OPzV2 200
OPzV 2-200
2V200Ah
OPzV Series SLA Battery
Range Summary
By combining the newly developed tubular positive plates with fumed
gelled electrolyte, BSB created the innovative OPzV range of batteries.
The range offers 20 years design life and very high deep cycling
capabilities. This range is recommended for telecom outdoor
applications, renewable energy systems and other harsh environment
applications.
Application
·
Medical Equipment
·
UPS
·
Railroad Utility
·
Photovoltaic System
·
Alternative Energy System
·
Telecommunications
·
Cable Television
·
Electric Utility
·
Control Equipment
·
Security System
General Features
·
Sealed and maintenance free operation.
·
Non-Spillable construction design.
·
ABS containers and covers(UL94 V0, optional).
·
Safety valve installation for explosion proof.
·
High quality and high reliability.
·
Super long service life.
·
Lowest self discharge characteristic.
·
Super reliability.
7mm (0.28inch)
20mm (0.79inch)
M8mm (0.31inch)
Construction
Safety valve
Terminal
Separator
Electrolyte
Lead dioxide
Lead
ABS
ABS
Epoxy Resin
......
......
......
......
EPDR
Copper
Polymer
Thixotropic Gel
390mm(15.4inch)
206mm(8.11inch)
Battery Model
OPzV 2-200
Designed Floating Life
Capacity(20oC)
Dimensions
103mm(4.06inch)
Terminal Dimensions
354mm(13.9inch)
Positive ......
Negative ......
Container ......
......
Cover
Sealant ......
20 Years
20HR(10.7A,1.80V)
10HR(20A,1.80V)
214Ah
200Ah
5HR(33.5A,1.80V)
168Ah
102Ah
Length
Width
Height
Total Height
103mm(4.06inch)
206mm(8.11inch)
354mm(13.9inch)
390mm(15.4inch)
Approx. Weight
16.3Kg (35.9 lbs)
Internal Resistance
Full charged at 20oC: 0.00095 Ohm
Self Discharge
2% of capacity declined per month at (20oC)
Capacity Affected
by Temp.(10HR)
Charge Voltage(20oC)
1HR(102A,1.80V)
40oC
109%
20oC
0oC
100%
85%
Cycle use
2.35V-2.40V(-5mV/ oC), max. Current: 40A
Page 1 of 2
-15oC
65%
Float use
2.25-2.29V(-3mV/ oC)
OPzV 2-200
2V200Ah
Charge
Voltage
o
Constant Charge At 0.2CA-2.35V (20 C)
(CA) (V/Cell)
(%)
120
2.35
100
80
0.20
Discharge Characteristic (20oC)
Charge Characteristic
Charge
Capacity
Charge
Voltage
2.17
100%Discharge
60
0.15
40
0.10
20
0.05
2.00
50%Discharge
1.83
Charge Current
0
0
0
2
4
6
8
10
Discharge Voltage (V/Cell)
Current
Charge
Charge
Capacity
OPzV Series SLA Battery
2.17
2.00
1.83
0.05CA
0.25CA 0.1CA
1.67
1.60
0
12
2
6
30
60
3
10
Hour
20
Self Discharge Characteristics
2.25
110
105
2.17
100
95
90
Capacity (%)
Battery Voltage (V/Cell)
12
Min
Relationship of OCV and state of charge
2.00
0.6CA
1.33
Time(hour)
2.08
1CA
85
80
75
70
65
60
55
50
1.92
45
1.83
0
10
20
30
40
50
60
70
80
90
100
40 0
o
3
20oC
30oC
40 C
6
9
12
15
18
21
24
27
30
Storage time:months
Remained Capacity(%)
Constant current discharge ratings-amperes at 20oC
F.V/Time
1.70V
15min
250
30min
172
1h
111
2h
66.8
3h
51.0
5h
34.5
8h
24.0
10h
21.0
20h
11.0
1.75V
1.80V
1.83V
1.87V
227
202
186
164
165
154
146
132
110
102
98.5
91.5
65.6
63.6
62.0
58.5
50.0
48.0
47.0
44.5
34.0
33.5
32.5
31.5
23.7
23.5
23.0
21.6
20.5
20.0
19.5
18.5
10.9
10.7
10.5
10.3
1.90V
148
120
85.0
55.0
42.0
30.0
20.5
18.0
10.1
3h
99.8
99.5
99.0
98.2
96.0
92.6
5h
75.7
73.7
72.0
70.1
69.5
67.0
8h
51.4
50.5
48.7
47.9
45.3
44.6
10h
42.9
40.9
39.7
39.1
37.5
36.4
20h
22.5
22.3
21.3
21.0
20.9
20.4
Constant power discharge ratings-watts at 20oC
F.V/Time
1.70V
1.75V
1.80V
1.83V
1.87V
1.90V
15min
416
368
326
311
290
276
30min
296
289
277
261
244
221
1h
234
211
194
185
181
174
2h
125
122
120
119
118
113
ISO9001
COPYRIGHT BSB POWER COMPANY LIMITED
Page 2 of 2
(Updated: 1-Nov-2010)
Was this manual useful for you? yes no