
[email protected]
SUBJECT
RECENT FAQs
TARGTED
AUDIENCE
System Integrator, End User, OEM, Tech Support.
CONTENTS
Family: ID PAC Platform
Range: Modicon M340
Question:
Do any of the M340 Ethernet modules have Email functionality?
Answer:
FAQ1
Yes the v2.0 M340 PLCs BMXP342020 & BMXP342030 can be configured to send an email out of the
embedded Ethernet port on the CPU.
Note: Unity Pro v4.0 is required for this functionality and it is only available on the embedded
Ethernet port of the CPU.
CONTENTS
FAMILY: ID PAC Platform
RANGE: Modicon M340
Question:
What is the procedure for upgrading M340 BMXNOE0100 module using the SD memory
card.
Answer :
The procedure is for M340 BMXNOE0100 modules…
User loads new firmware onto the SD Card using Unity Loader Tool
FAQ2













Connect to M340 NOE with Unity Loader tool
Click the Firmware Tab:
Select the location of the new firmware on left window
Check the “Save on Memory Card” check mark
Press the “Transfer” button
Disconnect from the Unity Loader tool
User can send SD (BMXRMS008M) card to end user, End User loads SD card into NOE SD card
slot
Unplug the Ethernet cable from the NOE0100 module.
Press the reset button on the NOE module and NOE card will automatically load new firmware
from SD card (Notice the green LED on the front SD card slot of NOE flashing for a few min.)
When flashing stops the “ETH STS” LED on the face of the NOE will be flashing three times.
Plug the ethernet cable back into the NOE and “ETH STS” LED should go solid.
SD card will no longer have firmware on it
New firmware will have to be reloaded on SD card to perform this procedure on more NOE
modules
Find the answers you need with our new FAQ Technical Knowledge base. Over 3000 regularly updated FAQs
available.
http://www.schneider-electric.co.in/sites/india/en/support/faq/faq_main.page
3
Schneider Electric,
[email protected]
SUBJECT
TECHNOTES
TARGTED
AUDIENCE
System Integrator, End User, OEM, Tech Support.
CONTENTS
Technote on "How to setup communication between XBTGx xxxx with Lexium 32
connected via Modbus RTU”.
TECHNICAL
NOTE
This document describes the communication setup between XBT HMI and Lexium 32 Drive
and to control the Drive in various operating modes via Modbus RTU.
Click here download the technote.
CUSTOMER
VALUE



Setup the serial communication with Pinout for both the device.
Setting up the Modbus Control Mode in Lexium 32 Drive.
Execution of Motion Sequence Mode in Lexium 32M drive via Script in Vijeo Designer.
NEWS FLASH:
“Keep Safe-Post Floood Health Counseling ”
Schneider Electric conducted a Health Counseling session for Chennai employees and contractors on 11 December.
The session aimed at providing counseling to participants and make them understand the situation, the imminent
dangers of epidemic and DO’s and DON’T’s and to protect from diseases. Employees were encouraged to visit the
counsel unit and discuss with doctors and medical staff their health concerns as also take Tips on sanitization, Die t,
Water usage and others. A handout was issued as a ready reckoner for employees to take back home with them and
share with family and friends
4
Schneider Electric,
[email protected]
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project